Multilevel Converters Analysis Modulation Topologies and Applications
Multilevel Converters Analysis Modulation Topologies and Applications
Converters
Analysis, Modulation,
Topologies, and Applications
Edited by
Gabriele Grandi and Alex Ruderman
Printed Edition of the Special Issue Published in Energies
www.mdpi.com/journal/energies
Multilevel Converters
Multilevel Converters: Analysis,
Modulation, Topologies,
and Applications
Editorial Office
MDPI
St. Alban-Anlage 66
4052 Basel, Switzerland
This is a reprint of articles from the Special Issue published online in the open access journal Energies
(ISSN 1996-1073) from 2018 to 2019 (available at: https://www.mdpi.com/journal/energies/special
issues/multilevel converters)
For citation purposes, cite each article independently as indicated on the article page online and as
indicated below:
LastName, A.A.; LastName, B.B.; LastName, C.C. Article Title. Journal Name Year, Article Number,
Page Range.
c 2019 by the authors. Articles in this book are Open Access and distributed under the Creative
Commons Attribution (CC BY) license, which allows users to download, copy and build upon
published articles, as long as the author and publisher are properly credited, which ensures maximum
dissemination and a wider impact of our publications.
The book as a whole is distributed by MDPI under the terms and conditions of the Creative Commons
license CC BY-NC-ND.
Contents
Ming Wu, Zhenhao Song, Zhipeng Lv, Kai Zhou and Qi Cui
A Method for the Simultaneous Suppression of DC Capacitor Fluctuations and Common-Mode
Voltage in a Five-Level NPC/H Bridge Inverter
Reprinted from: energies 2019, 12, 779, doi:10.3390/en12050779 . . . . . . . . . . . . . . . . . . . . 66
Jingyuan Yin, Wen Wu, Tongzhen Wei, Xuezhi Wu and Qunhai Huo
A Novel Fault-Tolerant Control of Modular Multilevel Converter under Sub-Module Faults
Based on Phase Disposition PWM
Reprinted from: energies 2019, 12, 20, doi:10.3390/en12010020 . . . . . . . . . . . . . . . . . . . . 80
Zongbin Ye, Anni Chen, Shiqi Mao, Tingting Wang, Dongsheng Yu and Xianming Deng
A Novel Three-Level Voltage Source Converter for AC–DC–AC Conversion
Reprinted from: energies 2018, 11, 1147, doi:10.3390/en11051147 . . . . . . . . . . . . . . . . . . . 136
v
Salvatore Foti, Giacomo Scelba, Antonio Testa and Angelo Sciacca
An Averaged-Value Model of an Asymmetrical Hybrid Multi-Level Rectifier
Reprinted from: energies 2019, 12, 589, doi:10.3390/en12040589 . . . . . . . . . . . . . . . . . . . . 186
Fabio Viola
Experimental Evaluation of the Performance of a Three-Phase Five-Level Cascaded H-Bridge
Inverter by Means FPGA-Based Control Board for Grid Connected Applications
Reprinted from: energies 2018, 11, 3298, doi:10.3390/en11123298 . . . . . . . . . . . . . . . . . . . 282
Zhi Wu, Jiawei Chu, Wei Gu, Qiang Huang, Liang Chen and Xiaodong Yuan
Hybrid Modulated Model Predictive Control in a Modular Multilevel Converter for
Multi-Terminal Direct Current Systems
Reprinted from: energies 2018, 11, 1861, doi:10.3390/en11071861 . . . . . . . . . . . . . . . . . . . 377
Jiazheng Lu, Siguo Zhu, Bo Li, Yanjun Tan, Xiudong Zhou, Qinjun Huang, Yuan Zhu and
Xinguo Mao
Low-Harmonic DC Ice-Melting Device Capable of Simultaneous Reactive Power Compensation
Reprinted from: energies 2018, 11, 2596, doi:10.3390/en11102596 . . . . . . . . . . . . . . . . . . . 394
vi
Yajun Ma, Hua Lin, Zhe Wang and Zuyao Ze
Modified State-of-Charge Balancing Control of Modular Multilevel Converter with Integrated
Battery Energy Storage System
Reprinted from: energies 2019, 12, 96, doi:10.3390/en12010096 . . . . . . . . . . . . . . . . . . . . 411
Salvatore Foti, Antonio Testa, Salvatore De Caro, Tommaso Scimone, Giacomo Scelba and
Giuseppe Scarcella
Multi-Level Open End Windings Multi-Motor Drives
Reprinted from: energies 2019, 12, 861, doi:10.3390/en12050861 . . . . . . . . . . . . . . . . . . . . 431
Xiaoqiong He, Haijun Ren, Jingying Lin, Pengcheng Han, Yi Wang, Xu Peng and
Zeliang Shu
Power Flow Analysis of the Advanced Co-Phase Traction Power Supply System
Reprinted from: energies 2019, 12, 754, doi:10.3390/en12040754 . . . . . . . . . . . . . . . . . . . . 467
vii
About the Special Issue Editors
Gabriele Grandi received his M.Sc. (cum laude) and Ph.D. degrees in Electrical Engineering
from the University of Bologna, Bologna, Italy, in 1990 and 1994, respectively. He has been with
the Department of Electrical, Electronic, and Information Engineering, University of Bologna as
Research Associate (since 1995), Associate Professor (since 2005), and most recently as Full Professor
(since 2016) in Electrical Engineering. He is the Founder and Leader of the research laboratory
“SolarTronic-Lab” at University of Bologna, dealing with power electronic circuits, multiphase and
multilevel converters, photovoltaics, electric vehicle chargers, and circuit modeling. He has authored
or co-authored more than 160 papers in conference proceedings and international journals, mainly
with the IEEE. Dr. Grandi serves as Editor-at-Large for IET Power Electronics, Academic Editor for
MDPI Energies and MDPI Electronics, and Associate Editor for IEEE Trans. on Industrial Electronics.
Alex Ruderman obtained his M.Sc. (cum laude) and Ph.D. degrees from the Electrotechnical
University and Polytechnic University (former Leningrad, USSR; now St. Petersburg, Russia) in 1980
and 1987 respectively. In 1995–2003, he worked as an R&D engineer for Intel Microprocessor
Development Center, Haifa, Israel. In 2004–2013, Alex taught electronics-related courses in Bar
Ilan University, Ariel University and Holon Institute of Technology as Adjunct Professor. In 2006,
he joined Elmo Motion Control, Petach Tikva, Israel, the makers of compact intelligent servo drives,
as a Chief Scientist (Elmo drives are used by NASA in Mars Curiosity and InSight missions).
Since 2013, Alex has been Associate Professor at Nazarbayev University School of Engineering and
Digital Sciences, Electrical and Computer Engineering Department. Alex is a regular reviewer for
IEEE Transactions on Industrial Electronics and Power Electronics and a program committee member for
several international Power Electronics Conferences. His major research focus is multilevel power
converters—he has authored over 60 conference and journal papers on the subject. Alex is an IEEE
Senior Member and Associate Editor for the IET Journal of Power Electronics.
ix
Preface to ”Multilevel Converters: Analysis,
Modulation, Topologies, and Applications”
Multilevel inverters (MLIs) have been widely used for medium- and high-voltage power
applications in the recent decades, mainly for grid-connected applications to interface with renewable
energy sources. Compared to basic two-level inverters, MLIs offer many advantages, such as
reduced voltage rating of power switches, reduced voltage and current harmonic distortion, reduced
electromagnetic interference, as well as flexibility and modularity.
