SH-Corrective Action - Maintenance Plot Control Panel
SH-Corrective Action - Maintenance Plot Control Panel
Incident details
Date and Time of the 07/10/2024, 11:30 am
Incident
Location Maintenance Plot - Temporary Power Generator Area
Reported by Angelo R. Panotes
Type of Incident The temporary power distribution panel board was found with open
door panel.
Dust and dirt accumulated inside the enclosure with can potentially
cause contact resistance to the electrical connection between wires
and circuit breaker terminals.
Contact resistance is one of the causes of heating at the terminals of
the circuit breaker which could lead to arc flash incident.
Corrective Actions
Responsible Personnel:
• Electrical Supervisor
• Maintenance Technician
Completion Timeline:
Prepare By : Nagalingam