MIL-PRF-19004B
MIL-PRF-19004B
com
INCH-POUND
MIL-PRF-19004B
25 May 2001
SUPERSEDING
MIL-F-19004A
18 April 1983
PERFORMANCE SPECIFICATION
1. SCOPE
1.1 Scope. This specification covers centrifugal fans for use in Naval
shipboard heating, ventilating, and air conditioning systems.
2. APPLICABLE DOCUMENTS
2.1 General. The documents listed in this section are specified in Sections
3 and 4 of this specification. This section does not include documents cited
in other sections of this specification or recommended for additional
information or as examples. While every effort has been made to ensure the
completeness of this list, document users are cautioned that they must meet
all specified requirements documents cited in sections 3 and 4 of this
specification, whether or not they are listed.
2.2 Government documents.
MIL-PRF-19004B
STANDARDS
DEPARTMENT OF DEFENSE
MIL-STD-167-1 Mechanical Vibrations of Shipboard Equipment
(Type I - Environmental and Type II - Internally
excited)
MIL-STD-1399 Interface Standard for Shipboard Systems, Sect
300, Electric Power, Alternating Current
MIL-STD-2031 Fire & Toxicity Test Methods and Qualification
Procedures for Composite Systems
MIL-STD-2142 Magnetic Silencing Characteristics, Measurement
of
PUBLICATIONS
2
Downloaded from http://www.everyspec.com
MIL-PRF-19004B
(Application for copies should be addressed to the Air Movement and Control
Association, Inc., 30 West University Drive, Arlington Heights, IL 60004-
1893.)
2.4 Order of precedence. In the event of a conflict between the text of this
specification and the references cited herein, the text of this specification
takes precedence. Nothing in this document however, supersedes applicable
laws and regulations unless a specific exemption has been obtained.
3
Downloaded from http://www.everyspec.com
MIL-PRF-19004B
3. REQUIREMENTS
3.2.1.1 Composite fan casing. Fan casing shall withstand a full-scale fire
performance test.
3.2.1.2 Fan internal components. Composite material to be used for motor,
vanes, impeller and conduit shall withstand small-scale material specimen fire
tests as outlined in 4.8.2.
3.2.3 Fasteners. Material for all bolts, nuts, studs, screws and similar
fasteners shall be corrosion-resistant passivated or of a material rendered
resistant to corrosion. Sheet metal screws shall not be used. Galling shall
be prevented. Tapped holes shall be reinforced where shearing of thread can
occur.
3.2.6 Dissimilar metals. The fan and components shall not degrade due to
electrolysis (see 6.7).
3.3.1 Factory coating. Equipment and component items shall be delivered with
the manufacturers standard finish, except as to comply with the requirements
of 3.2.
4
Downloaded from http://www.everyspec.com
MIL-PRF-19004B
3.4.1 Fan identification code. The size and characteristics of Navy standard
fan motor units shall be designated by a code formed by alternate letters and
numbers arranged in the following sequence:
Examples: 3
1. CC5A4W6CW-NS-WT represents a nominal 5000 ft /min centrifugal, non-
sparking watertight construction fan, clockwise rotation, driven by
a 440-V, 3-phase, 60 Hz ac, spraytight, 149 °F ambient temperature
motor. Navy standard fans with special electrical characteristics
shall have shortened fan codes, with electrical characteristics
identified by text and preceded by the letter
3
“S”.
2. X-CC6A4W6CCW represents a nominal 6000 ft /min centrifugal fan,
counterclockwise rotation, with commercial motor, driven by a 440-V,
3-phase, 60 Hz ac, 149 °F ambient temperature motor.
5
Downloaded from http://www.everyspec.com
MIL-PRF-19004B
a. Manufacturer’s identification.
b. Fan code.
c. CID number.
d. Direction of airflow and rotation.
e. Manufacturer’s serial number and drawing number.
f. Bearing Lubrication.
