Power System Protection Using SCADA Technology
Power System Protection Using SCADA Technology
Reasonable e orts have been made to publish reliable data and information, but the author and
publisher cannot assume responsibility for the validity of all materials or the consequences of
their use. e authors and publishers have attempted to trace the copyright holders of all material
reproduced in this publication and apologize to copyright holders if permission to publish in this
form has not been obtained. If any copyright material has not been acknowledged please write and
let us know so we may rectify in any future reprint.
Except as permitted under U.S. Copyright Law, no part of this book may be reprinted, reproduced,
transmitted, or utilized in any form by any electronic, mechanical, or other means, now known or
hereafter invented, including photocopying, micro lming, and recording, or in any information
storage or retrieval system, without written permission from the publishers.
For permission to photocopy or use material electronically from this work, access www.
copyright.com or contact the Copyright Clearance Center, Inc. (CCC), 222 Rosewood Drive,
Danvers, MA 01923, 978-750-8400. For works that are not available on CCC please contact
[email protected]
Trademark notice: Product or corporate names may be trademarks or registered trademarks and
are used only for identi cation and explanation without intent to infringe.
DOI: 10.1201/9781003394389
Typeset in Times
by codeMantra
Dedicated to my great parents who never stop giving of
themselves in countless ways; my beloved brothers and sisters;
my dearest wife, who leads me through the valley of darkness
with the light of hope and support; and my beloved kids Daniah
and Mustafa, whom I can’t force myself to stop loving.
Samir I. Abood
Dedicated to my family and especially to my wife Sherylle,
who has been beside me in reaching this point in life,
and highest regards to my mother, Bernice Fuller, who
sacri ced so that this period in time is a reality.
John Fuller
Contents
Preface....................................................................................................................xvii
Acknowledgments ...................................................................................................xix
Authors ....................................................................................................................xxi
vii
viii Contents
8.12 Three Phases to Ground Fault at the Loaded Transformer ... 269
8.13 Phase-to-Ground External Fault at the Loaded
Transformer ........................................................................... 270
8.14 Two-Phase-to-Ground Fault at the Loaded Transformer ...... 271
Problems ........................................................................................... 271
xvii
xviii Preface
faults. The last three unsymmetrical fault studies will require the knowledge and use
of tools of symmetrical components. This chapter also deals with network models,
shunt elements, fault analysis, and algorithms for short-circuit studies.
The description of fuses and circuit breakers, their types, and their speci cations
are discussed in Chapter 5. This chapter includes an introduction to the construc-
tion and working of a fuse, its characteristics, and its applications. It also discusses
high-voltage circuit breakers. A directional overcurrent time protection design using
Lucas-Nülle GmbH power system/SCADA network devices is explained.
Chapter 6 presents the overcurrent relay, PSM, time grading, and relay coordina-
tion method; this chapter also discusses requirements for proper relay coordination
and hardware and software for overcurrent relays. Overvoltage and undervoltage
protection using Lucas-Nülle GmbH power system/SCADA network devices is
explained. Also, the directional power protection system using SCADA technology
is discussed in this chapter.
Chapter 7 describes the preceding transmission lines protection, distance relay as
impedance, reactance, and MHO relay. The fundamentals of differential protection
systems used to protect transmission lines are also discussed. Protection of parallel
lines (parallel operation) and parametrizing non-directional relays using the SCADA
system are discussed. Directional time overcurrent relays and high-speed distance
protection using SCADA technology are explained in this chapter.
Chapter 8 presents transformer protection, types, connection, and mathematical
models for each type of device. Overcurrent relays, differential relays, and pressure
relays may secure the transformer and be controlled with winding temperature mea-
surements, and chemical analysis of the gas above the insulating oil for incipient
trouble is discussed in this chapter.
Chapter 9 deals with generator protection and generator fault types. It also pres-
ents motor and busbar protection. This chapter brie y discusses the types of internal
faults and various abnormal operating and system conditions. Additional protective
schemes, such as overvoltage, out of step, and synchronization, should also be con-
sidered depending on the generator’s cost and relative importance.
Chapter 10 presents the concept of feeder con guration, HIF modeling, nonlinear
load modeling, and capacitor modeling. The three test case systems’ designs and data
are presented in this chapter. Also, the technique validation and algorithm veri ca-
tion are presented in this chapter.
Finally, descriptions about earthing in the power system, types, and speci ca-
tions are discussed in Chapter 11. Also, it includes analysis procedures of electric
power system grounding. Besides, it identi es techniques that can be applied to eval-
uate substation grounding systems (as well as indication line towers grounding). It
also presents soil resistivity measurement methods; two measurement methods are
de ned: the three-limit method and the four-limit method.
Acknowledgments
The authors acknowledge Prairie View A&M University for providing a platform
where faculty, administrators, PhD students, and private and governmental entities can
contribute to a book that will be used in the education of future power engineers and for
providing a resource to contribute to advancing the knowledge of power systems and
continuing the technical foundation building for the production of future engineers.
It is our pleasure to acknowledge the outstanding help and support of the team at
CRC Press in preparing this book, especially from Nora Konopka and Prachi Mishra.
The authors appreciate the suggestions and comments from several reviewers,
including Professor Zainab Ibrahim, Electrical Engineering Department, University
of Baghdad, and Dr. Muna Fayyadh, American InterContinental University. Their
frank and positive criticisms improved this work considerably.
Finally, we express our profound gratitude to our families, without whose coop-
eration this project would have been dif cult, if not impossible. We appreciate feed-
back from professors and other users of this book. We can be reached at siabood@
pvamu.edu and [email protected].
xix
Authors
Samir I. Abood received his BS and MS from the University of Technology,
Baghdad, Iraq, in 1996 and 2001, respectively. He earned his PhD in the Electrical
and Computer Engineering from Prairie View A&M University. From 1997 to 2001,
he worked as an engineer at the University of Technology. From 2001 to 2003, he
was a professor at the University of Baghdad and Al-Nahrain University. From 2003
to 2016, he was a Middle Technical University/Baghdad-Iraq professor. He is an
electrical and computer engineering professor at Prairie View A&M University in
Prairie View. He is the author of 30 papers and 12 books. His main research interests
are sustainable power and energy systems, microgrids, power electronics and motor
drives, digital PID controllers, digital methods for electrical measurements, digital
signal processing, and control systems.
xxi
1 Introduction to Power
Protection Systems
1.1 INTRODUCTION
Power system protection is a philosophy of system reliability with maximum safety
protection and other aspects related to protection coordination. It is a science of mon-
itoring power systems, detecting faults, initiating an operation to isolate faulted parts,
and ultimately tripping the circuit breaker.
The aims of power system protection are to:
DOI: 10.1201/9781003394389-1 1
2 Power System Protection and Relaying
TABLE 1.1
Typical Short-Circuit Type Distribution
Type Rate of Occurrence (%)
Single-phase ground 70–80
Phase-phase ground 17–10
Phase-phase 10–8
Three-phase 3–2
The frequency of the faults incidence on different items in a power system is given
in Table 1.1.
iii. Stability: It is the relay’s ability to remain unaffected by incidents outside its
security region, including external faults or heavy load situations.
iv. Selectivity: It is the ability to isolate only the faulted zone.
v. Safety: It is the ability to secure against improper activity.
It should be affordable and should not restrict the rating of primary plants
and equipment. It should not have any “blind spots,” i.e., unprotected zones.
vi. Discrimination: It is between load (normal) and fault (abnormal) condi-
tions. It should not be confused with non-damaging transient conditions.
Discrimination is a relay system’s ability to discriminate between internal
and external faults to its intended protective zones.
vii. Dependability: A relay is dependable if it trips only when expected.
Dependability is the degree of certainty that the relay will operate correctly.
It can be improved by increasing the sensitivity of the relaying scheme.
viii. Reliability: It is the ability not to “fail” in its function. It can be achieved
by redundancy. Redundancy in protection depends on the criticality of the
apparatus. Reliability can be improved by providing backup protection.
The number of the desired tripping can be greater than or equal to the correct
tripping.
The optimal implementation and coordination of protective relays are obtained
considering the objectives, the system’s topology to be protected, the typical opera-
tion scenarios, and the probable fault occurrences.
Example 1.1
An overcurrent relay was monitored and had an observed performance over one
year. It was found that the relay operated 15 times, out of which 13 were correct
trips. If the relay failed to issue a trip decision on four occasions, compute the
relay’s dependability, security, and reliability.
Solution
= 13/17 = 76.47%
(
Reliability = Number of correct trips/ Number of desired trips + number of incorrect trips )
= 13/ (17 + 2 ) = 68.42%
i. PR – Protection relay.
ii. CB – Circuit breaker.
iii. Equip protected item.
iv. CT – Current transformer.
v. VT – Voltage transformer.
vi. DC Aux – DC auxiliary supply.
vii. HMI – Human–machine interface.
viii. PCL communications link.
ix. Tr CB – Trip coil.
Bus bar CB
Power system
CT
TR
PCL
Relay
Control
VT
DC MMI
Aux.
The rst line of defense for protecting the devices is the primary relay.
Backup safety relaying only works when (they are slow in action) the primary
relaying system fails.
1.7 TRANSDUCERS
Apart from nonelectrical quantities (temperature, pressure, etc.), the principal item in
this category are transformers.
There are:
These equipment required to reduce the sampled quantity in their secondary as faith-
fully as possible.
CTs and VTs are used.
i. To reduce the power system currents and voltages to a safe, adequate low
value for measurements and protection use.
ii. To insulate the relay circuit from the primary power circuit.
iii. To permit the use of standardized current and voltage ratings for relays.
Ip
Iron
core Secondary
windings
Ns
Is
Relay
• Iron core.
• Secondary winding.
• Primary conductor.
• External insulation.
Some current transformers do not have a primary conductor. In those cases, the
primary is the line or bus itself. The core and secondary winding are sometimes
directly installed in the circuit breakers or transformers’ bushing. These CTs are
called “bushing CTs.”
Some current transformers may have a primary that consists of several turns.
Typically, the primary number of turns is 1.
The total load connected to the CT terminal (g and h in this case) is called
“burden.”
Ideally, the secondary current of a CT is perfectly proportional to the primary
current. It will be shown later that, in reality, this is sometimes not true.
Figure 1.3 shows an equivalent circuit of CT, an exact circuit, and an approximate
circuit.
+ + +
Ep Es V2 ZB
_ _ _
(a)
Lm ie ZB
Es V2
(b)
FIGURE 1.3 Equivalent circuit of CT. (a) Exact circuit. (b) Approximate circuit.
the accuracy class; P represents protection; and 20 represents the accuracy limit cur-
rent factor.
Table 1.2 shows standard current transformer ratios, and Table 1.3 shows CT
classes and accuracies (accuracy class).
TABLE 1.2
Standard Current Transformer Ratios
50:5 100:5 150:5 200:5 250:5 300:5
400:5 450:5 500:5 600:5 800:5 900:5
1,000:5 1,200:5 1,500:5 1,600:5 2,000:5 240:5
2,500:5 3,000:5 3,200:5 4,000:5 5,000:5 6,000:5
TABLE 1.3
CT Classes and Accuracies (Accuracy Class)
Class %Error Application
0.1 ±0.1 Metering
0.2 ±0.2
0.5 ±0.5
1.0 ±1.0
5P ±1 Protection
10P ±3
Introduction to Power Protection Systems 9
TABLE 1.4
Standard VT Ratios
1:1 2:1 2.5:1 4:1 20:1 25:1 40:1 60:1 200:1
300:1 400:1 500:1 600:1 800:1 1,000:1 2,000:1 3,000:1 4,500:1
Line
ip 110 V or
Np:Ns 120 V
+ + +
Vp Ep Es V2 ZB
_ _ _
+ + +
Vp Ep Es Rc jX e V2 ZB
_ _ _
m1
Electromagnetic
unit
Voltage divider 110/√3 V
capacitors
1a
1n
2a
m2
2n
110 V
nVs − Vp
VTerror = × 100% (1.4)
Vp
CTs and VTs have ratio and phase angle errors to certain degrees. Errors are more
pronounced in CTs under transient conditions and core saturation. The load on CTs
and VTs is commonly known as their burden.
Introduction to Power Protection Systems 11
High-voltage
conductor
High-voltage
conductor
Bushing
Bushing
Caoacitor
units
Bushing Tap
ground
shield
Auxiliary
capacitor
(a) (b)
TABLE 1.5
Voltage Transformers’ Error Limits
Class Primary Voltage Voltage Error (%) Phase Error (±minutes)
0.1 0.8 Vn, Vn, and 1.2 Vn 0.1 0.5
0.2 0.2 10
0.5 0.5 20
1.0 1.0 40
0.1 0.5 Vn 1.0 40
0.2 1.0 40
0.5 1.0 40
1.0 2.0 80
0.1 Vn 0.2 80
0.2 2.0 80
0.5 2.0 80
1.0 3.0 120
12 Power System Protection and Relaying
A
B
C
a b c
(a)
A
B
C
a b c
(b)
A
B
C
a b c
(c)
FIGURE 1.8 Different types of VT connections. (a) Open delta connection, (b) delta–star
connection, and (c) star–star connection.
Example 1.2
The delta VT connection is shown in Figure 1.9, suppose VAB = 230 ∠0° kV,
VBC = 230 ∠ − 120° kV, VCA = 230∠120° kV, the VT ratio is 110 kV/120 V, calculate
vab , vbc , and vca . If the dot mark is moved to b, recalculate the above voltage.
Introduction to Power Protection Systems 13
A
B
C
a b c
Solution
110, 000
VT ratio = = 916.6
120
1
vab = ( 230∠0° kV ) = 250.92∠0° V
916.6
1
vbc =
916.6
( )
230 ∠ − 120° kV = 250.92∠ − 120° V
vca = − ( vab + vbc ) = 250.92∠120° V
1
vab =
916.6
( )
230 ∠0° kV = 250.92∠0° V
1
vbc = −
916.6
( )
230 ∠ − 120° kV = 250.92∠60° V
vca = − ( vab + vbc ) = 434.6∠ − 150° V
A
B
C
a b c
Iline V line
CT
VT
Current Voltage
coil coil
Vline Vrelay K VT K
Z line = = × = Z relay × VT (1.7)
I line I relay K CT K CT
1.9 CT ERROR
Ideally, the CT secondary is connected to a current-sensing device with zero imped-
ance, but in practice, the secondary current divides, with most owing through the
low-impedance-sensing device and some owing through the CT shunt excitation
impedance. CT excitation impedance is kept high to minimize excitation current.
The excitation impedance causes an error in the reading of the secondary current
(Tables 1.6 and 1.7).
Introduction to Power Protection Systems 15
TABLE 1.6
Current Transformer Speci cation IEC 185–IEC 44-1
Current Error at Phase Displacement at Composite Error (%)
Accuracy Rated Primary Rated Primary Current at Rated Accuracy
Class Current (%) Minutes Centiradians Line Primary Current
5P ±1 ±60 ±1.8 5
10P ±3 10
TABLE 1.7
Current Transformer Speci cation IEC 44-6
Ratio Error Phase Displacement at Maximum Instantaneous
(%) at Primary Rated Primary Current Value Error (%) at Rated
Class Rated Current Minutes Centiradians Accuracy
TPX ±0.5 ±30 ±0.9 ε = 10
±1.0 ±60 ±1.8 ε = 10
±1.0 180 ± 18 5.3±0.6 ε = 10
Example 1.3
100
63
E2 (V)
1 10
Ie (A)
Solution
From the magnetizing curve, substitute the points (1, 36) and (10, 100) in Frohlich’s
equation:
A ⋅ Ie
E2′ =
B + Ie
A ⋅1
63 =
B +1
A ⋅ 10
100 =
B + 10
Solving to get the constants A and B, where A = 107 and B = 0.698, Frohlich’s equa-
tion will be
107 I e
E2′ =
0.698 + I e
i. Z T = Z 2 + Z L
E2 = I 2 ⋅ Z 2
5
= × 400 × 5.009 = 20.4 V
500
20.4
Ie = 2
107
52 + 1 +
0.698 + I e
I e = 0.163 A
107 × 0.163
E2′ = = 20.3 V
0.698 + 0.163
E2′ 20.3
I2 = = = 3.97 A
Z T 5.009
4 − 3.97
CT error% = ⋅ 100 = 0.7%
4
Introduction to Power Protection Systems 17
I e = 0.894 A
E2 = 60.1 V
I 2 = 11.78 A
CT error % = 1.8%
Example 1.4
Assume that a CT has a rated current ratio of 500/5 A. The impedance of the sec-
ondary winding Z2 = 0.242 Ω, and the burden impedance ZB = 0.351 Ω. The core
area A = 0.00193 m2. The CT must operate at a maximum primary current of 10 kA.
