BACS

Riyadh Metro Project


Amtech Cable Design Guidelines
239762-REP-E-0001

Issue | 27 October 2016

This report takes into account the particular


instructions and requirements of our client.
It is not intended for and should not be relied
upon by any third party and no responsibility
is undertaken to any third party.

Job number 239762

Ove Arup & Partners Ltd


13 Fitzroy Street
London
W1T 4BQ
United Kingdom
www.arup.com
Document Verification

Job title Riyadh Metro Project Job number


239762
Document title Amtech Cable Design Guidelines File reference

Document ref 239762-REP-E-0001


Revision Date Filename AmtechCableDesignGuidelines-Rev0.docx
Draft 1 1 Jun Description First draft
2016

Prepared by Checked by Approved by


Apostolos
Name Gordon Capperauld David Deighton
Tellakis
Signature

Issue 8 Jul Filename Riyadh-AmtechCableDesignGuidelines-Rev1.docx


2016 Description Issue 1

Prepared by Checked by Approved by


Andrew
Name Gordon Capperauld David Deighton
Goodfellow
Signature

Issue 22 Sep Filename Riyadh-AmtechCableDesignGuidelines-Rev2.docx


2016 Description Issue 2

Prepared by Checked by Approved by


Name Gordon Capperauld Saa Dunbar David Deighton
Signature

Issue 27 Oct Filename Riyadh-AmtechCableDesignGuidelines-Rev3.docx


2016 Description Issue 3

Prepared by Checked by Approved by


Andrew
Name Gordon Capperauld David Deighton
Goodfellow
Signature

Issue Document Verification with Document 

239762-REP-E-0001 | Issue | 27 October 2016


X:\4 INTERNAL DATA\17 1B2\03 REPORTS\04 ELECTRICAL\ELECTRICAL LEAD FOLDER\RIYADH-AMTECHCABLEDESIGNGUIDELINES-REV3.DOCX
BACS Riyadh Metro Project
Amtech Cable Design Guidelines

Contents
Page

1 Purpose of Document 1

2 Clarifications 1

3 Voltage Drop Allowances 2

4 Transformer Inputs 3

5 Main & ATS Busbar Inputs 4


5.1 Main Busbar to Switchboard 4
5.2 Busbar to ATS 4
5.3 Gen Busbar to Switchboard 4

6 Main Switchboard Inputs 5

7 Generator Inputs 6

8 Submain to DP/EDP 7

9 Submain to DB Inputs 8
9.1 Small Power Final Circuit Loads 9
9.2 Lighting Final Circuit Loads 11

10 Submain to Essential DB Inputs 13


10.1 Fire Power Final Circuit Loads 14

11 Submain to MCC inputs 16


11.1 MCC Final Circuit Loads 18

12 Submain to Chiller Inputs 19

13 Submain to Fire Pump Inputs 20

14 Submain to Lifts/Escalators Inputs 21

15 Submain to Large Motor Load Inputs (TVF, TP, etc) 22

16 Submain to PFC inputs 24

17 Submain to CBS inputs 25


17.1 CBS inputs 26
17.2 Submain to Essential Lighting DBs 27

239762-REP-E-0001 | Issue | 27 October 2016


X:\4 INTERNAL DATA\17 1B2\03 REPORTS\04 ELECTRICAL\ELECTRICAL LEAD FOLDER\RIYADH-AMTECHCABLEDESIGNGUIDELINES-REV3.DOCX
BACS Riyadh Metro Project
Amtech Cable Design Guidelines

239762-REP-E-0001 | Issue | 27 October 2016


X:\4 INTERNAL DATA\17 1B2\03 REPORTS\04 ELECTRICAL\ELECTRICAL LEAD FOLDER\RIYADH-AMTECHCABLEDESIGNGUIDELINES-REV3.DOCX
BACS Riyadh Metro Project
Amtech Cable Design Guidelines

1 Purpose of Document
This document has been produced to provide design guidance for the Arup electrical team for the Amtech
cable design on the Riyadh Metro Project.
It should be used for internal design purposes only and should not be issued externally.

2 Clarifications
Only general inputs are provided. Project specific information such as lengths and loads should be included
by the station design teams.
Always set the inputs as you would like them to be and let the software tell you where these inputs are
failing and need to be changed. Do not set any cable size setting to auto.
All cable types are still to be finally agreed with the Client. The cable types modelled using Amtech may
not be 100% correct. Where different to what we are actually going to specify we’ll need to highlight the
differences in a schedule.
MCC final circuits should be fully modelled.
At 100% design stage, all final circuits should be fully modelled.
The guidelines within this document are presented in the following order;
1) Voltage Drop Allowances
2) Transformer Inputs
3) Main Busbar Inputs
4) Main Switchboard Inputs
5) Interconnecting Busbar Inputs
6) Generator Inputs
7) Submain to DP/EDPs
8) Submain to DB Inputs
a. Small Power Final Circuit Loads
b. Lighting Final Circuit Loads
9) Submain to MCC inputs
10) Submain to Chiller Inputs
11) Submain to Fire Pump Inputs
12) Submain to Lifts/Escalators Inputs
13) Submain to Large Motor Load Inputs
14) Submain to PFC inputs
15) Submain to CBS inputs
a. CBS inputs
b. Submains to Essential Lighting DBs
i. Essential Lighting Final Circuit Loads

239762-REP-E-0001 | Issue | 27 October 2016 Page 1


X:\4 INTERNAL DATA\17 1B2\03 REPORTS\04 ELECTRICAL\ELECTRICAL LEAD FOLDER\RIYADH-AMTECHCABLEDESIGNGUIDELINES-REV3.DOCX
BACS Riyadh Metro Project
Amtech Cable Design Guidelines

3 Voltage Drop Allowances


The following voltage drop allowances should be used for the Riyadh electrical design.
The overall voltage drop limit should be met under all operational scenarios i.e. running on mains, running
on mains when operating both switchboards on a single transformer, running on generator (single gen worst
case) and running on central battery inverter.
As long as the voltage drop from the source to the final load is below the overall limit then there can be
some flexibility on the different cable section voltage drops.

