• The text and graphics included in this manual are for the purpose of illustration and reference
only. The specifications on which they are based are subject to change without notice.
• Information in this document is subject to change without notice.
Catalog Number
2.1 Warnings
• To avoid electric arcing and hazards to personnel and electrical contacts, never
connect/disconnect the servo drive while the power source is on.
• Power cables can carry a high voltage, even when the motor is not in motion. Disconnect the
Gold Bell from all voltage sources before servicing.
• The high voltage products within the Gold Line range contain grounding conduits for electric
current protection. Any disruption to these conduits may cause the instrument to become hot
(live) and dangerous.
• After shutting off the power and removing the power source from your equipment, wait at least
1 minute before touching or disconnecting parts of the equipment that are normally loaded
with electrical charges (such as capacitors or contacts). Measuring the electrical contact points
with a meter, before touching the equipment, is recommended.
2.2 Cautions
• The maximum DC power supply connected to the instrument must comply with the parameters
outlined in this guide.
• When connecting the Gold Bell to an approved isolated control power supply, connect it
through a line that is separated from hazardous live voltages using reinforced or double
insulation in accordance with approved safety standards.
• Before switching on the Gold Bell, verify that all safety precautions have been observed and
that the installation procedures in this manual have been followed.
3.1.1 Accessories
• Cable Kit (TBD)
Note on current ratings: The current ratings of the Gold Bell are given in units of DC
amperes (ratings that are used for trapezoidal commutation or DC motors). The RMS (sinusoidal
commutation) value is the DC value divided by 1.41.
Elmo offers a 200 VDC maximum output rating selection of Gold Bell, according to the following
technical data:
Amplitude sinusoidal/DC A 3 6 9
continuous current
STO TTL √
Single Ended 1
Communication USB √
Option
EtherCAT √
CAN √
Feature Details
Operating ambient temperature 0 °C to 40 °C (32 °F to 104 °F)
according to IEC60068-2-2
Storage temperature -20 °C to +85 °C ( -4 °F to +185 °F)
The related standards below apply to the performance of the servo drives as stated in the
environmental conditions in section 4.2.3 Environmental Conditions above.
STO IEC 61800-5-2:2007 SIL 3 Adjustable speed electrical power drive systems –
Safety requirements – Functional
Chapter 5: I nstallation
The Gold Bell must be installed in a suitable environment and properly connected to its voltage
supplies and the motor.
4. Verify that the Gold Bell type is the one that you ordered, and ensure that the voltage meets
your specific requirements.
The part number at the top provides the type designation. Refer to the appropriate part
number in the section Catalog Number at the beginning of the installation guide.
7.2 COMRET
For details of the COMRET, refer to the section 5.4 in the MAN-G-Board Level Modules Hardware
Manual.
The connections to PE are essential, but must be done externally to the integration board.
• Power Zone
This area is dedicated to Power conductors only: VP+, PR, PE, VL+, VL-, VN- and motor leads.
• Control and Communication Zone
This area of the PCB is dedicated to Control low level signals
For more details, refer to the section 5.4 in the MAN-G-Board Level Modules Hardware Manual.
Earth Connection
Twisted-pair wires
Encoder Earthing.
The cable`s shield is connected to the
chassis (PE) in the connector.
Earthing the Encoder and connecting
the Earth (PE) to the drive COMRET is
mandatory to insure reliable
operation, high noise immunity and
rejection of voltage common mode
interferences.
Connector Location
Pin Positions
Note: The 12V to 195V DC power source must be from the Mains.
Connect the DC power source cable to the VP+ and PR terminals on the main power connector.
To connect your integration board to the DC power source:
1. The DC power supply source must be isolated from the Mains.
2. For best immunity, it is highly recommended to use twisted and shielded cables for the DC
power source. A 3-wire shielded cable should be used. The gauge is determined by the actual
current consumption of the motor.
3. Connect the cable shield to the closest earth connection near the power supply.
4. Connect the PE to the closest earth connection near the power supply.
5. Connect the PR to the closest earth connection near the power supply.
6. Before applying power, first verify the polarity of the connection.
Table of Contents |Connector J2 |www.elmomc.com
Gold Bell Installation Guide
MAN-G-BELIG (Ver. 1.200)
26
Note: The source of the Control Supply must be from the Mains.
Note: Make sure to connect the PR to the closest earth connection near the power supply.
* It is strongly recommended to add a filter on the VL+ Input Pin at the Gold Bell, in order to avoid
interference from the power stage e.g. noises. The following figure describes the filter
recommended.
Figure 9: Single Power Supply Connection Diagram with VL+ Connected Internally to
Recommended Filter
Note: Make sure to connect the PR to the closest earth connection near the power supply.
Figure 10: Single Power Supply Connection Diagram with VL+ connected externally
Note: Make sure to connect the PR to the closest earth connection near the power supply.
Note: Make sure to connect the PR to the closest earth connection near the power supply.
• Endat 2.2
• Biss C and Biss B
• Pansonic
• Tamagawa
• SSI
• Sanyo Danki
• Hiperface
The following is the diagram connection of the Endat, Biss, SSI:
Figure 14: Absolute Serial Encoder – Recommended Connection Diagram for Endat, Biss, SSI
Figure 15: Absolute Serial Encoder – Recommended Connection Diagram for Pansonic, Tamgawai,
Sanyo-Danki
9.6.1.4 Hiperface
The following figure describes the connection diagram.
Figure 16: Absolute Serial Encoder – Recommended Connection Diagram for Stegmann
Hiperface
Note: When the Hiperface protocol is used the RS232 in not available
9.6.2.3 Resolver
Figure 23: Standard RS232 Voltage Level incorporating RS232 TX/RX Transceiver Connection
Diagram
Note ①: In the Gold Bell the shield of the USB connector should be connected to the COMRET
and not the PE.
9.6.7 EtherCAT/Ethernet
The Gold Bell serves as an EtherCAT slave device, therefor it includes EtherCAT_IN and
EtherCAT_OUT ports. It also includes LED indicators. The EtherCAT_IN port can be configured to an
Ethernet port.
The following figure describes EtherCAT connection with a standard RJ-45 connector that includes
transformer isolation.
9.6.8 CAN
Figure 26 displays the CAN connectivity.
Figure 28: Digital Output Connection Diagram – Isolated Open Collector and Open Emitter
Connection
Caution:
Before applying power, ensure that the DC supply is within the specified range
and that the proper plus-minus connections are in order.
• Thermal time constant: Approximately 240 seconds (thermal time constant means that the Bell
will reach two-thirds of its final temperature after 4 minutes.)
6.0
Heatsink
Power Dissipation (W)
Required
5.0
Standard 40 °C Ambient Temp.
4.0
Heatsink
3.0 not Required
2.0
1.0
0.0
85VDC
0
5
1
5
2
5
3
5
4
5
5
0.
1.
2.
3.
4.
70VDC
Peak Current (A)
50VDC