setare declansator electronic_EATON Example
setare declansator electronic_EATON Example
1. Overview around
trip units
Trip unit
Common trip units for IZMX16 and IZMX40
Trip units – basic offer
Sample: P-Type
IZMX40H3-A32W 1150 LSI(G/A)
U-Type
520M LSI(G)
V-Type
520 LSI(G)
A-Type
520 LI
Professional protection
Universal protection
Selective protection
Distribution protection
Basic functions and optional functions
Catalog - overview
Page 6
Catalog - overview
Page 7
Catalog - excerp:
Further trip unit options
Page 39
Digitrip - trip units
Pictures of variants
2. Overview
trip units
top -> down
IZMX16 and IZMX40 circuit breaker
Digitrip trip units
For all trip units same function:
Reset-Button:
• Optional:
- Automatic RESET
- Remote RESET (magn. Coil with different
voltages)
NEU
IZMX16 and IZMX40 circuit breaker
Digitrip trip units
For all trip units same function:
Test socket:
• connecting test devices:
IZM-TEST-KIT or
IZM-SIM-KIT
3. Setting of the
protection
parameters
Digitrip trip units
„overview“ – setting of the protection parameters
For all trip units A,V, U same function
all time
all settings
LED‘s for current
tripping settings
cause
Digitrip trip units
„overview“ – setting of the protection parameters
time (t)
In=4000A
Ir=0,5-1 xIn
L
2-24s
S 2-10 xIn
100-500ms
10
LD = 1.0x
TIME IN SECONDS
LDT = 4 s
4
3 SD = 4x
2 SD = Flat
SDT = 0.3s
1
0.9 INST = Off
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
1 4 6 10
Current in multiples of Ir
Time Current Curves – Long and Short
Ir = 1.0
0.9 x 1000A = 500A
0.5 1000A
900A
20
10
0.9
LD = 0.5
1.0
TIME IN SECONDS
LDT = 4 s
4
3 SD = 4
2 SD = Flat
SDT = 0.3s
1
0.9 INST = Off
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
1 4 6 10
Current in multiples of Ir
Time Current Curves – Long and Short
Ir = 1.0 x 1600A
1000A = 1600A
1000A
20
10 1600A
LD = 1.0x
TIME IN SECONDS
LDT = 10
4 ss
4
3 SD = 4x
2 SD = Flat
SDT = 0.3s
1
0.9 INST = Off
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
1 4 6 10
Current in multiples of Ir
Time Current Curves – Long and Short
Ir = 1.0 x 1000A = 1000A
20
10
LD = 1.0x
TIME IN SECONDS
4
LDT = 4 s
3 4x
SD = 10x
2 SD = Flat
SDT = 0.3s
1
0.9
0.8
INST = Off
0.7
0.6
0.5
0.4
0.3
0.2
0.1
1 4 6 10
Current in multiples of Ir
Time Current Curves – Long and Short
Ir = 1.0 x 1000A = 1000A
20
10
LD = 1.0x
TIME IN SECONDS
LDT = 4 s
4
3 SD = 4x
2 SD = Flat
SDT = 0.3s
0.5s
1
0.9 INST = Off
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
1 4 6 10
Current in multiples of Ir
Time Current Curves – Long and Short
Ir = 1.0 x 1000A = 1000A
20
10
LD = 1.0x
TIME IN SECONDS
LDT = 4 s
4
3 SD = 4x
2
2 SD = IFlat
t
SDT = 0.3s
1
0.9 INST = Off
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
1 4 6 10
Current in multiples of Ir
Time Current Curves – Instantaneous
Ir = 1.0 x 1000A = 1000A
LDT
LDT == 44 ss
4
3 SD
SD == 4x
4x
2 SD
SD == Flat
Flat
SDT
SDT == 0.3s
0.5s
0.5s
1
0.9 INST
INST == Off
10x
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
1 4 6 10
Current in multiples of Ir
Time Current Curves – Instantaneous
2.0
1.0
LD = 1.0x
TIME IN SECONDS
0.5
0.4
LDT = 4 s
0.3 SD = 4x
0.2 SD = Flat
SDT = 0.5s
0.1
0.09
0.08
INST = 10x
0.07
0.06
0.05
0.04
0.03
0.02
0.01
1 4 6 10
Current in multiples of In
Catalog
Main optional trip unit functions
4. Catalog
Options
(G) Earth fault protection
(A) Earth fault alarm
(M) ARMS
(Z) ZSI (Zone selective interlocking)
Catalog (G) Earth fault protection
Power System Grounding
L1 L1
L1
L2 L2
L2 L3
L3 L3
N
L1
L2
L1 L1
L3
L2 L2
L3 L3
N
L1
L2
L3
Ground Current Protection
3 Phasen + Neutral Grit
Load
CT with copper
termination
Required:
External current transformer – to be
wired on the auxiliary terminals 17
and 18. and a jumper on Terminal
19 and 20.
