CHAPTER 10
CHAPTER 10
In general copper or lead tin alloy may be used as as an ordinary fuse elements
or fuse wire.
fuse link: it is the part of the fuse which needs replacement when the fuse blows
out.
Rated current: The rated current of is the rms value of the current it can carry
indefinitely without fusing.
Minimum fusing current:
the minimum using current in the minimum rms value of the current at which
the fuse element will melt. Generally, the minimum fusing current is more than
the rated current of the fuse.
The minimum fusing current depends upon various factors such as shape and
area of cross section of the fuse element, size and location of the terminals, fuse
material length, the of enclosure employed and the no. of strands in the stranded
fuse wire.
The approximate value of minimum fusing current
For a round wire it is given as
3
I Kd 2
a) I2t characteristics
b) Rupturing characteristics
c) Cut-off current characteristics
4) depending upon the extinction of arc extinction in liquid medium
a) Oil-break circuit breaker fuses
b) Oil expulsion fuses
c) Oil-blast fuses
Fuse carriers: Fuse is a device which cuts off the circuit when more than
predetermined value current flows in the circuit.
It is the weakest point of circuit which breaks when more than normal current
flows in the circuit. The fuse is a wire or strip of short length having low melting
point held in porcelain fuse carrier and inserted in an electrical circuit as a
protective device. The porcelain fuse carrier is used for safe handling of fuse
wire.
Rewirable type fuse or Kit-Kat fuse unit:
It is the most important and common type of fuse unit used for all day to day
work in domestic installations.it can be rewired, even if the cut-out terminals are
energized without taking any safety precautions. The part fuse carrier which
holds the fuse wire is a separate unit and be taken out or inserted with care in the
base to which the incoming and outgoing live wire is permanently connected.
The unit in which the incoming and outgoing line or phase wire is connected
permanently with help of connecting terminals is known as base while
removable parts which holds fuse wire and fits in to base when inserted is known
as fuse carrier. The metallic part of the carrier when inserted in the base touches
metallic part of the base thus making continuity from one base terminals to the
second base terminals through the fuse wire and keeps the continuity.
These are simple in operation. Rewiring of fuse wire can be handled safely even
if the main supply is ON. Usually these are kept in cast iron boxes. But now a
days they are kept in moulded plastic boxes.
Cartridge fuse: cartridge fuse means any shape similar to the bullet containing
some enclosed material. In cartridge type fuse the fuse wire is enclosed in a tube,
bulb or case of some good insulating heat resistance material of the whole unit
is sealed off.
In case the fuse blows out due to some fault or over load it is replaced by a fresh
unit as the cartridge cannot be rewired due to its sealing. And some of cartridge
fuses are Rewirable type. These are fixed in its fuse carrier like the Kit-Kat unit.
H.R.C fuse: H.R.C fuse means high rupturing capacity fuse. It is in similar
construction to the cartridge type with the exception that the fuse wire (material)
can carry short circuit heavy current for a known time period. During this time
if the fault is removed, then it does not blow off otherwise it blows off and breaks
the continuity of the circuit.
The cartridge unit is either of glass or some other chemical compound that
is air tight construction to avoid the effect of atmosphere on the fuse material.
This effect may lower its related capacity due to continuous slow oxidation of
the wire materials. HRC cartridge fuse consists of a ceramic body having metal
end caps to which are welded fusible silver (or bimetallic) current carrying
elements.
The space within the body surrounding the elements is complexly packed with
a powder. This type of fuse is reliable and has inverse time characteristics.
Current Carrying Capacity of Fuse Element: the current carrying capacity of
a fuse element mainly depends on the metal used and the sectional area but it is
also affected by the length, the state of surface and the surrounding of the fuse.