If the frequency is 60 Hz and the core is built from silicon steel:
Solution
I s′ ≈ I s = 100 A.
Es = I s ( Z B + Z 2 )
Es = 4.44 × f × N 2 × A × Bm
Bm = 1.2 T
18 Power System Protection and Relaying
Es = 59.29 V is I e = 0.1 A.
Ie 0.1
ii. CTerror % = × 100% = × 100% = 0.1%
Is 100
i. Local backup: Clears fault in the same station where the failure has occurred
(see Figure 1.13).
ii. Remote backup: Clears fault on station away from where the failure has
occurred (see Figure 1.14).
Main relay
Backup relay
Example 1.5
Consider the following simple power system, and discuss the local and remote
backup protection for two fault locations in Figure 1.15.
2 3 10 11
1 8 F2 9 14 F1 15
12 13
4 6
5 7
Example 1.6
Example 1.6
B
A
F1 D
CB1 CB5
CB3 CB4 F2
CB2 CB6
CB7
C
CB8
CB9
B
A
F1 D
CB1 CB5
CB3 CB4 F2
CB2 CB6
CB7
C
CB8
CB9
FIGURE 1.17 Protection zones for the power system of Example 1.6.
iii. Mark that all circuit breakers will operate when faults P1 and P2 occur, as
shown in parts (i) and (ii).
Solution
i. Figure 1.17 illustrates the distribution of the protective zone on the power
system.
ii. To modify the system in Figure 1.17, add three circuit breakers at node D
(CBs 10, 11, and 12), as shown in Figure 1.18.
iii. For part (i), if the fault occurs at point F1, circuit breakers 3, 4, and 7 will
operate, and for a fault at F2, circuit breakers 4, 5, and 6 will operate.
For part (ii), if the fault occurs at point F1, circuit breakers 3 and 10 will operate,
and for the fault at F2, circuit breakers 4, 5, and 6 will operate.
Z = R + jX = Z e jθ (1.8)
22 Power System Protection and Relaying
B
A
F1 CB10 D CB11
CB1 CB5
CB3 CB4 F2
CB7
C
CB8
CB9
In addition to the plot of the operating characteristics of a given relay, the system
condition affecting the operation of this relay can be superimposed on the same R–X
diagram so that the response of the relay can be determined. The system character-
istics must be within the relay characteristics’ operation region to achieve this relay
operation. Note that the superimposed system and relay characteristics have to be in
terms of the plane quantities and the same scale. These can be both in p.u., where
Ohm is used. Both have to be on either a primary or a secondary basis, using
CT ratio
Secondary Ω′s = Primary Ω′s × (1.9)
VT ratio
Vs = I ⋅ Z L + VR (1.10)
ZL
I P+jQ
Vs VR
and
Vs
Zs = (1.11)
I
VR
ZR = (1.12)
I
also
Zs = Z L + Z R (1.13)
Z R = RR + jX R (1.14)
where
2
V P
RR = (1.15)
P2 + Q2
and
2
V Q
XR = (1.16)
P2 + Q2
Example 1.7
Assume that a short transmission line has the receiving end load apparent power SR
and voltage |VR| of 2.5 + j0.9 and 1.0 p.u., respectively. If the line ZL = 0.1 + j0.25 p.u.,
determine
Solution
2
V P
RR =
P 2 + Q2
1.0 ( 2.5)
2
= = 0.3541 p.u.
2.52 + 0.9 2
24 Power System Protection and Relaying
θR
δ
ZR
ZL ZS
θS
R
1.0 ( 0.9 )
2 2
V Q
XR = = = 0.1275 p.u.
P 2 + Q 2 2.52 + 0.9 2
PROBLEMS
1.1. A CT has a rated current ratio of 500/5 A, Z 2 = 0.1 + j0.5 Ω, and a magnetiza-
tion curve equation as
105 I e
E2 =
0.65 + I e
1.2. A CT has a rated ratio of 500:5 A, Z 2 = 0.1 + j0.5 Ω, and the magnetization
curve is shown in Figure 1.21, compute the primary current I and the CT
error for the following cases. Will the relay detect the primary current?
a. Z B = 4.9 + j 0.5 Ω, I ′ = 4 A ( Load current ) .
b. Z B = 4.9 + j 0.5 Ω, I ′ = 12 A ( Fault current ) .
c. Z B = 14.9 + j1.5 Ω, I ′ = 12 A ( Fault current ) .
FIGURE 1.22 Excitation curve for a multi-ratio bushing current transformer of Problem 1.3.
1.4. Figure 1.23a–c shows three typical bus arrangements. Draw the protective
zones.
i. Identify the circuit breakers that will remove the faults when the fault
occurs at P1, P2, and P3.
ii. Identify the lines removed from the service under primary protection
during a bus fault P1, P2, and P3.
Introduction to Power Protection Systems 27
(a)
(b)
P1
B1 B3 B5 B7
Line 1 Line 2 Line 3 Line 4
P3
B2 B4 B6 B8
P2
(c)
FIGURE 1.23 Power system con gurations for Problem 1.4. (a) Ring bus. (b) Breaker and a
half double bus. (c) Double breaker double bus.
1.5. Assume that a short transmission line has the receiving end load SR and
|VR| of 2.8 + j1.0 and 1.0 p.u., respectively. If the line Z L = 0.15 + j 0.3p.u.,
determine
i. Receive end Z R.
ii. Send-end impedance Zs.
iii. Draw the R–X diagram.
iv. The power angle δ.
1.6. What is the effect of the fault on the power system?
1.7. An overcurrent relay was monitored and performed over one year. It was
found that the relay operated 16 times, out of which 13 were correct trips. If
the relay failed to issue a trip decision on four occasions, compute the relay’s
dependability, security, and reliability.
28 Power System Protection and Relaying
1.8. The delta VT connection is shown in Figure 1.24, suppose VAB = 100 ∠0° kV,
VAB = 100∠ − 120° kV, VAB = 100∠120° kV, the VT ratio is 110 kV/120 V,
calculate vab , vbc , and vca . If the dot mark is moved to b, recalculate the
above voltage.
A
B
C
a b c
1.9. A CT with an excitation curve in Figure 1.22 has a rated current ratio of
400:5 A and a secondary leakage impedance of 0.15 + j 0.56 Ω . Calculate
the CT secondary output current and the CT error for the following cases:
i. The impedance of the terminating device is 5 + j1.5 Ω , and the primary
CT load current is 500 A.
ii. The impedance of the terminating device is 5 + j1.5 Ω , and the primary
CT fault current is 1250 A.
iii. The impedance of the terminating device is 15 + j 2.5 Ω, and the primary
CT load current is 400 A.
iv. The impedance of the terminating device is 15 + j 2.5 Ω, and the pri-
mary CT fault current is 1250 A.
2 Protective Relays
2.1 INTRODUCTION
A protective relay is an electrical system designed to respond to an abnormal input
condition, remove it, and trigger a contact operation after a speci ed condition is
met. Relays are used in all power transmission systems, in-home communications
systems, and industries.
In an irregular or unsafe device condition and an appropriate control circuit
initiation, a protective relay is identi ed as a relay whose function is detecting a
faulty line, apparatus, or other power condition. A fuse is often used as security
and is characterized as an overcurrent protective device with a fuse component in a
circuit opening due to heating and severed by an overcurrent condition.
This chapter presents aspects of data required for the relay setting and types of
relays; it also discusses the digital relay operation, signal path for microprocessor
relays, and digital relay construction.
i. Short-circuit level of the power system involved, showing the type and
rating of the protection devices and their CTs.
ii. The maximum and minimum values of short-circuit currents.
iii. The impedances of the system components.
iv. Starting current and settling time of the induction motor.
v. The maximum load current.
vi. Decrement curve showing the rate of decay of the fault current supplied by
the generator.
vii. The performance curve of the CTs.
The relay setting is rst determined to give the shortest operating time at maximum
fault levels and then checked to see if the operation will also be satisfactory at the
minimum fault current expected.
All power systems aim to maintain a very high standard of service status and
reduce downtime when intolerable conditions arise. Power loss, voltage drop,
and overvoltage will occur due to natural disasters, physical injuries, equipment
malfunction, and human error disturbance.
Safety is the science, skill, and art of applying, setting, and/or fusing to provide
full sensitivity to a fault and unwanted situation.
DOI: 10.1201/9781003394389-2 29
30 Power System Protection and Relaying
Protective relays are typically linked to the power system via CT and/or VT.
In normal operation and when the circuit breaker CB is closed, the contact closes
to energize the CB trip coil, which operates to open the breaker’s main contact and
energize the attached circuit.
The fault sequence of the event and disturbance recording indicate
• What happened?
• What did the current and voltage signals look like (CT saturation)?
• When did the protection device issue a trip signal?
• How long did the circuit breaker need to operate?
• What was the magnitude of the interrupted current?
• How did the system behave after the circuit breaker tripped?
i. Normally open contact (N/O): is open when the relay is not energized.
ii. Normally closed contact (N/C): is closed when the relay is not energized.
iii. Operating force or torque: that which tends to close the relay contacts.
iv. Restrain force or torque: opposes the operating force or torque and prevents
the relay contacts’ closure.
v. Pick-up: A relay is said to pick up when it moves from OFF to ON. The value
of the characteristic quantity above this change occurs, known as the pick-
up value.
Protective Relays 31
vi. Pick-up level: The value of the actuating quantity (current or voltage) on the
border above which the relay operates.
vii. Drop-out or reset level: The current or voltage value below which a relay
opens its contacts and returns to its original position.
viii. Operating time: The time that elapses between the instant when the actuat-
ing quantity exceeds the pick-up value and when the relay contacts close.
ix. Reset time is when the actuating quantity falls below the reset value to when
the touch of the relay returns to its normal location.
x. Primary relays are the relays connected directly in the circuit to be
protected.
xi. Secondary relays are connected in the circuit to be protected through CTs
and VTs.
xii. Auxiliary relays work to assist another relay in performing its role in
response to its operating circuit’s opening or closing. This relay may be
instantaneous or may have a time delay.
xiii. Reach: A distance relay operates whenever the relay impedance is less than
a prescribed value; this impedance or reactance corresponding distance is
known as the relay’s reach.
xiv. Instantaneous relay: One with no intentional time delay operates in <0.1
seconds.
xv. Blocking prevents the protective relay from tripping due to its characteris-
tics or an additional relay.
xvi. Time delay relay: One which is designed with a delaying means.
xvii. Protective relay: An electrical device designed to initiate isolation of a part
of an electrical installation or to operate an alarm signal in the event of an
abnormal condition or a fault.
xviii. Energizing quantity: The electrical quantity (current, voltage, phase shift, or
frequency), alone or in combination, is required for the relay’s functioning.
xix. Characteristics quantity: The quantity to which the relay is designed to
respond, e.g., current in overcurrent, phase angle in a directional relay, and
so forth.
xx. Setting: The actual value of the energizing or characteristics quantity at
which the relay is designed to operate under given conditions.
xxi. Flag or target: A device used for indicating the operational relay.
xxii. Overreach or underreach: Errors in relay measurements resulting in opera-
tion or failure, respectively.
xxiii. It reinforces relay, which is energized by the main relay’s contacts and its
contacts in parallel with those of the main relay.
xxiv. Pilot channel: A means of interconnection between relaying points for
protection.
xxv. Protective scheme: The coordinated arrangements for the protection of a
power system. It may include several protective systems.
TABLE 2.1
List of Device Numbers
Code Types Code Types
1 Master element 52 AC circuit breaker
2 Closing relay/time delay starting 53 DC generator/exciter relay
3 Interlocking relay or checking 54 High-speed DC circuit breaker
4 Master contactor 55 Power factor relay
5 Stopping device 56 Field application relay
6 Starting circuit breaker 59 Overvoltage relay
7 Anode circuit breaker 60 Current/voltage balance relay
8 Control power disconnecting device 61 Machine split phase current balance
9 Reversing device 62 Time delay stopping/opening relay
10 Unit sequence switch 63 Pressure switch
12 Overspeed device 64 Ground detector relay
13 Synchronous-speed device 65 Governor
14 Under-speed device 66 Starts per hour
15 Frequency and speed matching device 67 AC directional overcurrent relay
20 Elect. operated valve (solenoid valve) 68 Blocking relay
21 The distance relay 69 Permissive control device
23 Temperature control device 71 Level switch
25 Synchronism check device/ 72 DC circuit breaker
synchronizing
26 Apparatus thermal device 74 Alarm relay
27 Under-voltage relay 75 Position changing mechanism
29 Isolating contactor 76 DC overcurrent relay
30 Annunciator relay 78 Phase-angle measuring/out-of-step protective relay
32 Power directional relay 79 AC-reclosing relay
36 Polarizing voltage/polarity device 81 Frequency relay
37 Under-current or under-power relay 83 Automatic selective control/transfer relay
38 Bearing protective device 84 Operating mechanism
39 Mechanical conduction monitor 85 Carrier/pilot-wire receiver relay
40 Field relay 86 Lockout relay
41 Field circuit breaker 87 Differential protective relay
42 Running circuit breaker 89 Line switch
43 Manual transfer/selector device 90 Regulating device
46 Phase-balance/reverse-phase relay 91 Voltage directional relay
47 Phase-sequence voltage relay 92 Power and voltage directional relay
48 Incomplete-sequence relay 94 Trip-free relay/tripping
49 Transformer thermal relay 95 Reluctance torque synchro check
50 Instantaneous overcurrent 96 Autoloading relay
51 AC time overcurrent relay
Types of relays
Other: pressure,
Electromagnitic Solid state Computerized
temperature
Attracted Plunger
armature type
Wattmetric Induction
Shaded pole
type type
However, only attracted armature and induction forms have an important applica-
tion; more modern equivalents have replaced all other types. Electromagnetic relays
are constructed of electrical, magnetic, and mechanical parts, durable, inexpensive,
and effective, and have an operating coil and different contacts.
i. Wattmeter type.
ii. Induction type.
iii. Shaded pole.
Figure 2.2 shows a force distribution of the induction relay; the principle operation of
the electromagnetic induction relay is:
Torque
Ф1 Ф2
iФ2 F1 F2 iФ1
iФ1 iФ2
The two magnets of the induction-type relay produce two alternating magnetic
elds ϕ1 and ϕ 2
ϕ 2 = ϕ 2 m sin (ω t + θ ) (2.2)
dϕ 1
iϕ1 ∝ (2.3)
dt
dϕ 2
iϕ 2 ∝ (2.4)
dt
or
iϕ 2 ∝ ϕ 2m cos (ω t + θ ) (2.6)
Thus,
Solving to get
T = Fr ∝ F (2.10)
r
F
The characteristics of the induction principle are suitable for AC systems. The torque
does not differ with time: no vibration, DC offset inherent rejection, and low overreach.
Main
windings
Disc
carrying Moving contact
contacts To trip
circuit
Fixed contact
Closed
secondary
windings
Input
Plug
Tapping
bridge
Upper
magnetic
Disc
carrying
contacts
Lower
magnetic
Current
Magnetic
core
Voltage
Voltage
Cup-
carrying
contacts
Current
Fe = kI 2 = k ( I m sin ω t )
2
1
=
2
(
k I m2 − I m2 cos2ω t )
This shows that the electromagnetic force consists of two components: constant inde-
pendent of time and pulsation at double the frequency.
Hence the relay armature vibrates at a double frequency; this causes the relay to
hum and produce noise and damage to the relay contacts (unreliable operation). This
can be overcome by dividing the ux into two components acting simultaneously but
differing in the time phase so that the resultant Fe is always positive, and if this force
is always greater than the restraint force, then the armature will not vibrate.
The electromagnetic section is short-circuited by utilizing a copper ring or coil.
This creates a ux in the area in uenced by the short-circuited section (the so-called
shaded section), which lags the ux in the non-shaded section, see Figure 2.7.
Note that the main coils have taps; the number of turns is adjustable.
