PID Controller
PID Controller
Proportional Tuning
This type of tuning involves adjusting or correcting the desired signal
proportional to the current error signal e(t). The error signal is the difference
between the setpoint or the target value and the actual value. The current
error signal is further multiplied with the pre-calculated proportional constant
to obtain the output. If the error value is equal to zero, the controller output
value is also zero. Here, the desired value rarely gets achieved as it never
reaches the steady-state condition. The control devices that make use of
proportional tuning or the p controllers, provide a stable operation but tend to
maintain a steady-state error. The proportional constant is directly comparable
to the speed of response of the device. This means that when the proportional
constant Kc is increased, the speed of response increases accordingly. If this
type of controller is not used in combination with the other type of controller, it
requires manual reset and proper biasing.
Integral Tuning
The ‘P’ controllers or the controllers that make use of proportional tuning are
susceptible to suffer a limitation that there always exists a steady-state error,
which is an offset between the setpoint and the feedback process variable. This
type of limitation can be eliminated by employing the ‘I’ controllers. I-
controllers make use of integral tuning to generate the output signal to
manipulate various physical parameters. This type of tuning tends to integrate
the error signal with respect to time until a minimum or zero value of the error
is achieved. In case of a negative error value, the integral control tends to
decrease the output. The speed of response and the stability of the system;
however, get affected during the process. A PI controller is susceptible to
undergo integral wind up conditions due to the non-linearities present in the
plant. Under this condition, the integral output continues to increase even at a
zero error state. To overcome this disadvantage, the ‘I’ controller output is
limited to a certain range. The integral gain of the ‘I’ controllers, usually
denoted by Ki, is indirectly proportional to the speed of response of the system.
This means that if the integral gain is increased, the speed of response of the
system gets reduced by a comparable value. Similarly, the integral gain is
directly proportional to the steady-state error. This means that the steady-state
error gets reduced by reducing the integral gain of the controller and vice
versa. PI controllers are typically used in applications where the high response
time of the system is not primarily important.
Derivative Tuning
The ‘D’ controllers or derivative tuning is normally used to overcome certain
limitations of the ‘I’ tuning. For instance, an ‘I’ controller does not have the
ability to predict the future behaviour of the error value. Such devices tend to
act normal even when the set fixed point or the desired value is changed. The
output of the derivative controllers is equal to the rate of change of the error
signal with respect to time multiplied by the derivative constant. The derivative
tuning helps in improving the system response and decreasing the settling time
of the output. The derivative gain Kd is directly proportional to the responding
speed of the system. This means that an increase in the derivative gain of the
controller tends to increase the response time of the system.
Types of a PID Controller
On the basis of the type of control system used, the PID controllers can be
broadly classified into three categories, namely ON/OFF, proportional, and
standard type controllers.
ON/OFF Control
The on/off control is one of the simplest types of devices used to adjust or tune
the temperature of a particular area. Here, the controller tends to switch the
device to the ON state, once the output signal crosses a particular desired fixed
point. One of the most commonly used on/off control devices is a limit
controller. A limit controller makes use of a latching relay for its operation. The
relay is required to be operated manually. The temperature or the other
variable parameter is set to a particular value. The device tends to maintain the
off state if the output or the resultant signal falls behind the target value. Once
the threshold or the set point is achieved, the device gets turned on.
ON OFF Control Characteristics
Proportional Control
Proportional control is basically designed to overcome and remove the cycling
limitation of an on/off control. This type of control prohibits the controller to
exceed a particular pre-decided threshold value. The device tends to achieve
the desired point to maintain the physical parameter value at a constant level;
however, it does not exceed the fixed threshold point. For instance, a heater
that makes use of a proportional control tends to maintain the temperature at a
constant value and avoids overheating. When the temperature of the heater
tries to surpass the threshold value, the controller gets activated. The supply
gets cut off and the temperature of the device is reduced.
Proportional Control Characteristics
2. Most manufacturing industries make use of huge furnaces to melt and heat
different elements. The temperature of such furnaces is required to be
monitored periodically. Also, one must be able to control and vary the
temperature to maintain the temperature of the furnace at the desired constant
value. For this purpose generally, a PID controller is employed.
6. PID controllers are also used in pH, flow, and speed control devices.
1. Most of the modern devices equipped with PID controllers are inexpensive.
2. The tuning and operation of PID controllers do not require much experience.
Hence, an unskilled person can also operate such devices.
3. PID controllers are process independent.
4. They provide precise control of the setpoint, thereby allowing the user to fix
the temperature or pressure value to a particular constant value.
6. The devices and systems equipped with PID controllers have significantly
improved responsiveness.
3. The controller may sustain oscillations around the operating point and cause
problems.
4. The continuous variation in the load tends to affect the dynamic performance
of the system.
5. Repeated tuning of the controller may reduce the life span and cause wear
and tear.