s Data Sheet

Fire Safety & Security Products

Intelligent Detection Devices


Intelligent Thermal Detector
[For use with FireFinder® XLS and MXL Panels]
Model FPT-11
ARCHITECT AND ENGINEER SPECIFICATIONS
 Innovative technology provides high-speed,
fault-tolerant system / detector
communications
 Compatible with Model DPU or FPI-32
field programmer / tester
 Multi-color, detector-status
light-emitting diode (LED)
 Optional fully-programmable relay
and audible bases Microprocessor-based design

 UL and ULC Listed;  Two-wire operation


FM, CSFM & NYCFD Approved  Rate compensated
Product Overview Specifications
The Intelligent Thermal Detector (Model FPT-11) from Model FPT-11 is a plug-in, two-wire thermal detector that is
Siemens ─ Fire Safety provides an advanced method of compatible with FireFinder XLS and MXL FACPs. Each
detection, address programming and supervision ─ Model FPT-11 detector has microcomputer-chip
combined with sophisticated fire alarm control panel technology, as well as highly stable, solid-state electronic
(FACP) communication. Model FPT-11 uses a state-of-the- circuitry.
art thermistor that provides up to 135°F (57.2°C) rate- Model FPT-11 utilizes a modern, accurate and shock-
compensated temperature. resistant thermistor to sense temperature changes. This
Model FPT-11 is compatible with Model DPU and FPI-32 electronic sensing method virtually eliminates thermal lag
Field Programmer / Testers, which are compact, portable associated with mechanical-temperature sensing devices,
and menu-driven accessories that make programming and provides almost instantaneous temperature
and testing detectors faster, easier and more reliable information to the FACP.
than other methods.
Model FPT-11 is a 135°F (57.2°C) rate-compensated
Each of these field programmers / testers eliminate the detector. The microprocessor for Model FPT-11 detector
need for cumbersome, unreliable mechanical uses the EEPROM means to store the detector’s address.
programming methods, and they reduce installation and Communications within the detector, as well as between
service costs, via electronically erasable programmable Model FPT-11; the FACP, or with each field programmer /
read-only memory (EEPROM), and can test Model FPT-11’s tester, are supervised and safeguarded against disruption
performance (for proper function) before the detector is by reliable microprocessor-based error-checking routines.
even installed. Moreover, mechanical-addressing
Additionally, the microprocessor supervises all EEPROM
mechanisms ─ such as program jumpers, DIP switches or
memory locations, and provides a high tolerance to
rotary dials ─ are no longer necessary to use.
EEPROM faults.