In the electromagnetic induction theory, the relay part has a non-magnetic rotor
(an aluminum or copper disk or cylinder) where coils produce magnetic uxes that
cause circulating currents. The interaction between the uxes and the circulating
currents creates torque. This is the theory of operation for induction motors.
The magnetic eld and the magnetic ux in the iron core are both sinusoidal
if the current is sinusoidal, and the iron core is believed to have a linear behavior.
Remember that the ux is split into two components: One ows through the normal
and shaded poles, and the other ow is equal in magnitude but different in angle.
These two uxes are identical.
Permanent
magnet Spring
Ф1 Ф2
Disk Main
coil Nr Taps
turns
Axis
K1 I 2 = K 2
so
K2
I= constant (2.15)
K1
Electromagnet
part
To trip
circuit
Trip
Armature contact
F (t ) ∝ ϕ 2 (2.16)
mmf N i
ϕ= = (2.17)
R R
where
lg
R= ∝ lg = reluctance (2.18)
µo ⋅ A
so
Ni
ϕ∝ (2.19)
lg
or
N 2 i2
ϕ2 ∝ (2.20)
lg2
Hence
F (t ) = kϕ ⋅ ϕ 2 (2.21)
where
kϕ is the constant
Coil
Fixed
contact
Moving Piston
contact
Spring
N 2 i2 N2
F (t ) = kϕ ⋅ 2
= k1i 2 , k1 = kϕ ⋅ 2 (2.22)
lg lg
Fn (t ) = F (t ) − k2 = k1i 2 − k 2 (2.23)
0 = k1i 2 − k2
K1 I 2 = K 2 ,
So that,
K2
I= constant (2.24)
K1
I = RMS value of i
The restraining tension of the spring or the solenoid circuit’s resistance may be
varied to control the value at which the relay begins to work, thus changing the
restricting power. Effectively, attraction relays have no time delay and are commonly
used when instantaneous operations are needed.
Example 2.1
Solution
i. For 3 A current:
10
I= = 4.08 A
0.6
FA = k1 I A (2.25)
FB = k2 I B (2.26)
I A k2
= = constant (2.27)
I B k1
Force has been overcome, which requires a current representing the calibration level
of the relay. Since the fault current level changes with generating conditions, obtain-
ing selectivity based on current magnitude is seldom possible. Most applications
require adding a timer function so that the relay nearest the fault location, having the
most current, will trip rst.
There are dif culties in obtaining selectivity in the relay of a single quantity
measuring element. Most high-speed relays measure a derived quantity, a combi-
nation of several simple quantities, such as impedance, admittance, the current
I
k 1V– k 2I k 1V+ k2I
ratio, and the like, in which two simple quantities are compared in magnitude and
phase relation.
The relay usually makes the comparison by turning the electrical quantities into
force, with MMF or EMF being proportional to the two quantities compared.
The phase relation and amplitude are a function of the system conditions; the
relay compares these two fundamental aspects. The principal part of the relay is the
comparator, which can be a phase or amplitude comparator.
V
Divide by I and substitute Z = = R + jX
I
k1 + k 2 ( R + jX ) = k 3 + k4 ( R + jX )
(k 2
2 ) ( ) ( )
− k42 R 2 + k 22 − k42 X 2 + 2 ( k1 k 2 − k3 k 4 ) R + k12 − k32 = 0 (2.29)
x 2 + y 2 + 2 gx + 2hy + c = 0
where
x = R, y = X
k1 k 2 − k3 k 4
g=
k 22 − k42
h=0
k12 − k32
c=
k22 − k42
• Advantage:
i. The low burden on CT and VT.
ii. Low mechanical inertia and bouncing.
iii. High-speed operation and long life.
iv. Low maintenance.
v. Quick reset action.
vi. Unconventional characteristics are possible.
vii. Low energy is required.
viii. Easy ampli cation.
ix. High sensitivity.
• Limitation:
i. Temperature-sensitive.
ii. Low short-term overload capacity.
iii. Aging effect on the relay characteristics.
iv. Vulnerability to voltage spike (use of lters and shielding to overcome
this limitation).
R1
R
Ii
Tr 2 C1
R2 D1
Tr1
D2
CT Rectifier
R3 D3
Vin C R5
R4
Example 2.2
i. R = 10 kΩ;
ii. R = 1 MΩ.
iii. Sketch the output Vo(t) versus time for cases (i) and (ii).
Solution
i. When R = 100 kΩ
+ +
Vi C Vo
_ _
+ +
Vi C Vo Solid-state relay
_ _
(
Vo = Vc 1 − e − t /τ )
−
tdelay
3 = 6 × 1 − e 1
tdelay = 0.693seconds.
ii. When R = 1 MΩ
τ = R ⋅ C = 1 × 10 6 × 10 × 10 −6 = 10 seconds.
(
Vo = Vc 1 − e − t /τ )
−
tdelay
3 = 6 × 1 − e 10
At R1=100k
At R2=1M
Vo (Volt)
CT
ADC DAC Alarm
Input
VT
Input ADC
Data
Microcomputer communication
system
Microcomputer – control
relay
FIGURE 2.16 Digital relays (numerical relays for protection, monitoring, and control).
digitized and re- ltered with a digital lter. Numerical operating quantities are then
calculated from the processed waveforms.
CT
Analog Analog to Digital
Magnitude
low digital cosine
and
pass conversion filter and
impedance
filter (A/D) phasor
VT
FIGURE 2.17 The signal path for voltage and current input signals to the microprocessor relays.
Protective Relays 49
Microprocessor
Operation
signalling
. Discrete
input
.
subsystem . Communication
. ports
Read Last
sample n
Digital
filtering
Phasor
calculation
Protection
Modify
method
Relay logic
No trip
Trip order
TABLE 2.2
Comparison between Electromagnetic Relay and Computer Relay
Computer Relay
Characteristics Electromagnetic Relay Digital Relay Numerical Relay
Function Mechanical operation Static Static
Mechanical vibration High vibration No vibration No vibration
Burden effect High Low Low
Time type Clock Count Count
Reset time High Low Low
Accuracy Depend on temperature Stable Stable
Programming No Yes Yes
Auxiliary supply Necessary Necessary Necessary
SCADA connection No Yes Yes
Response time Slow Fast Very fast
Size Large Small Compact
Operation reliability High High High
Indication of the fault By ag By light By light
Monitoring No Self Self
Setting range Limited Wide Wide
Internal resistance Small High High
Maintenance Frequent Low Very low
Events recording No Yes Yes
PROBLEMS
2.1. What are the advantage and limitations of static relays? Sketch the different
scheme connections for stator protection of a delta-connected generator.
2.2. What does the fault sequence of event and disturbance recording indicate?
2.3. Draw the signal path for voltage and current input signals to the micropro-
cessor relays.
2.4. An RC circuit used to produce time delay for a solid-state relay is shown in
Figure 2.20. For a step input voltage Vi(t) = 10 U(t), the output voltage Vo(t) = 6 V
and C = 12 μF. Determine the time delay (tdelay) for the following cases:
+ +
Vi C Vo
_ _
i. R = 100 kΩ;
ii. R = 1 MΩ.
iii. Sketch the output Vo(t) versus time for cases (i) and (ii).
2.5. An RC circuit used to produce time delay for a solid-state relay is shown
in Figure 2.21. For a step input voltage Vi(t) = 8 U(t), the output volt-
age Vo(t) = 4 V and C = 6 μF. Determine the time delay (tdelay) for the
following cases:
i. R = 1 kΩ;
ii. R = 10 kΩ.
iii. Sketch the output Vo(t) versus time for cases (i) and (ii).
+ +
Vi C Vo
_ _
2.6. Compare wattmeter type, induction type, and shaded pole relay.
2.7. What is the class of measuring relays?
2.8. What are the data required for the relay setting?
3 Protection Systems with
SCADA Technology
3.1 INTRODUCTION
The term “SCADA” means supervisory control and data acquisition, which is a
software that allows the supervision and control of industrial processes, including
manufacturing, production, power generation, fabrication, and re ning.
Through SCADA programs, a simple personal computer (PC) can become
a workstation to watch and control processes to communicate with the eld.
Programmable logic controllers (PLCs) and remote telemetry units (RTUs), also
known as intelligent devices, are essential components utilized in diverse industries
for process automation, machinery control, and system monitoring. Allowing for the
graphic representation of a plant, the supervision of its processes, modi cation of
certain parameters, elaboration of reports, emission of alarms, and other functions.
The processes can be controlled remotely or locally to make changes to the param-
eters of the process on-site (local way) or adjustments in a control room (remote way).
3.2 BACKGROUND
SCADA is a control system architecture that uses computers, networked data trans-
mission, and graphical user interfaces for high-level process supervisory management.
It utilizes additional auxiliary devices such as PLCs and discrete PID controllers
to connect to equipment or processing plants.
Each of these levels will be covered in depth in this chapter, along with how they
work, how SCADA has developed over the last 30 years, and how security needs and
regulatory compliance affect SCADA system operation.
The SCADA system was created as an all-encompassing way to provide standard
automation protocols access to various local control modules from various vendors.
Large SCADA systems now work quite similarly to distributed control systems in
reality. However, they use a variety of plant interfaces. They can manage large-scale
operations that may span several locations and long distances.
Our vital infrastructure is under the supervision and control of SCADA systems.
The United States has 15 essential infrastructures. Included in this list are the fol-
lowing: (i) energy; (ii) waste and water systems; (iii) telecommunications; (iv) trans-
portation; (v) chemical; (vi) dams; (vii) emergency services; (viii) nancial services;
(ix) commercial facilities; (x) government facilities; (xi) critical manufacturing; (xii)
defense; (xiii) food and agriculture; (xiv) healthcare and public health; and (xv) infor-
mation technology (IT).
These vital infrastructures rely on one another. For instance, the energy sector
would be signi cantly impacted by an assault on the telecom industry.
DOI: 10.1201/9781003394389-3 53
54 Power System Protection and Relaying
SCADA systems provide utilities in the electric power sector with useful informa-
tion and capabilities to distribute electricity dependably and securely. A utility’s most
important and expensive distribution, transmission, and generating assets must be
operated effectively, which depends on an ef cient SCADA system.
Modern SCADA systems have incorporated new communication and network
technologies to make the power grid smart and interactive. They are widely used
to monitor and manage real-time electric power networks, especially those dealing
with generation, transmission, and distribution. In the United States, electric power
systems have been using SCADA systems for more than 50 years.
3.2.2 APPLICATIONS
SCADA is utilized to produce petrochemicals, food, oil and gas, water, waste, and
manufactured goods. In electrical power systems, it is commonly employed. The
most important and expensive utility distribution, transmission, and generating
assets must operate effectively; this is where SCADA solutions come into play. Power
system components, including power plants, transmission facilities, and substations,
are monitored and controlled remotely via SCADA systems. Power-producing facili-
ties experience automation before transmission and distribution.
Network connectivity analysis, state estimation, load ow application, voltage VAR
control, load shed application, fault management, system restoration, loss minimization
Protection Systems with SCADA Technology 55
through feeder recon guration, load balancing through feeder recon guration, opera-
tion monitoring, and distribution load forecasting are the main applications of SCADA
in power systems. This text will carefully examine two of these applications.
The monitoring and management of multiple remote stations pose signi cant
challenges in electric power distribution systems. In addition to maintaining the
proper voltages, currents, and power factors, they provide capabilities like real-time
visibility into the processes. They employ RTU to automatically monitor, safeguard,
and regulate a variety of equipment in distribution systems.
Substation control: Substations are essential for sustaining the ow of electricity
and managing load. The SCADA system continually assesses the condition of dif-
ferent substation components and then sends them the appropriate control signals.
It carries out tasks including bus voltage regulation, bus load balancing, circulating
current regulation, and overload regulation.
3.2.3 CHALLENGES
Due to multiple vulnerabilities in the communications network, securing SCADA
systems in a power utility context is dif cult. To save money and advance technol-
ogy, bigger SCADA systems are linked to other networks such as the Internet. Due to
its interconnectedness, SCADA systems in the power grid are susceptible to various
communication security challenges, including new types of threats and cyberattacks,
including man-in-the-middle, denial-of-service, social engineering, and insider
assaults. The attackers’ objective is to undermine network security elements, includ-
ing availability, authentication, con dentiality, or integrity.
The communication link between the SCADA server and RTU is the most prob-
able target for an attack. Security devices for encryption and decryption of informa-
tion exchange should be implemented at two locations to combat this hack.
Additionally, access permission is needed between the master systems and RTUs.
In addition to password authorization, smart cards, rewalls, and intrusion detection
systems are additional security measures. Vendors should include built-in security
safeguards in their systems to address security issues.
SCADA system installation is costly and time-consuming in addition to providing
security. Costs go up when SCADA software is updated and staff members training
to utilize the new program. A system may have components from many vendors that
communicate via various proprietary protocols.
i. Field instrumentation,
ii. PLCs and/or RTUs,
iii. Communications networks, and
iv. SCADA Host software.
56 Power System Protection and Relaying
Laptops
Servers
have gradually, over time, been supplied with feedback sensors, such as limit switches,
allowing communication for these wired devices into a local PLC or RTU, delivering
data relay to the SCADA Host program.
The capacity to design, install, and maintain equipment today demands greater
technical knowledge than in the past, but this is offset by the lower cost of automating
operations and workers’ better technical skill levels. Most eld equipment, including
valves, is now equipped with actuators so that a PLC or RTU can control the device
instead of manually operating it. With this feature, the control system can respond
more rapidly to unexpected occurrences and shut down or optimize production.
To guarantee that an electrical device has no unfavorable impacts on its surround-
ings or other electrical devices, instrumentation must also adhere to any EMC (elec-
tromagnetic compatibility) regulations that may be in place.
In the past 10–15 years, many customers have converted to radio or satellite com-
munications to save expenses and eliminate troublesome cabling dif culties. Twenty
years ago, the communication network would have been leased lines or dial-up
modems, which were highly costly to construct and operate. Cellular communica-
tions and upgraded radio equipment that offer faster transmission rates and better
diagnostics are among the newer communication kinds that have become accessible.
For contemporary, dispersed SCADA systems, the fact that these communication
mediums are still prone to malfunction is a signi cant problem.
The protocols changed at the same time as the communication medium. PLCs and
RTUs exchange data via protocols, which are electronic languages, either with other
PLCs and RTUs or SCADA Host systems. Protocols have often been exclusive and
the work of a particular company. As a further step, several manufacturers tended to
stick with a single standard, MODBUS, but added proprietary components to satisfy
certain functionality needs.
In recent years, true non-proprietary protocols such as DNP have emerged (dis-
tributed network protocol). These protocols were developed independently of any one
manufacturer and have become more of an industry standard thanks to the partici-
pation of several people and businesses in their creation. These procedures haven’t
advanced suf ciently yet, to be widely applicable to the application procedure and
regulatory requirements (Figure 3.2).
Laptops
Servers
Host software development. Additionally, it implies that IT, which has historically
been kept apart from SCADA systems, is now actively engaged in maintaining net-
works, database interfaces, and user access to data.
Many of the rst SCADA Host products weren’t equipped with the telemetry com-
munication characteristics needed by SCADA systems for geographically dispersed
assets since they were created particularly for the industrial setting, where a SCADA
system was housed in a single building or complex (Figure 3.3).
These rst-generation SCADA Hosts sometimes require a hybrid PLC or RTU,
often a front-end driver (FED) or front-end processor, to manage connections with
remote devices (FEP). This had several problems since it cluttered communications
and the need for specialist programming that couldn’t be done on the SCADA Host
platform. Several FED or FEP devices were utilized to alleviate part of this, but due
to their specialized nature, their development and upkeep came with extra costs.
Since contemporary SCADA software already provides telemetry features, these
hybrid PLCs are no longer required for communications. They now use software pro-
grams called “drivers” integrated into the SCADA Host. Software drivers comprise
the many protocols to connect to remote devices such as RTUs and PLCs.
As technology developed, software platforms for SCADA Host bene ted from a
wide range of new functionalities. These included developing integrated databases
that could handle hundreds of changes per second for extremely large systems and
were speci cally designed with SCADA Host software requirements in mind.
Third-party
database Remote client
ACCESS
Client
Include: Communication
SCADA host platform drivers, real-time database,
alarm and event journal,
historic archive, and
configuration database
The SCADA Host program cannot offer data access to external databases without
these criteria. Remote client access to the SCADA Host is another technology that
has allowed users to operate and keep an eye on SCADA systems, whether on the go
or in other locations.
