AMIOA08 8DI-8DO Module-Instructions For Use

The AMIOA08 8DI-8DO manual describes a device with 8 optoelectronic isolated digital input channels and 8 Darlington tube digital output channels, utilizing RS485 MODBUS RTU for communication. It operates on a voltage range of DC 7-25V and supports various baud rates, with isolation protection for both communication and digital input ports. The device is designed for industrial signal collection and control, featuring standard DIN rail installation and specific wiring diagrams for input and output connections.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
134 views3 pages

AMIOA08 8DI-8DO Module-Instructions For Use

The AMIOA08 8DI-8DO manual describes a device with 8 optoelectronic isolated digital input channels and 8 Darlington tube digital output channels, utilizing RS485 MODBUS RTU for communication. It operates on a voltage range of DC 7-25V and supports various baud rates, with isolation protection for both communication and digital input ports. The device is designed for industrial signal collection and control, featuring standard DIN rail installation and specific wiring diagrams for input and output connections.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

AMIOA08 8DI-8DO Mamual

DEMO : https://youtu.be/qS2_hhnYAhk

1 Product description
8ch optoelectronic isolation digital input channel (NPN Low level input)
8ch Darlington tube digital output channel (ULN2803 NPN output)
RS485 MODBUS RTU standard communication protocol
Netted with configuration software, PLC or industry touch panel
Communication circuit designed for thunder protection and interference immunity
Used for signal collection and control in industrial field

2 Specification
1 Working voltage: DC 7-25V (9V 12V 24V)
2 Working current: 8-50MA
3 8 optically isolated input ports (NPN active low)
4 8 Darlington tube outputs (ULN2803 NPN output), the maximum load current of each
channel is 300MA
5 RS485 communication isolation protection 3000VDC, DI digital input port isolation
protection 3000VDC
6 Standard MODBUS RTU command (function code, 05/06/15/16 Write, 01/02/03 Read )
7 Baud rates: 1200 2400 4800 9600 (default) 19200 38400 57600 115200
8 Parity bits: None (default) /Even /Odd
9 Installation method Standard DIN rail installation
10 Dimensions 125×70×30mm
11 Weight: 114 grams
3 Interface definition:
VCC : Power input+
GND: Power input-
DO1: digital output channel 1
DO2: digital output channel 2
DO3: digital output channel 3
DO4: digital output channel 4
DO5: digital output channel 5
DO6: digital output channel 6
DO7: digital output channel 7
DO8: digital output channel 8
DI1 : Digital input channel 1
DI2 : Digital input channel 2
DI3 : Digital input channel 3
DI4 : Digital input channel 4
DI5 : Digital input channel 5
DI6 : Digital input channel 6
DI7 : Digital input channel 7
DI8 : Digital input channel 8
A+: RS485 signal A+
B-: RS485 signal B-

1Digital Input Wiring Diagram


2 Digital output wiring diagram
Note: The Darlington tube has only two states of "high resistance" and "conduction",
and the output level cannot be measured with a multimeter.

RS485 Networking Diagram

For Modbus rtu Command, please refer to "AMIOA08 MODBUS