Three-Phase Motor Report

The document presents the results of the installation of a three-phase induction motor. The motor plate with its technical specifications is shown. The nominal current of the motor is calculated through interpolation, resulting in 10.05 A. Based on this, a 12 AWG copper conductor capable of supporting 12.56 A is selected. A disconnect device rated at 11.55 A is also calculated. Finally, photographs of the conductor and device selected according to the calculations are shown.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
40 views15 pages

Three-Phase Motor Report

The document presents the results of the installation of a three-phase induction motor. The motor plate with its technical specifications is shown. The nominal current of the motor is calculated through interpolation, resulting in 10.05 A. Based on this, a 12 AWG copper conductor capable of supporting 12.56 A is selected. A disconnect device rated at 11.55 A is also calculated. Finally, photographs of the conductor and device selected according to the calculations are shown.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 15

Engine installation report

Three-phase induction

MA1 Diaz San Martin Juan Alfonso

MA1 Villamizar Fernando Stop

Naval School for Petty Officers “ARC Barranquilla”

“Electromechanics AC and DC Electric Motors”

Specialization

Walter Luna Rivera

Colombia, Barranquilla

2020
2

Engine installation report

Three-phase squirrel cage

Content
1. Goals.....................................................................................................................................3

2. Introduction...........................................................................................................................4

3. Results of the three-phase electric motor Squirrel Cage......................................................5

Literature........................................................................................................................................14
3

Engine installation report

Three-phase squirrel cage

1. Goals

 Apply the concepts learned in the Electromechanics Electric Motors course.

 Illustrate procedure for estimating nominal current.

 Calculate the different elements that must be taken into account for the

installation of an electric motor.

 Select the elements in the manufacturer's catalogue for the installation of an

electric motor, based on the calculations obtained.

2. Introduction

Three-phase induction motors are a type of alternating current motor, where they convert

electrical energy into mechanical energy. In the process of installing a starting circuit in three-
4

phase motors, the characteristics of the motor plate are taken into account, and it is also carried

out in accordance with the provisions of NTC 2050 in section 430, which sets out the elements

that must be used during the process (bibliography).

The purpose of this report is to analyze the proper installation process of a three-phase

induction motor, under the mathematical models agreed upon in the Colombian technical

standard 2050. When selecting the installation elements, it is necessary to take into account

different variables such as nominal current, conductor selection, selection device, among others.

In the development of this report, we will focus on a three-phase induction motor for

refrigeration systems of air conditioning plants in naval units, since its operation is continuous

service, which is of vital importance for the work carried out by these types of motors.

3. Results of the three-phase electric motor Squirrel Cage

- Photograph of the motor plate:


5

Illustration 1. Three-phase motor plate

Illustration 1 is the selection of the three-phase electric motor, such plate contains the

characteristics necessary for the development of the calculations. The corresponding data for

such a plate are presented below (Table 1):

Motor plate data


Power 3 HP (2.2KW)
Speed 3450 RPM
Voltage 220-440 V
Amperage 7.95-3.97 A
FREQUENCY 60Table 1. Motor plate data

- Nominal current estimation procedure for calculations:

According to the provisions of NTC 2050 in its article 430-6ª, it is established that table
430-150 (Table 2) is used to estimate the nominal current.
6

Board 2. NTC Table 430-150 on Full Load Current of Motors


Three-phase alternating current

A voltage of 220 V is taken according to the data on the plate, but such voltage is not

found exactly in table 430-150, so the values are interpolated (Table 3).

Voltage Amperag
(V) e (A)
208 10,6
220 X
230 9,6
Board 3. Data for Interpolation of
Amperage

X (Interpolacción)=10 , 05 A
7

With the power supplied (3 HP) by the plate, said characteristic was located in Table 2.

From this, the motor power equivalent to 2.238 KW was obtained. Regarding the nominal

amperage, the result was 10.05 A at full load. It can be seen that the higher the voltage, the lower

the amperage will be.

In the calculations of conductors, switches, short circuit protection, the nominal current

will be used.

- Calculation of the driver for the three-phase motor:

For conductors that supply a single motor, they must have a capacity greater than or equal
to 125% (≥125%) of the motor's capacity at full load. This capacity will be taken into
account for the calculation of the conductor with a nominal amperage at full load of 10.05
A.

Conductor =Amperaje∗125 %
Equation 1. Driver

Conductor =10 , 05 A∗125 %=12 , 56 A

The conductor must support a minimum of 12.56 A, since if a lower amperage conductor
is used, it may tend to have insulation problems, overheat and melt.

Now we proceed to calculate the caliber:


To calculate the caliber, the Colombian technical standard 2050 is necessary, specifically table
B-310-3 (Table 4).
8

Board 4. Current carrying capacity for multi-conductor cables with not more than three insulated conductors, nominal
0 to 2000 V in open air.
Taken from Table B-310-3, NTC 2050

The maximum temperature from Table 4 is selected due to the high temperatures in the engine
rooms of naval units, so the copper conductor was taken at the nominal temperature of 90 °C,
which is equivalent to 32A with 12AWG gauge.

- Selection from manufacturer's catalogue with driver's photo:

Braided Electric Cable 3x12 Description:

Centelsa X Meter Color BRV Cable Type: 3x12 Stranded Electrical Cable

Brand: Centelsa

Reference: THHN/THWN-2

90°C 12 AWG 600V GR II

30

AMPColor White Green Red.