The SCADA Host systems are under pressure to be operationally safe from the oil and
gas industry. The 49 CFR 195.446 Control Room Administration guidelines analyze the
SCADA Host software’s operations, maintenance, and management. The degree of inte-
gration, use of open standards, and architecture of the SCADA system are also covered.
3.6 SECURITY
In recent years, security for SCADA systems has become a signi cant and con-
tentious issue. In the past, SCADA systems were solitary objects that belonged to
operators, engineers, and technicians. As a result, platforms for SCADA Hosts
were not always designed with secure connectivity to public networks. As a result,
many SCADA Host systems were vulnerable to assault since they could not defend
themselves.
Security has been a problem with distant assets communicating back to a SCADA
Host for many years due to various recorded assaults on SCADA systems. However,
an open standard has only recently made possible a safe encrypted and authenticated
data transmission between distant assets and a SCADA Host platform.
Security solutions for SCADA Host and remote asset communications have very
distinct needs. Security must be regarded holistically and in terms of the SCADA
system. One wouldn’t need to use the SCADA system to interrupt production, for
instance, if one decided to do so. A trespasser might readily threaten a gas well head
site or a monitoring station on a gas pipeline if they are located in a rural area. Other
options that may or might not be included in the SCADA system would have to be
considered if the asset is very signi cant, such as security camera monitoring.
The majority of unauthorized accesses to a SCADA system occur via the SCADA
Host or PCs that connect to the system for maintenance or diagnostics, not from or
at the distant assets themselves. For example, the recent Stuxnet virus assault was
carried out by inserting a thumb drive into a computer that was used to access a
SCADA system.
62 Power System Protection and Relaying
Many standards exist that outline how to protect a SCADA system, not only in
terms of the technology used but also in practices and processes. This is crucial since
the security solution for SCADA is a combination of behaviors and processes with
technology solutions rather than a single technological panacea. These practices and
procedures would include training materials, access to SCADA Hosts, and steps to
take if SCADA security has been hacked. IT departments should be involved in
building up processes and procedures and adopting technologies in contemporary
SCADA systems since they are essential to developing and maintaining SCADA
security for an organization.
Table 3.1 lists all the devices used in the power system/SCADA networks. The essen-
tial elements of protection technology are described brie y in Table 3.2.
Before using the SCADA system for the rst time, you must make a one-time
hardware connection for mutual communication. In some cases, the various devices
are connected via different interfaces to the PC. Refer to the subsequent overview
to nd out how individual devices should be linked to the PC. The con guration for
each type of connection is described in the corresponding discussion of this section.
Table 3.3 shows a multi-function relay. Table 3.4 shows an analog/digital multimeter.
The currents and voltages used with this instrument are to be transformed by a
factor of 1:1000. In other words, 1 V in the model corresponds to 1 kV in real energy
TABLE 3.1
Lucas-Nülle GmbH Power System/SCADA Networks Devices
Device Designation
Adjustable three-phase power supply (0–400 V/2
A, 72 p.u.)
(Continued)
64 Power System Protection and Relaying
Current transformer
Voltage transformer
(Continued)
Protection Systems with SCADA Technology 65
Resistive load
(Continued)
66 Power System Protection and Relaying
(Continued)
Protection Systems with SCADA Technology 67
(Continued)
68 Power System Protection and Relaying
TABLE 3.2
Lucas-Nülle GmbH Protection Technology Elements
Multi-function relay, power controller, power factor
controller, synchronization unit
(Continued)
Protection Systems with SCADA Technology 69
(Continued)
70 Power System Protection and Relaying
TABLE 3.3
Lucas-Nülle GmbH Multi-Function Relay
Multi-function relay, power controller,
cos(φ) controller, synchronization unit
(Continued)
Protection Systems with SCADA Technology 71
(Continued)
72 Power System Protection and Relaying
(Continued)
Protection Systems with SCADA Technology 73
Transformer/generator differential
protection relay
74 Power System Protection and Relaying
TABLE 3.4
Lucas-Nülle GmbH Analog/Digital Multimeter
Analog/digital multimeter, power/power
factor meter, software
DOI: 10.1201/9781003394389-4 75
76 Power System Protection and Relaying
The protective relaying system, intended to sense the fault and initiate selective
switching, bases its operation upon the fault current’s magnitude and directions.
The magnitude of bus voltages during short circuits determines the transient gen-
erator power outputs and the “transient stability.”
Fault studies form an important part of power-system analysis. The problem con-
sists of determining bus voltages and line currents during various faults. The three-
phase balanced fault information is used to select and set phase relays, while the
line-to-ground fault is used for ground relays. Fault studies are also used to obtain
the rating of the protective switchgear.
For fault studies, generator behavior can be divided into three periods:
1. The subtransient period lasts only for the rst few cycles.
2. The transient period covers a relatively long time.
3. The steady-state period.
Before about 1950, matrices were used only as research tools. They systematized the
arrangement of materials and generally forced the research worker to be organized.
Matrices reduced the computational effort; however, the absence of high-speed com-
puters limited investigations to small sets of equations involving only very small
matrices. The rst generation of small-scale computers extended the use of matrices
in solving network problems of limited size.
Note that three fault types involve line-to-ground (Earth fault). Most of these result
from insulator ashovers for weather conditions and insulation quality. The balanced
three-phase fault is the rarest in occurrence, accounting for above 5% of the total
faults, and it is the least complex of all types of short-circuit studies as far as the
calculations are concerned.
The types of faults commonly occurring in practice are illustrated in Figure 4.1,
and the most common of these is the short circuit of a single conductor to earth.
Often the path to earth contains resistance in the form of an arc, as shown in
Figure 4.1f.
Although the single line-to-ground fault is the most common, calculations are
frequently performed with the three-line, balanced short circuit (Figure 4.1d and e).
This is the most severe fault and the most interesting calculation.
As well as fault current, fault MVA is frequently considered; this is obtained from
{ }
the expression 3 VL I F × 10 −6 where VL is the nominal line voltage of the faulted
78 Power System Protection and Relaying
(A) (B)
(C) (D)
(E) (F)
Rf
FIGURE 4.1 Common types of faults. (a) Single line-to-ground fault. (b) Line-to-line
faults. (c) Double line-to-ground faults. (d) Three phase to ground fault. (e) Three phase fault.
(f) Fault through resistor.
part before the fault. The MVA is often referred to as the fault level. The calculation
of fault currents can be divided into the following two main types:
1. Faults short-circuiting all three phases when the network remains balanced
electrically. Normal single-phase equivalent circuits may be used as in ordi-
nary load- ow calculations for these calculations.
2. Faults other than three-phase short circuits when the network is electrically
unbalanced.
The main objects of fault analysis may be enumerated as follows:
i. To determine the maximum and minimum three-phase short-circuit
currents.
ii. To determine the unsymmetrical fault current for single and double line-
to-ground, line-to-line, and open-circuit faults.
iii. To investigate the operation of protective relays.
iv. To determine rated rupturing capacity of breakers.
v. To determine fault-current distribution and busbar–voltage levels during
faults.
Xf X kd
X ad
Ignoring winding resistance, the equivalent reactance of Figure 4.2, known as the
direct axis subtransient reactance, is:
−1
1 1 1
X d′′ = X l + + + (4.1)
ad
X X f X kd
If the damper winding resistance Rk is inserted in Figure 4.2, and Thevenin’s induc-
tance seen at the terminals of Rk is obtained, the circuit time constant, known as the
direct axis short-circuit subtransient time constant, becomes:
−1
1 1 1
X kd + + +
X l X f X ad
τ d′′ = (4.2)
Rk
For two-pole, turbo-alternator (X d′′ = 0.07 − 0.12p.u.) and for the water-wheel alter-
nator (X d′′ = 0.1 − 0.35 p.u.).
where X d′′ is only used in calculations if the effect of the initial current is impor-
tant, as, for example, when determining the circuit breaker short-circuit rating.
τ d′′ is very small, around 0.035 seconds, because the damper circuit has relatively
high resistance. Thus, this component of the current decays quickly. It is then per-
missible to ignore the reactance of the damper circuit X kd , and the equivalent circuit
reduces to Figure 4.3.
Ignoring winding resistance, the equivalent reactance of Figure 4.3, known as the
direct axis short-circuit transient reactance, is:
−1
1 1
X d′ = X l + + (4.3)
X ad X f
Xl
Xad Xf
If the eld winding resistance R f is inserted in Figure 4.3, and Thevenin’s inductance
seen at the terminals of R f is obtained, the circuit time constant, known as the direct
axis short-circuit transient time constant, becomes:
−1
1 1
Xf + +
X l X ad
τ d′ = (4.4)
Rf
where X d′ may lie between 0.1 and 0.25 p.u, and τ d′ is usually in the order of (1–2)
seconds.
The eld time constant, which characterizes the decay of transient with the arma-
ture open-circuited, is called the direct axis open-circuit transient time constant.
This is given by
Xf
τ do
′ = (4.5)
Rf
X d′
τ d′ = τ do
′ (4.6)
Xd
Finally, when the disturbance is over, there will be no hunting of the rotor. Hence,
there will not be any transformer action between the stator and the rotor, and the
circuit reduces to Figure 4.4.
The equivalent reactance becomes the direct axis synchronous reactance:
X d = X l + X ad is the same X d which is obtained in a steady-state condition.
Similar equivalent circuits are obtained for reactances along the quadrature
axis. These reactances are X q′′, X q′ , and X q . These reactances may be considered for
cases when the circuit resistance results in a power factor appreciably above zero.
The armature reaction is not necessarily totally on the direct axis, except that the
machine’s equivalent circuits are represented only by the direct axis’s reactances.
The manufacturers provide synchronous machine reactances and time constants.
A short-circuit test can obtain these values.
Xl
Xad
The angle α is the phase of the voltage wave at which the switch is closed
At t = 0 +, the instantaneous voltage equation for the circuit:
di(t )
Ri(t ) + L = Vm sin (ω t + α ) (4.8)
dt
where
Vm L
Im = ; τ = ; θ = tan −1 ω L /R;
Z R
Z = R 2 + (ω L )2 = R 2 + X 2
The fault current {i ( t )} in Equation 4.9, called the asymmetrical fault current, con-
sists of two components:
1. The rst term is the ac fault current (also called symmetrical or steady-state
fault current), which is a sinusoid and given by:
R L t=0
i(t)
V(t)=
Vm sin(ωt+α)
At (t = 0), iac (t ) and idc (t ) are equal and opposite to satisfy the condition for zero initial
currents.
The magnitude of the dc component, which depends on α (i.e., depends on the
instant of application of the voltage to the circuit), varies from 0 when α = θ to I max
when α = (θ ± π/2 ) radians.
Note that a short circuit may occur at any instant during a cycle of the ac source;
that is, α can have any value. Since we are primarily interested in the largest fault
current, we choose α = (θ − π/2 ).
Then i ( t ) becomes:
i1
–i2
i=i1-i2
(a)
i1
–i2
i=i1-i2
(b)
FIGURE 4.6 Current waveform. (a) With no dc offset. (b) With maximum dc offset.
84 Power System Protection and Relaying
a
b
c
FIGURE 4.7 Steady-state current and transient current terms combine to form the resultant
current.
A detailed study of Equation 4.9 will show the conditions which make for the
maximum possible i ( t ). The maximum of dc offset current is usually assumed to
be the result of those conditions that make sin (α − θ ) = 1 or sin (α − θ ) = −1. See
Figure 4.7, which shows that i ( t ), iac (t ) , and idc ( t ) when L > R, θ = 85°, sin (α − θ ) = −1,
α = 355° , at t = 0, e ≈ 0.
If
| I‡|
Sub-transient
current
| I›| Transient
current Steady state
current
|I|
time
‡
Td
‹
Td
FIGURE 4.8 Fault current in one phase shows the subtransient, transient, and steady-state
currents.
|I‡|
|I›|
i(t)
|I|
time
‡
Td
‹
Td
Referring to Figure 4.9, the amplitude of the varying ac fault current (r.m.s) as a
function of time is given by:
E E − t / τ d′′ E E − t / τ d′ E
I ac (t ) = − e + − e + (4.13)
X d′′ X d′ X d′ X d Xd
1 t
1 − τ d′′ 1
t
1 − τ d′ 1
iac (t ) = 2 E − e + − e + × sin (ω t + α − θ ) (4.14)
X d′′ X d′ X d′ X d X d
where E is the r.m.s line-to-neutral pre-fault terminal voltage of the unloaded syn-
chronous machine, an armature resistance is neglected in Equation 4.14. Note that at
t = 0, when the fault occurs, the r.m.s value of iac ( t ) in Equation 4.14 is:
E
I ac (0) = = I d′′ (4.15)
X d′′
which is called the r.m.s subtransient fault current, I d′′ . The duration of I d′′ is deter-
mined by the time constant τ d′′ .
At a later time, when t is large compared to τ d′′ but small compared to the τ d′ , the
rst exponential term in Equation 4.14 has decayed almost to zero, but the second
exponential has not decayed signi cantly. The r.m.s ac fault current then equals the
r.m.s transient fault current, given by:
E
I d′ = (4.16)
X d′
When t is much larger than τ d′ , the r.m.s ac fault current approaches its steady-state
value, given by:
E
I ac (∞) = = Id (4.17)
Xd
In addition to the ac fault current, each phase has a different dc offset. As in the R-L
circuit, the dc offset depends on the instantaneous value of the voltage applied (i.e.,
angle α ).
The time constant associated with the decay of the dc component of the stator cur-
rent is known as the armature short-circuit time constant (τ a). Most of the decay of
the dc component occurs during the subtransient period. For this reason, the average
value of the direct axis and quadrature axis subtransient reactance is used for nding
τ a. It is given by:
X d′′ + X q′′
τa = (4.18)
2ω Ra
Faults Analysis 87
E −t /τ a
I dc ( t ) = 2 e sin (α − θ ) (4.20)
X d′′
1 t
1 − τ d′′ 1
t
1 − τ d′ 1
iasy (t ) = 2 E − e + − e +
X d′′ X d′ X d′ X d X d
t
E −τ a
× sin (ω t + α − θ ) − 2 e sin (α − θ ) (4.24)
X d′′
In Equation 4.24, the degree of asymmetry depends upon the point of the voltage
cycle at which the fault occurs, and if ω L R, then θ ≅ π/2.
The r.m.s value of iasy ( t ) is of interest. Since iasy ( t ) in Equation (4.31) is not strictly
periodic. Its r.m.s value is not strictly de ned. However, treating the exponential
term (dc component) as a constant, we stretch the r.m.s concept to calculate the r.m.s
asymmetrical fault current with maximum dc offset, as follows:
2 2
E E
( I d′′)2 + ( )
2
I asy(max) (0) = + 2 = 2 I d′′
X d′′ X d′′
In practice, the momentary duty of a circuit breaker (CB) is given in terms of the
asymmetrical short-circuit current, that is, mean:
The factor is normally taken as 1.6 instead of 3 in assessing the momentary current
for the CB above 5 kV. This factor was reduced for voltage under 5 kV.
The momentary duty is not to be confused with the interrupting capacity of
the CB.
To calculate the interrupting capacity of the CB, the subtransient currents are
used. The calculation depends on the CB’s speed, the ratio of X to R in the circuit, the
distance between the fault and the generating station, and so forth. If X/R is small,
the dc component will decay quickly; therefore, a smaller multiplying factor must be
used. Of course, the faster the breaker, the higher the multiplying factor.
Typical values of multiplying factor for CBs of different speeds are as provided
subsequently.
Example 4.1
A bolted short circuit occurs in the series R-L circuit, with V = 18 kV, X = 10 Ω,
R = 0.5 Ω, and dc offset. The CB opens three cycles after fault inception. Determine:
Solution
Vm V
1. I ac(max) = , and I ac( rms) = rms
Z Z
20 × 10 3 18 × 10 3
∴ I ac( rms) = = = 1.797 kA
(8)2 + (0.8)2 10.0124
Faults Analysis 89
Vrms
= 1 + 2e −2t / τ = I ac( rms) 1 + 2e −2t / τ
Z
L X X 10 20
τ= = = = =
R ω R 2πfR 2πf (0.5) 2πf
τ
t=
f
0.75
∴ t=
f
t 0.75/f
= = 0.75π
τ 1/ ( π ⋅ f )
Therefore,
Example 4.2
Solution
1. The no-load voltage before the fault occurs E = 1.06 p.u. The subtransient
fault current that occurs in each of the three phases is:
E 1.06
I d′′ = = = 4.24 p.u.