Cable Section DB Supplies DB MCC Direct Tunnel Supply Tunnel Supply


Supplies Supplies Connected (Direct via CBS
fed from Loads Connected
DP/EDP Loads)
Transformer/Gen to ~0.5% ~0.5% ~0.5% ~0.5% ~0.5% ~0.5%
Switchboard
Submain 1 ~1.5% ~0.5% ~2.5% N/A ~1% ~0.5% (to CBS)
Submain 2 N/A ~1.0% N/A N/A N/A ~1%
(to tunnel elec
room)
Final Circuit ~2% ~2% ~1% ~3.5% ~2.5% ~2% (tunnel)
Overall Voltage <=4% <=4% <=4% <=4% <=4% <=4%
Drop Limit

239762-REP-E-0001 | Issue | 27 October 2016 Page 2


X:\4 INTERNAL DATA\17 1B2\03 REPORTS\04 ELECTRICAL\ELECTRICAL LEAD FOLDER\RIYADH-AMTECHCABLEDESIGNGUIDELINES-REV3.DOCX
BACS Riyadh Metro Project
Amtech Cable Design Guidelines

4 Transformer Inputs

VOLTAGE
Primary Voltage: 33kV (Three Phase)
Secondary Voltage: 400V (Three Phase)
Frequency: 60Hz
Supply Type: Private Supply
User Defined: Voltage Drop Limit 4% [recent Client request from 5% to match Saudi regs]

FAULT CONDITIONS
Primary Fault Level: 250MVA
Rating (Tx): 1500kVA [Final rating TBC by Siemens – specific to each station]
Impedance: 6%

PROTECTION
Generic Relay BS142 Extremely Inverse set at 40A [use for now – final protection TBC by Siemens]
Protection Rated At: 100%

239762-REP-E-0001 | Issue | 27 October 2016 Page 3


X:\4 INTERNAL DATA\17 1B2\03 REPORTS\04 ELECTRICAL\ELECTRICAL LEAD FOLDER\RIYADH-AMTECHCABLEDESIGNGUIDELINES-REV3.DOCX
BACS Riyadh Metro Project
Amtech Cable Design Guidelines

5 Main & ATS Busbar Inputs

5.1 Main Busbar to Switchboard


DETAILS
Manufacturer: Siemens
Range: LR
Type: Copper
Rating: 3200A
Temp (°C): 30°C/45°C – to suit circuit route – discuss with mechanical team
Installation: Horizontal

5.2 Busbar to ATS


DETAILS
Manufacturer: Siemens
Range: LR
Type: Copper
Rating: 3200A
Temp (°C): 30°C/45°C – to suit circuit route – discuss with mechanical team
Installation: Horizontal

5.3 Gen Busbar to Switchboard


DETAILS
Manufacturer: Siemens
Range: LR
Type: Copper
Rating: 4000A
Temp (°C): 30°C/45°C – to suit circuit route – discuss with mechanical team
Installation: Horizontal

239762-REP-E-0001 | Issue | 27 October 2016 Page 4


X:\4 INTERNAL DATA\17 1B2\03 REPORTS\04 ELECTRICAL\ELECTRICAL LEAD FOLDER\RIYADH-AMTECHCABLEDESIGNGUIDELINES-REV3.DOCX
BACS Riyadh Metro Project
Amtech Cable Design Guidelines

6 Main Switchboard Inputs

DIVERSITY
Define Load: Use the load from your load assessment for each LPS (MDB+EMDB added together)
Power Factor: 1
3rd Harmonic (%): 0 [Under review]

EARTHING
Earth at Supply Source Only – No Local Earthing at Board

SWITCHBOARD INCOMING CIRCUIT BREAKER FROM TRANSFORMER


Manufacturer: Schneider
Family: Masterpact NW ACB
Type: NW40H1
Protection: MLogic 5.0 Std
Rating: 3200A
Overload Setting: 3200A
Detailed Settings inside the View Graph feature: See Selectivity Study Report

BUSBAR COUPLER PROTECTION (BETWEEN MDB and EMDB)


No Protection – only switch disconnector [under review]

SWITCHBOARD INCOMING CIRCUIT BREAKER FROM GENERATOR


Manufacturer: Schneider
Family: Masterpact NW ACB
Type: NW40H1
Protection: MLogic 5.0 Std
Rating: 3200A
Overload Setting: 3200A
Detailed Settings inside the View Graph feature: See Selectivity Study Report
Note:
The switchboard incomer may have restricted earth protection relays but if you select the Micrologic 6.0
relay, Amtech will assume it is an unrestricted earth fault relay and apply it to all faults downstream.
239762-REP-E-0001 | Issue | 27 October 2016 Page 5
X:\4 INTERNAL DATA\17 1B2\03 REPORTS\04 ELECTRICAL\ELECTRICAL LEAD FOLDER\RIYADH-AMTECHCABLEDESIGNGUIDELINES-REV3.DOCX
BACS Riyadh Metro Project
Amtech Cable Design Guidelines

7 Generator Inputs

VOLTAGE
Supply Voltage: 400V (three phase)
Frequency: 60Hz
Supply Type: Private Supply
User Defined: Voltage Drop Limit 4% [recent Client request from 5% to match Saudi regs]
Parallel Sources: 2

FAULT CONDITIONS:
Rating: 2x1600kVA=3200kVA [Rating TBC by Siemens]
Z%: 33% - This represents an achievable scenario where the AVR provides 300% Irated for 10secs.

Note: Model the generator as a lumped source of the total generator system capacity.

239762-REP-E-0001 | Issue | 27 October 2016 Page 6


X:\4 INTERNAL DATA\17 1B2\03 REPORTS\04 ELECTRICAL\ELECTRICAL LEAD FOLDER\RIYADH-AMTECHCABLEDESIGNGUIDELINES-REV3.DOCX
BACS Riyadh Metro Project
Amtech Cable Design Guidelines

8 Submain to DP/EDP
LOAD

As identified within the station specific load assessment.


