Riyadh AmtechCableDesignGuidelines Rev3
Riyadh AmtechCableDesignGuidelines Rev3
Contents
Page
1 Purpose of Document 1
2 Clarifications 1
4 Transformer Inputs 3
7 Generator Inputs 6
8 Submain to DP/EDP 7
9 Submain to DB Inputs 8
9.1 Small Power Final Circuit Loads 9
9.2 Lighting Final Circuit Loads 11
1 Purpose of Document
This document has been produced to provide design guidance for the Arup electrical team for the Amtech
cable design on the Riyadh Metro Project.
It should be used for internal design purposes only and should not be issued externally.
2 Clarifications
Only general inputs are provided. Project specific information such as lengths and loads should be included
by the station design teams.
Always set the inputs as you would like them to be and let the software tell you where these inputs are
failing and need to be changed. Do not set any cable size setting to auto.
All cable types are still to be finally agreed with the Client. The cable types modelled using Amtech may
not be 100% correct. Where different to what we are actually going to specify we’ll need to highlight the
differences in a schedule.
MCC final circuits should be fully modelled.
At 100% design stage, all final circuits should be fully modelled.
The guidelines within this document are presented in the following order;
1) Voltage Drop Allowances
2) Transformer Inputs
3) Main Busbar Inputs
4) Main Switchboard Inputs
5) Interconnecting Busbar Inputs
6) Generator Inputs
7) Submain to DP/EDPs
8) Submain to DB Inputs
a. Small Power Final Circuit Loads
b. Lighting Final Circuit Loads
9) Submain to MCC inputs
10) Submain to Chiller Inputs
11) Submain to Fire Pump Inputs
12) Submain to Lifts/Escalators Inputs
13) Submain to Large Motor Load Inputs
14) Submain to PFC inputs
15) Submain to CBS inputs
a. CBS inputs
b. Submains to Essential Lighting DBs
i. Essential Lighting Final Circuit Loads
4 Transformer Inputs
VOLTAGE
Primary Voltage: 33kV (Three Phase)
Secondary Voltage: 400V (Three Phase)
Frequency: 60Hz
Supply Type: Private Supply
User Defined: Voltage Drop Limit 4% [recent Client request from 5% to match Saudi regs]
FAULT CONDITIONS
Primary Fault Level: 250MVA
Rating (Tx): 1500kVA [Final rating TBC by Siemens – specific to each station]
Impedance: 6%
PROTECTION
Generic Relay BS142 Extremely Inverse set at 40A [use for now – final protection TBC by Siemens]
Protection Rated At: 100%
DIVERSITY
Define Load: Use the load from your load assessment for each LPS (MDB+EMDB added together)
Power Factor: 1
3rd Harmonic (%): 0 [Under review]
EARTHING
Earth at Supply Source Only – No Local Earthing at Board
7 Generator Inputs
VOLTAGE
Supply Voltage: 400V (three phase)
Frequency: 60Hz
Supply Type: Private Supply
User Defined: Voltage Drop Limit 4% [recent Client request from 5% to match Saudi regs]
Parallel Sources: 2
FAULT CONDITIONS:
Rating: 2x1600kVA=3200kVA [Rating TBC by Siemens]
Z%: 33% - This represents an achievable scenario where the AVR provides 300% Irated for 10secs.
Note: Model the generator as a lumped source of the total generator system capacity.