X d′′ 0.25
90 Power System Protection and Relaying
Srated 600
I base = = = 19.245 kA
3 Vrated ( 3 )(18)
∴ I d′′ in p.u. = ( 4.24 )(19.245 ) = 81.6 kA
t
−
I dc(max) ( t ) = 2 (81.6) e 0.23 = 115.4 e − t / 0.23 kA
τ 3 cycle
t= = = 0.05seconds.
f 60
1 1 − 0.025 1
0.05
1 −
0.05
1
I ac ( 0.05) = 1.06 − e + − e 2.1 +
0.25 0.34 0.34 1.2 1.2
= 3.217 p.u.
= (3.217)(19.245) = 61.91kA
0.05
−
I dc ( 0.05) = 2 I d′′ e −0.05 / τ a = 2 (81.6 ) e 0.23 = 92.852 kA
= (61.91) 2 + (92.852)2
= 111.6 kA
E ′′ = V + jX d′′I L (4.28)
E ′ = V + jX d′ I L (4.29)
E = V + jX d I L (4.30)
Faults Analysis 91
” ’
X d ,X d ,X d
E”,E’,E G Load
(a)
j X d IL
E
E”
E’ ‘
j X d IL
”
j X d IL
V
(b)
FIGURE 4.10 One-phase diagram showing the subtransient, transient, and steady-state cur-
rents. (a) Circuit diagram. (b) Phasor diagram.
Va2
Vc1 Va1
Vao
Vb2
Vbo
Vco
V b1 Vc2
FIGURE 4.11 Three sets of balanced phasors are the symmetrical components of three
unbalanced phasors.
The de ning equations for the symmetrical components, where Va, Vb, and Vc are
the original unbalanced phasors, are:
Va = Va1 + Va 2 + Va 0
Vb = Vb1 + Vb 2 + Vb 0 (4.31)
Vc = Vc1 + Vc 2 + Vc 0
Vc 2 = a 2 Va 2 , 1 + a + a 2 = 0
Vc1 = a Va1 , Vc 0 = Vb 0 = Va 0
Therefore, it can use previous relations to nal Va, Vb, and Vc;
Va = Va1 + Va 2 + Va 0
Vb = a 2 Va1 + a Va 2 + Va 0 (4.32)
Vc = a Va1 + a 2 Va 2 + Va 0
V ao
Va V a2
V c2 V c1
V co V a1
Vc
Vb
V b1
V bo
V b2
Va 1 1 1 Va 0
Vb = 1 a2 a Va1 (4.33)
Vc 1 a a2 Va 2
And these transformations can do it for currents, too, as
Ia 1 1 1 I a0
Ib = 1 a2 a I a1 (4.34)
Ic 1 a a2 I a2
where [Z abc] is a matrix of dimension (3 × 3) that gives self- and mutual impedance in
phases and between them.
The important Equation 4.38 found that [Z abc] is not diagonal but somewhat sym-
metrical, while [Z 012] is diagonal; these make the analysis very easy.
All of the high-voltage magnitudes lead to low voltages by (30°), and from many
tries, it can say that “for each star delta, delta star named the phasors as make positive
sequence magnitudes in high voltage side lead more than positive sequence mag-
nitudes in low voltage side by (30°) and vice versa according to negative sequence
magnitudes.”
a Ia
In +
Ea
Zn
-
Eb
Ec
b Ib
c
Ic
Va1 = Ea – I a1 Z1 (4.42)
Va 2 = – I a 2 Z 2 (4.43)
a Ia1
Z1
+
Ea
-
Eb
Z1 Ec Z1
b Ib 1
c
Ic1
a Ia 1
Z1
V a1
+
Ea
-
FIGURE 4.16 The path for phase current of positive sequence in the generator (a) and the
corresponding sequence networks (b).
Z 0 = 3 Z n + Z g0 (4.44)
98 Power System Protection and Relaying
a Ia 2
Z2
Z2 Z2
b Ib 2
c
Ic2
a Ia 2
V a2
Z2
FIGURE 4.17 The path for phase current of the negative sequence in the generator (a) and
the corresponding sequence networks (b).
The equations for the components of voltage drop from point (a) of phase (a) to the
reference but (or ground) are, as may be deduced from Figure 4.18b,
Va 0 = – I a 0 Z 0 (4.45)
a Ia0
Z0
In
3 Zn
Z0 Z0
b I b0
c
Ic0
a Ia0
Z2
V a0
3 Zn
FIGURE 4.18 The path for phase current of zero sequence in the generator (a) and the cor-
responding sequence networks (b).
1. Make a detailed diagram for the circuit and determine all phases connected
to the fault position, as shown in Figure 4.19.
2. Write down all circumstances of fault dealing with phase current and phase
voltage.
3. Transform magnitudes of phase current and phase voltage (a-b-c) that are
determined in item (2) above to sequence components (0 1 2) by using [A] or
[A]−1.
4. Determine the connection of sequence network terminals (N, F) using the
information of sequence currents determined in item (2).
5. Determine the connection of recent sequence components terminals of the
network and all impedances concerning the fault using items (3, 4).
Va 0 0 Z0 0 0 I a0
Va1 = Ea − 0 Z1 0 I a1 (4.46)
Va 2
0
0 0 Z2 Ia2
100 Power System Protection and Relaying
Za Zb Zc
+ + +
Va Vb Vc
_ _ _
Ia Ib Ic
Ib = Ic = 0 (4.47)
Single line-to-ground
Vag = Z f I a (4.48)
As
Va = Z f I a (4.49)
Faults Analysis 101
Zf
+ + +
Va Vb Vc
Ib =0 Ic =0
_ _ _
Ia=If
Therefore,
Va = 3 Z f I a1 (4.50)
Va 0 + Va1 + Va 2 = 3 Z f I a1 (4.51)
Then from Figure 4.21, the sequence components of the fault current are:
Vf
I a 0 = I a1 = I a 2 = (4.52)
Z 0 + Z1 + Z 2 + ( 3 Z f )
Ia = 0 (4.53)
Ic = – I b (4.54)
a Ia 1
Z1
V a1
+
Ea1
-
Ia 2
Z2
V a2
Ia0
Z0
V a0
3 Zn
Ib Ic
+ + +
Va Vb Vc Zf
_ _ _
Ia=0
and
I a 0 = 0, I a 2 = − I a1 (4.57)
Z f I a1 = Va1 – Va 2 (4.58)
Ia = 0 (4.59)
line-to-line fault
I a1 = − I a 2 (4.60)
Va1 – Va 2 = Z f I a1 (4.61)
104 Power System Protection and Relaying
Zf
Ia1
Z1 Z2
V a1 V a2
+
Ea1
Ia2
-
Vf
I a1 = (4.62)
( Z1 + Z2 + Z f )
Ia0 = 0 (4.63)
Ia = 0 (4.64)
Vbg = Z f ( I b + I c ) (4.66)
I a 0 + I a1 + I a 2 = 0 (4.67)
Va 0 – Va1 = ( 3 Z f ) I a 0 (4.68)
Va1 = Va 2 (4.69)
I a 0 + I a1 + I a 2 = 0 (4.70)
Faults Analysis 105
Ib Ic
Zf Zf
+ + +
Va Vb Vc
_ _ _
Zg
Ia=0
The domain is satis ed from fault conditions in sequence by connecting the zero,
positive, and negative-sequence networks in parallel at the fault terminal; addition-
ally, (3Zf) is included in the zero-sequence network series. This connection is shown
in Figure 4.25 from this gure; the positive-sequence fault current is
Vf
I a1 = (4.73)
Z2 ( Z 0 + 3Z f )
Z1 +
Z 2 + Z 0 + 3Z f
Using the current division in Figure 4.25, the negative and zero-sequence fault
currents are
Z0 + 3Z f
I a 2 = ( − I a1 ) (4.74)
Z 0 + 3Z f + Z 2
Z2
I a 0 = ( − I a1 ) (4.75)
Z 0 + 3Z f + Z 2
106 Power System Protection and Relaying
3 Zn
Ia1
Z1 Z2 Z0
V a1 V a2 V a0
+
Ea1
Ia2 Ia0
-
• Recursion fault: It occurs due to the contact between the conductors and
comes back to normal operation and may contact conductors, and hence,
these cases may occur due to heavy wind.
• Not recursion fault: It occurs due to contact between the conductors, then to
return to normal operation and remove the contact.
Thus, the rst part of this presentation will deal with the balanced and unbalanced
fault calculation in general and conventional methods for small systems. The second
part will deal with a large system using a digital approach.
Let (Vr) be the reference phase voltage for the faulted part of the system,
3Vr2
VA 3 ph(base) = 3Vr ⋅ I r = (4.78)
Zr
t
an
(4.79)
Ean
3Vr 3 Ean
( Fault VA ) = Zt
(4.81)
108 Power System Protection and Relaying
Ean
3Vr Ean V ( Ean ) p.u.
(Fault VA) p.u = = r = (4.82)
3Vr2 Zt ( Zt ) p.u.
Z Zt Z
r r
then
( Fault VA ) p.u. = Z1 t
(4.83)
Example 4.3
Draw the positive, negative, and zero sequences for the power system shown in
Figure 4.26 (Figures 4.27–4.29)
Solution
2 4
3
1 10
5
6
11 7
9
8
1 2 10
4
0.2 0.3 0.4 0.08 0.15
0.06
3
0.45 0.6
0.15
5 0.7
0.43 6
11
0.25 0.1
0.35 0.48
7 8 9
1 2 10
4
0.2 0.3 0.4 0.08 0.15
0.06
3
0.45 0.6
0.15
5 0.7
0.43 6
11
0.25 0.1
0.35 0.48
7 8 9
1 2 10
∞ 4
0.06 0.06 0.8 0.08 0.19
3
1.1
5
0.8 6
11
0.08 ∞
0.7 0.9
0.34
7 8 9
Fault
Transmission
line
Generator Circuit
breaker
expeditiously at the speci ed supply voltage. The current should be switched off as
soon as the desired readings have been obtained (Figure 4.30).
I a = 1.1
FIGURE 4.31 Lucas-Nülle GmbH test circuit for determining zero-sequence impedance
emulator at PVAMU.
Faults Analysis 111
I n = I a /3 = 1.1/3 = 0.36
Z 0 = V0 I 0 = 100/0.36 = 272 Ω.
R0 = P0 I 02 = 13/0.362 = 100 Ω,
So Z 0 = Z m + 3 ⋅ Z E
Voltage L1 − L2 ( at linestart ) = 0 V
Current L1 = 1.1 A
FIGURE 4.32 Lucas-Nülle GmbH test circuit for measurements in the event of a three-pole
short-circuit emulator at PVAMU.
The power measurement reveals that the reactive power component predominates in
the event of a short circuit. This is easily understandable because any existent load
resistances are bridged during the short circuit, and a high-voltage line’s reactance is
always much higher than its active resistance.
When the connection to the neutral conductor is removed, and because a sym-
metric short circuit is involved, the measured values do not change. In the case of a
three-pole short circuit, the return conductor remains de-energized (except for minor
asymmetries attributable to the components).
FIGURE 4.33 Lucas-Nülle GmbH test circuit for measurements in the event of a single-pole
short-circuit emulator at PVAMU.
FIGURE 4.34 Lucas-Nülle GmbH test circuit for measurement in the event of a two-pole
short-circuit emulator at PVAMU.
114 Power System Protection and Relaying
Raise the line-to-line voltage at the start of the line to 110 V, then measure the
parameters listed subsequently.
Compare the measurement results with the calculated values (ascertained using the
method of symmetric components):
Relationship for the short-circuit current:
I sctwo-pole = j ⋅ 3 ⋅ E ′′ ⋅Z g ( Zm ⋅ Z g + Z m ⋅ Z0 + Z 0 ⋅ Z g ) .
The impedances Z m , Z g , and Z 0 calculated previously result in the following denomi-
nator for the fraction discussed earlier:
N = ( Z m ⋅ Z g + Z m ⋅ Z 0 + Z 0 ⋅ Z g ) = ( −60,977 + j 14,807) Ω2 .
Accordingly, the value of the two-pole short-circuit current is: I sc two-pole = 0.26 A.
A detailed calculation of the two partial currents and intact line-to-earth volt-
age is dispensed here. The previous equations result in the following values: I 2
I 2 = 0.69 A, I 3 = 0.66 A, V1 = 94 V.
Compare the measurement results with the calculated values (ascertained using the
method of symmetric components):
A value of 110 V/ 3 is to be used again for the driving voltage E”. Moreover,
Z m = Z g = ( 7.2 + j 86.7 ) Ω. The calculation results in the following amperages for
the two short-circuited outer conductors:
I 2 = I 3 = I sc = 0.63A
Faults Analysis 115
FIGURE 4.35 Lucas-Nülle GmbH test circuit for measurements with an earth-fault quench-
ing coil fault emulator measurement at PVAMU.
116 Power System Protection and Relaying
FIGURE 4.36 Lucas-Nülle GmbH test circuit for measurements in the event of an earth-
fault emulator measurement at PVAMU.
Function Trip Trip Trip Block I> Block I>> f t I> t I>
DIP switch 1 2 3 4 5 6 7 8
ON Inverse Strong i. Extreme i. Yes Yes 60 Hz × 10 seconds × 100 seconds
OFF DEFT DEFT DEFT No No 50 Hz × 1 seconds × 1 seconds
To determine the reset ratio in the case of a symmetric, three-pole short circuit:
Connect the power-switch module as shown in Figure 4.38 so that the right-hand
side is bridged and the left-hand side is connected to all three phases at the overhead
line’s end. For this connection, disconnect the relay output from power switch 1 to
prevent premature tripping.
Faults Analysis 117
Fault
Transmission
Line
Generator Circuit
Breaker
(a)
(b)
FIGURE 4.37 Lucas-Nülle GmbH test circuit for measurements in the event of an overcur-
rent time protection. (a) Power-system con guration. (b) Layout plan.
PROBLEMS
4.1. A single-line diagram of a power system is given in Figure 4.41. Positive-
sequence, negative-sequence, and zero-sequence reactances in per unit are
also given. The synchronous generator operates at a rated MVA and is 5%
above the rated voltage. The neutrals of the generator and Δ-Y transformers
are solidly grounded. The motor neutral is grounded through a reactance
Xn = 0.03 per unit on the motor base. Pre-fault voltage is VF = 1.05∠0° per unit.
The pre-fault load current and Δ-Y transformer phase shifts are neglected.
1 2
Line
X1=X2=0.1
100 MVA 100 MVA X0=0.2 100 MVA 100 MVA
13.8 KV 13.8/138KV 138/13.8KV 13.8 KV
X1=X2=0.2 X=0.13 X=0.132 X1=0.195
X0=0.1 X2=0.2
X0=0.1
T.L 1 T.L 2
T1 1 2 3 T2
G1 G2
Fault
Types Three-Phase SingleLine-to- Line-to-Line Double Line-to-
Required Fault Ground Fault Fault Ground Fault
If
Ia
Ib
Ic
Va
Vb
Vc
Item Connection X1 X2 X0
Generator Grounded star 0.1 0.1 0.05
Transformer Grounded star for both sides 0.2 0.2 0.2
Faults Analysis 121
X1=X2=0.1
X1=X2=0.2 X=0.1 1 X0=0.2 2 X=0.1 X1=X2=0.2
X0=0.1 X0=0.1
Draw the zero, positive, and negative-sequence system and nd the fault
current for
A. The three-phase fault occurs on bus 2.
B. The line-to-line fault occurs on bus 2.
C. Double line-to-ground fault occurs on bus 2.
4.8. The synchronous generator in Figure 4.45 operates at rated MVA, 0.9 p.f and
lagging, and at 5% above-rated voltage when a three-phase short circuit occurs
at bus 2. Calculate the per unit and the actual values of (a) subtransient fault
current, (b) subtransient generator and motor currents, neglecting pre-fault cur-
rent, and (c) subtransient generator and motor currents, including pre-fault.