DETAILS
Essential Loads - Prysmian FP600S Fire resistant cable Cu
Non Essential Loads
Type (Cable):
Route through Non-Public Space: Multicore 90°C thermosetting insulated, non-armoured LSF Table 4E2
Route through Public Space: Multicore 90°C thermosetting insulated, armoured LSF Table 4E4
Installation Method:
Cable tray, ladder systems, cleats, wire mesh tray
On horizontal/vertical perforated tray [where cable route through public spaces make cable run within ducts]
Size: As required for Length/Amps but Not Set to Auto
Ambient Temp: 30°C/45°C – to suit circuit route – discuss with mechanical team

GROUPING
Arrangement: Horizontal Touching
Grouping with other circuits: Total no of grouped circuits 10 (or as relevant for station)
Subject to simultaneous overload: Not checked
If using parallel cable, make sure the derating is for 10+2=12 cables and not 10x2=20 cables
No. trays: 1 By setting this to 1 tray, this gives the worst case derating factor
CPC
Separate/Integral conductor ONLY
Separate Conductor
Greater than or equal to ½ circuit phase size [under discussion with Client]
UNLESS required by disconnection time and then uprate phase and associated resultant CPC to meet
disconnection time (CPC remains ½ circuit phase size)

CIRCUIT PROTECTION
Schneider Compact NSX MCCB NSX H Micrologic 2.2 – Ampere device & trip rating to suit load and to
achieve discrimination
Overload Setting: To suit load
(View Graph) Instantaneous Trip = 8 x In (Isd)

239762-REP-E-0001 | Issue | 27 October 2016 Page 7


X:\4 INTERNAL DATA\17 1B2\03 REPORTS\04 ELECTRICAL\ELECTRICAL LEAD FOLDER\RIYADH-AMTECHCABLEDESIGNGUIDELINES-REV3.DOCX
BACS Riyadh Metro Project
Amtech Cable Design Guidelines

9 Submain to DB Inputs
LOAD

As identified within the station specific load assessment.


DETAILS
Type (Cable):
Route through Non-Public Space: Multicore 90°C thermosetting insulated, non-armoured LSF Table 4E2
Route through Public Space: Multicore 90°C thermosetting insulated, armoured LSF Table 4E4
Installation Method:
Cable tray, ladder systems, cleats, wire mesh tray
On horizontal/vertical perforated tray [where cable route through public spaces make cable run within ducts]
Size: As required for Length/Amps but Not Set to Auto
Ambient Temp: 30°C/45°C – to suit circuit route – discuss with mechanical team
External DB Cable: Should be armoured Table 4E4 routed within ducts

GROUPING
Arrangement: Horizontal Touching
Grouping with other circuits: Total no of grouped circuits 10 (or as relevant for station)
Subject to simultaneous overload: Not checked
If using parallel cable, make sure the derating is for 10+2=12 cables and not 10x2=20 cables
No. trays: 1 By setting this to 1 tray, this gives the worst case derating factor

CPC
Separate/Integral conductor ONLY
Separate Conductor
Greater than or equal to ½ circuit phase size [under discussion with Client]
UNLESS required by disconnection time and then uprate phase and associated resultant CPC to meet
disconnection time (CPC remains ½ circuit phase size)

CIRCUIT PROTECTION
Schneider Compact NSX MCCB NSX100H Micrologic 2.2 100A
Overload Setting: 63A [Default project setting–only change if required by DB load/discrimination purposes]
(View Graph) Instantaneous Trip = 8 x In (Isd)
NSX100 with a 63A trip unit will allow total discrimination with downstream MCBs up to 40A.
239762-REP-E-0001 | Issue | 27 October 2016 Page 8
X:\4 INTERNAL DATA\17 1B2\03 REPORTS\04 ELECTRICAL\ELECTRICAL LEAD FOLDER\RIYADH-AMTECHCABLEDESIGNGUIDELINES-REV3.DOCX
BACS Riyadh Metro Project
Amtech Cable Design Guidelines

9.1 Small Power Final Circuit Loads


FOR 100% INCLUDE ACTUAL CIRCUIT DETAILS FOR EACH CIRCUIT
Long Test Circuit – Cable & Id No. – DPBXX-SP-L
CIRCUIT PROTECTION
Schneider Acti9 MCB iC60H Type B BS EN60947-2 20A
CPD Breaking Capacity: Fully Rated
CABLE
DETAILS
Type: Single-core, 90°C thermosetting insulated, non-arm LSF Cu Table 4E1
Installation Method:
In trunking/ducting (Reference B)
In suspended trunking
Size: 4mm2 31A
Length: 60m (adopt suitable length for station)
Trunking: Metal
Ambient Temp: 30°C/45°C – to suit circuit route – discuss with mechanical team

GROUPING
With other circuits: Total no of grouped circuits 10 (or as relevant for station)

CPC
Separate conductor ONLY
Separate Conductor
Size: 4mm2

LOAD
Type: Fixed equipment single phase and neutral
Load: 5A
Power Factor: 1

239762-REP-E-0001 | Issue | 27 October 2016 Page 9


X:\4 INTERNAL DATA\17 1B2\03 REPORTS\04 ELECTRICAL\ELECTRICAL LEAD FOLDER\RIYADH-AMTECHCABLEDESIGNGUIDELINES-REV3.DOCX
BACS Riyadh Metro Project
Amtech Cable Design Guidelines

Short Test Circuit – Cable & Id No. – DPBXX-SP-S


CIRCUIT PROTECTION
Schneider Acti9 MCB iC60H Type B BS EN60947-2 20A
CPD Breaking Capacity: Fully Rated
CABLE
DETAILS
Type: Single-core, 90°C thermosetting insulated, non-arm LSF Cu Table 4E1
Installation Method:
In trunking/ducting (Reference B)
In suspended trunking
Size: 4mm2 31A
Length: 20m
Trunking: Metal
Ambient Temp: 30°C/45°C – to suit circuit route – discuss with mechanical team

GROUPING
With other circuits: Total no of grouped circuits 10 (or as relevant for station)