Illustration 2. Copper conductor
Taken from: https://articulo.mercadolibre.com.co/MCO-558556866-cable-electrico-trenzado-3x12-centelsa-
x-metro-color-brv-_JM?
matt_tool=40494112&matt_word&gclid=CjwKCAjwzIH7BRAbEiwAoDxxTvBFnpR8g9iYaGYfCJ27Rqpj8oUTXq6Zm
VI8PeklbFX564C4MsgJBhoCm2IQAvD_BwE&quantity=1
9

- Calculation of the disconnecting device for the three-phase motor:

Disconnecting devices for motor circuits rated 600V or less shall have a current rating of

at least 115% of the full-load current rating of the motor. According to the conditions and

exceptions of a sectioning device we can determine that none of them apply to this motor,

for the following reasons:

Dispositivo seccionador =Amperaje∗115 %


Equation 2. Disconnecting device

Dispositivo seccionador =10 , 05 A∗115 %=11,55 A

A device with a minimum rating of 11.6 A must be selected.

- Selection from manufacturer's catalogue with photograph of the sorting


device:

Circuit breaker Specific Features: 16/22 Amps AC, Selector Switch Operator,

NEMA Size S0, Max Voltage. 600VAC.

Description: Circuit Breaker, Selector Switch Operator, NEMA

Size S0, NEMA Enclosure Rating No Enclosure, Number of

Terminals Required 1, AC Amps 16/22, Overload Relay Ampere

Setting 16/22, Starter Type Automatic with Thermal Protection,

Number of Poles 3.

Illustration 3. Catalogue Selector Device


Taken from: https://www.grainger.com.mx/producto/SIEMENS-Interruptor-Autom%C3%A1tico%2C16-22A%2C3-Polos/p/44KN23
10

- Calculation of short circuit protection device:

This element is intended to protect circuit conductors, motor controllers and the motors

themselves from countercurrent due to short circuits or ground faults. For the

development of the respective calculation, the data from Table 430-152 of NTC 2050

(Table 5) are taken into account.

B
oard 5. Maximum rated capacity or trip setting of devices
protection for branch circuits of motors against short circuit and ground fault.,
Taken from Table 430-152, NTC 2050

The nominal amperage at full load (10.05 A) was taken by the value of the non-time-delay fuse
equivalent to 300%.
Model approach to calculation:

Ajuste dispositivo de protección=Amperaje nominal∗Fusible retardo de tiempo


Equation 3. Trigger protection device setting

Ajuste dispositivo de protección=10 , 05 A∗300 %=30 , 15 A


11

- Selection in manufacturer's catalogue with short-circuit protection


photograph:

Tripolar Magnetic Thermo Switch Three-pole thermal magnetic switch

32 A Nominal current 32A brand: STECK

MODEL: SDD63C32

Device capable of interrupting the electric

current of the circuit when it exceeds the

value estimated in the calculation.

Illustration 4. Short circuit protection catalogue


Taken from: http://intrave.com/wp-content/uploads/2017/05/CATALOGO-STECK.pdf

- Calculation of the engine switching device:

The switching device is normally used to start and stop a motor, the nominal power in W
(HP) at the motor voltage must be taken into account, equal to or greater than the nominal
power of the motor.

220 V → Potencia nominal del motor es de 3 HP o 2 ,2 KW


12

Selection in manufacturer's catalogue with photograph:

- Calculation of overload protection device:

Continuous duty motors greater than 1 HP (746 W) must be protected against overload.
This device must be calibrated to trip at the following percentages of the nominal current
taken from the motor's nameplate.

Calculation model:

Prorección contra sobrecarg a=Corriente nominal placa∗Factor de servicio


Equation 4. Overload protection

Protección contra sobrecarga=7 , 95 A∗125 %=9 , 94 A

- Selection in manufacturer's catalogue with photograph overload protection.


13

Thermal Relay - Thermal Relay 9-13a Description: Thermal Relay Brand CHINT

Reference NR2-25/Z 9-13 Amperage range 9

to 13 Amps.

The thermal relay is a mechanism that serves

as an element of protection of the motor

against overloads and heating. Its mission is to

disconnect the circuit when the intensity

consumed by the motor exceeds a certain

intensity time, preventing the winding from

“burning”.

Illustration 5. Overload protection catalog


Taken from: https://www.google.com/search?
rlz=1C1RLNS_esCO908CO908&biw=1366&bih=657&tbm=shop&sxsrf=ALeKk02nGMXXz86ug6QC84Ah644Bu73o5g
%3A1600180881370&ei=kdJgX8aMFsOL5wKKh6DgDA&q=catalogo+de+reles+termicos+10+amperios&oq=catalogo+de+reles+termi
cos+10+ampere&gs_lcp=Cgtwcm9kdWN0cy1jYxADOgQIIxAnUJnNAVjh2AFg49sBaABwAHgAgAHxAYgBngiSAQUwLjIuM5gBAKABAaoBD3
Byb2R1Y 3RzLWNjLXdpesABAQ&sclient=products-
cc&ved=0ahUKEwiGmYqosuvrAhXDxVkKHYoDCMwQ4dUDCAs&uact=5#spd=15017802839482549488_0
14

4. Literature