G M
4.9. For the power system shown in Figure 4.34 (in Problem 4.8), a bolted dou-
ble line-to-ground fault occurred at bus 2. Use Sb = 150 MVA, V b = 138 kV
in the transmission line circuit, assume that X” = X2, X0 = 0.05 p.u. for
the generator and motor, X0 = 3X1 and X1 = X2 for the transmission line,
Transformers are the star to ground connected. Calculate in p.u.
i. The subtransient fault current in each phase.
ii. The neutral fault current.
iii. The motor contribution to the fault current.
122 Power System Protection and Relaying
4.10. A bolted short circuit occurs in the R-L circuit, with V = 22 kV, X = 12 Ω,
R =0.55 Ω, and dc offset. The circuit breaker opens 3.5 cycles after fault
inception. Determine:
i. The r.m.s ac fault current.
ii. The r.m.s momentary current at τ = 0.5 cycles passes through the
breaker before it opens.
iii. The r.m.s asymmetrical fault current that the breaker interrupts.
4.11. A 600 MVA 18 kV, 60 HZ synchronous generator with reactances
X d′′ = 0.15, X d′ = 0.35, X d = 1.25 p.u. and time constants τ d′′ = 0.015,
τ d′ = 1.8, τ a = 0.25 seconds is connected to a circuit breaker. The generator
operates at 6% above-rated voltage and no load when a bolted three-phase
short circuit occurs on the breaker’s load side. The breaker interrupts the
fault three cycles after fault inception. Determine:
i. The subtransient fault current in per-unit and KA r.m.s
ii. Maximum dc offset as a function of time
iii. r.m.s asymmetrical fault current, which the breaker interrupts, assum-
ing maximum dc offset.
5 Fuses and Circuit
Breakers
5.1 INTRODUCTION
A fuse is a device linked in series with conductors attached to the current-carrying
load device. The oldest and most operational system for safety fuses was introduced
in 1890 when Thomas Edison invented electric fuses. There are many kinds of fuses,
and every type of fuse has a purpose. The various types of fuses, their design, func-
tion, and applications are discussed in this chapter.
The fuse is a level detector consisting of a sensor and an intermediate sensor. A
fuse element will respond to a high current ow when mounted in series with the
system being protected and/or triggered. The melting time of the fuses is inversely
proportional to the current owing through the fuse. During interrupting the cur-
rent ow, the fuse connection is broken. For delivering multiple shots, there can be
mechanical arrangements of fuse con guration.
Fuses may only be capable of interrupting currents up to the maximum short-
circuit ratio or limiting the size of the short-circuit current by interrupting the ow
until the maximum value is reached. This current-limiting action is a signi cant fea-
ture with applications in many industrial applications and low-voltage installations.
The description of fuses and circuit breakers, types, and speci cations are dis-
cussed in this chapter. The chapter includes an introduction to the construction and
working of a fuse, the characteristics of a fuse, and fuses applications. Also, the
chapter discusses high-voltage circuit breakers.
(a)
Filter material
(b)
Trigger spring
Conductor
(c)
FIGURE 5.1 Short-circuit elements. (a) Non-current limiting, non-time-delay fuse; (b) cur-
rent-limiting non-time-delay fuse; and (c) current-limiting time-delay fuse.
a level that causes the bound portion of the link to melt if an overload current occurs
and lasts for more than a short time. The results of this overload lead to
Usually, fuse requirements depend on the following four variables (Figure 5.2):
i. DC rating: Without melting and washing, the fuse can hold RMS current
inde nitely.
ii. Voltage rating: This RMS voltage de nes the fuse’s ability to suppress the
internal arc after the fuse connection’s melting. Its voltage level must be able
to survive a blown fuse. Most low-voltage fuses have a 250–600 V rating,
and the fuse rate of medium voltage varies from 2.4 to 34.5 kV.
iii. Rated interrupt current: The fuse can safely cut the biggest RMS asymmet-
ric current. For medium voltage, the normal interrupting rate is 65, 80, and
100 kA.
iv. Response time: A fuse’s melting and winding time depend on the overcur-
rent magnitude de ned by the curve of “current time.”
Fuses and Circuit Breakers 125
10,000
1000
100
Ti me (s ec)
10
80
1
100 125
160
0.1
0.01
100 1000 10,000
Current (A)
Technically, the fuses form the protective relay background, especially for radial
feeders such as distribution lines or auxiliary systems of power stations. The two
main drawbacks of fuses are the following.
The protective relays were developed as logic components separate from the circuit
interrupt function to overcome these drawbacks. Relays require low-level inputs (volt-
ages, currents, or contacts). They derive their input from power transformers, such as
current or voltage and switching contacts. They are only fault detection devices and
require an associated interrupt device – a circuit breaker – to clear the fault. One of
the most important developments was the separation of the fault detection function
and the outage function, giving the relay designer the ability to design a protection
system that matched the power system’s needs.
126 Power System Protection and Relaying
Inverse
overcurrent
Time
relay
Recloser
Fuse
Total
clearing
Min. melt
Current
Total time of clearance (TCT) is the total time elapsed from the onset of overcur-
rent to terminal circuit interruption, i.e.,
It is important not to mix fuse types such as ANSI “K” or “T.” Operational character-
istics differ enough that there may be a lack of cohesion. While implementing other
safety devices, such as overcurrent relays, the same precaution must be taken. In
general, while the fuses or relays may be identical, there are variations in output and
subtle differences in operating characteristics that will trigger coordination, current
level, and capture mode dif culties.
Fuses have various load-carrying capabilities with various fusion curves, which
must be considered. Most manufacturers’ application tables display three load cur-
rent values: continuous capture, hot load, and cold load capture. The continuous load
is the highest estimated current that will not affect the fuse for three hours or more.
The sum of that, a hot load, is without in ating; it can be carried continuously, inter-
rupted, and reactivated instantly. A 30-minute break follows the cold load and is
elevated due to loss of diversity when service is restored. Because during this time,
the fuse will also cool down, capturing the cold and hot loads that will approach
similar values.
International standards and requirements have been established for ease of
replacement and installation due to the large size of the distribution system’s equip-
ment. Unique distribution systems-related equipment such as potheads (transition
conductors and insulators) monitor the expense and alternative inventory rather than
the speci c application. Besides the fuse itself, the interrupters are sectional devices
and reclosers. It is dif cult to interrupt the partition by error.
It “counts” the times it “sees” a fault current and turns on after a predetermined
number while the circuit de-energizes. The recloser cannot interrupt the fault and
re-shutdown automatically in a programmed sequence.
Figure 5.4 shows the three locations of a fault
i. The branch fuse must be removed in location A, leaving the service unob-
structed to the mainline and other branches.
ii. The splitter should remove the fault in location B, but since the splitter can-
not cut the fault, the passenger makes the actual clearing. However, the
divider “sees” the fault current and records a single number. The divider
Circuit
breaker Recloser Sectionalizer
C B
Fuse Fuse Fuse
R
B1 B2 F2 B3
F1
will experience the second count of the fault current if the fault remains.
The recloser will get stuck again, allowing section opening and error clear-
ing; the recloser will successfully reset and restore service until broken.
iii. For fault in location C, the recloser jogs and re-closes as programmed. The
divider does not see the error and does not calculate.
The relays in a distribution station must recognize these potential short-circuit cur-
rent differences in the same way as in a grid system.
Switching from feeder to feeder provides a backup source if a substation trans-
former is out of service or part of the distribution system must be deactivated.
In Figure 5.5, switch S is normally open, and each terminal transformer feeds its
load. In the event of a permanent failure at F1, the sectional parts or re-locking devices
on the transformer side will automatically open. The line must then be de-energized
by opening the circuit breaker, closing switch S, and transferring the remaining load
to the other transformer. For the transformer fault at F2, the breakers of stations (B1)
and (B2) are opened, and the entire load can be fed from the other station.
Switching from one substation to another changes the magnitude and path of
the fault current, and when applying and tuning line defense systems, this must be
considered. Similarly, in the distribution system, the cogenerator’s use adds another
source of electricity, both separate and far from the utility substation, which in u-
ences the fault current’s size and direction. Usually, this move is performed manually
by assigning workers to various locations. If the transition could be performed auto-
matically, a substantial saving of time and resources would be possible.
will protect the other circuits from defective loads once the sideways current travels
and will not return to the same point due to this difference in the current ELCB. If
the neutral current is not earthed, the fault current will be high, the full fault current
will return through the ELCB, and there will be no difference in current.
melts within the fuse. The fuse thus separates the source of power from the con-
nected device. The fuse wire is just a part with very low resistance in normal circuit
operation and does not affect the device’s normal operation connected to the power
supply.
The choice of a suitable fuse and its estimated size for electrical appliances
depends on various factors and environments. The basic formula for choosing fuse
size
Example 5.1
Find the right fuse size for a 10 A two-pin socket with a rating of 500 W socket
supply a 110 V.
273 + θ m
I 2t = 11.5 × 10 4 A2 log10
273 + θ o
273 + θ m
I 2t = 5.2 × 10 4 A2 log10
273 + θ o
If the pre-arcing I2t is not exceeded, there will be no fuse performance deterioration.
This is taken into account when discrimination is required between fuses. If the total
I2t of the smaller fuse is less than the pre-arcing I2t of the larger fuse, then the smaller
fuse would operate without causing any deterioration of the larger fuse.
Example 5.2
It is proposed to use a No.30 AWG copper wire as a fuse element. If its initial
temperature is 50°C, calculate the following:
Solution
30 AWG = 0.0507 mm 2
273 + θ m
a. I 2t = 11.5 × 10 4 A2 log10
273 + θ o
273 + 1083
= 11.5 × 10 4 ×0.05072 × log10
273 + 50
= 184 A2 seconds.
b. For a current of 30 A:
30 2 t = 184
t = 0.2 seconds
Example 5.3
It is proposed to use a No.30 AWG copper wire as a fuse element. If its initial
temperature is 60°C, calculate the following:
Solution
273 + θ m
I 2t = 5.2 × 10 4 A2 log10
273 + θ o
273 + 1000
= 5.2 × 10 4 ×0.0507 2 × log10
273 + 60
= 77.844 A2 seconds.
252 t = 77.844
t = 0.125seconds
Fuses and Circuit Breakers 133
Once fuses are used, the consumer needs to manually replace these fuses; switch
fuses are inexpensive and commonly used in most electronics and electrical systems.
If an overcurrent, overload, or unmatched load link event occurs.
On the other hand, after the service, the resettable fuse resets automatically when
the device faults.
The present limiting fuse generates a high resistance for a short time. In contrast,
in high current ow, the non-CL fuse produces an arc to disrupt the corresponding
circuit’s current.
i. AC fuses
ii. DC fuses
There is a slight difference between AC and DC fuses used in the power systems,
which have been reviewed as follows.
134 Power System Protection and Relaying
5.8.1 DC FUSES
In the case of a DC system, when the metallic wire melts due to the heat generated
from the excess current, the electric arc is produced, and it is very dif cult to extin-
guish this arc due to the constant value of the DC. The DC fuse is slightly larger than
the AC fuse to reduce the arc by increasing the distance between the electrodes to
reduce this arc.
5.8.2 AC FUSES
In the case of an AC system, the voltage at a frequency of 50 or 60 Hz changes the
capacitance from 0 to 50 or 60 times every second so that the arc can be easily
mutated compared to DC. Therefore, AC fuses are a bit small compared to DC fuses.
The fuses can be classi ed based on one-time or multiple operations.
Depending on the fuse current rating, the fuses can be one of the following types
for LV applications:
Figure 5.7 shows the types and classi cation of LV and HV fuses.
Fuses
DC AC
fuses fuses
FIGURE 5.7 Types & classi cation of low-voltage and high-voltage fuses.
Fuses and Circuit Breakers 135
Both types range from 250 to 600 V AC and can be rated on the knife’s end cap or
blade. Cartridge fuses are connected to a base and can be split into more cartridge
attachment fuses and cartridge fuses of type D.
5.12 HV FUSES
In the power system, the high-voltage (HV) fuses are used to secure the power trans-
former, distribution transformers, instrument transformer, and the like, where circuit
breakers may not protect the system. HV fuses are classi ed for more than 1500 V
and up to 13 kV.
The HV fuse part is usually copper, silver, or tin. In the case of expulsion-style
HV fuses, the fuse connection chamber can be lled with boric acid.
HV fuses are of three main types:
Figure 5.10 shows the open (drop out) type, commonly used for voltages up to 33 kV.
Some additional types of SMD fuses and lead fuses are described as follows:
Letter Description
G Conductors and cables protection
M Motor circuits protection
R Semiconductors protection
S Semiconductors protection
Tr Transformers protection
N Conductors protection (North American standards)
D Time-delay fuse for protecting motor circuits (North American standards)
Fuses and Circuit Breakers 139
TABLE 5.1
Non-Fusing and Fusing Currents
Ratings (Inf) Non-Fusing (If) Fusing (t) Conventional
Current (A) Current Current Time (hours)
In ≤ 4 1.5 In 2.1 In 1
4 < In ≤ 10 1.5 In 1.9 In 1
10 < In ≤ 25 1.4 In 1.75 In 1
25 < In ≤ 63 1.3 In 1.6 In 1
63 < In ≤ 100 1.3 In 1.6 In 2
100 < In ≤ 160 1.2 In 1.6 In 2
160 < In ≤ 400 1.2 In 1.6 In 3
400 < In 1.2 In 1.6 In 4
140 Power System Protection and Relaying
5.15.6 SELECTIVITY
A current generally crosses several protected devices in series. These devices are
distributed according to the various circuits to be protected. The protective device
must select the appropriate area to interrupt if a fault occurs.
Terminal
Porcelain
carrier
circuit again. A polymeric positive temperature coef cient device (PPTC, commonly
known as a resettable fuse, multi-switch, or multi-fuse) is a passive electronic com-
ponent that protects against short-current faults in electronic circuits (Figure 5.13).
The application of resettable fuses is overcome where manual fuse replacement is
dif cult or nearly impossible; this type is used in speci c applications such as fuses
in the nuclear system or the space system.
i. Cell phones.
ii. Game systems.
iii. DVD players.
iv. LCD monitors.
v. Scanners.
vi. Hard disk drives.
vii. Digital cameras.
viii. Motors and transformers.
ix. Home distribution boards.
x. Laptops.
xi. Air-conditioners.
xii. General electrical appliances and devices.
xiii. Printers.
xiv. Battery packs.
xv. Portable electronics.
xvi. Power converters.
142 Power System Protection and Relaying
Example 5.4
A distribution system operating at 415 V is shown in Figure 5.14. Select the fuse’s
suitable rating for each load and incoming circuit using the fuse time–current char-
acteristic in Figure 5.15.
Lighting load:
20 kW
I lighting = = 27.8 A
3 × 415 V
Select 32 A fuse
Heating load:
30 kW
I heating = = 41.7 A
3 × 415 V
Select 50 A fuse
Motor load:
Pout 30 kW
Pin = = = 32.6 kW
η 0.92
415 V
20 kW
lighting
load
F1
Incoming
source 30 kW
heating
load
F4 F2
30 kW
motor load
η=92%
P.f =0.83
F3
32.6 kW
I motor = = 54.7 A
3 × 415 V × 0.83
The starting current for ten seconds is seven-time than the full load current,
therefore
I = 7 × 54.7 = 383 A
From the time–current curve shown in Figure 5.16, an 80 A fuse would withstand
383 A for only six seconds.
Therefore, a 125 A fuse, which would withstand 383 A for longer than ten
seconds, would be necessary.
To provide discrimination, the fuse at the incoming circuit must meet the
following requirements:
It must carry the normal load current:
From the time–current curve, a 125 A fuse would withstand 452.5 A for more than
ten seconds.
144 Power System Protection and Relaying
Example 5.5
A 400 V distribution system is shown in Figure 5.17. Select the fuse’s suitable rat-
ing for each load and incoming circuit using the fuse time–current characteristic
in Figure 5.15.
Solution
Select 50 A fuse
Motor load:
Pout 20 kW
Pin = = = 22.2 kW
η 90%
22.2 kW
I motor = = 40 A
3 × 400 V × 0.8
Fuses and Circuit Breakers 145
400 V
30 kW
lighting
load
F5
Incoming
source 30 kW
heating
load
F4 F2
20 kW
motor load
η=90%
P.f =0.8
F3
The starting current for ten seconds is seven-time than the full load current,
therefore
I = 7 × 40 = 280 A
From the time–current curve shown in Figure 5.18, an 80 A fuse would withstand
280 A for 20 seconds. More than ten seconds.
To provide discrimination, the fuse at the incoming circuit must meet the fol-
lowing requirements:
It must carry the normal load current:
From the time–current curve, a 125 A fuse would withstand 348.6 A for more than
ten seconds.