CPC
Separate conductor ONLY
Separate Conductor
Size: 4mm2

LOAD
Type: Fixed equipment single phase and neutral
Load: 5A
Power Factor: 1

239762-REP-E-0001 | Issue | 27 October 2016 Page 10


X:\4 INTERNAL DATA\17 1B2\03 REPORTS\04 ELECTRICAL\ELECTRICAL LEAD FOLDER\RIYADH-AMTECHCABLEDESIGNGUIDELINES-REV3.DOCX
BACS Riyadh Metro Project
Amtech Cable Design Guidelines

9.2 Lighting Final Circuit Loads


FOR 100% INCLUDE ACTUAL CIRCUIT DETAILS FOR EACH CIRCUIT
Long Test Circuit – Cable & Id No. – DPBXX-L-L
CIRCUIT PROTECTION
Schneider Acti9 MCB iC60H Type C BS EN60947-2 10A
CPD Breaking Capacity: Fully Rated
CABLE
DETAILS
Type: Single-core, 90°C thermosetting insulated, non-arm LSF Cu Table 4E1
Installation Method:
In trunking/ducting (Reference B)
In suspended trunking
Size: 2.5mm2 31A
Length: 70m (adopt suitable length for station)
Trunking: Metal
Ambient Temp: 30°C/45°C – to suit circuit route – discuss with mechanical team
External Lighting Circuit: Cable to be armoured Table 4E4 routed in ducts

GROUPING
With other circuits: Total no of grouped circuits 10 (or as relevant for station)

CPC
Separate conductor ONLY
Separate Conductor
Size: 2.5mm2

LOAD
Type: Lighting Radial Circuits
Length to First Fitting (m): 40m
Load: 3A
Power Factor: 1

239762-REP-E-0001 | Issue | 27 October 2016 Page 11


X:\4 INTERNAL DATA\17 1B2\03 REPORTS\04 ELECTRICAL\ELECTRICAL LEAD FOLDER\RIYADH-AMTECHCABLEDESIGNGUIDELINES-REV3.DOCX
BACS Riyadh Metro Project
Amtech Cable Design Guidelines

Short Test Circuit – Cable & Id No. – DPBXX-L-S


CIRCUIT PROTECTION
Schneider Acti9 MCB iC60H Type C BS EN60947-2 10A
CPD Breaking Capacity: Fully Rated
CABLE
DETAILS
Type: Single-core, 90°C thermosetting insulated, non-arm LSF Cu Table 4E1
Installation Method:
In trunking/ducting (Reference B)
In suspended trunking
Size: 2.5mm2 31A
Length: 20m
Trunking: Metal
Ambient Temp: 30°C/45°C – to suit circuit route – discuss with mechanical team
External Lighting Circuit: Cable to be armoured Table 4E4 routed in ducts

GROUPING
With other circuits: Total no of grouped circuits 10 (or as relevant for station)

CPC
Separate conductor ONLY
Separate Conductor
Size: 2.5mm2

LOAD
Type: Lighting Radial Circuits
Length to First Fitting (m): 5m
Load: 3A
Power Factor: 1

239762-REP-E-0001 | Issue | 27 October 2016 Page 12


X:\4 INTERNAL DATA\17 1B2\03 REPORTS\04 ELECTRICAL\ELECTRICAL LEAD FOLDER\RIYADH-AMTECHCABLEDESIGNGUIDELINES-REV3.DOCX
BACS Riyadh Metro Project
Amtech Cable Design Guidelines

10 Submain to Essential DB Inputs


LOAD
As identified within the station specific load assessment.

DETAILS
Type (Cable): Prysmian FP600S Fire resistant cable Cu
Installation Method:
Cable tray, ladder systems, cleats, wire mesh tray
On horizontal/vertical perforated tray
Size: As required for Length/Amps but Not Set to Auto
Ambient Temp: 30°C/45°C – to suit circuit route – discuss with mechanical team

GROUPING
Arrangement: Horizontal Touching
Grouping with other circuits: Total no of grouped circuits 10 (or as relevant for station)
Subject to simultaneous overload: Not checked
If using parallel cable, make sure the derating is for 10+2=12 cables and not 10x2=20 cables
No. trays: 1 By setting this to 1 tray, this gives the worst case derating factor

CPC
Separate/Integral conductor ONLY
Separate Conductor
Greater than or equal to ½ circuit phase size [under discussion with Client]
UNLESS required by disconnection time and then uprate phase and associated resultant CPC to meet
disconnection time (CPC remains ½ circuit phase size)

CIRCUIT PROTECTION
Schneider Compact NSX MCCB NSX100H Micrologic 2.2 100A
Overload Setting: 63A [Default project setting–only change if required by DB load/discrimination purposes]
(View Graph) Instantaneous Trip = 8 x In (Isd)

239762-REP-E-0001 | Issue | 27 October 2016 Page 13


X:\4 INTERNAL DATA\17 1B2\03 REPORTS\04 ELECTRICAL\ELECTRICAL LEAD FOLDER\RIYADH-AMTECHCABLEDESIGNGUIDELINES-REV3.DOCX
BACS Riyadh Metro Project
Amtech Cable Design Guidelines

10.1 Fire Power Final Circuit Loads


FOR 100% INCLUDE ACTUAL CIRCUIT DETAILS FOR EACH CIRCUIT
Long Test Circuit – Cable & Id No. – DPBXX-F-L
CIRCUIT PROTECTION
Schneider Acti9 MCB iC60H Type B BS EN60947-2 20A
CPD Breaking Capacity: Fully Rated
CABLE
DETAILS
Type: Prysmian FP200 Fire resistant cable Cu [Final cable type subject to Client confirmation]
Installation Method:
Cable tray, ladder systems, cleats, wire mesh tray
On horizontal/vertical perforated tray
Size: 4mm2 31A
Length: 60m (adopt suitable length for station)
Ambient Temp: 30°C/45°C – to suit circuit route – discuss with mechanical team

GROUPING
With other circuits: Total no of grouped circuits 10 (or as relevant for station)