3
I Kd 2
K=proportional constant
Application of fuses:
Protection cables
Protection of bus bars
Protection of motors
Protection of low voltage distribution systems against over load and short
circuits
Back up protection to circuit breakers
Protection of semiconductor devices
ARC PHENOMENON:
The arc consists of a column of ionized gas I.e., a gas which molecules have lost
one or more of their electrons resulting in positive ions and electrons.the
ionization is facilitated by
An increase in field strength.
Increase in mean free path.
High temperature.
The electrons which have a negative charge are attracted towards the positive
contact i.e., anode and the electrons being light moves towards anode quickly.the
positive ions are attracted towards the negative contact i.e., cathode, but as the
positive ions comprise almost the entire weight of the atom they move towards
the negative of the atom they move towards the negative contact collide slowly.
Thus the fast moving electron collides with the slow moving ion constituting an
arc between the contacts. When a fault occurs in power system, an enormous
power can be fed into the fault, which requires the opening of circuit.the circuit
can be opened with the help of a circuit breaker. while opening the contacts of
circuit breaker an arc is established between the contacts. This arc should be
extinguished as early as possible.
Arc Voltage:
The voltage drop across the arc is called arc voltage.
The arc voltage and current characteristics can be expressed as
Rated voltage:
The rated maximum voltage of a circuit breaker is the highest rms
voltage above nominal system voltage, for which the circuit breaker ids
designed and is the upper limit for operation.
Rated current:
The rated normal current of a circuit breaker is the designed limit
of current in rms amperes which it shall be capable of carrying
continuously without exceeding the limit of observable temperature
rise.
Rated symmetrical and asymmetrical breaking capacities: Breaking
current of the circuit breaker is the current in that pole at the instant
constant-separation. It is expressed by two values.
Symmetrical breaking current:
It is the value of symmetrical breaking current, which the circuit
breaker is capable of breaking at stated recovery voltage and stated
reference RV (recovery voltage) under prescribed conditions. This is the
rms value of AC component in the pole at the instant of contact separation.
x
I rms I sym
2
Asymmetrical breaking current: It is the value of asymmetrical
breaking current, which the circuit breaker is capable of breaking at stated
recovery voltage and stated reference RV (recovery voltage) under
prescribed conditions. This is the rms value of the total current comprising
the AC and DC components in the pole at the instant of contact separation.
x
2
I asym y2
2
Rated making capacities: the making current of a circuit breaker when
closed on a short circuit. The making capacity of a circuit breaker is the
current that the circuit breaker is capable of making as stated voltage
under prescribed conditions of use and behavior.
3.Test values
Compare bolted connection resistance to values of similar connections.
Microhm or millivolt drop values shall not exceed the high levels of
the normal range as indicated in the manufacturer's published data. If
manufacturer's data is not available, checks investigate values, which
deviate from similar connections by more than 50 percent of the lowest
value.
Control wiring insulating resistance should be a minimum of 1 meg
ohms.
Trip characteristic of breakers shall fall within manufacturer's
published time-current characteristic tolerance band, including
adjustment factors.
Instantaneous pickup values of moulded-case circuit breakers shall be
within the tolerances, shown in Table -6
10.5.7 Low voltage Power Circuit Breakers
1. Visual and Mechanical Inspection
Compare equipment nameplate data with drawings and specifications.
Inspect physical and mechanical condition.
Confirm correct application of manufacturer’s recommended
lubricants.
Inspect anchorage, alignment and grounding. Inspect arc chutes.
Inspect moving and stationary contacts for condition, wear and
alignment.
Check that all maintenance devices are available for servicing and
operating the breaker.
Check the primary and secondary contact wipe and other dimensions
vital to satisfactory operation of the breaker are correct.
Perform all mechanical operation and contact alignment test on both
the switch and its operating mechanism.
Inspect all bolted electrical connections for high resistance.
Check cell fit and element alignment
Check racking mechanism.
2. Electrical tests
Perform a contact-resistance test.
Perform resistance measurements through all bolted connections with
low-resistance ohmmeter, if applicable.
