HT_AB_CABLE
HT_AB_CABLE
TECHNICAL SPECIFICATION
FOR HT AB CABLE
(amended on 01.06.2017)
Unless otherwise stipulated in this specification, the following standard with latest amendment shall be
applicable:
IS:7098 (Part-II)-2011 Specification for Cross linked polyethylene insulated thermoplastic sheathed
and its amendment Cables- for working voltages from 3.3 KV up to and including 33 KV.
IS : 8130-1984 and its Specification for Conductors for Insulated Electric Cables and flexible Cords.
amendment
IS : 398 (Part-IV)-1994 Specification for Aluminium Conductors for overhead Transmission purposes:
and its amendment Aluminium Alloy Stranded Conductors (Aluminium-Magnesium- Silicon type)
IS:10418-1982 and its Specification for Drums for Electric Cables
.
amendment
IS: 5831-1984 and its Specification for PVC insulation and Sheath of Electric Cables.
amendment
900C 2500C
Note : The resistance values given in the Table are the max. permissible one.
10.0 DETAILS OF MESSENGER (NEUTRAL CONDUCTOR)
Bare Messenger Conductor shall consist of aluminium alloy wires. Aluminium Alloy Wires shall be tested
as per IS:398(Part-IV) /1994 with latest amendments.
Messenger Conductor shall be Stranded non-compacted Circular & shall have smooth round surface
to avoid damage to the outer insulating sheath of single core phase cables twisted around the messenger.
There shall be no joints in any wire of the stranded messenger conductor except those made in the base
rod or wires before finally drawing.
The technical characteristics of the messenger wire shall be as follows:
Nominal Cross sectional Area Messenger Conductor Maximum DC
of Phase Conductor (Stranded Al Alloy IS 398 Part-4) resistance at
(sq. mm) Nominal Area of No. of Strand Strand dia. of 20oC
Aluminium Alloy in of Aluminium Alloy (ohm/km)
Messenger Wire Aluminium (mm)
(sq. mm) Alloy
35 70 7 3.57 0.48
50 70 7 3.57 0.48
70 70 7 3.57 0.48
95 70 7 3.57 0.48
95 80 7 3.81 0.425
11.0 LAYING UP :
Three Power Cores having colour tape marking shall be twisted over bare messenger wire with right
hand direction of lay. This will from the Aerial Bunched Cable.
v) Loss of mass in air oven, heat shock and thermal stability Test
f) Bending test.
i) As a function of Voltage.
l) Flammability test.
f) Tensile Strength & elongation at break test for insulation & Sheath
ROUTINE TEST ;
The following tests shall be carried out as routine tests on all sizes of all drums of un armoured cables by
the supplier in presence of the purchaser’s representative if so directed by the purchaser and shall be got
approved before despatch.
Type test/acceptance test/Routine tests and any other tests not covered as stated in different clauses of
the specification but required as per relevant Indian Standards shall also to be carried out.
13. INSPECTION :
The Cable shall be inspected at manufacturer’s works before despatch as per IS-7098 (Part- II)/2011
(with latest amendments). All the acceptance tests embodied in the above shall be performed by
the Inspecting Officer. The Manufacturer shall arrange without making any extra charges with all the
necessary machinery, apparatus and labour requirement for the testing purpose. The cost requirement
for testing shall be to Firm’s Account.
6 copies of type test certificate lot wise for each type of cable shall be sent to the purchaser for
acceptance. Type test certificate for each lot and routine test certificate for each drum of cables
shall be submitted to purchaser for approval before despatch of cables from the works. The test
certificate shall be completed with all results.
14. SEQUENTIAL MARKING :
Supplier shall provide non-erasable sequential marking of length on any one of phase cores by
printing/engraving for each metre of length with sequential marking machine having automatic length
measuring meter. The Cable supplied without sequential marking will not be accepted and no deviation
shall be allowed under any circumstances
a) Manufacturer’s Name
j) Number of Cores.
m) Year of Manufacture.
The standard Drum Length will be 250 mtrs. in each Drum for all sizes subject to a maximum
tolerance of + 5% and overall quantity tolerance should be -1%.
b) Nominal Thickness
c) Method of application Extrusion
d) Colour Black
11 Voltage Grade of Cable
a) Maximum operating voltage of the Cable 12 KV
Air Temp. 0C
13 Direction of Laying Right Hand Direction
Both polyethylene and PVC are waterproof, but PVC is more so. Additionally, PVC is much
more fire-resistant than polyethylene, because the chlorine atoms it releases during a fire
inhibit the process of combustion. PVC in its native form is brittle and hard, so it needs to
be softened and made flexible by adding other compounds called plasticizers.
Polyethylene's properties depend on the type. LDPE is much softer and more malleable than
linear polyethylenes such as high-density polyethylene, or HDPE.
There is no scope in our spec to include the following details of Messenger Conductor
Nominal dia of compacted Conductor
Approx. Mass Kg/KM
Breaking Load (KN)
There is no scope in our spec to include Designation and Parameters of finished Cables