CPC
Separate conductor ONLY
Separate Conductor
Size: 4mm2

LOAD
Type: Fixed equipment single phase and neutral
Load: 5A
Power Factor: 1

239762-REP-E-0001 | Issue | 27 October 2016 Page 14


X:\4 INTERNAL DATA\17 1B2\03 REPORTS\04 ELECTRICAL\ELECTRICAL LEAD FOLDER\RIYADH-AMTECHCABLEDESIGNGUIDELINES-REV3.DOCX
BACS Riyadh Metro Project
Amtech Cable Design Guidelines

Short Test Circuit – Cable & Id No. – DPBXX-F-S


CIRCUIT PROTECTION
Schneider Acti9 MCB iC60H Type B BS EN60947-2 20A
CPD Breaking Capacity: Fully Rated
CABLE
DETAILS
Type: Prysmian FP200 Fire resistant cable Cu [Final cable type subject to Client confirmation]
Installation Method:
Cable tray, ladder systems, cleats, wire mesh tray
On horizontal/vertical perforated tray
Size: 4mm2 31A
Length: 20m
Ambient Temp: 30°C/45°C – to suit circuit route – discuss with mechanical team

GROUPING
With other circuits: Total no of grouped circuits 10 (or as relevant for station)

CPC
Separate conductor ONLY
Separate Conductor
Size: 4mm2

LOAD
Type: Fixed equipment single phase and neutral
Load: 5A
Power Factor: 1

239762-REP-E-0001 | Issue | 27 October 2016 Page 15


X:\4 INTERNAL DATA\17 1B2\03 REPORTS\04 ELECTRICAL\ELECTRICAL LEAD FOLDER\RIYADH-AMTECHCABLEDESIGNGUIDELINES-REV3.DOCX
BACS Riyadh Metro Project
Amtech Cable Design Guidelines

11 Submain to MCC inputs


LOAD
As identified within the station specific load assessment.

DETAILS
Essential Loads - Prysmian FP600S Fire resistant cable Cu
Non Essential Loads
Type (Cable):
Route through Non-Public Space: Multicore 90°C thermosetting insulated, non-armoured LSF Table 4E2
Route through Public Space: Multicore 90°C thermosetting insulated, armoured LSF Table 4E4
Installation Method:
Cable tray, ladder systems, cleats, wire mesh tray
On horizontal/vertical perforated tray
[where cable route through public spaces make cable run within ducts]
Size: As required for Length/Amps but Not Set to Auto
Ambient Temp: 30°C/45°C – to suit circuit route – discuss with mechanical team

GROUPING
Arrangement: Horizontal Touching
Grouping with other circuits: Total no of grouped circuits 10 (or as relevant for station)
Subject to simultaneous overload: Not checked
If using parallel cable, make sure the derating is for 10+2=12 cables and not 10x2=20 cables
No. trays: 1 By setting this to 1 tray, this gives the worst case derating factor

CPC
Separate/Integral conductor ONLY
Separate Conductor
Greater than or equal to ½ circuit phase size [under discussion with Client]
UNLESS required by disconnection time and then uprate phase and associated resultant CPC to meet
disconnection time (CPC remains ½ circuit phase size)

CIRCUIT PROTECTION
Schneider Compact NSX MCCB NSX100H Micrologic 2.2 100A [Default project setting–only change if
required by MCC load/discrimination purposes]
239762-REP-E-0001 | Issue | 27 October 2016 Page 16
X:\4 INTERNAL DATA\17 1B2\03 REPORTS\04 ELECTRICAL\ELECTRICAL LEAD FOLDER\RIYADH-AMTECHCABLEDESIGNGUIDELINES-REV3.DOCX
BACS Riyadh Metro Project
Amtech Cable Design Guidelines

Overload Setting: 63A [Default project setting–only change if required by MCC load/discrimination
purposes]
(View Graph) Instantaneous Trip = 8 x In (Isd)

239762-REP-E-0001 | Issue | 27 October 2016 Page 17


X:\4 INTERNAL DATA\17 1B2\03 REPORTS\04 ELECTRICAL\ELECTRICAL LEAD FOLDER\RIYADH-AMTECHCABLEDESIGNGUIDELINES-REV3.DOCX
BACS Riyadh Metro Project
Amtech Cable Design Guidelines

11.1 MCC Final Circuit Loads


FOR 100% INCLUDE ACTUAL CIRCUIT DETAILS FOR EACH CIRCUIT
CIRCUIT PROTECTION
Distribution board format and circuit breaker selection to suit the ampere load and load type
Use a panelboard if load > 250A or if there are large motor loads:
Motor loads – Use NS 80H MA with the appropriate trip unit selected
Other loads – Use NSX 100 with the appropriate trip unit selected
Use a distribution board if all loads are low ampere and total is low
Use Schneider Acti9 MCB iC60H Type C
CABLE
DETAILS
Type: [Final cable types subject to Client confirmation]
Essential Loads - Prysmian FP600S Fire resistant cable Cu
Non-essential Loads
Type (Cable):
Route through Non-Public Space: Multicore 90°C thermosetting insulated, non-armoured LSF Table 4E2
Route through Public Space: Multicore 90°C thermosetting insulated, armoured LSF Table 4E4
Installation Method:
Cable tray, ladder systems, cleats, wire mesh tray
On horizontal/vertical perforated tray
[where non-essential cable route through public spaces make cable run within ducts]
Size: To suit ampere load/length
Ambient Temp: 30°C/45°C – to suit circuit route – discuss with mechanical team

GROUPING
With other circuits: Total no of grouped circuits 10 (or as relevant for station)

CPC
Separate conductor ONLY
Separate Conductor
Greater than or equal to ½ circuit phase size [under discussion with Client]
UNLESS required by disconnection time and then uprate phase and associated resultant CPC to meet
disconnection time

239762-REP-E-0001 | Issue | 27 October 2016 Page 18


X:\4 INTERNAL DATA\17 1B2\03 REPORTS\04 ELECTRICAL\ELECTRICAL LEAD FOLDER\RIYADH-AMTECHCABLEDESIGNGUIDELINES-REV3.DOCX
BACS Riyadh Metro Project
Amtech Cable Design Guidelines

12 Submain to Chiller Inputs


WARNING: 2 supply cables may be required for the chiller. Check with chiller data sheet.