146 Power System Protection and Relaying
Example 5.6
A 450 V distribution system is shown in Figure 5.19. Select the fuse’s suitable rat-
ing for each load and incoming circuit using the fuse time–current characteristic
in Figure 5.15.
Solution
50 kW
I heating = = 64.15 A
3 × 450 V
Select 50 A fuse
Lighting load:
30 kW
I lighting = = 38.5 A
3 × 450 V
Select 32 A fuse
Motor load:
Pout 30 kW
Pin = = = 32.6 kW
η 0.92
32.6 kW
I motor = = 49.2 A
3 × 450 V × 0.85
Fuses and Circuit Breakers 147
450 V
50 kW
heating
load
F1
Incoming
source 30 kW
lighting
load
F4 F2
30 kW
motor load
η=92%
P.f =0.85
F3
The starting current for ten seconds is seven-time than the full load current,
therefore
I = 7 × 49.2 = 344.44 A
From the time–current curve shown in Figure 5.20, an 80 A fuse would withstand
344.44 A for only eight seconds.
Therefore, a 125 A fuse, which would withstand 344.44 A for longer than ten
seconds, would be necessary.
To provide discrimination, the fuse at the incoming circuit must meet the fol-
lowing requirements:
It must carry the normal load current:
From the time–current curve, a 125 A fuse would withstand 447.1 A for more than
ten seconds.
148 Power System Protection and Relaying
The triggering action that causes a circuit breaker to open is usually produced
through an overload relay that can detect abnormal line conditions. For example, the
relay coil in Figure 5.21 is connected to the secondary of a current transformer. The
primary carries the line current of the phase that must be protected. If the line cur-
rent exceeds a preset limit, the secondary current will cause relay contacts to close.
As soon as they close, the tripping coil is energized by an auxiliary DC source. This
causes the three mainline contacts to open, thus interrupting the circuit.
Power
system
A
B
CT
C
Tripping
coil
C1 C2
Relay
of methane, ethylene, and acetylene. The hydrogen gas cannot remain in molecular
form and is broken into its atomic form, releasing a lot of heat. The arc temperature
may reach up to 5000 K. Due to this high temperature, the gas is liberated and sur-
rounds the arc rapidly, forming an excessively fast-growing gas bubble around the
arc. It is found that the mixture of gases occupies a volume about 1000 times that
of the oil decomposed. We can assume how fast the gas bubble around the arc will
grow. Suppose this growing gas bubble around the arc is compressed by any means.
In that case, the rate of the deionization process of ionized gaseous media in between
the contacts will accelerate rapidly increasing the dielectric strength between the
contacts.
Consequently, the arc will be quenched at zero crossings of the current cycle. This
is the basic operation of the oil circuit breaker. The cooling effect of hydrogen gas
surrounding the arc path also helps the quick arc quenching in the oil circuit breaker.
There are mainly two types of OCB available, discussed subsequently.
If an overload occurs, the tripping coil releases a powerful spring that pulls on
the insulated rod, causing the contacts to open. As soon as the contacts separate, a
violent arc is created, which volatilizes the surrounding oil. The pressure of the hot
gases creates turbulence around the contacts. This causes cool oil to swirl around the
arc, thus extinguishing it.
i. The simplicity of the interrupting chamber, which does not need an auxil-
iary braking chamber.
ii. Autonomy provided by the puffer technique.
iii. The possibility to obtain the highest performance, up to 63 kA, with a
reduced number of interrupting chambers.
iv. Short break time of 2–2.5 cycles.
v. High electrical endurance, allowing at least 25 years of operation without
reconditioning.
vi. Possible compact solutions when used for GIS or hybrid switchgear.
vii. Integrated closing resistors or synchronized operations to reduce switching
overvoltages.
viii. Reliability and availability.
ix. Low noise levels.
Reducing the number of interrupting chambers per pole has simpli ed circuit break-
ers considerably and the number of parts and seals required. As a direct consequence,
the reliability of circuit breakers improved. Figure 5.24 shows an SF6 circuit breaker.
152 Power System Protection and Relaying
5.20.2.1 Disadvantages
The main disadvantages of SF6 circuit breakers are:
5.20.2.2 Applications
A typical SF6 circuit breaker consists of interrupter units capable of dealing with
currents up to 60 kA and voltages in the range of 50–80 kV. Several units are con-
nected in series according to the system voltage. SF6 circuit breakers have been
developed for voltages 115–230 kV, power ratings 10–20 MVA, and interrupting time
of fewer than three cycles.
FIGURE 5.26 A typical three-phase contact module of an air-blast circuit breaker (http://
zhwjpe.com/air-blast-circuit-breakers/).
The most powerful circuit breakers can typically open short-circuit currents of 40 kA
at a line voltage of 750 kV in three to six cycles on a 50 Hz line. The air-blast noise
is so loud that noise-suppression methods must be used when the circuit breakers
are installed near residential areas. Figure 5.26 shows a typical single-phase contact
module of an air-blast circuit breaker.
1. Axial blast type: The air blast is directed along the arc path, as shown in
Figure 5.27a.
2. Cross-blast type: The air blast is directed at right angles to the arc path, as
shown in Figure 5.27b.
3. Radial blast type: The air blast is directed radially, as shown in Figure
5.27c.
Fixed Fixed
contact contact
Air blast Air blast
direction direction
Moving Moving
contact contact
(a) (b)
Air Blast
direction
Fixed Moving
contact contact
(c)
FIGURE 5.27 A typical three-phase air-blast circuit breaker. Each phase is composed of
three contact modules connected in series. (a) Axial blast type, (b) cross-blast type, and (c)
radial blast type.
iii. No re hazard.
iv. High-speed operation.
v. Less maintenance and easy operation.
FIGURE 5.28 Lucas-Nülle GmbH normal inverse trip characteristic of directional, maxi-
mum-overcurrent time protection.
Record the characteristics TA(I) for the three different sensitivity stages of t> in a
diagram given in Figure 5.29.
Current I (A) 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
tI> = 1 17.7 10.1 7.5 6.2 5.5 4.9 4.6 4.2
tI> = 0.5 8.9 5.1 3.8 3.1 2.8 2.4 2.3 2.1
tI> = 0.1 1.8 1.1 0.8 0.6 0.5 0.5 0.4 0.4
FIGURE 5.30 Lucas-Nülle GmbH con guration for the reverse direction emulator at
PVAMU.
TABLE 5.2
Lucas-Nülle GmbH, the Protective Relay Setting Circuit
Emulator at PVAMU
Parameter Value
Pick-up value I> 0.3 A
Trip characteristic DEFT
Trip delay tI> forward 1 seconds
Trip delay tI> reverse 10 seconds
Characteristic angle 49
Frequency 60
Serial interface’s address 1
PROBLEMS
5.1. It is proposed to use a No.30 AWG copper wire as a fuse element. If its ini-
tial temperature is 60°C, calculate the following:
a. The I2t needed to melt the wire (copper melt at 1000°C).
b. The time needed to melt the wire if the short-circuit current is 40 A.
5.2. It is proposed to use a No.30 AWG aluminum wire as a fuse element. If its
initial temperature is 55°C, calculate the following:
a. The I2t needed to melt the wire (copper melt at 900°C).
b. The time needed to melt the wire if the short-circuit current is 45 A.
Fuses and Circuit Breakers 159
5.3. It is proposed to use a No.30 AWG copper wire as a fuse element. If its ini-
tial temperature is 50°C, calculate the following:
a. The I2t needed to melt the wire (copper melt at 1083°C).
b. The time needed to melt the wire if the short-circuit current is 30 A.
5.4. A distribution system operating at 415 V is shown in Figure 5.31. Select
the fuse’s suitable rating for each load and incoming circuit using the fuse
time–current characteristic in Figure 5.32.
420 V
40kW
lighting
load
F1
Incoming
source 30 kW
heating
load
F4 F2
30 kW
motor load
η=92%
P.f =0.83
F3
(i)
Operating ti me (sec)
(ii)
(iii-a)
(iii-c)
(iii-b)
(iii-d)
Multiple plug setting
Ti me (s ec)
I
Current (A)
6.2.2.1 Application
Ti me (sec)
Current (A)
Ti me (s ec)
Current (A)
Definite
minimum
time
Minimum
Current (A)
operating
current
Current (A)
Inverse Relay
Time (sec)
Current
Terminals
Plug
Tapping
bridge
Upper
magnetic
Moving contact
To trip
circuit
Fixed contact
Lower
magnetic
Directional relays are usually used in conjunction with other forms of relays,
usually over the current type; when used as an overcurrent relay, the combination
uses to select to respond to the fault current only in the protective zone’s direction
(Figures 6.9 and 6.10).
Overcurrent Relay 167
TC
OC
CB + _ relay
_ Aux. relay
TC
+
_
+
a Constant
time relay
b
OC
_
CB + relay
T = VI cos (θ − τ ) − K (6.1)
168 Power System Protection and Relaying
T = K1VI − K (6.2)
The feeder overcurrent relay‘s coordination curve should fall below the feeder
overload curve and the feeder short-circuit damage curves on the time–current char-
acteristics graph. An overcurrent relay (OCR) is a protection relay that operates when
the load current exceeds a preset value. The coordination curve of the feeder overcur-
rent relay should fall above the capacitance curve of the feeder. Overcurrent relays
generally contain multiples of the current setting of 50%–200% in steps of 25%,
which are referred to as plug setting (PS).
Two parameters determine each relay’s PS: maximum load current and minimum
fault current.
The protection relay coordination setting is made during the system design pro-
cess based on the fault current calculation. In coordinating overcurrent relays, the
goal is to de ne the time multiplier setting (TSM) and PSM for each relay. The total
operating time of the primary relays is appropriately reduced.
The overcurrent relay has a minimum operating current, known as the relay cur-
rent setting. The current setting should be chosen. The relay does not operate at the
maximum load current in the shielded circuit and operates at a current equal to or
greater than the expected minimum fault current. The relay’s current setting clos-
est to the source should always be higher than the previous setting of the relay. The
relays should have higher current settings than any current that could ow through
the relays under normal conditions: 110% of the rated current. Electronic relays and
microprocessors have current adjusting steps of 5%.
It is necessary to modify the timescale of the current–time characteristic to
implement the power system’s relay. The TMS should be chosen to relay the mini-
mum possible time at the end of the radial feeder. A time multiplier should be
selected in the preceding sections toward the source and given a selected interval
of the downstream relay at the maximum error conditions. The TMS should allow
for the cutter time and bypass the relay and the time errors allowed in the succes-
sive relays’ running time.
C
Tp = × TMS (6.3)
(I / I )
p
α
−1
(a) (b)
(c) (d)
FIGURE 6.11 Multiples plug setting operating time characteristics. (a) IEC normal inverse,
(b) IEC very inverse, (c) IEC long inverse, (d) IEC extremely inverse, (e) IEC ultrainverse, (f)
IEEE moderately inverse, (g) IEEE very inverse, and (h) IEEE extremely inverse.
(Continued)
Overcurrent Relay 171
(e) (f)
(g) (h)
FIGURE 6.11 (Continued) Multiples plug setting operating time characteristics. (a) IEC
normal inverse, (b) IEC very inverse, (c) IEC long inverse, (d) IEC extremely inverse, (e) IEC
ultrainverse, (f) IEEE moderately inverse, (g) IEEE very inverse, and (h) IEEE extremely
inverse.
172 Power System Protection and Relaying
TABLE 6.1
IEC Standard Table
Type of Characteristics C α
Normal inverse 0.14 0.02
Very inverse 13.5 1
Extremely inverse 80 2
Long-time inverse 120 1
Short time inverse 0.05 0.04
Inverse 9.4 0.7
Example 6.1
Solution
5
I = 3000 × = 25 A
600
150
Is = × 5 = 7.5
100
I 25
PSM = = = 3.333
I s 7.5
Example 6.2
Solution
1
I= × 4000 = 10 A
400
125
Is = × 1A = 1.25 A
100
Overcurrent Relay 173
I
PSM =
Is
The PSM
10
PSM = =8
1.25
Example 6.3
Determine the operation time of a relay of rating 5 A and having a plug setting of
125% and a time multiplier of 0.5. The supplying CT is rated 600:5 A, and the fault
current is 4000 A.
If
PSM =
I CT secondary × PS × CT
4000
PSM = = 5.3
5 × 125% × 600 / 5
From the plug setting multiplier time log–log data given in Figure 6.12, for PSM = 5.3
t = 4.2 seconds
Example 6.4
An IDMT overcurrent relay has a current setting of 150% and a TMS of 40%. The
time of operation of a relay rating is 5 A. The relay is connected in the circuit
through a CT ratio of 500/5. Calculate the time of operation of the relay if the cir-
cuit carries a fault current of 6000 A.
If
PSM =
I CT secondary × PS × CT
6000
PSM = =8
5 × 150% × 500 /5
From the plug setting multiplier time log–log data given in Figure 6.12, for PSM = 8
t = 3.3 seconds
1 1.3 2 2.5 3 4 5 6 7 8 9 10 12 14 16 18 20
Time (second)
Example 6.5
For the relay R in the system shown, determine the current tap setting (CTS). If the
maximum three-phase fault current is 2400 A and the TDS = 2.0 nds the operat-
ing time, the relay type is CO-8 (inverse type) (Figure 6.13).
Solution
S 4.5 × 10 6
IL = = = 196.82 A
3 V 3 × 13.2 × 10 3
5
I R = 196.82 × = 3.28 A
300
5
Relay side fault current = 2400 × = 40 A
300
40
Multiple selected CTS = = 10
4
13.2 kV
300/5
21
5 MVA
top = 0.31seconds.
Example 6.6
If the rated current (pick-up current) of a relay is 3 A, and the time dial setting is 1.
a. How long does it take the relay to trip if the supply CT is rated at 400:5 A,
and the fault current is 480 A? The type of OC relay is CO-8 (Figure 6.15).
b. Solve using the standard curve equation and compare the results.
Solution
5
I s = 480 × =6A
400
Is 6
∴ Multiple tap value current = = =2
I tap 3
400/5 A
480 A
Is
CO
-8
12
Operating t im e (sec )
10
8
TDS = 4
6
TDS = 3
4
TDS = 2
2
TDS = 1
0
0 2 4 6
Multiples of plug setting
Example 6.7
The 60 MVA, 10/30 kV transformer shown in Figure 6.17 operates at 20% over-
load. The transformer’s CB is equipped with a 1000/5 CT ratio, the feeder’s CBs
have a 500/5 CT ratio, the feeder relays are set at 125%, and TMS = 0.4. Use the
time–PSM given in Table 6.2 and a discrimination margin of 0.5 seconds for a
three-phase fault current of 3000 A at point F, nd (Table 6.3)
Solution
i.
3000 × 5/500
PSM = = 4.8
5 × 125%
F
CB
TABLE 6.2
The Time–PSM Characteristics Table for TSM = 1.0
Time (seconds) 2.2 2.5 2.8 3.5 4.0 5.0 8.0 10.0 ∞
PSM 20.0 15.0 10.0 6.4 5.0 4.0 3.2 2.0 1.0
Overcurrent Relay 177
TABLE 6.3
System Data
Generator 10 kV 40 MVA X = 0.15 p.u.
Transformer 10/30 kV 60 MVA X = 0.2 p.u.
Feeder (each) 30 kV 50 MVA R = 0.05 p.u., X = 0.25 p.u.
t op = TMS × t
60 × 10 3
ii. The overload current = 1.25 = 1443.37 A
3 × 30
5
1443.37 ×
PSM = 1000
5 × PS
1.443
=
PS
iii.
3000 × 5/1000
PSM = =2
5 × 150%
t = 10 seconds
top 2.42
TMS = = = 0.242
t 10
178 Power System Protection and Relaying
i. Discrimination by time,
ii. Discrimination by current, and
iii. Discrimination by both current and time.
The three methods used for correct relay coordination. Though the methods are dif-
ferent, they follow the same goal of isolating only the system’s faulty section and
leaving the rest of the system undisturbed.
A B C D
t2 t1
Distance
1 2 3 4
B3 B2 B1
FIGURE 6.19 Coordinate delay time (CDT) (or time step delay) (or discrimination margin).