MLIs became a standard for applications such as in medium voltage drives and HVDC
grids, and are promising for lower voltage applications such as in battery chargers, active filters,
static compensators, dynamic voltage restorers, rectifiers, grid-tied inverters, and many more.
Increased efficiency and reduced harmonic distortion are beneficial for photovoltaic systems and
uninterruptible power supplies. The introduction of multilevel topologies has shifted the power
converter design paradigm, including control and modulation strategies, component selection and
requirements, reliability aspects, amongst others. While relatively low-power applications employ
high-frequency PWM, for high-voltage/current applications, the switching frequency of the power
semiconductors is limited to few kHz by switching loss considerations, and the use of multilevel
converters becomes mandatory.
xi
energies
Article
A Full-bridge Director Switches based Multilevel
Converter with DC Fault Blocking Capability
and Its Predictive Control Strategy
Jin Zhu, Tongzhen Wei *, Qunhai Huo and Jingyuan Yin
Institute of Electrical Engineering, Chinese Academy of Sciences, Haidian District, Beijing 100190, China;
[email protected] (J.Z.); [email protected] (Q.H.); [email protected] (J.Y.)
* Correspondence: [email protected]; Tel.: +86-182-1116-1108
1. Introduction
The modular multilevel converter (MMC) has been accepted as a suitable solution for high-voltage
and high-power application fields due to several inherent features [1–8]. However, blocking the DC
fault current becomes a difficult problem because the anti-parallel diodes are still conducting after
the insulated-gate bipolar transistors (IGBTs) of HBSM are turned off [9].
To solve this problem, recent research has highlighted a number of interesting converter
topologies which combine the features of the multilevel output AC voltage waveform and DC
fault blocking capacity [9–22]. Full-bridge sub-module (FBSM) based MMC (F-MMC) is a basic
configuration with DC fault current blocking capacity [10,11]. However, the DC fault current blocking
capability comes at a cost of nearly doubling power losses and number of semiconductor devices.
Some other type of sub-module is proposed instead of FBSM to make a further optimization in
reducing the number of IGBTs, such as a clamp double sub-module (CDSM) proposed in [14,15]
and a three-level cross-connected sub-module (TCSM) proposed in [16]. Several hybrid MMC
topologies are also proposed, based on HBSM and those various types of sub-module [9,12,13,16–19,23],
for further reducing the cost and loss on the premise of having the DC fault blocking capacity,
such as hybrid MMC based on CDSM and HBSM (CH-MMC). However, there are still some drawbacks,
for example, as they are composed of a large number of sub-modules, the system needs to be more
complicated and the converter station bulkier.
The alternate-arm multilevel converter (AAMC) based on the hybrid topology of HBSM
and director switches is proposed in [20–22]. The AAMC further improves the traditional MMC
topology by cutting the number of sub-modules, reducing DC bus voltage, and gaining the ability
to block DC fault currents [22]. However, some features still have the possibility for further
optimization, such as the size and cost of the overall system. One of the main technical challenges
associated with the control of such a director switches based multilevel converter is to simultaneously
keep the capacitor voltages balanced and provide good output current tracking performance,
while the director switches keep switching in low frequency.
In order to further optimize the size and cost of the voltage source converter-based high-voltage
direct current transmission system (VSC-HVDC) converter with the blocking ability of DC faults,
this paper proposes a full bridge director switches based alternate-arm multi-level converter (FA-MMC)
and a corresponding control strategy:
1. The size and cost of the overall system can be significantly reduced by reducing the number of
SM capacitors, IGBTs, and other related devices. In addition, an FA-MMC retains the ability to
block DC-side faults since it uses H-bridge SMs as the AAMC.
2. Similar to AAMC, a systematic multi-objective control method is needed for this kind of topology
to minimize the error of output AC current and the capacitor voltage of the sub-module
while the director switches are operated in low-frequency mode. A suitable predictive control
strategy for this kind of topology is presented in this paper to achieve the flexibility to include
the previously mentioned multiple system requirements.
2. Proposed Topology
Pÿ
Vdc/2 P
Upper stack of Cell
H-bridge cells SiVci
Vupper Cell C Vci
Cell Vstack Stack of
H-bridge cells
t Cell
Buffer inductor t
Director switch B
Vdirector
Vac
O Vac ib Buffer inductor
UDC t
M t
t
Vlower S1 S2
Director
t
Cell switch A C
R Ls
Lower stack of is
H-bridge cells Cell
-Vdc/2 S3 S4
Nÿ N
(a) (b)
The voltage of the director switches (Udirector in Figure 1b) is equal to the DC voltage
(UDC in Figure 2) plus the voltage produced by the stack of H-bridge SMs which can be considered
as only one controllable voltage source. Therefore, the voltage of director switches can be adjusted
flexibly so that the switching of S1 –S4 can switch at near to zero voltage. The ideal voltage waveform
is shown in Figure 2a.
2
Energies 2019, 12, 91
(a) (b)
Figure 2. The voltage waveform and state of S1–S4: (a) without energy balance mode; (b) with energy
balance mode.
The working cycle of S1 –S4 is synchronized with the output AC voltage. S1 and S4 are conducting
and S2 and S3 are turned off while the output AC voltage (Uac in Figure 1b is in its positive half-cycle,
in contrast, S2 and S3 are conducting and S1 and S4 are turned off while the output AC voltage is
in its negative half-cycle. This ensures that the four director switches can switch at low-frequency
and at the point of zero-voltage-crossing as shown in Figure 2a. These features lead to low switching
losses, and low demand for dynamic voltage sharing at the switching instant of the series switches,
so that the system design has been simplified.
∧ ∧
3 V AC I AC
E AC = π cos( ϕ), (1)
2 ω
∧
6UDC I AC
EDC = cos( ϕ), (2)
ω
For EAC to equal EDC , the relationship between the DC voltage magnitudes and AC voltage
magnitudes mentioned in Equations (1) and (2) can be given as
π∧
UDC = V , (3)
4 AC
However, since the converters can’t operate in the perfect given by Equation (3), an energy
balancing strategy should be used.
Reference [22] presented two methods to achieve energy balance for AAMCs that can also be
used in this topology: Overlap current and third harmonic current injection. In this paper the overlap
current method is used to extend the period when the current directed from S1 and S4 to S2 and S3
is extended and S1 –S4 are all conducting. The overlap current is used to exchange power between
3
Energies 2019, 12, 91
the sub module capacitors and the DC bus. The load current is only slightly affected, since the overlap
time is very short and the inductance can smooth the change in current. Considering its effect on
the grid current, the overlap time is determined to be less than 0.8 ms.
dib
UDC − VPB − Lb = VMN (4)
dt
dis
VAC = Ls + Ris (5)
dt
VAC = Sd VMN (6)
As presented in Section 2, the value of Lb is small and the voltage on it can be ignored; S1 –S4 have
five switching state combinations depending on a switching function Sd as shown in Table 1.
