Fire Protection For Electrical Equipment
Fire Protection For Electrical Equipment
0917-8514228 / 0922-8553251
[email protected]
Data Center Fire Protection
A data center is a building, dedicated space within a building, or a group of buildings
used to house computer systems and associated components, such as
telecommunications and storage systems.
Since IT operations are crucial for business continuity, it generally includes redundant or
backup components and infrastructure for power supply, data communication
connections, environmental controls (e.g. air conditioning, fire suppression) and various
security devices.
Data Center Fire Protection
No business interruptions.
Keep data safe at all times.
Personal injury must be prevented.
Asset damage must be kept to an absolute
minimum.
Environmental damage, for example due to
extinguishing water must be avoided.
Data Center Fire Protection
Fires can occur within the digital equipment, wires, cables, HVAC equipment,
raised floors, suspended ceilings, and other combustibles found in data
centers. These fire risks lead data centers to address fire protection at three
different levels – building level, room level, and a rack-level (in-cabinet).
Data Center Fire Protection
The first level of fire protection is at the building level. The main
goal is to protect the building and employees from fire. The
type of fire protection most commonly used is fire sprinklers
and handheld extinguishers.
The National Fire Protection Association (NFPA) sets the standards for
room level protection. Standards for data center fire protection at the room
level are the:
Fire sprinkler systems are the least expensive option for data
center fire protection.
The gaseous systems use either inert gas and clean agent
gas. An inert gas system uses a mixture of argon and nitrogen
gases to decrease oxygen levels present in the room which
naturally puts out the fire.
The physical footprint is smaller than inert gas systems because they don’t
require as much agent to fill up an entire room. Clean agent gases are
electrically non-conductive, non-corrosive, and leave no residue upon
evaporation. This makes them the ideal fire suppression agents in data
centers. Like fire sprinklers, these systems have a piping system installed
throughout the room.
The system activates through smoke and heat detection, and the clean
agent gas disperses evenly throughout the room through nozzles. These
systems are total flood or engineered systems.
Data Center Fire Protection
2. Room Level Fire Protection
Data Center Fire Protection
3. Rack Level Fire Protection
The last level of data center fire protection is at the rack level. This fire
protection is essential to protecting specific equipment and limiting damage.
The mandatory fire sprinklers will protect the building and the room from
fire, but the equipment, valued at 57% of the cost in the room, is not
unprotected.
This creates a need to protect the equipment from a fire at the rack level to
save the investment. Installing a pre-engineered automatic fire suppression
system will protect the equipment by detecting the fire within seconds and
suppress it before the total flood or sprinkler system activates. This
prevents equipment damage causes by a water-based sprinkler and avoids
the discharge of large amounts of agent in a total flood cylinder which is
expensive to refill.
Data Center Fire Protection
3. Rack Level Fire Protection
Data Center Fire Protection
• All fuel tank size restrictions are provided with the exception
that tanks of any size may be installed within engine or
mechanical rooms provided the room is “designed using
recognized engineering practices with suitable fire-
detection, fire suppression, and containment means to
prevent the spread of fire beyond the room of origin.” The
exception is subjective, so any attempt to take credit for the
exception should be discussed with the AHJ early in the
project.
NFPA 37 - Fuel supply
This chapter defines sizing power generation systems and supplies design
information on basic generator accessories. Generators can have different ratings
indicating overall operating capacity shown below:
Standby - 60 to 70% of the rating for 24-hour periods up to 500 hours per year
operating time.
Emergency Standby - 60 to 70% of the rating for 24-hour periods up to 200 hours
per year operating time.
Prime - 60 to 70% of the rating for extended periods with 10% overload for one
hour, with unlimited operating hours.
Mission Critical - 85% of the rating for extended periods with up to 500-hour per
year operating time.
Continuous - 100% of the rating for extend periods with unlimited operating hours.
NFPA 110 - Chapter 5: Generator Ratings &
Fuel Storage
Fuel storage and day tank sizing are defined in this chapter.
The most common style of switch in use for emergency generator is the
Automatic Transfer Switch (ATS). When utility power is lost the switch
transfers the load to the emergency generator when it's ready to accept
it. Once utility power is returned, the ATS transfers load back to the utility
system. Only component specifications are provided, not manufacturer.
NFPA 110 - Chapter 7: Generator Installation
Requirements
An installed emergency generator system that fails under load or does not perform
to specifications defeats the purpose of the installation. Chapter 7 defines
installation requirements of both the generator and supporting systems. Design
considerations must be made when building an emergency power system that
operates in extreme weather conditions. Such as, a generator must be located in
an area not subject to flooding.
For generators located indoors, ventilation must be considered, heat from engine
radiator, alternator, and exhaust system must be vented to atmosphere to obtain
proper room temperature. The room in which the generator is loctaed must have a
two-hour fire rating addressed by the ventilation system. These are but a few of the
generator and support system standards in the chapter. When all of the installation
standards are met, Failures due to improper installation reduced greatly.