DETAILS
Type (Cable):
Route through Non-Public Space: Multicore 90°C thermosetting insulated, non-armoured LSF Table 4E2
Route through Public Space: Multicore 90°C thermosetting insulated, armoured LSF Table 4E4
Installation Method:
Cable tray, ladder systems, cleats, wire mesh tray
On horizontal/vertical perforated tray
[where non-essential cable route through public spaces make cable run within ducts]
Size: As required for Length/Amps but Not Set to Auto
Ambient Temp: 30°C/45°C – to suit circuit route – discuss with mechanical team

GROUPING
Arrangement: Horizontal Touching
Grouping with other circuits: Total no of grouped circuits 10 (or as relevant for station)
Subject to simultaneous overload: Not checked
If using parallel cable, make sure the derating is for 10+2=12 cables and not 10x2=20 cables
No. trays: 1 By setting this to 1 tray, this gives the worst case derating factor

CPC
Separate/Integral conductor ONLY
Separate Conductor
Greater than or equal to ½ circuit phase size [under discussion with Client]
UNLESS required by disconnection time and then uprate phase and associated resultant CPC to meet
disconnection time (CPC remains ½ circuit phase size)

CIRCUIT PROTECTION
Schneider Compact NSX MCCB NSX630 [Default project setting–only change if required by chiller load]
Overload Setting: 630A [Default project setting–only change if required by chiller load]
(View Graph) Instantaneous Trip = 3 x In (Isd) (very long runs of cable > 200m will need Iinst = 2)

239762-REP-E-0001 | Issue | 27 October 2016 Page 19


X:\4 INTERNAL DATA\17 1B2\03 REPORTS\04 ELECTRICAL\ELECTRICAL LEAD FOLDER\RIYADH-AMTECHCABLEDESIGNGUIDELINES-REV3.DOCX
BACS Riyadh Metro Project
Amtech Cable Design Guidelines

13 Submain to Fire Pump Inputs


DETAILS
Type (Cable): Prysmian FP600S Fire resistant cable Cu
Installation Method:
Cable tray, ladder systems, cleats, wire mesh tray
On horizontal/vertical perforated tray
Size: As required for Length/Amps but Not Set to Auto
Ambient Temp: 30°C/45°C – to suit circuit route – discuss with mechanical team
Cable(s) to sized for 125% of running current of fire pump

GROUPING
Arrangement: Horizontal Touching
Grouping with other circuits: Total no of grouped circuits 10 (or as relevant for station)
Subject to simultaneous overload: Not checked
If using parallel cable, make sure the derating is for 10+2=12 cables and not 10x2=20 cables
No. trays: 1 By setting this to 1 tray, this gives the worst case derating factor

CPC
Separate/Integral conductor ONLY
Separate Conductor
Greater than or equal to ½ circuit phase size [under discussion with Client]
UNLESS required by disconnection time and then uprate phase and associated resultant CPC to meet
disconnection time (CPC remains ½ circuit phase size)

CIRCUIT PROTECTION
Supply cable from Transformer
Circuit Breaker Rating: Breaker ampere rating In > Locked Rotor Current (LRA) of Fire Pump
e.g. FLA=300A, LRA=7x300A= 2100A, rating of breaker > 2100A i.e. 2500A.
Instantaneous Setting: In x 2

Supply cable from Generator


Circuit Breaker Rating: Breaker ampere rating In > Starting Current of Fire Pump
Instantaneous Setting: In x 2

239762-REP-E-0001 | Issue | 27 October 2016 Page 20


X:\4 INTERNAL DATA\17 1B2\03 REPORTS\04 ELECTRICAL\ELECTRICAL LEAD FOLDER\RIYADH-AMTECHCABLEDESIGNGUIDELINES-REV3.DOCX
BACS Riyadh Metro Project
Amtech Cable Design Guidelines

14 Submain to Lifts/Escalators Inputs

DETAILS
Type (Cable): Prysmian FP600S Fire resistant cable Cu
Installation Method:
Cable tray, ladder systems, cleats, wire mesh tray
On horizontal/vertical perforated tray
[where non-essential cable route through public spaces make cable run within ducts]
Size: As required for Length/Amps but Not Set to Auto
Ambient Temp: 30°C/45°C – to suit circuit route – discuss with mechanical team

GROUPING
Arrangement: Horizontal Touching
Grouping with other circuits: Total no of grouped circuits 10 (or as relevant for station)
Subject to simultaneous overload: Not checked
If using parallel cable, make sure the derating is for 10+2=12 cables and not 10x2=20 cables
No. trays: 1 By setting this to 1 tray, this gives the worst case derating factor

CPC
Separate/Integral conductor ONLY
Separate Conductor
Greater than or equal to ½ circuit phase size [under discussion with Client]
UNLESS required by disconnection time and then uprate phase and associated resultant CPC to meet
disconnection time (CPC remains ½ circuit phase size)

CIRCUIT PROTECTION
Schneider Compact NSX MCCB NSX100H Micrologic 2.2 100A [Default project setting–only change if
required by lift/escalator load/discrimination purposes]
Overload Setting: 63A [Default project setting–only change if required by lift/escalator load/discrimination
purposes]
(View Graph) Instantaneous Trip = 6 x In (Isd)

239762-REP-E-0001 | Issue | 27 October 2016 Page 21


X:\4 INTERNAL DATA\17 1B2\03 REPORTS\04 ELECTRICAL\ELECTRICAL LEAD FOLDER\RIYADH-AMTECHCABLEDESIGNGUIDELINES-REV3.DOCX
BACS Riyadh Metro Project
Amtech Cable Design Guidelines

