Comprehensiv SLD
Comprehensiv SLD
9/29/2023 2:10:05 PM
BIM 360://SA_SA215BIW_SAMI_AIC/40101-2-JCB-000000-1UE-CM-000001.rvt
GENERAL NOTES
A A
1. ALL ELECTRICAL EQUIPMENT, PROTECTIONS & SUPERVISION
REQUIREMENTS SHALL BE IN ACCORDANCE TO APPLICABLE SBC/SEC
SEC SUPPLY LOCAL REQUIREMENTS & SEC LATEST STANDARD TECHNICAL
(SS-7727) SPECIFICATION FOR ELECTRICAL WORKS & PROJECT SPECIFICATION.
2. FOR MV SWITCHGEAR, ALL INCOMERS AND OUTGOING FEEDERS
SHALLCOMMUNICATE WITH SCADA/PMS WITH IEC 61850 PROTOCOL,
MOTOR AND OUTGOING FEEDERS SHALL COMMUNICATE WITH SCADA/PMS
WITH MODBUS TCP/IP PROTOCOL.
13.8kV/0.42kV 13.8kV/0.42kV 3. CT AND PT RATINGS, CLASS, AND QUANTITY SHALL BE VERIFIED AND
300kVA 300kVA FINALIZED BY VENDOR.
611714-1EQ-TR-001 611714-1EQ-TR-002 4. EACH MV & LV SWITCHBOARD/ PANEL BOARD TO BE PROVIDED WITH 20%
OUTDOOR OUTDOOR SPARE FEEDERS ALONG WITH 10% SPACE FOR FUTURE.
611714-1EQ-DG-001
TRANSFORMER TRANSFORMER 5. ALL DISTRIBUTION BOARDS & PANELS TO BE CONSIDERED WITH ANALOGUE
300kVA,
Dyn11, ONAM, Dyn11, ONAM, AMMETER AND ANALOGUE VOLTMETER ALONG WITH ITS SELECTOR
400V, 3-PHASE,
%Z=4% %Z=4% SWITCH.
60Hz, GENERATOR
OLTC+/-5% OLTC+/-5% 6. THE PANEL/ DISTRIBUTION BOARD DETAILS SHALL COMPLY WITH SBC/SEC
IN STEPTS OF 2.5% IN STEPTS OF 2.5% REGULATIONS AND STANDARDS.
B 611714-1ES-MVSG-001
13.8kV MV SWITCHBOARD 7. ALL MOTOR STARTER COMPARTMENTS SHALL INCLUDE B
LOC: SS 08 (611714) LOCAL/AUTO/OFFSELECTOR SWITCH, START/STOP/RESET
611714-1ES-MDB-001 BUTTON/EMERGENCY STOP BUTTON, AND ASSOCIATED INDICATOR LAMPS
MAIN LV SWITCHBOARD 500A
2000A 2000A MCCB 8. ALL ASSOCIATED MOTOR PROTECTION DEVICES SHALL BE EQUIPPED IN
VCB ATS VCB LOC: SS 08 (611714) THE PANEL AS PER THE MOTOR MANUFACTURER RECOMMENDATION
NC 500A
NC NC 500A 9. FIRE RATED CABLES SHALL BE USED TO SUPPLY FIRE & LIFE SAFETY
ATS MCCB EQUIPMENT AS PER THE KSA FLS CODE
2000A, 13.8kV, 60HZ, MCCB NO
NC 10. THE SURGE PROTECTION DEVICE SELECTION (TYPE AND LOCATION) SHALL
25kA FOR 1SEC. 400V, 3-PHASE, BE FINALIZED BASED ON THE RECOMMENDATIONS OF THE APPROVED
4-WIRE, 60Hz, 500A, LIGHTNING PROTECTION SPECIALIST AND IN LINE WITH LOCAL
25kA FOR 1 SEC. REGULATIONS & INTERNATIONAL STANDARDS
11. THE RATING OF ELR/ RCD/ ELCB SHALL BE AS PER AUTHORITIES
REGULATION
630A 630A 800A 630A 800A 630A 630A 630A 630A 630A 630A 630A 800A 630A 800A 630A 630A 12. 20% SPARE FEEDERS AND 10% SPARE SPACE TO BE PROVIDED IN ALL
VCB VCB VCB VCB VCB VCB VCB VCB VCB VCB VCB VCB VCB VCB VCB VCB VCB BC-1 BC-2 DISTRIBUTIONS BOARDS AND SUB DISTRIBUTIONS BOARDS.
NO
13. FOR LEGENDS AND SYMBOLS REFER TO DRAWING NO. 40101-2-
MCCB JCB-000000-1UE-11-000001 (SITE ELECTRICAL LEGENDS, SYMBOLS SINGLE
NO NC
C BUS
SECTION 14.
LINE DIAGRAM).