Article: IZMX-EFS
Catalog
(A) Earthfault - Alarm
Patent of EATON
IZMX16 and IZMX40 circuit breaker
Digitrip trip units
without ARMS with ARMS
Additional
protection in cases
of maintanance
ARMS
In cases of an arc fault the tripping of
the trip unit speeds up. The released
energies are reduced as: Radiation,
Temperature, Pressure, Forces of
magnetic fields.
ARMS
Arc Reduction Maintenance System
• ARMS can be enabled
manually at the trip unit or
IZMX16 / IZMX40
automatically / remotely by a contact
before maintenance in the field begins
Remote: External contact on 33, 34
• An LED die displays ARMS active or an external
signal lamp on terminal 11, 12.
• ARMS is faster than the un-delayed short circuit
protection.
• A control voltage of 24 VDC (+, -10%) at the
terminals 21, 22 is required.
Catalog
(Z) ZSI = Zone Selectiv Interlocking
CB1
ZSI
tsd = 300ms
Zone 1
CB2 CB3
tsd =200ms ZSI tsd = 200ms ZSI
Zone 2 2
M
CB4 CB5
sd sd
t = 100ms ZSI t =100ms ZSI
Zone 3
3
IZMX16 and IZMX40 circuit breaker
Digitrip trip units
5. Further information
Thermal Memory
• Thermal Memory
Jumper on Digitrip
520 / 520M
• Program setting on
Digitrip 1150
Thermal Memory
For all trip units same function:
• A, V, U- trip unit
Thermal Memory is active when
the jumper is removed
• P- trip unit
Program setting
Upgrade (exchange) of trip units in the field
The trip units are now easier and saver Sockel
exchangeable. Re-wiring of the important
current transformers are no more risk.
• The socket contains the „acknowledge“ of the breaker
IZMX16 and IZMX40:
• Breakig capacity Icu / Ics
• Rated short circuit withstand Icw,
• max. rated current,
• Max. making current
…and belongs / remains in the breaker.
• The socket informs the exchangeable trip unit
about this breaker data
• Unmistakeable exchange of trip unit and via coding
even for the rating plug
• Toolless exchange (plug and work)
• Socket contains the Battery, (storage of tripping
causes)
• Battery Test- and Reset-Button. -> The Intensity of the
Battery-LED informs about the Battery condition.
Longer actuation resets the tripping cause information.
Rogowski-sensor
Input of 100A
Market Standard
for Breakers
60A 140A
Meter
Special
Bus Bar
Extra
Wiring
2.
• Rate to 690Vac,
• One PT Module for 16
breaker
IZMX16 (NF) • Switches integrated,
• Compact housing,
• DIN rail mounting on back
Protective Relay Features
To be highlighted:
• Relay Protection package
• User enable/disable with Time Delay
• Adjustable under/over voltage release (trip or alarm)
• Adjustable under/over frequency release (trip or alarm)
• Voltage unbalance (trip or alarm)
• Reverse power (trip)
• Phase Rotation (alarm)
Digitrip 1150 Slope Selection
• Slope • Slope
Selection Selection
• I2T • I4T
Digitrip 1150 Slope Selection
• Slope Selection
• I2T
• I4T
• IEC A (Normal Inverse)
• IEC B (Very Inverse)
• IEC C (Extremely Inverse)
Communication
„Interfaces“
PROFIBUS-DP
•V0 Slave
ModbusRTU ECAM
•Slave
PCAM
MCAM
Ethernet
•ModbusTCP i.V.
IZM
•SMTP Mail
•http(s) WebServer
ICAM
IncomBUS
(USA)
IZMX 16/40
IZMX Communication Modules
Flexible Communication Platform —
Modbus RTU
PROFIBUS DP
Ethernet
INCOM
Module / address stays with cassette
Communications “Open” and “Close” via
module not through trip unit
+24 Volt DC control power
Use with U- und P-trip units
Communications
Open / Close via bus - Wiring
The Communication modul Spring release SR and
contains change over Ashunt trip ST in the
contacts for ON and breaker
OFF coils
IZMX Communication module installation
IZMX16 and IZMX40 Switch disconnector
(without trip unit)
Switch disconnector INX…
•Without trip unit
•without internal current
transformer
•With making current
release (MCR)