Electrical Thumb Rules You MUST Follow Part 7

Uploaded by

dinesh.munaswamy
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

electrical-engineering-portal.com http://electrical-engineering-portal.

com/electrical-thumb-rules-you-must-follow-part-7

Electrical Thumb Rules You MUST Follow (Part 7)


jiguparmar

Electrical Thumb Rules You MUST Follow, part 7 (photo by joy russell via Flickr)

Continued from: Electrical Thumb Rules You MUST Follow (Part 6)

8 electrical thumb rules to follow:

1. Overhead conductor / cable size

Voltage Overhead Conductor Cable Size

33 KV ACSR-Panther/Wolf/Dog , AAAC 150,185,300,400,240 mm2 Cable

11 KV ACSR-Dog/Recon/Rabbit , AAAC 120, 150,185,300 mm2 Cable

LT ACSR-Dog/Recon/Rabbit , AAC, AAAC 95,120, 150,185,300 mm 2 Cable

Go back to Rules ↑

2. Transmission / distribution line (span, tower height)


Span Height of Tower

400KV = 400 Meter 400KV=30Meter (Base 8.8 Meter)

220KV = 350 Meter 220KV=23Meter (Base 5.2 Meter)

132KV = 335 Meter 220KV Double Circuit=28 Meter

66KV = 210 Meter 66KV=13Meter

Conductor Ampere Voltage wise Conductor

Dog = 300Amp 400KV=Moose ACSR=500MVA Load

Panther = 514Amp 220KV=Zebra ACSR=200MVA Load

Zebra = 720Amp 132KV=Panther ACSR=75MVA Load

Rabbit = 208Amp 66KV=Dog ACSR=50MVA Load

Moose = 218Amp

Go back to Rules ↑

3. Types of Towers

Type Used Angle/Deviation

A Suspension Tower Up to 2°

B Small Angle Tower 2° to 15°

C Medium Angle Tower 15° to 30°

D Large Angle / Dead End Tower 30° to 60° & Dead End

Go back to Rules ↑

4. Tower Swing Angle Clearance (Metal Part to Live Part)

Swing Angle Live Part to Metal Part Clearance (mm)

66KV 132KV 220KV 400KV

0° 915mm 1530mm 2130mm 3050mm

15° 915mm 1530mm 2130mm -

22° - - - 3050mm

30° 760mm 1370mm 1830mm -

44° - - - 1860mm

44° 610mm 1220mm 1675mm -

Go back to Rules ↑
5. Cable Coding, IS 1554 (A2XFY/FRLS/FRPVC/FRLA/PILC)

A Aluminium

2X XLPE

F Flat Armoured

W Wire Armoured

Y Outer PVC Insulation Sheath

W Steel Round Wire

WW Steel double round wire Armoured

YY Steel double Strip Armoured

FR Fire Retardation

LS Low Smoke

LA Low Acid Gas Emission

WA Non Magnetic round wire Armoured

FA Non Magnetic Flat wire Armoured

FF Double Steel Round Wire Armoured

Go back to Rules ↑

6. Corona Ring Size

Voltage Size

<170 KV 160mm Ring put at HV end

>170 KV 350mm Ring put at HV end

>275 KV 450mm Ring put at HV end & 350 mm Ring put at Earth end

Go back to Rules ↑

7. Load as per Sq.Ft

Type of Load Load/Sq.Ft Diversity Factor

Industrial 1000 Watt/Sq.Ft 0.5

Commercial 30 Watt/Sq.Ft 0.8

Domestic 15 Watt/Sq.Ft 0.4


Lighting 15 Watt/Sq.Ft 0.8

Go back to Rules ↑

8. Size of Ventilation Shaft

Height of Building in meter Size of ventilation shaft in sq meter Minimum size of shaft in meter

9.0 1.5 1.0

12.5 3.0 1.2

15 and above 4.0 1.5

Go back to Rules ↑