NFPA 110 - Chapter 7: Generator Installation
Requirements
Chapter 7.2: Location
Applicability of Agents.
1.4.1.1 The fire extinguishing agents
addressed in this standard shall be
electrically non-conducting and leave
no residue upon evaporation.
1.4.1.2* Agents that meet the criteria
of 1.4.1.1 shall be shown in Table
1.4.1.2.
1.4.1.3 The design, installation,
service, and maintenance of clean
agent systems shall be performed by
those skilled in clean agent fire
extinguishing system technology.
Chapter 1 Administration
Applicability of Agents.
1.4.1.1 The fire extinguishing agents
addressed in this standard shall be
electrically non-conducting and leave
no residue upon evaporation. FM200 Agent
1.4.1.2* Agents that meet the criteria
of 1.4.1.1 shall be shown in Table
1.4.1.2.
1.4.1.3 The design, installation,
service, and maintenance of clean
agent systems shall be performed by
those skilled in clean agent fire
extinguishing system technology.
Chapter 1 Administration
Water?
Inert
Gas?
Clean Agent Fire Suppression Agent
Comparison
IG-100 HFC227e
Novec
IG-55
1230
Installation Works
Inert Gas
CO2
FM200 / Novec
Novec
1230
FM200
Inert
Gas
Environment Budget
Safety Space
NFPA 850, 2015 Edition
Chapter 7
Chapter 4
Chapter 1 Identification of and Annex A Explanatory
Fire Protection Design
Administration Protection Against Material
Process
Hazards
Chapter 8 Identification
and Protection of
Chapter 2 Chapter 5 Annex B Sample Fire
Hazards for Combustion
Referenced Publication General Plant Design Report
Turbines and Internal
Combustion Engines
Chapter 15
High Voltage Direct Chapter 12 Annex F Informational
Current (HVDC) Geothermal Power Plants References
Converter Stations
NFPA 850, 2015 Edition
Chapter 14 - Generator Pit and Windings
14.5.3.3 Protection of generator pits containing
auxiliary circuits such as protection current
transformers (CTs), neutral transformers, and
grounding resistors that are associated with generator
protection should be provided by an automatically
actuated gaseous extinguishing system or water spray
system.
14.5.3.4 Gaseous suppression systems should be
actuated by protective relays, fire detection systems,
or both.
14.5.3.5 Operation of water spray rings should be
interlocked so that the unit will trip before the water
spray system activates. Immediately after the
generator has been sprayed with a water-based
system, it should be mechanically run (electrically
isolated and without excitation) for at least 24 hours to
avoid creating stator ground faults on both types of
winding materials.
NFPA 850, 2015 Edition
Chapter 14 - Cable Concentrations
14.5.4.1 Consideration should be given to the use of fire retardant cable
insulation such as those passing the flame propagation test in IEEE 1202,
Standard for Flame Propagation Testing of Wire and Cable.
14.5.4.3 Sprinkler or water
spray systems should be
designed for a density of
0.30 gpm/ft (12.2 mm/min)
2
Electrical Clearances
6.1.2.1 All system components shall be
located so as to maintain minimum electrical
clearances from live parts.
6.1.2.2 The electrical clearances in Table
6.1.2.2 shall apply to altitudes of 1000 m
(3300 ft) or less.
6.1.2.3 At altitudes in excess of 1000 m
(3300 ft), the electrical clearance shall be
increased at the rate of 1 percent for each
100 m (330 ft) increase in altitude above
1000 m (3300 ft).
6.1.3 Where the design BIL is not available
and where nominal voltage is used for the
design criterion, the highest minimum
clearance listed for this group shall be used.
NFPA® 15 - 2012 EDITION
Chapter 6 Installation Requirements
Electrical Clearances
Note: BIL values are expressed as kilovolts (kV), the number being the crest
value of the full wave impulse test that the electrical equipment is designed to
withstand. For BIL values that are not listed in the table, clearances can be
found by interpolation. *For voltages up to 161 kV, the clearances are taken
from NFPA 70, National Electrical Code. For voltages 230 kV and above, the
clearances are taken from Table 124 of ANSI C2, National Electrical Safety
Code.
A.6.1.2 The minimum clearances listed in Table 6.1.2.2 are for the purpose of
electrical clearance under normal conditions; they are not intended for use as
“safe” distances during fixed water spray system operation.
The clearances are based upon minimum general practices related to design
basic insulation level (BIL) values. To coordinate the required clearance with the
electrical design, the design BIL of the equipment being protected should be
used as a basis, although this is not material at nominal line voltages of 161 kV
or less.
Water Spray System for Transformer
Engr. Ronel R. Baes
PIFPO National President
Tel. No. 0917-8514229 / 0922-8553251
Email Add: [email protected]