15 Submain to Large Motor Load Inputs (TVF, TP, etc)


DETAILS
Essential Loads - Prysmian FP600S Fire resistant cable Cu
Non-essential Loads
Type (Cable):
Route through Non-Public Space: Multicore 90°C thermosetting insulated, non-armoured LSF Table 4E2
Route through Public Space: Multicore 90°C thermosetting insulated, armoured LSF Table 4E4
Installation Method:
Cable tray, ladder systems, cleats, wire mesh tray
On horizontal/vertical perforated tray
[where non-essential cable route through public spaces make cable run within ducts]
Size: As required for Length/Amps but Not Set to Auto
No. of conductors: If only motor at end of cable then you should contemplate using a 3core+earth cable and
omitting the neutral conductor. Investigate further with proposed motor manufacturer.
Ambient Temp: 30°C/45°C – to suit circuit route – discuss with mechanical team

GROUPING
Arrangement: Horizontal Touching
Grouping with other circuits: Total no of grouped circuits 10 (or as relevant for station)
Subject to simultaneous overload: Not checked
If using parallel cable, make sure the derating is for 10+2=12 cables and not 10x2=20 cables
No. trays: 1 By setting this to 1 tray, this gives the worst case derating factor

CPC
Separate/Integral conductor ONLY
Separate Conductor
Greater than or equal to ½ circuit phase size [under discussion with Client]
UNLESS required by disconnection time and then uprate phase and associated resultant CPC to meet
disconnection time (CPC remains ½ circuit phase size)

CIRCUIT PROTECTION
Breaker Type/rating to suit the load and proposed motor starter. If using ACB then use an L1 type unit.

239762-REP-E-0001 | Issue | 27 October 2016 Page 22


X:\4 INTERNAL DATA\17 1B2\03 REPORTS\04 ELECTRICAL\ELECTRICAL LEAD FOLDER\RIYADH-AMTECHCABLEDESIGNGUIDELINES-REV3.DOCX
BACS Riyadh Metro Project
Amtech Cable Design Guidelines

Overload Setting: To suit the motor being supplied. If only motor at end of cable then you should
contemplate using a motor rated circuit breaker which has only short circuit protection. This will allow the
cable to the motor to be reduced in size.
(View Graph) Instantaneous Trip = 3 x In (Isd)

239762-REP-E-0001 | Issue | 27 October 2016 Page 23


X:\4 INTERNAL DATA\17 1B2\03 REPORTS\04 ELECTRICAL\ELECTRICAL LEAD FOLDER\RIYADH-AMTECHCABLEDESIGNGUIDELINES-REV3.DOCX
BACS Riyadh Metro Project
Amtech Cable Design Guidelines

16 Submain to PFC inputs


USE THE LOAD COMPONENT IN AMTECH – NOT THE PFC COMPONENT
DETAILS
Type (Cable): Multicore, 90°C thermosetting insulated, non-armoured, LSF Cu Table 4E2
Installation Method:
Cable tray, ladder systems, cleats, wire mesh tray
On horizontal/vertical perforated tray
Size: As required for Length/Amps but Not Set to Auto
Ambient Temp: 30°C/45°C – to suit circuit route – discuss with mechanical team

GROUPING
Arrangement: Horizontal Touching
Grouping with other circuits: Total no of grouped circuits 10 (or as relevant for station)
Subject to simultaneous overload: Not checked
If using parallel cable, make sure the derating is for 10+2=12 cables and not 10x2=20 cables
No. trays: 1 By setting this to 1 tray, this gives the worst case derating factor

CPC
Separate/Integral conductor ONLY
Separate Conductor
Greater than or equal to ½ circuit phase size [under discussion with Client]
UNLESS required by disconnection time and then uprate phase and associated resultant CPC to meet
disconnection time (CPC remains ½ circuit phase size)

CIRCUIT PROTECTION
Manufacturer: Schneider
Family: Masterpact NT ACB FOR > 630A, Compact MCCB NSX <= 630A
Type: Use the L1 current limiting type for ACB
Protection: ACB = MLogic 2.0 Std
Rating: To suit PFC rating – breaker rating > 2 x kVA rating i.e. 500kVAr = 1000A ACB
Detailed Settings inside the View Graph feature: See Selectivity Study Report

239762-REP-E-0001 | Issue | 27 October 2016 Page 24


X:\4 INTERNAL DATA\17 1B2\03 REPORTS\04 ELECTRICAL\ELECTRICAL LEAD FOLDER\RIYADH-AMTECHCABLEDESIGNGUIDELINES-REV3.DOCX
BACS Riyadh Metro Project
Amtech Cable Design Guidelines

17 Submain to CBS inputs


DETAILS
Type (Cable): Prysmian FP600S Fire resistant cable Cu
Installation Method:
Cable tray, ladder systems, cleats, wire mesh tray
On horizontal/vertical perforated tray
Size: As required for Length/Amps but Not Set to Auto
Ambient Temp: 30°C/45°C – to suit circuit route – discuss with mechanical team

GROUPING
Arrangement: Horizontal Touching
Grouping with other circuits: Total no of grouped circuits 10 (or as relevant for station)
Subject to simultaneous overload: Not checked
If using parallel cable, make sure the derating is for 10+2=12 cables and not 10x2=20 cables
No. trays: 1 By setting this to 1 tray, this gives the worst case derating factor

CPC
Separate/Integral conductor ONLY
Separate Conductor
Greater than or equal to ½ circuit phase size [under discussion with Client]
UNLESS required by disconnection time and then uprate phase and associated resultant CPC to meet
disconnection time (CPC remains ½ circuit phase size)

CIRCUIT PROTECTION
Schneider Compact NSX MCCB NSX250H Micrologic 2.2 Trip Unit 160A [Default project setting–only
change if required by CBS rating]
Overload Setting: 160A [Default project setting–only change if required by CBS rating]
(View Graph) Instantaneous Trip = 8 x In (Isd)

239762-REP-E-0001 | Issue | 27 October 2016 Page 25


X:\4 INTERNAL DATA\17 1B2\03 REPORTS\04 ELECTRICAL\ELECTRICAL LEAD FOLDER\RIYADH-AMTECHCABLEDESIGNGUIDELINES-REV3.DOCX
BACS Riyadh Metro Project
Amtech Cable Design Guidelines

17.1 CBS inputs

The UPS component in Amtech is difficult to implement correctly.