Perform insulation resistance tests at 300 volts DC from pole-to-pole
and from each pole-to-ground with breaker closed and across open
contacts of each phase.
Perform insulation resistance tests at 300 volts DC on all control
wiring. Do not perform the test on wiring connected to solid state
components.
Make adjustments for final settings in accordance with coordination
study supplied by owner.
Determine minimum pickup current by primary current injection.
Determine long-time delay by primary current injection.
Determine short-time pickup and delay by primary current injection.
Determine ground-fault pickup and delay primary current injection.
Determine instantaneous pickup current by primary injection.
Activate auxiliary protective devices, such as ground-fault or under
voltage relays, to insure operation of shunt trip devices. Check the
operation of electrically operated breakers in their cubicles.
Check correct operation of any auxiliary features such as trip and
pickup indicators, zone interlocking, electrical close and trip operation,
trip-free, and anti pump function and verify trip unit battery condition
Check operation of charging mechanism.
3. Test values
Compare bolted connection resistance to values of similar connections.
Microhm or millivolt drop values shall not exceed the high levels of
the normal range as indicated in the manufacturer's published data. If
manufacturer's data is not available, investigate any values, which
deviate from similar connections by more than 50 percent of the lowest
value.
Control wiring insulating resistance should be a minimum of two
megohms.
Trip characteristics of breakers shall fall within manufacturer's
published time-current tolerance bands.
3. Test values
Compare bolted connection resistance to values of similar connections.
Microhm or millivolt drop values shall not exceed the high levels of
the normal range as indicated in the manufacturer's published data. If
manufacturer's data is not available, investigate any values which
deviate from similar connections by more than 50 percent of the lowest
value.
Circuit breaker insulation resistance should be in accordance with Table
–1.
Control wiring insulating resistance should be a minimum of two
megohms.
Dissipation-factor/ power-factor test results shall be compared with
previous tests of similar breakers or manufacturer's published data.
The insulation shall withstand the over potential test voltage applied.
Minimum pick up for trip and close coils shall conform to manufacturer's
published data.
2. Electrical tests
Perform a contact resistance test.
Remove a sample of insulating liquid and test for dielectric breakdown
voltage, colour, visual condition etc.
Trip circuit breaker by operation of each protective device.
Perform insulation-resistance tests pole-to-pole, pole-to-ground, and
across open poles at 2500V minimum.
Perform insulation resistance tests on all control wiring at 500V DC.
Do not perform this test on wiring connected to solid-state relays.
Perform dissipation factor/ power factor tests on each pole with
breaker open and each phase with breaker closed. Determine tank loss
index.
Perform power-factor/ dissipation factor tests on each bushing. Use
conductive straps and hot collar procedures if bushings are not
equipped with a power factor tap.
Check trip, close, trip-free and anti-pump functions.
Perform minimum pickup voltage tests on trip and close coils.
Perform an over potential test in accordance with manufacturer's
instructions.
3. Test values
Compare bolted connection resistance to values of similar
connections.
Microhm or millivolt drop values shall not exceed the high levels
of the normal range as indicated in the manufacturer's published
data. If manufacturer's data is not available, investigate any values,
which deviate from similar connections by more than 50 percent of
the lowest value.
Compare circuit breaker travel and velocity values to
manufacturer's acceptable limits.
Insulating-liquid test results should comply transformer insulating
oil standard.
Control wiring insulating resistance should be a minimum of two
meg ohms.
Dissipation-factor/ power-factor test results and tank loss index
shall be compared to manufacturer's published data. In the absence
of manufacturer's published data, the comparison shall be made to
similar breakers.
The insulation shall withstand the over potential test voltage
applied.
Minimum pick up for trip and close coils shall conform to
manufacturer's published data.
2. Electrical tests
Perform a contact-resistance test.
Perform minimum pick up voltage tests on trip and close coils.
Verify trip, close, trip-free and anti-pump function.
Trip circuit breaker by operation of each protective device.