The output voltage of each H-bridge sub module is equal to Vci (capacitor voltage of the ith sub
module (i = 1, 2, · · · , n)), −Vci , or zero, depending on the switching states, and depends on a switching
function Si ⎧
⎪
⎨ 1
Si = 0 (i = 1, 2, . . . , n). (7)
⎪
⎩ −1
The dynamic capacitor voltage of the cells of the H-bridge sub module in Figure 1b is formalized as
dVci
Si i b = C (10)
dt
4
Energies 2019, 12, 91
The relationship of currents is and ib in Figure 1b, which was also indicated by the switching
function Sd according to Table 1, is expressed as
ib = Sd is (Sd = 1 or − 1) (11a)
n
dib
L = UDC − ∑ Si Vci (Sd = 0) (11b)
dt i =1
The switching states of director switches operate in an energy balancing mode, as mentioned
in Table 1. As discussed previously, the current ib flows through the stack of H-bridge sub modules,
buffer inductor, and director switch to the DC side, charging or discharging the capacitor of
the H-bridge sub modules.
Only considering the basic operating mode, substituting Equations (5), (6), (9), and (11a) into (4),
a dynamic model of the single-phase proposed topology in basic operating mode can be expressed as
n
dis dis
Sd (UDC − ∑ Si Vci − Sd Lb ) = Ls + Ris (12)
i =0
dt dt
where L = Lb + Ls .
the value of Sd could be assumed as a constant value during a short sampling period of Ts . is (k) is
the actual AC current at time k and is (k + 1) is the predicted AC current at time k + 1, UDC (k) can be
considered as a constant value if the DC side voltage is controlled. Finally, Vci (k) is the capacitor
voltage of the sub module i at time k.
To reduce the error between the predicted current and the reference current, a cost function
associated with the current error is defined as
Ji =isre f (k + 1) − is (k + 1) (15)
where isref is the reference current and is (k + 1) is the predicted current obtained from Equation (14).
Ideally, Ji will be equal to its minimum value of (Jmin = 0 in Figure 4) if the AC-side current is
controlled well.
5
Energies 2019, 12, 91
Si ( k ) S d ( k ) i s ( k )
Vci (k + 1) = Vci (k ) + Ts (16)
C
where Vci (k) can be measured in real time. Another cost function for balancing the capacitor voltage of
sub modules is given as
n
Jvc = ∑ Vci (k + 1) − Vcire f (k + 1) (17)
i =1
where Vciref (k + 1) is the reference DC capacitor voltage of sub module i (with i between 1 and n),
n
∑ Vci (k +1)
which can be equal to the average voltage of all cells (given as i=1 n ), and Vci (k + 1) is a predicted
value, which can be obtained from Equation (16).
Consequently, by adding the above cost function together a combined cost function,
which can simultaneously achieve the two main control objectives mentioned above is given
as the linear combination
Jall = α Ji + β Jvc (18)
where α and β are weighing factors, α is adjusted based on the cost contribution allocated to the error of
AC-Side current, and β is adjusted based on the cost contribution allocated to the voltage deviations of
sub module capacitors. The empirical method to determine the value of cost function is presented in [24].
Within each sampling and computing period Ts , the combined cost function Jall is re-calculated,
and the best switching indicated to the minimum value for Equation (18) will be adopted for the current
control cycle.
1. Add the energy-balancing mode (Sd = 0 in Table 1) in to achieve energy balancing of the stack of
H-bridge by exchanging power with DC bus.
2. Avoid repeated switching of the director switches.
Replacing is (k) by isref (k), the necessary value of VAC at the current step can be expressed as
L
VACre f (k + 1) = Risre f (k + 1) + (i (k + 1) − isre f (k)) (20)
Ts sre f
where isref (k) is the reference value of the current of the current step. Voltage VACref (k + 1), obtained by
Equation (20), is a standard sine wave, which can avoid the fluctuation of VAC (k + 1) due to differences
between isref (k + 1) and is (k) during zero voltage crossings. Finally, the implementation procedure
of the proposed director switch control strategy is summarized in Part I of Figure 4. The schematic
diagram of the control system is shown in Figure 3.
6
Energies 2019, 12, 91
Vciref
UDC/n Si
isref Predictive Vci(i=1,2Ăn)
1-ph
Vci(i=1,2Ăn) control
FA-MMC is
algorithm Sd
is
4. Simulation Results
This section evaluates the performance of the proposed FA-MMC and control method with
a simulation. The simulation parameters are given in Table 2. Ă
7
Energies 2019, 12, 91
I Iref
1K
0.5K
0K
-0.5K
-1K
(a)
Figure 5. Cont.
8
Energies 2019, 12, 91
Vac
6K
4K
2K
0K
-2K
-4K
-6K
(b)
Vpc
4K
3K
2K
1K
0K
-1K
-2K
5K
4K
3K
2K
1K
0K
-1K
(d)
Figure 5. Simulation waveform of the single-phase FA-MMC in steady state operation: (a) Load current
and reference current; (b) output AC voltage; (c) voltage of the stack of H-bridges; (d) voltage across
the director switches S1 –S4 .
Vup1 Vup2
1.6K
1.55K
1.5K
1.45K
1.4K
1.35K
9
Energies 2019, 12, 91
S1 S2 S3 S4
0.8
0.6
0.4
0.2
(a)
S1 S2 S3 S4
0.8
0.6
0.4
0.2
Vnext Vref_next
6K
4K
2K
0K
-2K
-4K
-6K
10
Energies 2019, 12, 91
Ib Is
500
-500
I Iref
1K
0.5K
0K
-0.5K
-1K
(a)
I Iref
500
-500
(b)
Figure 10. Load current for a sudden change: (a) reference current and actual load current; (b) Detail of
the reference current and actual load current at the instant.
11
Energies 2019, 12, 91
Vac
5K
0K
-5K
5K
0K
-5K
(b)
Figure 11. Output AC voltage waveforms: (a) Output AC voltage ; (b) detail of the output AC voltage
at the instant.
Vup1 Vup2
1.6K
1.55K
1.5K
1.45K
1.4K
1.35K
1.5K
1.45K
1.4K
12
Energies 2019, 12, 91
Figure 13 shows the states of the director switches at the instant of the sudden change
of load current, demonstrating that the director switches are controlled well and operated in
low-frequency mode.
S1 S2 S3 S4
0.8
0.6
0.4
0.2
0
0.02 0.03 0.04 0.05 0.06
Time (s)
Ia Ib Ic
300
200
100
0
-100
-200
-300
-500
-1000
0.02 0.03 0.04 0.05 0.06
T i me (s)
(b)
Figure 14. Cont.
13
Energies 2019, 12, 91
2000
1500
1000
500
0
0.02 0.03 0.04 0.05 0.06
T i me (s)
(c)
Figure 14. Current and voltage simulation waveforms of a DC fault: (a) AC current; (b) DC current;
(c) capacitor voltages.
