BOQ

Product: Nurse Call System Model 4.0


Customer Name:SVIM Hospital, Agra
S. No. Area- Floors No. Of Central Station 19" LED No of Bed Head unit Toilet Calling Toilet Calling Unit Door indicator Door indicator NCRM with Bed/Room
Beds Module (CDU) Monitor CDU with Patient Unit withpull withpull Cord (NCS-S-DU15) ***Double SMS facility Numbers -
(NCS-S-CDM^) (NCS-P- Handset Cord **Multibedded Bedded Rooms (NCS-S- Finalised
LCD19) (NCS-S-BU35 ) *Single Rooms Rooms Only SMS9)
Only ( NCS-S-TCU10 ) (NCS-S-DU16)
( NCS-S-TCU9 )

1 Ground Floor
HDU 6 CDU 16 1 1 6 1 1 6
2 First Floor
MICU 12 CDU 16 1 1 12 1 1 0 12
Suite Room 4 CDU 16 1 1 4 4 4 0 4
Nursary 10 CDU 16 1 1 10 1 1 10
NICU 6 CDU 16 1 1 6 1 1 6
3 Second Floor
Pvt Room 9 CDU 16 1 1 9 9 0 9 0 9
Pvt Room 3 3 3 0 3 0 3
CDU 16 1 1
Semi Pvt 4 4 0 2 0 2 4
4 Third Floor
Dialysis Ward 5 CDU16 1 1 5 1 1 5
Ward - 1 5 5 1 1 6
Ward - 2 5 5 1 1 4
Ward - 3 7 7 1 1 7
Ward - 4 7 CDU 32 1 1 7 1 1 7
Ward - 5 7 7 1 1 7
Male Toilet 1
Female Toilet 2
5 Fifth Floor
CCU1 12 CDU 16 1 1 12 1 1 12
CCU2 7 CDU 16 1 1 7 1 1 7
6 Sixth Floor
Single Rooms 20 CDU24 1 1 20 20 20 20

129 12 12 129 36 17 48 2 129


Prepared By - Amit Soni Customer's Approval (Sign. Date & Stamp) -
Date: 12-10-2023
Product Specialist's Approval -

Remarks :BOQ as per discussion with customer during site visit and qty varified by

F/SA/24
Remarks :BOQ as per discussion with customer during site visit and qty varified by
Note:
customer on PO
*- Product Code: Toilet units for all Single Bedded Rooms.
**- Product Code: Toilet units for all multi Bedded Rooms.
***- Product code : Door Indicators for all Double Bedded Rooms only.
^ - Product code : According to number of beds for par nursing station (
Modules - 16/24/32/48/63)

Backend- BACKEND BOQ has been issued -YES/NO - If Yes, Date: If No, then tentative Date:

Site Requirement -Nurse Call System Model 4.0

Description of Power point Data cable


Sl. No. Mounting method / site requirements Remarks
modules requirement termination

CDU- Central
Display Unit
230V AC @ RJ45 information
(Nurse Station LCD/LED TV : WALL MOUNT require, identify and finalized the
50Hz, 5A UPS outlet within NCP Accessible
1 Display) LCD Height from floor and location; NCP (Nurse Call Processor ) :-
socket within 500mm; HDMI to Nursing staff
/LED TV ; NCP - Desktop recommended
500mm distance cable require from
Nurse Call LCD/LED TV to
Processor NCP
*All cables from
the rooms to Accessible for
Nurse station On a shelf (provided by customer) which is at an accessible location in 230V AC @ NSE/SRH to be Service
extender : Nursing station. Ensure that the cables drop from the top.NS_ 50Hz, 5A UPS identified using purspose.Wirin
2
NS_Extender Extenders can be stacked one above the other in the same shelf. Trap socket within ferrule sleeves and g as per GIVEN
(NSE) door required in case installed inside ceiling 500mm distance brought to the DRAWINGS
shelf. ONLY

Cat 6 cable from


Either cut-out provided in the bed headed panel or 4x3 metal gang NS controller,
Suggest at
boxes provided in the wall. Preferably to the left side of the patient. Toilet unit and
3 Bed Calling unit Nil height of 3’ft
Cut out dimension: 76 mm(W)*78mm (H) ; Door unit will
from floor
Hole to Hole Pitch is 86 mm (CTC) terminate in the
Bed unit

In line with the top of the door facing the corridor.Hole CTC is 40mm Above the door
Cat6 cable from
4 Door indicator , 1.5" Round type terminal MS box or In case of Ceiling placement Nil at height of 8’ft
the Bed unit
,require Cat 6 wire inside ceiling just above the center of door from floor

In line with the WC/commode at a height of 5/6 feet from ground level.
To be fixed in a metal gang box provided in the wall GI Box Cat6 cable from At water
5 Toilet calling unit Nil
dimensions : 102.5mm(W)*79.5mm(H) the Bed unit restricted wall
Plastic Back Box dimensions : 115mm(W)*85mm(H)

F/SA/24
In the cut-out provided in the bed headed panel or 4x3 metal gang box
provided in the wall. Preferably to the next of the Bed calling unit, Cut Cat6 cable from
6 Instrument Alarm Nil Next to bed unit
out dimension: 76 mm(W)*78mm (H) ; the Bed unit
Hole to Hole Pitch is 86 mm (CTC)

Suggest at
Bed Call unit with In the cut-out provided in the bed headed panel or 5x3 metal gang box Cat6 cable from
7 Nil height of 3’ft
service Call provided in the wall. Preferably to the next of the Bed calling unit. the Bed unit
from floor

230V AC @
Recommended
Escalation Display On a Wall /Desk which is at an accessible location in head supervisor's 50Hz, 3A UPS Centralised
8 at Central
-Multimode NCP room/ MS Room..etc as per decided by customer socket within LAN/DATA point
location
500mm distance

Software requirements: Computer should have the following


230V AC @ LAN/DATA Point
installed: - Windows 10 pre loaded Microsoft office 7/10/11, Recommended
Computer 50Hz, 3A UPS at each nursing
9 .Hardware requirements: Computer should be kept on a table. It at server Room/
(NCRM) socket within station &
should have at least processor with LAN port/Monitor/Keyboard/1Tb MS room
500mm distance computer loction
HD

F/SA/24