Perform resistance measurements through all bolted connections
with a low-resistance ohmmeter, if applicable,
Perform insulation-resistance tests pole-to-pole, pole-to-ground,
and across open poles at 2500 volts minimum.
Perform vacuum bottle integrity (over potential) test across each
vacuum bottle with the breaker in the open position in strict
accordance with manufacturer's instructions.
Perform insulation-resistance tests at 500 volts on all control wiring
DC. For units with solid-state components, follow manufacturer's
recommendations.
Perform dissipation factor/ power factor tests on each pole with
breaker open and each phase with breaker closed.
Perform dissipation-factor/ power factor tests on each bushing. Use
conductive straps and hot collar procedures if bushings are not
equipped with a power factor tap.
Perform an over potential test in accordance with manufacturer's
instructions.
3. Test values
Compare bolted connection resistance to values of similar
connections.
Bolt-torque levels should be in accordance with Table 7.12 unless
otherwise specified by manufacturer.
Microhm or millivolt drop values shall not exceed the high levels
of the normal range as indicated in the manufacturer's published
data. If manufacturer's data is not available, investigate any values
which deviate from similar connections by more than 50 percent of
the lowest value.
Contact displacement shall be in accordance with factory recorded
data marked on the nameplate of each vacuum switch or bottle.
The interrupter shall withstand the overpotential voltage applied.
Compare circuit breaker timing value to manufacturer's published
data.
Control wiring insulating resistance should be a minimum of two
megohms.
Dissipation-factor/ power-factor test results and tank loss index
shall be compared to manufacturer's published data. In the absence
of manufacturer's published data, the comparison shall be made to
similar breakers.
Dissipation-factor/ power-factor and capacitance test results should
be within ten percent of nameplate rating for bushings.
The insulation shall withstand the over potential test voltage
applied.
2. Electrical tests
Perform a contact resistance test.
Perform resistance measurements through all bolted connections
with a low-resistance ohmmeter, if applicable
Perform insulation-resistance tests pole-to-pole, pole-to ground,
and across open poles at 2500 volts minimum.
Perform insulation-resistance tests on all control wiring at 500
volts DC. For units with solid-state components, follow
manufacturer's recommendations.
Perform dissipation factor/ power factor tests on with breaker and
bushings.
Perform an over potential test in accordance with manufacturer's
instructions.
Perform minimum pick-up voltage test on trip and close coils.
Check trip, close, trip-free, and anti pump functions.
Trip circuit breaker by operation of each protective device.
3. Test values
Compare bolted connection resistance to values of similar connections.
Microhm or millivolt drop values shall not exceed the high levels of
the normal range as indicated in the manufacturer's published data. If
manufacturer's data is not available, investigate any values which
deviate from similar connections by more than 50 percent of the lowest
value.
Compare time-travel data with manufacturer's published data.
Control wiring insulation resistance should be a minimum of two meg
ohms.
Dissipation-factor/ power-factor test results and tank loss index shall
be compared to manufacturer's published data. In the absence of
manufacturer's published data, the comparison shall be made to similar
breakers.
Dissipation-factor/ power factor and capacitance test results should be
within ten percent of nameplate rating for bushings.
The insulation shall withstand the over potential test voltage applied.
Minimum pickup for trip and close coils shall conform to
manufacturer's published data.
2. Electrical tests
Perform a contact resistance test.
Remove a sample of insulating liquid. Sample shall be tested for
the following: -
Dielectric breakdown voltage:
Trip circuit breaker by operation of each protective device.
Check trip, close, trip-free and anti-pump function.
Perform insulation-resistance tests pole-to-pole, pole-to-ground,
and across open poles at 1500 volts minimum.
*Perform insulation-resistance tests on all control wiring at 500
volts DC. For units with solid-state components, follow
manufacturer's recommendations.
Perform power-factor tests on each pole with breaker open and
each phase with breaker closed. Determine tank loss index.