EACH VCB & ACB FEEDER SHALL BE PROVIDED WITH 6 NOS. INDICATING C
2000A VCB BUS BUS LAMPS. VIZ. ON, OFF, TRIP, SERVICE, TEST, OPERATION.
SECTION SECTION 15. SERIAL NUMBER (SR.NO) INDICATED IN THE FEEDER SCHEDULE TABLE
500A 500A REPRESENTS THE SEQUENCE OF FEEDERS.
MCCB MCCB 16. COMMUNICATION BETWEEN NUMERICAL RELAYS FOR CONTACTOR
CONTROLLED MOTOR/HEATER FEEDERS AND EPDMS/PAS SHALL BE
SPARE
SPARE
SPARE
SPARE
THROUGH LAYER-3 SWITCH WHICH WILL BE PART OF PAS (ICSS) SYSTEM.
17. THE SEC MVSG PANEL 611714-1ES-MVSG-001 TO BE AS PER SEC
SPECIFICATION & STANDARDS NUMBER 32-SDMS-08 AND 32-SDMS-09. FINAL
TYPICAL EQUIPMENT SELECTION TO BE DECIDED BY CONTRACTOR BASED ON THE
DB MENTIONED SEC SPECIFICATIONS, STANDARDS, AND MANUFACTURER
RECOMMENDATION.
18. ALL THE SEC PROTECTION AND METERING INSTRUMENT TRANSFORMERS
CT & PT SIZING TO BE AS PER SEC STANDARD NUMBER TES-P-119.28. FINAL
EQUIPMENT SELECTION TO BE DECIDED BY CONTRACTOR BASED ON THE
MENTIONED SEC STANDARD, AND MANUFACTURER RECOMMENDATION..
D D
614401- Grenades
Manufacturing
800A 800A
VCB ATS VCB
630A 630A 630A 630A NC
VCB VCB VCB VCB NC
NO 13.8kV, 3-PHASE, 3-
WIRE, 60Hz, 800A, 25kA
FOR 1 SEC.
BUS
F SECTION
800A VCB
F
BUS 630A
630A 630A 630A
SECTION VCB
VCB VCB VCB
NO 800A VCB
611715-1EQ- 611715-1EQ- 614201 - MEDIUM 611709 - CENTRAL
TR-003 TR-004 CALIBER 611715-1EQ- 611715-1EQ-
COMPRESSED AIR
2000kVA 2000kVA MANUFACTURING TR-005 TR-006
BUILDING 02 PUMPS
13.8/0.42kV, 13.8/0.42kV, 611715-1EQ-DG-001 2000kVA 2000kVA
AN, Dyn 11 AN, Dyn 11 FURTHER DETAIL 2000kVA, 13.8/0.42kV, 13.8/0.42kV,
Z=6% Z=6% 40101-2-JCB-614201- 400V, 3-PHASE, AN, Dyn 11 AN, Dyn 11
OLTC+/-5% OLTC+/-5% 1EP-08-000001 60Hz, GENERATOR Z=6% Z=6%
OLTC+/-5% OLTC+/-5% 611713-1EQ- 611713-1EQ-
611713-1EQ- 611713-1EQ- TR-005 TR-006
TR-003 TR-004 611705 - CHILLER 2000kVA 2000kVA
400V, 400V, 400V, 400V,
2000kVA 2000kVA PLANT PUMPS 13.8/0.42kV, 13.8/0.42kV, STAMP
3200A 3200A 3200A 3200A AN, Dyn 11 AN, Dyn 11
13.8/0.42kV, 13.8/0.42kV,
BUSDUCT BUSDUCT BUSDUCT BUSDUCT
G AN, Dyn 11
Z=6%
AN, Dyn 11
Z=6%
Z=6%
OLTC+/-5%
Z=6%
OLTC+/-5% G
OLTC+/-5% OLTC+/-5%
3200A 3200A
3200A 3200A
ACB ACB 3200A
ACB ACB
NC NC ACB
ATS NO NC ATS
NC 400V, 400V,
3200A 3200A 611715-1EQ-DG-001 400V, 400V,
400V, 3-PHASE, 400V, 3-PHASE, 3200A 3200A
4-WIRE, 60Hz, 3200A, 4-WIRE, 60Hz, 3200A, BUSDUCT BUSDUCT 1600kVA,
400V, 3-PHASE, BUSDUCT BUSDUCT
25kA FOR 1 SEC. 25kA FOR 1 SEC.
60Hz, GENERATOR
3200A
3200A ACB 2500A KEYPLAN
ACB 3200A 3200A
NC ACB
BC-1 BC-2 BC-1 NC ATS ACB ACB
MCCB MCCB NO NC ATS
NC
NO NC NO 400V, 3-PHASE,
4-WIRE, 60Hz, 3200A, 400V, 3-PHASE,
H BUS
25kA FOR 1 SEC. 4-WIRE, 60Hz, 3200A,
25kA FOR 1 SEC.
