Assignment 4 2024
Assignment 4 2024
Assignment 4
Problem 1
A three phase Y/Y transformer delivers a load of 66 MW at 0.8 p.f. lagging and 138 KV (line to line). The
primary voltage under these conditions is 14.34 KV (line to line), the apparent power is 86 MVA and the
power factor is 0.78 lagging.
Problem 2
Find the inductive reactance per mile per phase for a single-phase line with phase separation of 30 ft and conductor
radius of 0.09 ft.
Problem 3
A 1000 KV, single phase, bundle conductor line has 10 sub-conductors per phase. The phase spacing is D1 =
16 m, and the sub-conductor spacing is S = 55cm. Each sub-conductor has a diameter of 6 cm. Calculate the
line inductance.
Problem 4
Calculate the inductance per phase of an H-Type three phase solid conductor line if the conductor diameter is 6 cm
and the phase separation between the middle conductor and the left or the right conductor is 10 m.
Problem 5
Calculate the inductance in H/m per phase for 1100 KV, bundle conductor line shown in Fig. 1. Assume
phase spacing D1 = 15.24 m, bundle separation S = 45.72 cm, and conductor diameter is 3.556 cm.