5. Experimental Results
Experiments on an FA-MMC-based inverter were also carried out to verify the proposed topology
and test the predictive control strategy. The parameters for the experiment are listed in Table 3.
A photo of the inverter is shown in Figure 15 and an IGBT is utilized as the power switch. The main
control algorithms were implemented in a combination of a DSP and FPGA. The DC-link voltage
was obtained via a three-phase autotransformer.
Figure 15. Photo of the modular multilevel converter (MMC)-based inverter for the experiment.
14
Energies 2019, 12, 91
To test the system balance ability, a 100 Ω resistor was shunted to capacitor SM2. The topology
worked in this unbalanced condition by appropriately setting the value of the weighting factor β,
which is used to balance the capacitor voltage of the two SMs to zero. In this paper, we set the weighting
factor α to a fixed value of 50, and set weighting factor β to 0 or 100 to compare the waveforms.
Figure 16 shows the capacitor voltages of the two SMs. At first, the capacitor voltage of SM1 is lower
than SM2, and the fluctuation is larger due to the unbalanced condition. After giving a suitable
value to weighting factor β, each cell capacitor voltage is well regulated to their reference value
and the fluctuation of the two cells is also the same.
Figures 17 and 18 show the output current and voltage of this topology, which are both measured
during balanced and unbalanced operation. From Figure 18 we can see that the voltage ripple of
the two cell capacitors does not affect the current, apparently due to the robustness of the predictive
control. When the weighting factor β is set to 100, meaning that the capacitor voltage balance is
considered as a control goal, only a slight distortion is introduced into the output current.
15
Energies 2019, 12, 91
Figure 17. The waveform of the output current under balanced and unbalanced conditions.
Figure 18. The waveform of the output voltage under balanced and unbalanced conditions.
To test the dynamic performance, the behavior of the FA-MMC and corresponding control
method for a step in the angle of the reference current is shown in Figure 19. The waveforms show
that the voltage changed quickly to drive the current to its new reference value and that the current is
well-tracked. Figure 19 also shows that the dynamic capacitor voltage waveform is not influenced by
the step in the angle of the reference current. Figure 20 shows a detailed view of the output voltage
and current for a step in the angle of the reference current. The reference tracking of the proposed
method that considered the possible switching states adjacent to VAC (k + 1) is fast, because extreme
voltage changes are possible. The results are similar to simulation results.
16
Energies 2019, 12, 91
Figure 19. Waveform of the voltage and current for a step in the angle of the reference current.
Figure 20. Detail of the output voltage and current for a step in the angle of the reference current.
17
Energies 2019, 12, 91
connected in series, as shown in Figure 21. The equivalent capacitor value in Figure 21 can be
expressed as
Ce = C/ncell_FA (21)
where C is the capacitance of the capacitor in each cell and ncell_FA is the number of cells in one phase
of the FA-MMC. The AC source charges the equivalent capacitor and inductors (including the Ls , Lb , Ld )
through the DC fault current, thus, limiting the rising rate of the fault current. Consequently, the value
of Uce will rise rapidly, and the DC fault current will be blocked.
Figure 21. The equivalent circuit of the insulated-gate bipolar transistors (IGBTs) blocking when a DC
fault occurs.
∧ ∧
V MN U AC
nS = = (24)
URATED URATED
Given the same AC output voltage, we also can deduce the DC voltage, number of cells, and IGBTs
needed in an AAMC. The relationship between DC and AC voltage magnitudes in an AAMC,
which has been derived in [22], can be expressed as
π∧
Vdc = V (25)
2 AC
18
Energies 2019, 12, 91
It can be seen from Equation (3) and (25) that the FA-MMC can reduce the DC bus voltage by half
with the same AC output voltage and same active/reactive power flow compared with an AAMC.
Considering the sum of the sub-module capacitor voltage must be greater than the peak value
of the line-to-line voltage to achieve DC current blocking capability, the number of sub-modules of
an AAMC can be expressed as
√ Λ
3U AC
ncell_AA = (26)
URATED
But, it only has two direct switches, so considering Equation (24) and (26), the number of IGBTs of
a single-phase AAMC is given by
√ ∧
(4 3 + 2)U AC
n IGBT2 = 4ncell_AA + 2nS = (27)
URATED
To summarize, the number of IGBTs of the FA-MMC is less than that of the AAMC, and the DC
voltage and number of sub-modules of the FA-MMC is nearly half those of the AAMC, leading to
smaller size, less need for insulation, and lower cost. And the comparison results of the number of
IGBTs and sub-module capacitors between FA-MMC, AAMC and various MMC topologies mentioned
in the introduction is shown in Table 4.
19
Energies 2019, 12, 91
Topology Economy Efficiency Volume DC Fault Blocking Capacity Demand for Insulation
H-MMC +++ +++ + + +
F-MMC + + + ++ +
CH-MMC ++ ++ + ++ +
AAMC ++++ +++++ ++ ++ ++
FA-MMC +++++ ++++ +++ ++ +++
7. Conclusions
In this paper, a FA-MMC topology and its predictive control scheme have been proposed.
The effectiveness of the proposed topology and proposed control strategy under various operating
conditions are evaluated based on simulation studies in the PowerSIM environment and experiments,
and the comparisons with other topological structures are also given. Through the analysis
and demonstration mentioned above, the characteristics of this topology and its predictive control
strategy are summarized as follows:
(1) The sub-module capacitor number of FA-MMC reduce significantly while connecting to
the same AC voltage level and power level, results in a more compact structure;
(2) Further, it reduces the number of needed IGBTs while retaining the ability to block a DC-side
fault compared with other topologies, so that the cost of the system is reduced;
(3) The algorithm the algorithm has been proved to be able to achieve multiple control
objectives of FA-MMC simultaneously (i.e., capacitor voltages balancing and ac-side currents control).
The developed control strategy also contains a director switch control function so that the director
switch maintains operation in low-frequency and zero voltage switching mode.
Author Contributions: Conceptualization, J.Z.; methodology, T.W.; software, J.Y.; validation, J.Z., Q.H. and J.Y.;
writing—original draft preparation, J.Z.
Funding: This work was supported by National Key R&D Program of China (2016YFB0900900), the National
Natural Science Fund of China (No. 51607171).
Conflicts of Interest: The authors declare no conflict of interest. The funders had no role in the design of the study;
in the collection, analyses, or interpretation of data; in the writing of the manuscript, or in the decision to publish
the results.
Glossary of Terms
EAC The amount of energy transferred from AC side over half the fundamental period
EDC The amount of energy going to DC side over half the fundamental period.