H
BUS BUS
616003 - DEPOT SECTION 613001 - CHEMICAL 613002 - SECTION 613002 - 613004 - WAREHOUSE 616003 - DEPOT SECTION
SECURITY GATE 3200A ACB STORAGE WAREHOUSE 01 3200A ACB WAREHOUSE 01 03 (FUTURE) SECURITY GATE 3200A ACB
MCCB BC-1 BC-2
FURTHER DETAIL FURTHER DETAIL FURTHER DETAIL FURTHER DETAIL FURTHER DETAIL BC-1
40101-2-JCB-616003- 40101-2-JCB-613001- 40101-2-JCB-613002- 40101-2-JCB-613002- 40101-2-JCB-616003-
1E0-08-000002 1EP-08-000001 1EP-08-000001 1EP-08-000001 1E0-08-000002 NO NC
NO
611709 - CENTRAL EVSE - ELECTRIC
611701 - PROCESS 641702 - CONTROL BUS BUS
COMPRESSED AIR VEHICLES BUS
613003 - WAREHOUSE 613004 - WAREHOUSE 613001 - CHEMICAL 613003 - WAREHOUSE 614401- Grenades WATER ROOM-RADIO MAST SECTION 611704 - MAIN 641702 - CONTROL 611704 - JOCKEY SECTION
BUILDING 02 CHARGER - 1,2 & 3 SECTION
02 (FUTURE) 03 (FUTURE) STORAGE 02 (FUTURE) Manufacturing TREATMENT PLANT 3200A ACB ELECTRIC FIRE ROOM-RADIO MAST PUMP (EMERGENCY) 3200A ACB
3200A ACB
FURTHER DETAIL PUMP (EMERGENCY) xxx 12-SEP-23 ISSUED FOR REVIEW
FURTHER DETAIL 40101-2-JCB-611709- 611704 - PUMP 611703 - IRRIGATION
40101-2-JCB-613001- 00E 01-AUG-23 ISSUED FOR REVIEW
1E0-08-000001 ROOM AND WATER TANKS AND 616001 - 616002 - GATE 611705 - CHILLER
1EP-08-000001 MAIN GATE NO.1 - MOI 00D 19-JUN-23 ISSUED FOR REVIEW
K. NARGUNDE
614402-40mm 614201-Medium Caliber TANKS PUMPING STATION PLANT
S. WILHOITE
00C 24-NOV-22 ISSUED FOR REVIEW
R. MUMTAZ
Grenades HE Loading Manufacturing 611713 - Outdoor 611702 - SEWAGE
R. TATIA
Area Lighting TREATMENT PLANT FURTHER DETAIL FURTHER DETAIL FURTHER DETAIL 00B 22-AUG-22 ISSUED FOR REVIEW
J FURTHER DETAIL
40101-2-JCB-611704- 40101-2-JCB-616001- 40101-2-JCB-616002- 40101-2-JCB-611705-
00A 05-MAY-22 ISSUED FOR REVIEW
J
1E0-08-000002 1E0-08-000002 1E0-08-000002 1E0-08-000001
APPROVED
DESIGNED
CHECKED
DRAWN
REV. NO DATE REASON FOR ISSUE
631701-1ES-RMU-001 13.8kV MV SWITCHGEAR
DRAWING
STATUS 90% DESIGN
621702-1ES-RMU-001 13.8kV MV SWITCHGEAR KINGDOM OF SAUDI ARABIA
13.8kV/420V 13.8kV/420V
REFERENCE DRAWING: 1250kVA 1250kVA
631701-1EQ-TR-001 631701-1EQ-TR-002
DRAWING NUMBER DRAWING TITLE 631701-1EQ-DG-001
DRY TRANSFORMER DRY TRANSFORMER
630kVA,
Dyn11, AN, Dyn11, AN,
400V, 3-PHASE,
40101-2-JCB-000000-1UE-06-000001 PROTECTION SCHEMATIC DIAGRAM MV SWITCHGEAR 01 %Z=5% %Z=5%
60Hz, GENERATOR
13.8kV/420V 13.8kV/420V OLTC+/-5% OLTC+/-5%
40101-2-JCB-000000-1UE-06-000002 PROTECTION SCHEMATIC DIAGRAM MV SWITCHGEAR 02 1000kVA 1000kVA IN STEPTS OF 2.5% IN STEPTS OF 2.5%
K 40101-2-JCB-000000-1UE-06-000003 PROTECTION SCHEMATIC DIAGRAM LV SWITCHGEAR 621702-1EQ-TR-001 621702-1EQ-TR-002 621702-1EQ-DG-001 K
DRY TRANSFORMER DRY TRANSFORMER 800kVA, 400V, 400V,
Dyn11, AN, Dyn11, AN, 2000A 2000A
Jacobs Engineering. No part of this document or the information it contains may be reproduced or transmitted in any form or by any means electronic or mechanical,