SGP - Unit-II (Relays)
SGP - Unit-II (Relays)
RELAYS
************************************************************************************************
Electromagnetic Relays - Basic Requirements of Relays – Primary and Backup Protection -
Construction Details of – Attracted Armature, Balanced Beam, Induction Type and
Differential Relays – Universal Torque Equation – Characteristics of Over Current, Direction
and Distance Relays. Static Relays – Advantages and Disadvantages – Definite Time,
Inverse and IDMT. Static Relays – Comparators – Amplitude and Phase Comparators.
Microprocessor Based Relays – Advantages and Disadvantages – Block Diagram for Over
Current (Definite, Inverse and IDMT) and Distance Relays and Their Flow Charts.
*****************************************************************************************
Relay: A relay is an automatic device which detects faults and initiates the circuit
breaker to isolate the faulty element of the system.
The relays detect the abnormal conditions in the electrical circuits by
constantly measuring the electrical quantities which are different under normal and
fault conditions. The electrical quantities which may change under fault conditions
are voltage, current, frequency and phase angle.
PSM =
PSM =
Time/PSM curve: The curve between the time of operation and PSM of a
relay. Horizontal axis: PSM representing the no. of
times the relay current is in excess of current
setting. Vertical axis calibrated in terms of time
required for relay operation
Time from time/PSM curve =
(m) Time setting Multiplier (TSM):
Adjusting the time of operation of the relay using time
setting dial is called time setting multiplier. The dial is
calibrated in steps; these values are multipliers to be used to
convert the time curve into the actual operating time.
Actual relay operating time = TMS x operating time from time/PSM curve.
Procedure to calculate the relay operating time:
Convert the fault current into relay coil current using CT ratio.
Calculate PSM, i.e., Express the relay current as multiple of current setting.
(i) Based on the technology they use for their construction and operation:
i. Electromechanical Relays (Electromagnetic and thermal relays).
ii. Static Relays.
iii. Numerical (Microprocessor Based) Relays.
where K1, K2, K3 are the tap setting or constant of V and I. The K4 is the
mechanical restraint due to spring or gravity.
1. Impedance relays:
An impedance relay measures the
impedance of the line at relay location. When a
fault occurs on the protected line section, the
measured impedance is the impedance between
the relay location and the point where the fault
has occurred. It is proportional to the line length
of the line.
The Relay operates if the measured impedance Z is less than the given
constant K (predetermined or pick up value).
Operating characteristics of impedance relay:
Figure shows the operating characteristics
of an impedance relay in terms voltage and
current.
In case of electromagnetic relay, the
characteristics are slightly bent near the origin
due to the effect of the control spring. In case of
microprocessor based or static relay, the
characteristics will be straight line.
MHO relays are used for protection of long transmission line against phase
faults.
STATIC RELAYS:
In static relays the comparison or measurement of electrical quantities is
performed by a static circuit which gives an output signal for the tripping of a circuit
breaker.
A static relay employs semiconductor diodes, transistors, zener diodes, logic
gates etc. as its components. Now a day’s integrated circuits are being used in the
place of transistors. They are more reliable and compact.
Comparators:
When a fault occurs on a system, the magnitude of voltage and current and
phase angle between the voltage and current may change. These quantities during
faulty conditions are different from those under normal conditions.
The static relay circuitry is designed to identify the changes and to distinguish
between normal and faulty conditions.
The part of the circuitry which compares the two actuating quantities either
amplitude or phase is known as comparators.
There are two types of comparators:
1. Amplitude comparator.
2. Phase comparator.
Amplitude comparator:
An amplitude comparator compares the magnitude of two input quantities
irrespective of the angle between them. One of the inputs is the operating quantity
and the other a restraining quantity. When the amplitude of the operating quantity
exceeds that of restraining quantity, the relay sends a tripping signal to the circuit
breaker.
Phase comparator:
A phase comparator compares two input quantities in phase angle irrespective
of their magnitudes and operates; if the phase angle between them is less than or
equal to 900.
phase angle between the M and N is less than 900.it means that the comparator with
the modified inputs has now become a phase comparator for the original input
signals M and N. this has been illustrated with the phasor diagrams shown in figure.
Phase comparator compares the phases of input signals M and N, operates
when the phase angle between two signals M and N is φ < 900.
Now change the inputs to (M+N) and (M-N). with these changed inputs, the
comparator will operate when the angle between the (M+N) and (M-N) i.e. τ < 900.
This condition will be satisfied only when | | >| |.
In other words, the phase comparator with the modified inputs has now
become a amplitude comparator for the original input signals M and N.
There are two full wave rectifiers, one for the operating quantity and the other
for restraining quantity. The output of these bridges is applied to a dc 17olarized
relay. When the operating quantity exceeds the restraining quantity then the relay
operates.
The below figure shows the block diagram of phase comparator. The
sinusoidal inputs are first converted into square waves then are applied to an AND
gate. The output of AND gate is chain of pulses as show in below figure (b). This is for
Φ < 900, i.e. ψ > 900. The relay provides a trip output. The output of the AND gate is
Overcurrent Relays:
A relay which operates when the actuating current exceeds a pick up value.
Instantaneous Overcurrent Relay:
The block schematic diagram of
the static instantaneous Overcurrent
relay is shown in the figure.
There are two main types of phase comparators used for the purpose. One of
these is the Hall Effect type comparator which has been used in USSR, whereas all
other countries have preferred the rectifier bridge type of comparator due to its lower
cost and the higher output obtainable as compared to the Hall elements.
< K (As Vm and Idc are proportional to r.m.s values V and I, respectively)
Z sinΦ < K
X<K
The block schematic
diagram of the interface for
the realization of reactance
relay is as shown
The microcomputer
reads the output of the zero
crossing detectors to
examine whether the
current has crossed its zero
point. As soon as the
current crosses its zero point, the
microcomputer sends a command to the
multiplexer to switch on channel S5, and gets
the instantaneous value of the voltage, i.e.
VmsinΦ through the A/D converter. Then the
microcomputer sends a command to the
multiplexer to switch on the channel S7 to get
the rectified current. Thereafter, the
microcomputer calculates X, the reactance as
seen by relay and compares it with X1,
predetermine value of the reactance for the
first zone of protection. the microcomputer
sends a tripping signal instantaneously, if
measured value of X<X1.
if X > X1, but less than X2 ,tripping
signal sent after predetermined delay. If X is
more than X2 but lies within the protection
zone of the directional unit which also acts as
third unit as shown in figure, that tripping
signal is sent after a grater predetermine
delay. As the reactance relay is non-
directional relaying unit, directional relay is
used in conjunction with it to provide
directional features. The directional unit also
serves the purpose of the third unit. the
directional unit used for reactance relays has
<
M<K
Where K1, K2 and K are constants.
Sol: PSM = =
= 5 x 1.5 = 7.5A
PSM = = =4
PSM = = =8