3.6.1 Reliability. Reliability shall meet specified values (see Appendix C).
3.9.1 High impact shock resistance. Unless otherwise specified (see 6.2),
Type CC fan-motor units shall meet the shock requirements of MIL-S-901 for
Grade A, class 1 equipment.
3.9.2 Vibration and balance. Fan-motor units shall be designed such that no
damage will occur or malfunction is caused by the environmental vibrations
specified in MIL-STD-167-1. Fan-motor units shall be in static and dynamic
balance. The vibration amplitude shall not exceed the limits for type II
bearing vibration as specified in MIL-STD-167-1.
6
Downloaded from http://www.everyspec.com
MIL-PRF-19004B
3.11 Sizes. Sizes of CC and X-CC fans shall be limited to those listed in
Table I.
3.15 Fan and motor base. The fan and motor bases shall be designed so that
they can accommodate a fan discharge of any possible discharge position
through 360 degrees, without modification as per AMCA 2406-66.
7
Downloaded from http://www.everyspec.com
MIL-PRF-19004B
3.16.2 Conduit box. A conduit box shall be provided on the motor. It shall
meet tightness requirements of motor enclosure.
TABLE II. Speed and horsepower of 440 V,3 phase, 60 Hz motors, type CC and
X-CC fans.
3.16.5 Bearing temperature rise. Bearing temperature rise shall not exceed
63 °F in 149 °F ambient as measured on bearing outer ring. For quiet
bearings, temperature rise shall not exceed 45 °F in 149 °F ambient as
measured on bearing outer ring.
3.16.6 Drains. All spraytight motors shall be provided with not less than
four condensate drain holes fitted with plugs. The holes shall be positioned
around the motor end bell(s).
8
Downloaded from http://www.everyspec.com
MIL-PRF-19004B
3.17.1 Volume and pressure. The design point for each size of Navy standard
centrifugal fans is the volume-pressure point at the maximum total pressure
(TP) shown for that size on Table I and Figure 2. The TP shall rise
continually from free delivery to a value at least as high as the stated value
shown in Table
3
I, and throughout this range shall exhibit stable performance.
Volume in ft /min shall be within 5 percent of the volume on the applicable
curve of Figure 2, as indicated on system characteristic curves. Total
pressure developed by a fan is the pressure at the fan discharge, and the
volume is the volume at fan inlet.
TORQUE
Locked Pullup
Fan Locked rotor current rotor Breakdown as percent
Size percent specified minimum
minimum
1/4 NEMA MG 1 + 10 percent 70 NEMA MG 1 70
1/2 NEMA MG 1 + 10 percent 70 NEMA MG 1 70
1 NEMA MG 1 + 10 percent 70 NEMA MG 1 70
1-1/2 NEMA MG 1 + 10 percent 70 NEMA MG 1 70
2 NEMA MG 1 as specified 70 NEMA MG 1 70
3 NEMA MG 1 as specified 70 NEMA MG 1 70
4 NEMA MG 1 as specified 70 NEMA MG 1 70
5 NEMA MG 1 as specified 70 NEMA MG 1 70
6 NEMA MG 1 as specified 70 NEMA MG 1 70
8 NEMA MG 1 as specified 70 NEMA MG 1 70
10 NEMA MG 1 as specified 70 NEMA MG 1 70
3.17.3 Airborne noise. The total sound power levels for the fan-motor unit
shall not exceed the levels stated in Table IV when measured in accordance
with procedures stated in 4.7.5. Exceeding the total sound power levels
specified in Table IV shall be cause for rejection.
9
Downloaded from http://www.everyspec.com
MIL-PRF-19004B
4. VERIFICATION
4.2 First article inspection. First article inspection shall consist of the
examinations of 4.6 and tests as specified in Table V. The tests specified
shall be performed on each size fan-motor unit.
10
Downloaded from http://www.everyspec.com
MIL-PRF-19004B
11
Downloaded from http://www.everyspec.com
MIL-PRF-19004B
4.7.1.1 Shock on lightweight machine. The motor and fan support shall be
mounted as shown on Figure 4c of MIL-S-901. The test shall consist of nine
blows with the unit operating at maximum speed and nine blows with the unit
not engaged.