8 Submain to DP/EDP
LOAD
GROUPING
Arrangement: Horizontal Touching
Grouping with other circuits: Total no of grouped circuits 10 (or as relevant for station)
Subject to simultaneous overload: Not checked
If using parallel cable, make sure the derating is for 10+2=12 cables and not 10x2=20 cables
No. trays: 1 By setting this to 1 tray, this gives the worst case derating factor
CPC
Separate/Integral conductor ONLY
Separate Conductor
Greater than or equal to ½ circuit phase size [under discussion with Client]
UNLESS required by disconnection time and then uprate phase and associated resultant CPC to meet
disconnection time (CPC remains ½ circuit phase size)
CIRCUIT PROTECTION
Schneider Compact NSX MCCB NSX H Micrologic 2.2 – Ampere device & trip rating to suit load and to
achieve discrimination
Overload Setting: To suit load
(View Graph) Instantaneous Trip = 8 x In (Isd)
9 Submain to DB Inputs
LOAD
GROUPING
Arrangement: Horizontal Touching
Grouping with other circuits: Total no of grouped circuits 10 (or as relevant for station)
Subject to simultaneous overload: Not checked
If using parallel cable, make sure the derating is for 10+2=12 cables and not 10x2=20 cables
No. trays: 1 By setting this to 1 tray, this gives the worst case derating factor
CPC
Separate/Integral conductor ONLY
Separate Conductor
Greater than or equal to ½ circuit phase size [under discussion with Client]
UNLESS required by disconnection time and then uprate phase and associated resultant CPC to meet
disconnection time (CPC remains ½ circuit phase size)
CIRCUIT PROTECTION
Schneider Compact NSX MCCB NSX100H Micrologic 2.2 100A
Overload Setting: 63A [Default project setting–only change if required by DB load/discrimination purposes]
(View Graph) Instantaneous Trip = 8 x In (Isd)
NSX100 with a 63A trip unit will allow total discrimination with downstream MCBs up to 40A.
239762-REP-E-0001 | Issue | 27 October 2016 Page 8
X:\4 INTERNAL DATA\17 1B2\03 REPORTS\04 ELECTRICAL\ELECTRICAL LEAD FOLDER\RIYADH-AMTECHCABLEDESIGNGUIDELINES-REV3.DOCX
BACS Riyadh Metro Project
Amtech Cable Design Guidelines
GROUPING
With other circuits: Total no of grouped circuits 10 (or as relevant for station)
CPC
Separate conductor ONLY
Separate Conductor
Size: 4mm2
LOAD
Type: Fixed equipment single phase and neutral
Load: 5A
Power Factor: 1
GROUPING
With other circuits: Total no of grouped circuits 10 (or as relevant for station)
CPC
Separate conductor ONLY
Separate Conductor
Size: 4mm2
LOAD
Type: Fixed equipment single phase and neutral
Load: 5A
Power Factor: 1
GROUPING
With other circuits: Total no of grouped circuits 10 (or as relevant for station)
CPC
Separate conductor ONLY
Separate Conductor
Size: 2.5mm2
LOAD
Type: Lighting Radial Circuits
Length to First Fitting (m): 40m
Load: 3A
Power Factor: 1
GROUPING
With other circuits: Total no of grouped circuits 10 (or as relevant for station)
CPC
Separate conductor ONLY
Separate Conductor
Size: 2.5mm2
LOAD
Type: Lighting Radial Circuits
Length to First Fitting (m): 5m
Load: 3A
Power Factor: 1
DETAILS
Type (Cable): Prysmian FP600S Fire resistant cable Cu
Installation Method:
Cable tray, ladder systems, cleats, wire mesh tray
On horizontal/vertical perforated tray
Size: As required for Length/Amps but Not Set to Auto
Ambient Temp: 30°C/45°C – to suit circuit route – discuss with mechanical team
GROUPING
Arrangement: Horizontal Touching
Grouping with other circuits: Total no of grouped circuits 10 (or as relevant for station)
Subject to simultaneous overload: Not checked
If using parallel cable, make sure the derating is for 10+2=12 cables and not 10x2=20 cables
No. trays: 1 By setting this to 1 tray, this gives the worst case derating factor
CPC
Separate/Integral conductor ONLY
Separate Conductor
Greater than or equal to ½ circuit phase size [under discussion with Client]
UNLESS required by disconnection time and then uprate phase and associated resultant CPC to meet
disconnection time (CPC remains ½ circuit phase size)
CIRCUIT PROTECTION
Schneider Compact NSX MCCB NSX100H Micrologic 2.2 100A
Overload Setting: 63A [Default project setting–only change if required by DB load/discrimination purposes]
(View Graph) Instantaneous Trip = 8 x In (Isd)
GROUPING
With other circuits: Total no of grouped circuits 10 (or as relevant for station)
CPC
Separate conductor ONLY
Separate Conductor
Size: 4mm2
LOAD
Type: Fixed equipment single phase and neutral
Load: 5A
Power Factor: 1
GROUPING
With other circuits: Total no of grouped circuits 10 (or as relevant for station)
CPC
Separate conductor ONLY