VAC Output ac voltage
IAC AC current
UDC DC voltage of FA MMC
Ce Equivalent capacitance while all capacitors in cells connected in series
Uce_int Initial voltage of Ce when dc fault blocking
ϕ Angular position of AC current
ncell_FA Number of cells of FA-MMC each phase
URATED The rated voltage of IGBT
nIGBT1 The needed number of IGBTs of FA-MMC each phase
n The needed number of IGBTs of S1–S4
ncell_AA The needed number of cells of AAMC each phase
nIGBT2 The needed number of IGBTs of AAMC each phase
Vdc DC voltage of AAMC while the output AC voltage is equal to FA MMC
VPB The voltage produced by the stack of H-bridge cells of FA MMC
Si Switching function of the ith cell
Vci The capacitor voltage of the ith cell
20
Energies 2019, 12, 91
Lb Buffer inductor
Ib The current through Lb
C The capacitor value of cell
Sd Switching function of director switch
Ls Filter inductor
Is The current through Ls
Ts Sampling period
Jall , Ji , Jvc Cost function
α, β Weighting factor
References
1. Wang, Y.; Yang, B.; Zuo, H.; Liu, H.; Yan, H. A DC Short-Circuit Fault Ride Through Strategy of MMC-HVDC
Based on the Cascaded Star Converter. Energies 2018, 11, 2079. [CrossRef]
2. Xiao, L.; Li, Y.; Xiao, H.; Zhang, Z.; Xu, Z. Electromechanical Transient Modeling of Line Commutated
Converter-Modular Multilevel Converter-Based Hybrid Multi-Terminal High Voltage Direct Current
Transmission Systems. Energies 2018, 11, 2102. [CrossRef]
3. Wu, Z.; Chu, J.; Gu, W.; Huang, Q.; Chen, L.; Yuan, X. Hybrid Modulated Model Predictive Control
in a Modular Multilevel Converter for Multi-Terminal Direct Current Systems. Energies 2018, 11, 1861.
[CrossRef]
4. Li, Z.; Tan, G. A Black Start Scheme Based on Modular Multilevel Control-High Voltage Direct Current.
Energies 2018, 11, 1715. [CrossRef]
5. Pouresmaeil, E.; Mehrasa, M.; Rodrigues, E.; Godina, R.; Catalão, J.P.S. Control of Modular Multilevel
Converters Under Loading Variations in Distributed Generation Applications. In Proceedings of the 2018
IEEE International Conference on Environment and Electrical Engineering and 2018 IEEE Industrial
and Commercial Power Systems Europe (EEEIC/I CPS Europe), Palermo, Italy, 12–15 June 2018; pp. 1–6.
6. Hakimi, S.M.; Hajizadeh, A. Integration of Photovoltaic Power Units to Power Distribution System through
Modular Multilevel Converter. Energies 2018, 11, 2753. [CrossRef]
7. Jafarishiadeh, M.; Ahmadi, R. Two-and-One Set of Arms MMC-Based Multilevel Converter with Reduced
Submodule Counts. In Proceedings of the 2018 IEEE Transportation Electrification Conference and Expo
(ITEC), Long Beach, CA, USA, 13–15 June 2018; pp. 779–782.
8. Yang, D.; Yin, L.; Xu, S.; Wu, N. Power and Voltage Control for Single-Phase Cascaded H-Bridge Multilevel
Converters under Unbalanced Loads. Energies 2018, 11, 2435. [CrossRef]
9. Zhang, J.; Zhao, C. The Research of SM Topology with DC Fault Tolerance in MMC-HVDC. IEEE Trans.
Power Deliv. 2015, 30, 1561–1568. [CrossRef]
10. Dong., S.; He, H.; Yuan, Z.; Yang, Y.; He, J.; He, H. Transient over-voltage of the full-bridge MMC HVDC
system with overhead line fault. In Proceedings of the 2016 Power Systems Computation Conference,
Chengdu, China, 19–22 September 2016; pp. 1–4.
11. Lin, W.; Jovcic, D.; Nguefeu, S.; Saad, H. Protection of full bridge MMC DC grid employing mechanical DC
circuit breakers. In Proceedings of the 2017 IEEE Power Energy Society General Meeting, Chicago, IL, USA,
16–20 July 2017; pp. 1–5.
12. Zeng, R.; Xu, L.; Yao, L.; Williams, B.W. Design and Operation of a Hybrid Modular Multilevel Converter.
IEEE Trans. Power Electron. 2015, 30, 1137–1146. [CrossRef]
13. Li, R.; Adam, G.P.; Holliday, D.; Fletcher, J.E.; Williams, B.W. Hybrid Cascaded Modular Multilevel Converter
with DC Fault Ride-Through Capability for the HVDC Transmission System. IEEE Trans. Power Deliv. 2015,
30, 1853–1862. [CrossRef]
14. Marquardt, R. Modular Multilevel Converter: An universal concept for HVDC-Networks and extended DC-
Bus-applications. In Proceedings of the 2010 International Power Electronics Conference, Sapporo, Japan,
21–24 June 2010; pp. 502–507.
15. Marquardt, R. Modular Multilevel Converter topologies with DC-Short circuit current limitation.
In Proceedings of the 8th International Conference on Power Electronics, Jeju, South Korea,
30 May–3 June 2011; pp. 1425–1431.
21
Energies 2019, 12, 91
16. Qin, J.; Saeedifard, M.; Rockhill, A.; Zhou, R. Hybrid Design of Modular Multilevel Converters for HVDC
Systems Based on Various Submodule Circuits. IEEE Trans. Power Deliv. 2015, 30, 385–394. [CrossRef]
17. Li, R.; Fletcher, J.E.; Xu, L. A Hybrid Modular Multilevel Converter with Novel Three-level Cells for DC
Fault Blocking Capability. IEEE Trans. Power Deliv. 2015, 30, 2017–2026. [CrossRef]
18. Zeng, R.; Xu, L.; Yao, L. An improved modular multilevel converter with DC fault blocking capability.
In Proceedings of the 2014 IEEE PES General Meeting, National Harbor, MD, USA, 27–31 July 2014; pp. 1–5.
19. Xu, J.; Zhao, P.; Zhao, C. Reliability Analysis and Redundancy Configuration of MMC with Hybrid
Sub-Module Topologies. IEEE Trans. Power Electron. 2016, 31, 2020–2029. [CrossRef]
20. Davidson, C.C.; Trainer, D.R. Innovative concepts for hybrid multi-level converters for HVDC power
transmission. In Proceedings of the 9th IET International Conference an AC and DC Power Transmission,
London, UK, 19–21 October 2010; pp. 1–5.
21. Cross, A.M.; Trainer, D.R.; Crookes, R.W. Chain-link based HVDC Voltage Source Converter using current
injection. In Proceedings of the 9th IET International Conference an AC and DC Power Transmission,
London, UK, 19–21 October 2010; pp. 1–5.
22. Merlin, M.M.C.; Green, T.C.; Mitcheson, P.D.; Trainer, D.R.; Critchley, D.R.; Crookes, R.W. A new hybrid
multi-level Voltage-Source Converter with DC fault blocking capability. In Proceedings of the 9th IET
International Conference an AC and DC Power Transmission, London, UK, 19–21 October 2010; pp. 1–5.
23. Lee, H.Y.; Asif, M.; Park, K.H.; Lee, B.W. Assessment of Appropriate MMC Topology Considering DC Fault
Handling Performance of Fault Protection Devices. Appl. Sci. 2018, 8, 1834. [CrossRef]
24. Cortes, P.; Kouro, S.; Rocca, B.L.; Vargas, R.; Rodriguez, J.; Leon, J.I.; Vazquez, S.; Franquelo, L.G.
Guidelines for weighting factors design in Model Predictive Control of power converters and drives.