Perform power-factor tests on each bushing. Use conductive
straps and hot collar procedures, if bushings are not equipped with
a power factor tap.
Perform minimum pickup voltage tests on trip and close coils.
Perform an over potential test in accordance with manufacturer's
instructions.
3. Test values
Compare bolted connection resistance to values of similar
connections.
Microhm or millivolt drop values shall not exceed the high levels
of the normal range as indicated in the manufacturer's published
data. If manufacturer's data is not available, investigate any values
which deviate from similar connections by more than 50 percent of
the lowest value.
Compare circuit breaker travel and velocity values to
manufacturer's acceptable limits.
Insulating-liquid test results should comply transformer oil
requirements.
Control wiring insulating resistance should be a minimum of two
meg ohms.
Dissipation-factor/ power-factor test results and tank loss index
shall be compared to manufacturer's published data. In the absence
of manufacturer's published data, the comparison shall be made to
similar breakers.
Dissipation-factor/ power factor and capacitance test results should
be within ten percent of nameplate rating for bushings.
The insulation shall withstand the over potential test voltage
applied.
Minimum pick up for trip and close coils shall conform to
manufacturer's published data.
2. Electrical tests
Perform a contact resistance test.
Perform resistance measurements through all bolted connections with
a low-resistance ohmmeter.
Perform insulation-resistance tests pole-to-pole, pole-to-ground, and
across open poles at 2500 volts minimum.
Perform insulation-resistance tests on all control wiring at 500 volts
DC. For units with solid-state components, follow manufacturer's
recommendations.
Perform dissipation factor/ power factor tests on with breaker and
bushings.
Perform an over potential test in accordance with manufacturer's
instructions.
Perform minimum pick-up voltage test on trip and close coils.
Check trip, close, trip-free, and anti-pump functions.
Trip circuit breaker by operation of each protective device. \
3.Test values
Compare bolted connection resistance to values of similar connections.
Microhm or millivolt drop values shall not exceed the high levels of
the normal range as indicated in the manufacturer's published data. If
manufacturer's data is not available, investigate any values, which
deviate from similar connections by more than 50 percent of the lowest
value.
Compare time-travel data with manufacturer's published data.
Control wiring insulation resistance should be a minimum of two meg
ohms.
Dissipation-factor/ power-factor test results and tank loss index shall
be compared to manufacturer's published data. In the absence of
manufacturer's published data, the comparison shall be made to similar
breakers.
Dissipation-factor/ power factor and capacitance test results should be
within ten percent of nameplate rating for bushings.
The insulation shall withstand the over potential test voltage applied.
Minimum pickup for trip and close coils shall conform to
manufacturer's published data.
contacts as per
1. Trip the circuit breaker by pressing the trip push button of the release.
This is necessary to check the mechanical setting of the release.
2. For Secondary Injection Method, disconnect all the wires from magneto
thermal release.
3. Set the release at point 1.0 for all three phase as shown below.
4. Wire normally open (NO) auxiliary contact of ACB in series with test
panel’s Auxiliary contact. (This is to cut off the current flowing through the
release as soon as ACB trips).
5. Find out the rated C.T. secondary current. For L&T ACB rated C.T.
secondary current is 8.75 AMP.
Calculate the test current as follows:
* For 2 times overload (200%)
Test current = Rated C. T. secondary current x No. of times of
overload
= 8.75 x 2
= 17.50 amps.
6. Find out the minimum and maximum trip time for 200% and 300%
overload from the manufacturer curves and noted down in the table below.
7. Switch on the supply and adjust the test current. Immediately switch off
the current. Keep the variac at adjusted position. Reset the time counter.
Release setting = one
Sr. Test Trip Time in Sec. Remarks
No. Current OK / Not
(Amp.) OK
Actual As Per Curve
R Y B Min. Ma
x.
8. Switch on the current and check trip time of the ACB. Fill up the data in
above table.