Separate Conductor
Size: 4mm2
LOAD
Type: Fixed equipment single phase and neutral
Load: 5A
Power Factor: 1
DETAILS
Essential Loads - Prysmian FP600S Fire resistant cable Cu
Non Essential Loads
Type (Cable):
Route through Non-Public Space: Multicore 90°C thermosetting insulated, non-armoured LSF Table 4E2
Route through Public Space: Multicore 90°C thermosetting insulated, armoured LSF Table 4E4
Installation Method:
Cable tray, ladder systems, cleats, wire mesh tray
On horizontal/vertical perforated tray
[where cable route through public spaces make cable run within ducts]
Size: As required for Length/Amps but Not Set to Auto
Ambient Temp: 30°C/45°C – to suit circuit route – discuss with mechanical team
GROUPING
Arrangement: Horizontal Touching
Grouping with other circuits: Total no of grouped circuits 10 (or as relevant for station)
Subject to simultaneous overload: Not checked
If using parallel cable, make sure the derating is for 10+2=12 cables and not 10x2=20 cables
No. trays: 1 By setting this to 1 tray, this gives the worst case derating factor
CPC
Separate/Integral conductor ONLY
Separate Conductor
Greater than or equal to ½ circuit phase size [under discussion with Client]
UNLESS required by disconnection time and then uprate phase and associated resultant CPC to meet
disconnection time (CPC remains ½ circuit phase size)
CIRCUIT PROTECTION
Schneider Compact NSX MCCB NSX100H Micrologic 2.2 100A [Default project setting–only change if
required by MCC load/discrimination purposes]
239762-REP-E-0001 | Issue | 27 October 2016 Page 16
X:\4 INTERNAL DATA\17 1B2\03 REPORTS\04 ELECTRICAL\ELECTRICAL LEAD FOLDER\RIYADH-AMTECHCABLEDESIGNGUIDELINES-REV3.DOCX
BACS Riyadh Metro Project
Amtech Cable Design Guidelines
Overload Setting: 63A [Default project setting–only change if required by MCC load/discrimination
purposes]
(View Graph) Instantaneous Trip = 8 x In (Isd)
GROUPING
With other circuits: Total no of grouped circuits 10 (or as relevant for station)
CPC
Separate conductor ONLY
Separate Conductor
Greater than or equal to ½ circuit phase size [under discussion with Client]
UNLESS required by disconnection time and then uprate phase and associated resultant CPC to meet
disconnection time
DETAILS
Type (Cable):
Route through Non-Public Space: Multicore 90°C thermosetting insulated, non-armoured LSF Table 4E2
Route through Public Space: Multicore 90°C thermosetting insulated, armoured LSF Table 4E4
Installation Method:
Cable tray, ladder systems, cleats, wire mesh tray
On horizontal/vertical perforated tray
[where non-essential cable route through public spaces make cable run within ducts]
Size: As required for Length/Amps but Not Set to Auto
Ambient Temp: 30°C/45°C – to suit circuit route – discuss with mechanical team
GROUPING
Arrangement: Horizontal Touching
Grouping with other circuits: Total no of grouped circuits 10 (or as relevant for station)
Subject to simultaneous overload: Not checked
If using parallel cable, make sure the derating is for 10+2=12 cables and not 10x2=20 cables
No. trays: 1 By setting this to 1 tray, this gives the worst case derating factor
CPC
Separate/Integral conductor ONLY
Separate Conductor
Greater than or equal to ½ circuit phase size [under discussion with Client]
UNLESS required by disconnection time and then uprate phase and associated resultant CPC to meet
disconnection time (CPC remains ½ circuit phase size)
CIRCUIT PROTECTION
Schneider Compact NSX MCCB NSX630 [Default project setting–only change if required by chiller load]
Overload Setting: 630A [Default project setting–only change if required by chiller load]
(View Graph) Instantaneous Trip = 3 x In (Isd) (very long runs of cable > 200m will need Iinst = 2)
GROUPING
Arrangement: Horizontal Touching
Grouping with other circuits: Total no of grouped circuits 10 (or as relevant for station)
Subject to simultaneous overload: Not checked
If using parallel cable, make sure the derating is for 10+2=12 cables and not 10x2=20 cables
No. trays: 1 By setting this to 1 tray, this gives the worst case derating factor
CPC
Separate/Integral conductor ONLY
Separate Conductor
Greater than or equal to ½ circuit phase size [under discussion with Client]
UNLESS required by disconnection time and then uprate phase and associated resultant CPC to meet
disconnection time (CPC remains ½ circuit phase size)
CIRCUIT PROTECTION
Supply cable from Transformer
Circuit Breaker Rating: Breaker ampere rating In > Locked Rotor Current (LRA) of Fire Pump
e.g. FLA=300A, LRA=7x300A= 2100A, rating of breaker > 2100A i.e. 2500A.