The relay’s operating time from the source should be minimum and increase as
we go toward the source (Figure 6.19).
The increase is by a discrimination margin of 0.4 or 0.5 seconds, which lates for
the rst relay to operate time plus to overtravel the next relay plus safety time factor.
CB time = 0.2seconds
The main application is when the fault levels at various locations do not vary
greatly (time-delay step) (Figure 6.20).
A B C D
B3 B2 B1
F
Time
t1
t2
t3
Distance
t1 > t2 > t3
A B C D
B3 B2 B1
F1 F2 F3 F4
A B C D
B3 B2 B1
F1 F2 F3
3000 A 2500 A 2200 A
I1
I2
I3
Distance
I1 >I2 > I3
For proper coordination on a radial system, the pick-up of a relay should be such
that it will operate for all faults in its zone and provide backup for faults in the
adjoined zones.
The backup setting should equal the fault current value when the fault is at the far
end. The next zone with minimum generation is connected to the system
With this characteristic, the operation time is inversely proportional to the current
level, and the actual characteristics are a function of both time and current settings.
For a large variation in fault current between the two ends of the feeder, faster oper-
ating times can be achieved by the relays nearest to the source, where the fault level
is the highest.
Overcurrent relay characteristics generally start with selecting the correct char-
acteristics for each relay, followed by choosing the relay current settings. Finally, the
grading margins and hence time settings of the relays are determined.
IDMT relays are used in this feeder protection for proper coordination among
various relays. A relay’s pick-up should be used to operate for all short circuits in
its line section and provide backup for short circuits in the immediately adjoining
section. On a radial system, the current setting of the relay farthest from the source
should be minimum and increase as it goes toward the source.
A B C
R Q P
t4
Time
Time
Time
t2
t5
t3
t1
If 2 If 3 If If 1 If 2 If If 1 If
1 2 3 4
| If |
A B C
Since the power source is only to the left of each line section, it is suf cient to provide
only one circuit breaker for each section at the source end (Figure 6.24).
Fault current is inversely proportional to distance, as shown in Figure 6.24.
The principle of backup protection with an overcurrent relay for any relay X back-
ing up the next downstream relay Y is that relay X must pick up:
A line-to-line fault will produce a fault current equal to 3 /2 times the three fault
currents
3
I f (L-L) = I f (three -phase) (6.4)
2
Example 6.8
The power system shown in Figure 6.25 performs current–time grading calcula-
tion, using Table 6.4 for data of the system and Table 6.5 as the time–PSM charac-
teristics table for TSM = 1.0.
Overcurrent Relay 183
TABLE 6.4
Data of the System
Relay CT Ratio Fault Current (A)
c 200/5 4000
b 200/5 5000
a 400/5 6000
TABLE 6.5
The Time–PSM Characteristics Table for TSM = 1.0
Time (seconds) 2.2 2.5 2.8 3.5 4.0 5.0 8.0 10.0 ∞
PSM 20.0 15.0 10.0 6.4 5.0 4.0 3.2 2.0 1.0
Solution
To achieve discrimination between the relay at B and that at C when fault takes
place just before C or just after C (i.e., no change in fault current), let discrimination
time = 0.5 seconds.
The operating time of relay B when fault takes place near C will be
0.22 + 0.5 = 0.72 seconds.
The secondary current in the relay at B when fault takes place near C will be
4000/40 = 100 A.
Assume relay B current setting = 125%
100
∴ PSM = = 16
125% × 5
So, the operating time from the characteristics is 2.5 seconds, but relay B operating
time when graded w.r.t relay C is 0.72 seconds
0.72
TMS for relay B = = 0.29
2.5
184 Power System Protection and Relaying
When the fault is near relay B, the PSM with an operating current is 6.25 A is
5000
PSM = = 20
6.25 × 40
Since the CT ratio at A is 400/5, which is high compared to the relay at B, the cur-
rent discrimination is inherent. Let the relay setting of relay A be 125%.
So, PSM of relay A when fault takes place near B
5000
PSM = = 10
5 × 125% × 80
1.138
∴ TMS of relay A = = 0.379
3
6000
When a fault is near A, the PSM = = 12
5 × 125% × 80
From the characteristics, the corresponding time = 2.6 seconds.
The actual operating time of relay A
The adjustment of the traveling distance of a relay is commonly known as a time set-
ting. This adjustment is commonly known as the TSM of the relay.
The following algorithm gives the theoretical calculation for overcurrent relay
setting:
1.3
PSof relay 2 > × PSof relay1 (6.5)
1.05
1.3
PSof relay 3 > × PSof relay 2 (6.6)
1.05
If
PSM = (6.7)
PS × CTratio
0.14
T= × TMS (6.8)
PSM 0.02 − 1
Example 6.9
The power system is shown in Figure 6.26. The MVA range of the source is between
120 and 250 MVA. Perform the current grading.
C
A B D
B3 j0.25 Ω B2 B1
j0.05 Ω
11 kV, 250 F1 F2 F3 F4
MVA rating
each j0.08 pu
5 MVA
11/4 kV
Solution
For fault at F1
11, 000
I f1 = 2 3 = 8652.38 A
11
+ 0.25
250
Hence, the relay controlling the circuit breaker at A and set to operate at a fault
current of 8652.38 A would protect the whole transmission line A–B.
For faults at F1: It is not practical to distinguish between faults at F1 and F2 since
the distance between these points can be only a few meters.
For fault at F3
11,000
I f3 = 3 = 8100 A
112
+ 0.25 + 0.05
250
For fault at F4
11, 000
I f4 = 3 = 3625 A
112 0.08 112
+ 0.25 + 0.05 + ×
250 2 5
Hence a relay controlling the CB at B and set to operate at a current of 3625 A plus
a safety margin would not operate for a fault at F4 and would thus discriminate
with the relay at A.
Assume a safety margin of 30%; it is reasonable to choose a relay setting of
130% of 3625 or 4713 A.
Example 6.10
A portion of the 13 kV radial system is shown in Figure 6.27. Assume the reac-
tances of transformers and transmission lines are given in ohm and referred to the
generator side to calculate the minimum and maximum fault current as a fault at
each bus.
A
C D E
B
j5.25 Ω j5 Ω j8 Ω
13 kV, 250 j4 Ω
MVA rating each
j6 Ω
each
Solution
Fault at bus E.
Maximum fault current (three-phase fault):
13, 000 / 3
I f three-phase = = − j327.38 A
132 6 4
j + + 5.25 + 5 + + 8
250 3 2
3
I f L-L = I f three-phase
2
3
I f L-L = ( − j327.38) = − j 283.52 A
2
Fault at bus D.
Maximum fault current (three-phase fault):
13, 000 / 3
I f three-phase = = − j502 A
132 6 4
j + + 5.25 + 5 +
250 3 2
3
I f L-L = I f three-phase
2
3
I f L-L = ( − j502) = − j 435.5 A
2
Fault at bus C.
Maximum fault current (three-phase fault):
13, 000 / 3
I f three-phase = = − j580.66 A
132 6
j + + 5.25 + 5
250 3
3
I f L-L = I f three-phase
2
3
I f L-L = ( − j580.66) = − j502.86 A
2
188 Power System Protection and Relaying
Fault at bus B.
Maximum fault current (three-phase fault):
13, 000 / 3
I f three-phase = = − j947 A
132 6
j + + 5.25
250 3
3
I f L-L = I f three-phase
2
3
I f L-L = ( − j947 ) = − j820 A
2
Fault at bus A.
Maximum fault current (three-phase fault):
13, 000 3
I f three-phase = = − j 2804 A
132 6
j +
250 3
3
I f L-L = I f three-phase
2
3
I f L-L = ( − j2804 ) = − j 2429 A
2
K
T=
In −1
where K = TMS.
I = input current to overcurrent relay in multiples of PSs.
n = constant deciding the inferences.
For different values of n, the characteristics are
K
T= ( n = 0 ) DTOC relay
I0
Overcurrent Relay 189
FIGURE 6.28 Lucas-Nülle GmbH layout plan for overvoltage test emulator at PVAMU.
TABLE 6.6
The Voltage Relay’s DIP Switches Using the Lucas-Nülle GmbH Test
Emulator at PVAMU
Function Un Un Un ps Supv. Hyst. Hyst. tU<tU>
DIP Switch 1 (V) 2 (V) 3 (V) 4 5 6 (%) 7 (%) 8
ON 110 230 400 Active Δ 6 10 ×1
OFF 100 100 100 Inactive Y 3 3 ×0.1
190 Power System Protection and Relaying
Once all these settings have been made, connect the transmission line and the load
by closing the power switches (ON buttons).
The operational state should be assumed (both red LEDs on the voltage relay are
OFF). If a relay is still energized (red LED on), turn the power switch off again and
check your settings.
FIGURE 6.29 Lucas-Nülle GmbH layout plan for hysteresis test emulator at PVAMU.
TABLE 6.7
The Voltage Relay’s DIP Switches Using the Lucas-Nülle GmbH Test
Emulator at PVAMU
Function Un Un Un ps Supv. Hyst. Hyst. tU<tU>
DIP Switch 1 (V) 2 (V) 3 (V) 4 5 6 (%) 7 (%) 8
ON 110 230 400 Active Δ 6 10 ×1
OFF 100 100 100 Inactive Y 3 3 ×0.1
Overcurrent Relay 191
TABLE 6.8
The Voltage Relay’s DIP Switches Using the Lucas-Nülle GmbH Test
Emulator at PVAMU
U < (%) U > (%) RPU (V) RRe (V) R = RRe/RPU
75 105 115 111 0.96
75 110 120 116 0.97
75 115 126 120 0.95
75 120 131 126 0.96
TABLE 6.9
Set the Hysteresis to 10% (DIP Switch 7) Using the Lucas-Nülle GmbH Test
Emulator at PVAMU
Function Un Un Un ps Supv. Hyst. Hyst. tU<tU>
DIP Switch 1 (V) 2 (V) 3 (V) 4 5 6 (%) 7 (%) 8
ON 110 230 400 Active Δ 6 10 ×1
OFF 100 100 100 Inactive Y 3 3 ×0.1
The adjustable three-phase power supply set the voltage to 110 V. The trip delay
is zero seconds in both cases, and the potentiometer to the rst overvoltage value is
indicated in Table 6.8. Slowly increase the voltage on the three-phase power supply
until the red LED “U>” comes on, and note the pick-up value under RPU. Gradually
decrease the voltage and record the release (or reset) value RRe in Table 6.8.
Calculate the average hysteresis with the help of the reset ratios.
H = 4.3%
H = 8.9%
192 Power System Protection and Relaying
TABLE 6.10
Set the Hysteresis to 10% (DIP Switch 7) Using the Lucas-Nülle GmbH Test
Emulator at PVAMU
U< (%) U> (%) RPU (V) RRe (V) R = RRe/RPU
90 120 101 110 1.09
85 120 96 106 1.1
80 120 90 100 1.11
75 120 84 94 1.12
TABLE 6.11
Show the Relay’s DIP Switches Setting Using the Lucas-Nülle GmbH Test
Emulator at PVAMU
Function Un Un Un t Return t RP> t P>
DIP Switch 1 (V) 2 (V) 3 (V) 4 5 6 (ms) 7 8
ON 110 230 400 Δ 40 ×10 ×10
OFF 100 100 100 Y 500 ×1 ×1
194 Power System Protection and Relaying
FIGURE 6.32 Lucas-Nülle GmbH layout for reverse power emulator at PVAMU.
PROBLEMS
6.1. Determine the operation time of a 5 A, three seconds overcurrent relay with
a plug setting of 125% and a time multiplier of 0.58. The supplying CT is
rated 600:5 A, and the fault current is 3500 A.
6.2. The 40 MVA, 11/30 kV transformer shown in Figure 6.33 operates at 25%
overload. The transformer’s CB is equipped with a 1000/5 CT ratio, the
feeder’s CBs have a 500/5 CT ratio, the feeder relays are set at 125%, and
F
CB
TMS = 0.35. Use the time–PSM given in Table 6.12 and a discrimination
margin of 0.4 seconds for a three-phase fault current of 3300 A at point F to
nd (Table 6.13):
TABLE 6.12
The Time–PSM Characteristics Table for TSM = 1.0
Time (seconds) 2.2 2.5 2.8 3.5 4.0 5.0 8.0 10.0 ∞
PSM 20.0 15.0 10.0 6.4 5.0 4.0 3.2 2.0 1.0
TABLE 6.13
System Data
Generator 11 kV 40 MVA X = 0.2 p.u.
Transformer 11/30 kV 60 MVA X = 0.12 p.u.
Feeder (each) 30 kV 50 MVA R = 0.05 p.u., X = 0.25 p.u.
6.3. The 25 MVA transformer shown in Figure 6.34 operates at 30% overload
and feeds n 11 kV bus through a circuit breaker. The transformer’s CB is
equipped with a 1000/5 CT ratio, the feeder’s CBs have a 400/5 CT ratio, the
feeder relays are set at 125%, and TMS = 0.375. Use the time–PSM given
in Table 6.12 and a discrimination margin of 0.4 seconds for a three-phase
fault current of 5000 A at point F to nd (Table 6.14):
i. The operating time of the feeder relay.
ii. The minimum setting of the transformer relay.
iii. The TMS of the transformer.
F
CB
TABLE 6.14
System Data
Generator 11 kV 25 MVA X = 0.1 p.u.
Transformer 11/33 kV 60 MVA X = 0.15 p.u.
Feeder (each) 33 kV 50 MVA R = 0.05 p.u., X = 0.25 p.u.
6.4. A 11 kV busbar has two incoming feeders, each tted with 1000/5 A CT
and an IDMTL (inverse de nite minimum time-lag) relay having a plug
and time setting of 150% and 0.4, respectively. The corresponding data for
an outgoing feeder is 400/5 A, 175%, 0.3. For a three-phase 280 MVA fault
along the outgoing feeder, calculate the difference between the operating
times of the relay for:
i. The two incoming feeders are in operation.
ii. One incoming feeder is in operation (the other is switched out).
iii. Show that the protection and a single incoming feeder will not operate
to a load of 20 MVA.
6.5. It is required to provide time–current grading for the following system in
Figure 6.35 (Table 6.15).
a b c
TABLE 6.15
System Data
Relay Plug Setting (PS) (%) CT Ratio Fault Current (A)
a 150 400/5 5100
b 125 300/5 4200
c 100 200 3300
Overcurrent Relay 197
1 1.3 2 2.5 3 4 5 6 7 8 9 10 12 14 16 18 20
Time (second)
6.6. For the relay R in the system shown, determine the current tap setting (CTS).
If the maximum three-phase fault current is 2400 A and the TDS = 2.0 nds
the operating time, the relay type is CO-8 (inverse type) (Figure 6.37).
13.2 kV
300/5
21
5 MVA
7.1 INTRODUCTION
A transmission line is the most important and integral part of a power system. Due to
more than 80% of disturbances or short-circuit faults in an overhead line, this section
has become the most vulnerable part of the electrical system. Therefore, it is neces-
sary to have designed a reliable protection system to protect against interference.
In order of ascending cost and complexity, the protective devices available for
transmission line protection are:
i. fuses
ii. sectionalizes, reclosers
iii. instantaneous overcurrent
iv. inverse, time delay, overcurrent
v. directional overcurrent
vi. distance
vii. pilot.
Z AF
A B
F
if If
vf Vf
Restrain
Operating
coil
coil
Relay
Z 3a
Z 2a Z 2c
Time Z 1a Z 1c
A B C D
Z 2b Z 1b Z 1d
Z 2d
Time Z 3d
FIGURE 7.2 Two sections line system is protected by three zones protection scheme.
For the simple impedance relay shown, the relay operates for Z = V / I below a
particular value, whereas above this value of Z, the relay will restain. If possible,
select a setting comparable along the time to be protected.
Strictly speaking, the impedance seen by the relay is not proportional to the dis-
tance between the relay and the fault in general because of the following reasons:
Figure 7.2 shows a two sections line system protected by three zones protection
scheme.
Z1a corresponds to ~80% of the length of line AB and is a high-speed zone. It was
extended only to 80% of the length to pass the impedance measurements’ inaccura-
cies, especially when the current is offset.
The second Z2a zone for relay A causes the remaining 100% of line AB plus 20%
of the adjoining section CD.