Intelligent Thermal Detector 6176


s Industry, Inc.
Building Technologies Division
Specifications ─ (continued)
Model FPT-11 is UL and ULC Listed as a self-testing device. Models DB-11, DB-X11 RS, and ADBX-11 use screw-clamp
The visible LED from Model FPT-11 flashes green every four terminals for all electrical connections and self-wiping
seconds to indicate Model FPT-11 is communicating with the contacts for reliability. The bases also contain a provision
FACP, as well as to signify Model FPT-11’s successful passing for an optional, concealed locking mechanism to prevent
of its self-test. Should the detector sense a fault or failure unauthorized removal of the detector head, Model LK-11.
within its systems, the LED will flash amber, and the detector
will transmit the fault or failure back to the FACP.
Application Data
A quick, visual inspection is sufficient to indicate the condition
FireFinder XLS uses Model MLC, but the MXL FACP uses
of the detector at any time. If more detailed information is Model ALD ─ with each respective circuit capable of
required, a printed report can be provided from the FACP, supporting up to 60 Model FPT-11 intelligent detectors.
indicating the status and settings assigned to each individual
detector. The detector (or group of detectors) require a minimum
two-wire circuit of 18 American Wire Gauge (AWG)
When Model FPT-11 moves to the Alarm mode, Model FPT-11
thermoplastic-fixture wire enclosed in conduit ─ or a
will flash amber, and will transmit data to the FACP. When
minimum 18 AWG-limited energy, shielded cable without
the FACP confirms the current condition of Model FPT-11, the
panel will instruct Model FPT-11 detector to flash red until the conduit, per local building codes. Wiring should conform
system is reset at the FACP. At that same time, any user- to local and national electrical codes, as well as the wiring
defined, system-alarm functions programmed into the specifications of the FACP. ‘T-tapping’ is permitted only
FireFinder XLS or MXL system are activated. Each Model for Class B (Style 4) wiring.
FPT-11 detector can operate one (1) remote alarm indicator; Locate Model FPT-11 on the ceiling, at least 4 inches from
one (1) auxiliary relay ─ or one (1) audible base, and only one the side walls. For an ideal, smooth-ceiling condition,
(1) accessory, per detector. place the detectors at a maximum center spacing of 50
Model DPU or Model FPI-32 is used to program and verify the feet (2,500 square feet) ─ 25 feet from side walls or room
address for Model FPT-11. The end-user selects the Program partitions. For FM-Approved installations, Model FPT-11
mode to enter the desired address. Then, the programmer / has a relative-temperature index (RTI) rating of ‘QUICK.’
tester automatically sets and verifies the address, as well as Use a maximum center spacing of 20 feet (400 square
test the detector. The programmer / tester contains feet) ─ 10 feet from side walls or room partitions.
rechargeable batteries in order for the address of Model FPT-
Actual job conditions and sound engineering judgment
11 to be programmed by the end-user from a portable
location. The user can also separately test the Model FPT-11 must determine detector spacing. Be sure to consider
detector for functionality. environmental factors, including ambient-temperature
fluctuation and the nature of the fire hazard. Room or
When the end-user selects the ‘test’ mode, a series of tests are
area configuration and ceiling type (sloped or flat; smooth
automatically conducted, and the user is informed whether
or beamed) also dictates placement.
Model FPT-11 detector has passed or failed.
Should questions arise regarding detector placement,
Model FPT-11 detector is compatible on the same
follow the drawings provided and / or approved by
initiating circuit with other Model IL-series, Model FP-series or
Siemens ─ Fire Safety, or by its authorized distributors.
Model ID-60-series addressable ionization, photoelectric, or
thermal detectors; Model MSI addressable manual stations;
Model TRI-series addressable interfaces, or Model CZM-series Technical Data
addressable conventional-zone modules.
Current Requirements: Normal: 750 µa
Each Model FPT-11 is capable of operating one (1) ‘X’ or ‘I’- Alarm: 750 µa
series remote-alarm indicator, or auxiliary relay or audible
base. Operating Temperatures: +32°F (0°C) to
Model FPT-11 detectors use a surface-mounting base (Model +120°F (49°C)
DB-11) which mounts on a 4-inch octagonal, square or single-
gang electrical box. Relay base Model DB-X11 RS mounts to a Relative Humidity: 0-93%;
4-inch square deep electrical box. Audible base Model ADBX- Non-condensing
11 also mounts to a 4-inch square deep electrical box.

s Industry, Inc.
Building Technologies Division
Mounting Diagram Details for Ordering
Model Part
Number Number Description

ADBX-11 500-096181 Audible Base for Series 11 Detectors


Detector Mounting Base for Series 11
DB-11 500-094151
Intelligent Detectors
DB-11E 500-094151E Small, 4.5-Inch Diameter Detector Base
DB-ADPT 500-094187 Base Adapter to Model DB-3S Base
DB-X11RS 500-096125 Relay Base for Series 11 Detectors
FPT-11 500-095918 Addressable Thermal Fire Detector
LK-11 500-695350 Base Locking Kit for Series 11 Detectors
Remote Alarm Indicator;
RLI-1 500-390673
octagon-box mount, red
Remote alarm Indicator;
RLI-2 500-695350
single-gang box mount, red

In Canada, order:
Model Part
Number Number Description

Audible Base for Series 11 Detectors,


ADBX-11C 500-096181C
[ ULC]
Detector Mounting Base for Series 11
DB-11C 500-095687
Intelligent Detectors, [ ULC]
Relay Base for Series 11
DB-X11RS 500-096125C
Intelligent Detectors, [ ULC]
Addressable Thermal Fire Detector,
FPT-11C 500-095918C
[ ULC]

s Industry, Inc.
Building Technologies Division
Notice: This marketing data sheet is not intended to be used for system design or installation purposes.
For the most up-to-date information, refer to each product’s installation instructions.

Fire Safety Fire Safety


8 Fernwood Road 2 Kenview Boulevard
s Industry, Inc. Florham Park, NJ 07932 Brampton, Ontario June 2012
Building Technologies Division Tel: (973) 593-2600 SII-FS L6T 5E4 / Canada Supersedes sheet dated 7/09
FAX: (908) 547-6877 Printed in U.S.A. Tel: (905) 799-9937 (Rev. 2)
URL: www.usa.Siemens.com/Fire FAX: (905) 799-9858