4.7.1.2 Shock on medium weight machine. The test of a fan-motor unit shall
consist of nine blows indicated in Table VI. The required mountings for
required tests in Table VI are as follows: (Designations for rotation and
discharge of centrifugal fans are in accordance with AMCA 2406-66).
Upon completion of the shock test, post-shock test inspection, and tests
specified in Table V, the fan-motor unit shall be returned to the contractor
for examination and further testing.
12
Downloaded from http://www.everyspec.com
MIL-PRF-19004B
on the edge of each flange, and one vertical measurement on the top edge of
each flange. The maximum amplitude of vibration shall be the maximum single
reading and not an average. The operating frequency at which the maximum
amplitude occurs shall be measured. Exceeding vibration limits specified in
3.9.2 is cause for rejection.
4.7.4.1 Stall and recovery. Tests shall be conducted in accordance with AMCA
210.
4.7.5 Airborne noise. Octave band sound power levels for a fan-motor unit
shall consist of the measurement of sound pressure levels and the computation
of sound power levels in accordance with procedures and instrumentation
requirements defined in AMCA 300-96, and amendments to those procedures as
identified herein. The fan-motor unit shall be operated at the design point
during airborne noise testing, see 3.17.1. Dual speed fans shall be operated
at high speed during noise tests. All sound measuring instrumentation shall
be laboratory calibrated within one year of the date of test, excluding the
reference sound source which shall comply with the laboratory calibration
requirements stated in AMCA 300-96. A random incidence response microphone
and a type I (precision) sound level meter conforming to the requirements of
AMCA 300-96 shall be used. The minimum distance between the extreme points of
the microphone swing as described in AMCA 300-96 shall be 27 ft., and the
speed of traverse of the microphone shall not exceed 2.4 ft./sec. Sound
pressure readings shall be a time-weighted average over an integral number
(one or more) of microphone swings. Sound pressure level readings shall be
averaged over a minimum period of observation of 30 sec. Resilient mounts
shall be loaded within the design load range for the type of mount selected.
The frequencies of the natural modes of vibration of the mounted fan in the
vertical direction shall not exceed 11 Hz or one-fourth of the lowest forcing
frequency of the fan, whichever is lower. When a duct section is attached to
a fan-motor unit to facilitate measurements, it shall have the same interior,
open cross sectional dimensions as that of the fan-motor unit to which it is
attached. There shall be no exposed sound absorbing material on the interior
or exterior surfaces of the attached ducts. No sound attenuating devices
shall be installed within attached ducts. An orifice plate shall be
installed if necessary to obtain design pressure at a known operating point.
If an orifice plate is installed, it shall be a quiet type that does not
produce excessive flow-induced noise.
13
Downloaded from http://www.everyspec.com
MIL-PRF-19004B
duct if necessary to obtain fan-motor unit operation at the design point. The
fan-motor unit with attached discharge duct shall be placed within the
chamber. A section of the discharge duct, approximately 2 to 3 duct diameters
long and housing an orifice plate, shall extend into the reverberant test
room, and sound pressure level measurements shall be made within the reverb-
erant test room. Acoustical treatments shall be placed within the chamber as
necessary to provide an acoustic seal at the penetration in the wall
separating the chamber from the reverberant room, and to ensure that no noise
contributions are transmitted from the chamber into the reverberant test room.
4.7.7.1 Air leakage rate. The motor of explosion-proof fan-motor units shall
have motor enclosure air leakage rate measured to determine whether the rate
of leakage exceeds that determined in 4.7.7. Any explosion-proof motor where
there is evidence that the predetermined rate of leakage is exceeded when
measured shall not be offered for delivery.
4.7.8 Casing tightness. The casing tightness test shall be conducted as
follows:
14
Downloaded from http://www.everyspec.com
MIL-PRF-19004B
a. Blank flanges (one with air supply and gauge connections) shall be
bolted to gasketed fan flanges.
b. Air at a pressure 50 percent higher than the maximum pressure
capability of the fan shall be supplied to the casing interior.
