DUA52.eng

The DUA52 is a DC undervoltage monitoring relay designed to measure its own power supply within ranges of 8-28 V DC and 38-58 V DC. It features adjustable hysteresis, a 5 A SPDT relay output, and is suitable for DIN-rail mounting. The device includes LED indicators for power and relay status, and is compliant with various safety and environmental standards.

Uploaded by

m azmi shah
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
21 views2 pages

DUA52.eng

The DUA52 is a DC undervoltage monitoring relay designed to measure its own power supply within ranges of 8-28 V DC and 38-58 V DC. It features adjustable hysteresis, a 5 A SPDT relay output, and is suitable for DIN-rail mounting. The device includes LED indicators for power and relay status, and is compliant with various safety and environmental standards.

Uploaded by

m azmi shah
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Monitoring Relays

DC Under Voltage
Type DUA52
• DC undervoltage monitoring relay
• Measuring if power supply is below the set level
• Measures its own power supply
• Measuring ranges: 8 - 28 V DC and 38 - 58 V DC
• Adjustable hysteresis: 4 to 50%
• Output: 5 A SPDT NE relay
• For mounting on DIN-rail in accordance with
DIN/EN 50 022
• 17.5 mm housing (DIN 43880)
• LED indication for relay and power supply ON

Product Description Ordering Key DUA 52 C 724


DUA52 is a voltage monitor- and hysteresis. Typical appli- Housing
ing relay that measure its own cations are monitoring of Function
power supply. The measuring backup batteries, batteries on Type
ranges are 8-28 VDC and 38- diesel generator sets and the Item number
58 VDC. It has separate like. Output
potentiometers for setpoint Power supply

Type Selection
Mounting Output Measuring range Supply : 12/24 VDC Supply: 48 VDC

DIN-rail SPDT 8 to 28 VDC DUA 52 C 724


DIN-rail SPDT 38 to 58 VDC DUA 52 C 748

Input Specifications Output Specifications


Input (voltage level) Terminals A1, A2 Output SPDT relay
Measures its own power Rated insulation voltage 250 VAC
supply Contact ratings (AgSnO2) µ
Measuring ranges Resistive loads AC 1 5 A @ 250 VAC
Direct Level DC 12 5 A @ 24 VDC
48 VDC 38 to 58 VDC Small inductive loads AC 15 2.5 A @ 250 VAC
12 to 24 VDC 8 to 28 VDC DC 13 2.5 A @ 24 VDC
Mechanical life ≥ 30 x 106 operations
Electrical life ≥ 105 operations
(at 8 A, 250 V, cos ϕ = 1)
Operating frequency ≤ 7200 operations/h
Dielectric strength
Dielectric voltage 2 kVAC (rms)
Rated impulse withstand volt. 4 kV (1.2/50 µs)

Supply Specifications
Power supply Overvoltage cat. III
Rated operational voltage (IEC 60664, IEC 60038)
through terminals:
A1 and A2 724 8 to 28 VDC
748 38 to 58 VDC
Dielectric voltage None
Dielectric voltage
Supply to output 2 kV
Rated operational power 1.5 W

Specifications are subject to change without notice (08.06.10) 1


DUA52

General Specifications
Power ON delay < 200 ms Housing
Reaction time (input signal variation from Dimensions 17.5 x 81 x 67.2 mm
-20% to +20% or from Material PA66 or Noryl
+20% to -20% of set value) Weight Approx. 75 g
Alarm ON delay < 200 ms Screw terminals
Alarm OFF delay < 200 ms Tightening torque Max. 0.5 Nm
Accuracy (15 min warm-up time) acc. to IEC 60947
Temperature drift ± 1000 ppm/°C Product standard EN 60255-6
Alarm delay ± 10% on set value ± 50 ms
Repeatability ± 0.5% on full-scale Approvals UL, CSA
Indication for CE Marking L.V. Directive 2006/95/EC
Power supply ON LED, green EMC Directive 2004/108/EC
Output relay ON LED, yellow EMC
Immunity According to EN 60255-26
Environment According to EN 61000-6-2
Degree of protection IP 20 Emissions According to EN 60255-26
Pollution degree 3 According to EN 61000-6-3
Operating temperature -20 to 60°C, R.H. < 95%
Storage temperature -30 to 80°C, R.H. < 95%

Mode of Operation Range and Level Setting


DUA52 monitors the DC val- is rising above the setpoint Selection of level: Lower knob:
ue of its own power supply. plus hysteresis, and is deen- Setting of hysteresis on rela-
ergized when the measured Centre knob: tive scale
The output is energized voltage drops below the set- Setting of level on absolute
when the measured voltage point value. scale.

Operation Diagram Wiring Diagram

Hysteresis
Setpoint

Relay ON

Dimensions
17.5
67.2

18.7
81

45
2

2 Specifications are subject to change without notice (08.06.10)