In Proceedings of the 2009 IEEE International Conference on Industrial Technology, Gippsland, Australia,
10–13 February 2009; pp. 1–7.
25. Zhang, Z.; Xu, Z.; Xue, Y. Valve Losses Evaluation Based on Piecewise Analytical Method for MMC–HVDC
Links. IEEE Trans. Power Deliv. 2014, 29, 1354–1362. [CrossRef]
© 2018 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access
article distributed under the terms and conditions of the Creative Commons Attribution
(CC BY) license (http://creativecommons.org/licenses/by/4.0/).
22
energies
Article
A Harmonic Voltage Injection Based DC-Link
Imbalance Compensation Technique for Single-Phase
Three-Level Neutral-Point-Clamped (NPC) Inverters
Kyoung-Pil Kang 1 , Younghoon Cho 1, *, Myung-Hyo Ryu 2 and Ju-Won Baek 2
1 Department of Electrical Engineering, Konkuk University, Seoul 05029, Korea; [email protected]
2 Industry Application Research Laboratory, Korea Electrotechnology Research Institute,
Changwon 123456, Korea; [email protected] (M.-H.R.); [email protected] (J.-W.B.)
* Correspondence: [email protected]; Tel.: +82-10-6207-0431
Keywords: neutral-point-clamped (NPC) inverter; dc-link capacitor voltage balance; offset voltage injection;
harmonic component
1. Introduction
Recently, multilevel power inverters have been popularly employed in many electronic
applications [1,2]. For example, solid-state transformers (SST) and dc distribution systems, which are high
voltage (HV) or medium voltage (MV) applications, essentially require the use of multilevel topologies [3–7].
In multilevel topologies, three-level neutral-point-clamped (NPC) inverters have been widely used in MV
and HV applications. Compared to two-level inverters, three-level NPC inverters have some advantages,
as follows. NPC inverters have more output voltage levels than two-level inverters. Therefore, the output
voltages of an NPC inverter are more similar to sinusoidal waves than other topologies and NPC inverters
have less of a harmonic component on output voltage. Additionally, in NPC inverters, the voltage rating of
the switching device can be half of the one used in two-level inverters. In addition, NPC inverters generate
relatively less leakage current flowing through the ground paths, so electromagnetic interference (EMI)
induced problems are relatively lower than the two-level inverters.
However, the NPC inverter has a major drawback associated with the neutral-point voltage
located between the upper and the lower dc-link capacitors. The voltage between the positive
dc-link rail and the neutral-point should be identical to the voltage across the neutral-point and
the negative dc-link rail. Unfortunately, there is a voltage imbalance between the upper and lower
capacitors. This voltage imbalance harms the stability of the system, and limits the switching
operation of the power stage [8–11]. In order to mitigate the voltage imbalance, many strategies
that are based on additional hardware configurations or control algorithms have been proposed,
and have been successfully adapted in some applications [12–25]. In [12,13], additional circuits for
dc-link balancing were proposed. Although these methods achieved the dc-link voltage balancing
successfully, the increase in the cost and the losses were major defects. To avoid these disadvantages,
several modulation techniques for single-phase three-level NPC inverters have been presented
in [14–21]. Among these modulation techniques, the carrier-based pulse width modulation (CB-PWM)
approaches have been extensively preferred due to their simplicity of implementation. In [14],
the offset voltage injection with the zero-sequence component in the reference voltage was presented.
The zero-sequence component is calculated at every switching period based on the dc-link link voltage
and the grid current. Another type of offset voltage injection method was discussed in [15]. In this
paper, the offset voltage with a distribution factor was added into the modulation signal. However,
these strategies face difficulties in being implemented because they are a burden on the prediction
of the line current and the avoidance of nonlinearity in the injection signal. Additionally, the exact
parameter information is essential to implement these methods as the algorithms are highly dependent
on the system parameters. In [16], a simple signal injection method was proposed to balance out the
dc-link capacitor voltages by utilizing the harmonic signal consisting of the dc-link voltage difference
and the double frequency of the utility grid. The method can easily be implemented as well as reducing
the harmonic distortion in the input current of the NPC inverter.
In this paper, the method proposed in [16] was further extended and detailed. In the proposed method,
an even harmonic signal was added to the reference signal, which is generated by the current controller.
Compared to other harmonic injection methods, the proposed method showed less voltage distortion on
the synthesized output voltage. Furthermore, fast voltage balancing performance was obtained with the
proposed strategy. A 10-kW single-phase three-level NPC inverter was built and tested. Here, the input
grid voltage was 943 V in root mean square (RMS) and the output dc-link voltage was 1.8 kV. To artificially
create voltage imbalance conditions, an unbalanced load bank was attached to the individual capacitors in
the dc-link. The proposed method was compared with the method suggested in [14] through simulations.
The experimental results are presented to validate the effectiveness of the proposed method. This paper
is organized as follows. In Section 2, the pole voltage of the NPC inverter is analyzed with the proposed
offset voltage injection method. The theoretical analysis of control performance with the offset voltage
is discussed in Section 3. Simulations and experimental results with the proposed method are shown in
Section 4. Finally, Section 5 concludes this paper.
2. The Operation of the Single-Phase NPC Inverter and Its Neutral Current
Figure 1 illustrates a switching leg of the three-level NPC inverter and its conduction states.
As shown in Figure 1, the switching leg consists of four switching devices, Qx1 , Qx2 , Qx3 , and Qx4 ,
two clamping diodes, D1 and D2 , and two dc-link capacitors, CCH and CCL . The pole voltage vx0 has
three different levels, VCH , 0, and −VCL according to the values of the switch function Sx during the
conduction periods, as shown in Figure 1b–d. All parameters used in this paper are defined in Table 1.
Figure 1. The switching leg of the three-level neutral-point-clamped (NPC) inverter and its switching
states. (a) The circuit structure; (b) the conduction state with Sx = 1; (c) the conduction state with Sx = 0;
and (d) the conduction state with Sx = −1.
24
Energies 2018, 11, 1886
When Sx = 1, the upper two devices, Qx1 and Qx2 , are turned on. At this condition, shown in
Figure 1b, the output power is supplied by the upper dc-link capacitor CCH , so that vx0 becomes VCH .
If Sx is 0, the middle switches, Qx2 and Qx3 , conduct, and the output voltage is also clamped by the
clamping diodes. Here, the amplitude of vx0 is 0, and this state is illustrated in Figure 1c. In Figure 1d,
Sx is defined as −1, and the lower switching devices, Qx3 and Qx4 , are closed. The output voltage is
fed by the lower dc-link capacitor CCL , and vx0 becomes −VCL .
1
VC+
0
vx* 0
−1 VC−
Figure 2. The normalized pole voltage reference and the carrier signals.
Figure 2 shows the normalized pole voltage reference u∗x0 and two carrier signals VC+ and VC− .