4.7.9 Speed. The fan-motor unit shall be operated at each speed at free
delivery to determine whether the motor speed is at least 97 percent of the
design speed at rated voltage (see Table II). A speed of less than 97 percent
of the design speed is cause for rejection.
4.8 Composite material testing. Composite material shall be tested for flame
spread, smoke obscuration, combustion gas igniteability, heat release, and
mass consumed.
4.8.1 Fan casing and conduit box.
4.8.1.1 Internal fire test. Fan casing and conduit box material shall be
subjected to an internal fire insult as described in the full-scale Factory
Mutual test for horizontal duct FM-4922 with modifications see (Figure 3).
4.8.1.2 External fire test. Fan casing and conduit box material shall be
subjected to an external fire insult as outlined in Figure 4. Temperatures
around outside of test specimen shall exceed minimum temperatures prescribed
by ASTM-E-119 for at least 15 minutes.
4.8.2 Internal composite materials. Fan impeller, vanes, and motor composite
materials shall meet the smoke obscuration (ASTM-E-662) test as follows:
15
Downloaded from http://www.everyspec.com
MIL-PRF-19004B
6. NOTES
16
Downloaded from http://www.everyspec.com
MIL-PRF-19004B
6.5 Drawings. When final drawings are required (see 6.2) and comments on new
drawings are approved, adjudicated or reconciled, the contractor is
responsible to: (1) forward final fan and motor drawings to acquisition
activity; and (2) include special requirements of the contract or order prior
to distribution of final drawings. (See Appendix A)
17
Downloaded from http://www.everyspec.com
MIL-PRF-19004B
6.9.1 The reliability assurance program should include provisions for the
reliability review and evaluation of design as an integral part of the
contractor’s engineering design procedures. Design or engineering changes
occurring during development or production should be submitted to comparable
review procedures.
6.9.2 Use of composite material requires NAVSEA review of the fire and
toxicity performance for the composite material system. The Nonmetallic
Materials Branch of NAVSEA has review responsibility for use of composite
material systems on naval vessels.
6.11 Changes from previous issue. Marginal notations are not used in this
revision to identify changes with respect to the previous issue due to the
extent of the changes.
18
Downloaded from http://www.everyspec.com
MIL-PRF-19004B
19
Downloaded from http://www.everyspec.com
MIL-PRF-19004B
20
Downloaded from http://www.everyspec.com
MIL-PRF-19004B
THERMOCOUPLES
AS PER FM4922
FIRE PAN
FAN STEEL DUCT
The purpose of the test is to assess the structural integrity and the smoke
characteristics of the composite material separating the ship’s internal
compartments from the air flow within the confines of the composite envelope.
Gases released to weather are also assessed as they can be re-ingested into
the ship.
Modifications to FM4922 are as follows:
Test material
All of the test ducting described above (composite and supplemental steel
sections, if utilized), can be provided in the form of rectangular or circular
cross-sections (depending on the envisioned application; i.e., round for fan
casings, rectangular for cabinets) that are each 6ft long and flanged for
bolted connection (with gasketing) to each other to make up the entire
standard 24-ft test length. If rectangular ducting cross-sections are
utilized, the following nominal dimensions are recommended: 12 inches by 24
inches by nominal thickness (not to exceed 1.5 inches). If circular ducting
cross-sections are utilized, the internal diameter should not be less than 18
inches nor greater than 20 inches and the wall thickness of the test ducts
should not exceed 1.5 inches.
Test apparatus:
FIGURE 3. Modified factory mutual fire test for composite material (FM4922)
subject to internal fire insult.
21
Downloaded from http://www.everyspec.com
MIL-PRF-19004B
#5
#5
72”
36” #4
#4
#3 #2
#3, #2
#1 #1
60”
18” 30”
Notes
The fan-motor section material (1 ft by 2 ft by 6 ft long duct) is exposed for
15 minutes to a hexane fire capable of temperatures between 1400 to 1600
degrees F. The sealing flanges are to be cooled by a water spray. The air
pressure should be monitored with time. The fire tray is 18 inches by 30
inches, filled with hexane fuel floating on water. The fire tray is oriented
so that the longer side is perpendicular to the longitudinal axis of the duct.