Instantaneous Setting: In x 2
DETAILS
Type (Cable): Prysmian FP600S Fire resistant cable Cu
Installation Method:
Cable tray, ladder systems, cleats, wire mesh tray
On horizontal/vertical perforated tray
[where non-essential cable route through public spaces make cable run within ducts]
Size: As required for Length/Amps but Not Set to Auto
Ambient Temp: 30°C/45°C – to suit circuit route – discuss with mechanical team
GROUPING
Arrangement: Horizontal Touching
Grouping with other circuits: Total no of grouped circuits 10 (or as relevant for station)
Subject to simultaneous overload: Not checked
If using parallel cable, make sure the derating is for 10+2=12 cables and not 10x2=20 cables
No. trays: 1 By setting this to 1 tray, this gives the worst case derating factor
CPC
Separate/Integral conductor ONLY
Separate Conductor
Greater than or equal to ½ circuit phase size [under discussion with Client]
UNLESS required by disconnection time and then uprate phase and associated resultant CPC to meet
disconnection time (CPC remains ½ circuit phase size)
CIRCUIT PROTECTION
Schneider Compact NSX MCCB NSX100H Micrologic 2.2 100A [Default project setting–only change if
required by lift/escalator load/discrimination purposes]
Overload Setting: 63A [Default project setting–only change if required by lift/escalator load/discrimination
purposes]
(View Graph) Instantaneous Trip = 6 x In (Isd)
GROUPING
Arrangement: Horizontal Touching
Grouping with other circuits: Total no of grouped circuits 10 (or as relevant for station)
Subject to simultaneous overload: Not checked
If using parallel cable, make sure the derating is for 10+2=12 cables and not 10x2=20 cables
No. trays: 1 By setting this to 1 tray, this gives the worst case derating factor
CPC
Separate/Integral conductor ONLY
Separate Conductor
Greater than or equal to ½ circuit phase size [under discussion with Client]
UNLESS required by disconnection time and then uprate phase and associated resultant CPC to meet
disconnection time (CPC remains ½ circuit phase size)
CIRCUIT PROTECTION
Breaker Type/rating to suit the load and proposed motor starter. If using ACB then use an L1 type unit.
Overload Setting: To suit the motor being supplied. If only motor at end of cable then you should
contemplate using a motor rated circuit breaker which has only short circuit protection. This will allow the
cable to the motor to be reduced in size.