Here, u∗x0 is defined as Equation (1):
2v∗x0
u∗x0 = (1)
VCH + VCL
where v∗x0 is the reference of the pole voltage. Equation (2) defines the relationships between the
magnitudes of the carrier signals and the normalized pole voltage reference and the values of the
switching function. ⎧
⎧
⎪
⎪
⎨ VC+ ≤ u∗x0 ⎨ S x =1
⎪
if VC− ≤ u∗x0 ≤ VC+ , then Sx =0 (2)
⎪
⎩ ⎪
⎪
u∗x0 ≤ VC− ⎩S =−1
x
25
Energies 2018, 11, 1886
Let us consider that the switching frequency fsw is much higher than the frequency of u∗x0 . By doing
so, u∗x0 in the single switching period Tc can be assumed as a constant value. Consequently, the on-time
duration of the switch, τ x , is given as:
τx = |u∗x0 | Tc (3)
By using Equation (3), the average output pole voltage, v x0 , over one switching period is simply
written as follows:
τx VCH /Tc , u∗x0 ≥ 0
v x0 = (4)
−τx VCL /Tc , u∗x0 ≤ 0
If the upper and the lower capacitors have the same voltage, V CH = VCL = 0.5V DC , the pole voltage
shown in Equation (4) can be rewritten as:
τx VDC
v x0 = (5)
Tc 2
In order to be placed in the linear modulation range, the following conditions should be satisfied.
VDC
|u∗x0 | ≤ 1, |v x0 | ≤ (6)
2
Figure 3 represents the configuration of the single-phase three-level NPC inverter dealt with in
this paper. Here, two three-level switching legs were employed. In each switching leg, the middle
points of the clamping diodes were connected to the neutral point of the dc-link. By referring the
notations in Figure 3, the pole voltage references of the individual switching legs are written as follows:
where v∗g
and v∗z
are the line-to-line voltage reference and the virtual offset voltage between the
switching pole B and the neutral point of the dc-link, respectively. It should be noticed that both v∗A0
and v∗B0 should be operated in the linear modulation region. This means that they should satisfy the
conditions expressed in Equation (6). In addition, v∗z should be also placed in the linear modulation
region, because v∗z is identical to v∗B0 . From this analysis, the following condition can be derived:
QA1 QB1
CCH vCH
QA 2 QB 2
Lg i g
+
A
+
eg vg iA 0 Ro
− −
B
QA 3 QB 3
CCL vCL
QA 4 QB 4
26
Energies 2018, 11, 1886
Equation (9) offers that various virtual offset voltages can be selected with various control
purposes. The object of the approach taken in this paper was to balance the dc-link capacitor voltages.
To do this, the second-order harmonic injection approach was proposed in this paper. Here, v∗z is
selected as Equation (10):
1
v∗z = − v∗g + K (VCH − VCL ) sin (2ωt) (10)
2
where ω and K are the fundamental electrical angular frequency of the grid voltage eg and the
injection gain of the second harmonic voltage, respectively. By substituting Equation (10) into
Equations (7) and (8), the pole voltages are expressed as follows:
1 ∗
v∗A0 = v + K (VCH − VCL ) sin (2ωt) (11)
2 g
1 ∗
v∗B0 = v + K (VCH − VCL ) sin (2ωt) (12)
2 g
In Figure 3, the voltage of the lower capacitor was adjusted by injecting the neutral current idA
and idB , which are represented with the phase current from the switching pole A to the grid iA and the
switching functions of each switching leg, SA0 and SB0 , as follows.
The entire neutral current flowing into the neutral point is simply obtained as:
id (t) = idA (t) + idB (t) = [S2B (t) − S2A (t)]i A (t) (15)
The average value of the neutral current over a single switching period is calculated as below:
1
id = id (t)dt = (|u∗B0 | − |u∗A0 |)i A (16)
Tc
Tc
where i A is the average of iA (t) in the switching period. By applying the pole voltages, Equation (16) is
rewritten as Equation (17).
2
id = (|v∗ | − |v∗A0 |)i A (17)
VDC B0
By substituting Equations (11) and (12) into Equation (17), id is obtained, and is expressed in two
ways according to the polarities of v∗A0 and v∗B0 . When the polarities of the pole voltage references are
the same, the average neutral current is written as Equation (18).
2v∗g
id = ∓ (18)
VDC
If the polarities of v∗A0 and v∗B0 are different, Equation (19) is obtained.
4K
id = ∓ sin(2ωt) (19)
VDC
By adjusting the pole voltage references, the average current expressed by Equations (18) or (19)
is controlled to balance out the dc-link capacitors’ voltages.
27
Energies 2018, 11, 1886
0 Δ 2Δ 3Δ 4Δ Νt 0 Δ 2Δ 3Δ 4Δ Νt
vDC vDC
− − m i n ( v *g , 0 ) − − min( vg* ,0)
2 2
(a) (b)
v Z* v DC vZ* v DC
− m ax( v g* , 0) − max( v g* ,0)
2 2
1 * 1 *
v + K sin(ω t) v + K sin(2ω t)
2 g 2 g
0 Δ 2Δ 3Δ 4Δ Νt 0 Δ 2Δ 3Δ 4Δ Νt
v DC v DC
− − min( v *g ,0) − − min( v *g ,0)
2 2
(c) (d)
Figure 4. Limitation pole voltage vA0 * with the offset voltage vz *. (a) vz * = 0; (b) using distribution
factor μ; (c) fundamental component; and (d) second-order harmonic component.
Figure 4a shows the pole voltage reference when there was no difference between upper and
lower capacitor voltage in Equation (8). In this case, the pole voltage reference always satisfies the
range of the pole voltage (Equation (9)). Figure 4b shows the synthesized pole voltage reference
where this method was proposed in [15]. In this case, the offset voltage was composed of distribution
factor μ and the absolute value of the phase voltage reference. This method can cover the full range
of dc-link capacitor voltage difference, but this offset signal injection method requires repetitive
calculation since the absolute values are used in Equation (17). Figure 4c shows the synthesized
pole voltage where the offset voltage composed of the dc-link capacitor voltage difference and the
fundamental component was injected instead of the second-order harmonic component in the pole
voltage reference (Equation (9)). In this case, the maximum value of the pole voltage reference was
0.5 mV DC + K at π/2, and the minimum value of the pole voltage reference was −0.5 mVDC − K at
3π/2. Therefore, the voltage difference that can be injected for the dc-link capacitor voltage balance
is restricted by modulation index m. Figure 4d shows the pole voltage where the offset voltage is
composed of the dc-link capacitor voltage difference and the second-order harmonic component.
In this case, the maximum value can be found by calculating the divergence of the pole voltage vA0 *.