Five thermocouples are used to monitor the temperatures.
#1 thermocouple: under side of the duct in the middle, just above the fire
#2 thermocouple: inside the duct, in the middle
#3 thermocouple: along the side of the duct
#4 thermocouple: on top of the duct, in the middle
#5 thermocouple: about 2 feet above the duct, in the middle
22
Downloaded from http://www.everyspec.com
MIL-PRF-19004B
APPENDIX A
A.1 SCOPE
A.1.1 Scope. This appendix covers the technical content requirements that
should be included on drawings when required by the contract or order. This
appendix is not mandatory and is provided for informational purposes only.
A.2. APPLICABLE DOCUMENTS
A.2.1 Government documents.
A.2.1.1 Specification and standard. The following specification and standard
form a part of this document to the extent specified herein. Unless otherwise
specified, the issues of these documents are those listed in the issue of the
Department of Defense Index of Specifications and Standards (DODISS) and
supplement thereto, cited in the solicitation.
SPECIFICATION
DEPARTMENT OF DEFENSE
MIL-T-31000 Drawings, Engineering and Associated Lists
STANDARD
DEPARTMENT OF DEFENSE
MIL-STD-740-2 Structureborne Vibratory Acceleration
Measurements and Acceptance Criteria of
Shipboard Equipment
A.3 DRAWINGS.
A.3.1.1 Fan assembly drawing. The fan assembly drawing should include the
following:
23
Downloaded from http://www.everyspec.com
MIL-PRF-19004B
APPENDIX A
24
Downloaded from http://www.everyspec.com
MIL-PRF-19004B
APPENDIX B
B.1.1 Scope. This appendix covers the technical content requirements that
should be included in test reports when required by the contract or order.
This appendix is not mandatory and is provided for informational purposes
only.
B.3.1 Test reports. When required by the contract or order, test reports
should contain the following information:
a. Results first article tests (see 4.2).
b. Results of quality conformance tests (see 4.3).
c. Results of shock test (see 4.7.1) with the following unique
features:
25
Downloaded from http://www.everyspec.com
MIL-PRF-19004B
APPENDIX B
26
Downloaded from http://www.everyspec.com
MIL-PRF-19004B
APPENDIX C
RELIABILITY
C.1 SCOPE
C.1.1 Scope. This appendix covers the information and procedures necessary
to ensure that the reliability requirements of this specification are met.
This appendix is a mandatory part of the specification. The information
contained herein is intended for compliance.
27
Downloaded from http://www.everyspec.com
MIL-PRF-19004B
28
Downloaded from http://www.everyspec.com
6. SUBMITTER
a. NAME (Last, First, Middle Initial) b. ORGANIZATION
c. ADDRESS (Include Zip Code) d. TELEPHONE (Include Area Code) 7. DATE SUBMITTED
(1) Commercial (YYYYMMDD)
(2) DSN
(if applicable)
8. PREPARING ACTIVITY
a. NAME b. TELEPHONE (Include Area Code)
SEA O5Q Ruth Butler (1) Commercial (2) DSN
(202) 781-3726 326-3726
c. ADDRESS (Include Zip Code) IF YOU DO NOT RECEIVE A REPLY WITHIN 45 DAYS, CONTACT:
Commander, Naval Sea Systems Command Defense Standardization Program Office (DLSC-LM)
ATTN: SEA 05Q, 2531 Jefferson Davis Hwy 8725 John J. Kingman Road, Suite 2533,
Fort Belvoir, VA 22060-6221
Arlington, VA 22242-5160 Telephone (703) 767-6888 DSN 427-6888
DD Form 1426, FEB 1999 (EG) PREVIOUS EDITION IS OBSOLETE WHS/DIDR, Feb 99