As a result of this we have used the source component instead to represent the CBS operating under battery
supply conditions.

Central Battery Inverter as represented by a Source


VOLTAGE
Voltage: 400V
Frequency: 60Hz
Supply Type: Private Supply
User Defined: Voltage Drop Limit 4% [recent Client request from 5% to match Saudi regs]

FAULT CONDITIONS
Phase & Earth Fault Current (kA): Use 3 x full load current of CBS
i.e. 60kVA=87A => 87Ax3= 261A
The CB inverter should be able to supply 300% for long enough to trip the submain & final circuit breakers.

PROTECTION
Match the CBS protection device to the protection device of the submain to the CBS.
You have to include some device in here to make the program work but under battery operation, this device
will not actually exist. The cable from the central battery inverter to the central battery output switchboard
will be protected using electronic fuses within the CBS. The inclusion of the above protective device will
give rise to an error in Amtech, which can be ignored.

239762-REP-E-0001 | Issue | 27 October 2016 Page 26


X:\4 INTERNAL DATA\17 1B2\03 REPORTS\04 ELECTRICAL\ELECTRICAL LEAD FOLDER\RIYADH-AMTECHCABLEDESIGNGUIDELINES-REV3.DOCX
BACS Riyadh Metro Project
Amtech Cable Design Guidelines

17.2 Submain to Essential Lighting DBs


LOAD
As identified within the station specific load assessment.

DETAILS
Type (Cable): Prysmian FP600S Fire resistant cable Cu
Installation Method:
Cable tray, ladder systems, cleats, wire mesh tray
On horizontal/vertical perforated tray
Size: As Requested for Length/Amps but Not Set to Auto
Ambient Temp: 30°C/45°C – to suit circuit route – discuss with mechanical team

GROUPING
Arrangement: Horizontal Touching
Grouping with other circuits: Total no of grouped circuits 10 (or as relevant for station)
Subject to simultaneous overload: Check this box for submains to essential lighting DBs
If using parallel cable, make sure the derating is for 10+2=12 cables and not 10x2=20 cables
No. trays: 1 By setting this to 1 tray, this gives the worst case derating factor

CPC
Separate/Integral conductor ONLY
Separate Conductor
Greater than or equal to ½ circuit phase size [under discussion with Client]
UNLESS required by disconnection time and then uprate phase and associated resultant CPC to meet
disconnection time (CPC remains ½ circuit phase size)

CIRCUIT PROTECTION
Schneider Compact NSX MCCB NSX100H Micrologic 2.2 100A
Overload Setting: 40A [Default project setting–only change if required by DB load/discrimination purposes]
(View Graph) Instantaneous Trip = 4 x In (Isd)
These specific 40A breaker trip unit and instantaneous trip settings have been proposed to allow operation of
the submain MCCB when the system is running under a reduced fault level from the CBS batteries.

239762-REP-E-0001 | Issue | 27 October 2016 Page 27


X:\4 INTERNAL DATA\17 1B2\03 REPORTS\04 ELECTRICAL\ELECTRICAL LEAD FOLDER\RIYADH-AMTECHCABLEDESIGNGUIDELINES-REV3.DOCX
BACS Riyadh Metro Project
Amtech Cable Design Guidelines

17.2.1 Essential Lighting Final Circuit Loads


FOR 100% INCLUDE ACTUAL CIRCUIT DETAILS FOR EACH CIRCUIT
Long Test Circuit – Cable & Id No. – DPBXX-EL-L
CIRCUIT PROTECTION
Schneider Acti9 MCB iC60H Type C BS EN60947-2 10A
CPD Breaking Capacity: Fully Rated
CABLE
DETAILS
Type: Prysmian FP200 Fire resistant cable Cu [Final cable type subject to Client confirmation]
Installation Method:
Cable tray, ladder systems, cleats, wire mesh tray
On horizontal/vertical perforated tray
Size: 2.5mm2 31A
Length: 70m (adopt length to suit station)
Ambient Temp: 30°C/45°C – to suit circuit route – discuss with mechanical team

GROUPING
With other circuits: Total no of grouped circuits 10 (or as relevant for station)

CPC
Separate conductor ONLY
Separate Conductor
Size: 2.5mm2

LOAD
Type: Lighting Radial Circuits
Length to First Fitting (m): 40m (adopt length to suit station)
Load: 3A
Power Factor: 1

239762-REP-E-0001 | Issue | 27 October 2016 Page 28


X:\4 INTERNAL DATA\17 1B2\03 REPORTS\04 ELECTRICAL\ELECTRICAL LEAD FOLDER\RIYADH-AMTECHCABLEDESIGNGUIDELINES-REV3.DOCX
BACS Riyadh Metro Project
Amtech Cable Design Guidelines

Short Test Circuit – Cable & Id No. – DPBXX-EL-S


CIRCUIT PROTECTION
Schneider Acti9 MCB iC60H Type C BS EN60947-2 10A
CPD Breaking Capacity: Fully Rated
CABLE
DETAILS
Type: Prysmian FP200 Fire resistant cable Cu [Final cable type subject to Client confirmation]
Installation Method:
Cable tray, ladder systems, cleats, wire mesh tray
On horizontal/vertical perforated tray
Size: 2.5mm2 31A
Length: 20m
Ambient Temp: 30°C/45°C – to suit circuit route – discuss with mechanical team

GROUPING
With other circuits: Total no of grouped circuits 10 (or as relevant for station)

CPC
Separate conductor ONLY
Separate Conductor
Size: 2.5mm2

LOAD
Type: Lighting Radial Circuits
Length to First Fitting (m): 5m
Load: 3A
Power Factor: 1

239762-REP-E-0001 | Issue | 27 October 2016 Page 29


X:\4 INTERNAL DATA\17 1B2\03 REPORTS\04 ELECTRICAL\ELECTRICAL LEAD FOLDER\RIYADH-AMTECHCABLEDESIGNGUIDELINES-REV3.DOCX