(View Graph) Instantaneous Trip = 3 x In (Isd)
GROUPING
Arrangement: Horizontal Touching
Grouping with other circuits: Total no of grouped circuits 10 (or as relevant for station)
Subject to simultaneous overload: Not checked
If using parallel cable, make sure the derating is for 10+2=12 cables and not 10x2=20 cables
No. trays: 1 By setting this to 1 tray, this gives the worst case derating factor
CPC
Separate/Integral conductor ONLY
Separate Conductor
Greater than or equal to ½ circuit phase size [under discussion with Client]
UNLESS required by disconnection time and then uprate phase and associated resultant CPC to meet
disconnection time (CPC remains ½ circuit phase size)
CIRCUIT PROTECTION
Manufacturer: Schneider
Family: Masterpact NT ACB FOR > 630A, Compact MCCB NSX <= 630A
Type: Use the L1 current limiting type for ACB
Protection: ACB = MLogic 2.0 Std
Rating: To suit PFC rating – breaker rating > 2 x kVA rating i.e. 500kVAr = 1000A ACB
Detailed Settings inside the View Graph feature: See Selectivity Study Report
GROUPING
Arrangement: Horizontal Touching
Grouping with other circuits: Total no of grouped circuits 10 (or as relevant for station)
Subject to simultaneous overload: Not checked
If using parallel cable, make sure the derating is for 10+2=12 cables and not 10x2=20 cables
No. trays: 1 By setting this to 1 tray, this gives the worst case derating factor
CPC
Separate/Integral conductor ONLY
Separate Conductor
Greater than or equal to ½ circuit phase size [under discussion with Client]
UNLESS required by disconnection time and then uprate phase and associated resultant CPC to meet
disconnection time (CPC remains ½ circuit phase size)
CIRCUIT PROTECTION
Schneider Compact NSX MCCB NSX250H Micrologic 2.2 Trip Unit 160A [Default project setting–only
change if required by CBS rating]
Overload Setting: 160A [Default project setting–only change if required by CBS rating]
(View Graph) Instantaneous Trip = 8 x In (Isd)
FAULT CONDITIONS
Phase & Earth Fault Current (kA): Use 3 x full load current of CBS
i.e. 60kVA=87A => 87Ax3= 261A
The CB inverter should be able to supply 300% for long enough to trip the submain & final circuit breakers.
PROTECTION
Match the CBS protection device to the protection device of the submain to the CBS.
You have to include some device in here to make the program work but under battery operation, this device
will not actually exist. The cable from the central battery inverter to the central battery output switchboard
will be protected using electronic fuses within the CBS. The inclusion of the above protective device will
give rise to an error in Amtech, which can be ignored.
DETAILS
Type (Cable): Prysmian FP600S Fire resistant cable Cu
Installation Method:
Cable tray, ladder systems, cleats, wire mesh tray
On horizontal/vertical perforated tray
Size: As Requested for Length/Amps but Not Set to Auto
Ambient Temp: 30°C/45°C – to suit circuit route – discuss with mechanical team
GROUPING
Arrangement: Horizontal Touching
Grouping with other circuits: Total no of grouped circuits 10 (or as relevant for station)
Subject to simultaneous overload: Check this box for submains to essential lighting DBs
If using parallel cable, make sure the derating is for 10+2=12 cables and not 10x2=20 cables
No. trays: 1 By setting this to 1 tray, this gives the worst case derating factor
CPC
Separate/Integral conductor ONLY
Separate Conductor
Greater than or equal to ½ circuit phase size [under discussion with Client]
UNLESS required by disconnection time and then uprate phase and associated resultant CPC to meet
disconnection time (CPC remains ½ circuit phase size)
CIRCUIT PROTECTION
Schneider Compact NSX MCCB NSX100H Micrologic 2.2 100A
Overload Setting: 40A [Default project setting–only change if required by DB load/discrimination purposes]
(View Graph) Instantaneous Trip = 4 x In (Isd)
These specific 40A breaker trip unit and instantaneous trip settings have been proposed to allow operation of
the submain MCCB when the system is running under a reduced fault level from the CBS batteries.
GROUPING
With other circuits: Total no of grouped circuits 10 (or as relevant for station)
CPC
Separate conductor ONLY
Separate Conductor
Size: 2.5mm2
LOAD
Type: Lighting Radial Circuits
Length to First Fitting (m): 40m (adopt length to suit station)
Load: 3A
Power Factor: 1
GROUPING
With other circuits: Total no of grouped circuits 10 (or as relevant for station)
CPC
Separate conductor ONLY
Separate Conductor
Size: 2.5mm2
LOAD
Type: Lighting Radial Circuits
Length to First Fitting (m): 5m
Load: 3A
Power Factor: 1