Solving Equation (20) equal to zero, the roots are as follows:
dv∗A0 1
= mVDC cos(ωt) + 2K cos(2ωt) (20)
dωt 2
28
Energies 2018, 11, 1886
⎧
⎪
⎪ π − acos m− (32K2 + m2 ) /8K
⎪
⎪
⎪
⎪
⎪
⎨ π + acos m+ (32K2 + m2 ) /8K
ωt = (21)
⎪
⎪ π + acos m− (32K2 + m2 ) /8K
⎪
⎪
⎪
⎪
⎪
⎩ π − acos m+ (32K2 + m2 ) /8K
Among these roots, the maximum value and the minimum value exist at:
The other roots are imaginary roots when the value of K is below the specific value determined
by the modulation index m. In addition, the offset voltage vz * can be considered, which is composed
with the voltage difference K and the half-wave rectified by the second-order harmonic component.
In this case, the maximum value of the pole voltage vA0 * is the same as the condition that injected
the second-order harmonic component, but the minimum value was the same as the condition where
the dc-link voltage difference is zero. The reason each injection voltage was inserted in a subdivided
way as follows: for the 0 to π/2 region, the voltage difference was reduced, but within the next π/2 to
π region, the offset voltage signal made switching operations for each leg to diverge. In this region,
the switching state of leg A was increased to a 0 state and the switching state of leg B was increased to
a −1 state by a synthesized reference signal. Consequently, a new reference signal increase the voltage
difference, which turned on more low-side switches than the high-side ones. Therefore, the injection
voltage had to be inserted in a subdivided way.
Figure 5 shows the waveforms which are reference signal for legs A, B, and the offset signal that
has double the frequency of the reference signal. In addition, it also shows that the switching operation
changed every π/2 cycle, when the reference signal and offset signal were synthesized. In Figure 5a,
Region 1, the switching operation for leg A was increased to a 1 state by the synthesized reference
signal with the offset signal (SA = 1). On the other hand, the switching operation for leg B was increased
to the 0 state (SB = 0). In Region 2, the offset signal had a negative value. Therefore, the switching
operation for leg A was increased to the 0 state (SA = 0). In the same manner, the switching operation
for leg B was increased to the −1 state (SB = −1). In Region 3, the reference signal had a negative value
and the offset signal had a positive value. The switching operation for leg A was increased to the 0
state (SA = 0), and for leg B it was increased to the 1 state (SB = 1). In Region 4, the switching operation
for leg A was increased to the −1 state (SA = −1) and for leg B, it was increased to the 0 state (SB = 0).
In Figure 5b, the switching operation states for leg A and leg B could be easily observed by comparing
it with Figure 5a. In Regions 1 and 3, the increased switching state for each leg, (SA ,SB ), were (1,0) and
(0,1), respectively. In Regions 2 and 4, there was no offset signal, so the synthesized reference signals
were the same as the reference signal.
u *
0 ( for legA ) u 0* ( for legA )
* *
u offset u offset
T (S A = 1 ) ↑ T (S A = 0 ) ↑ T (S A = 0 ) ↑ T (S A = − 1 ) ↑ T ( S A = 1 ) ↑ No Change T ( S A = 0 ) ↑ No Change
Figure 5. Cont.
29
Energies 2018, 11, 1886
* *
u offset uoffset
T (S B = 0 ) ↑ T (S B = − 1 ) ↑ T (S B = 1 ) ↑ T (S B = 0 ) ↑ T ( S B = 0 ) ↑ No Change T ( S B = 1 ) ↑ No Change
(a) (b)
Figure 5. Waveforms pole voltage reference signal ux0 * and offset signal uoffset *. (a) Second-order
harmonic signal; and (b) half-wave signal of second-order harmonic.
The maximum and minimum values obtained from the previous equations were determined
by the voltage difference K and modulation index m. With the same modulation index m, the offset
voltage injection method with distribution factor μ could be adopted for the full range of capacitor
voltage difference such as from 0 V to VDC , but there were voltage oscillations on the dc-link voltage
when the balancing control was adopted [15]. In contrast, the offset voltage injection method with
the second-order harmonic component or the half-wave rectified can be adopted for smooth control.
Furthermore, the proposed method could easily configure the controller using Equations (11), (12),
and (22), and the PWM modulator described in Figure 6. However, the proposed method has
limitations on the range of capacitor voltage difference given the effects of the voltage difference
of the dc-link capacitor on the injection signal. This could be a larger reference signal than the previous
reference signal for dc-link voltage control. In this case, an over-distorted reference signal could not
control either the dc-link voltage control or dc-link capacitor voltage balancing control. The voltage
range of the proposed method is up to the point where the remaining two roots other than the
maximum and minimum are zero when the modulation index m is constant in Equation (21).
δg eg
sin δ g( ) PLL
ig
ig* v*g *
QA1
* uA0
vDC PI −1 PR PWM
Q A 2 1P3L
vDC ( )
sin 2δ g vg Eq.(11),
*
QB1 NPC
(12)and(22) uB 0 Conv.
K QB 2
vCH
vCL
VC+ VC−
30
Energies 2018, 11, 1886
for the dc-link capacitor voltage balance is as follows. The NPC inverter operates as a general PWM
rectifier that traces the dc-link capacitor voltage reference with the PI and PR controller before the
capacitor voltage imbalance occurs. In this case, the offset signal vz * in Equations (10) and (11) is
zero because there is no voltage difference on the dc-link capacitor, so the coefficient of vz *, K, is zero.
When a voltage difference occurs, the balancing control operates to reduce the voltage difference.
The parameters for balancing control are obtained as follows: the capacitor voltage (VCH , VCL ) and
input current ig are measured by the voltage and current sensor, respectively. The grid voltage phase
angle, δg , is calculated from the phased locked loop (PLL) scheme by measuring grid voltage eg . At this
point, the PWM modulator generates a new pole voltage reference by synthesizing the reference signal
and offset signal.
Radd
4% QB 1 4$ QA1
Lg
V 9&+ CCH 4% QB 2 4$ QA 2
kWh W
$
%
Ro W/kWh Q
eg
9&/
4% QB 3 4$ QA 3
CCL
4% QB 4 4$ QA 4
9FDUUB3
QA1
6
QA 3
UHIB1 6
9FDUUB1
QA 2
6
9LQMHFWLRQ
1 UHIB3
QA 4
K z
UHIB3 6
.
K
9JBUHI K UHIB1 QB 1
9&+ 9LQMHFWLRQ 9FDUUB3
6
9&/
9LQMHFWLRQ
1 UHIB3
QB 3
K z 6
UHIB1
9JBUHI K UHIB1
9FDUUB1
QB 2
9&+ 6
9&/ QB 4
Injection Signal Generator Pole Voltage Generator PWM Modulator
In the simulation, the dc-link capacitor voltage difference between the upper capacitor VCH and
lower capacitor VCL was intentionally made to generate an imbalance condition on the dc-link capacitor
by using the attached additional circuit on top of the dc-link capacitor in Figure 3. Figure 8 shows the
voltage levels of the upper and lower capacitors, and the NPC inverter controls the dc-link voltage
VDC to the dc-link voltage reference VDC * when the switch of the additional circuit was closed at t
= 0.02 s. If there were no additional controls for the dc-link capacitor voltage balancing, the upper
capacitor voltage value remained at a lower value than the lower capacitor voltage VCH .
31
Energies 2018, 11, 1886
The simulation parameters of a single-phase three-level NPC inverter adopting the proposed
balancing control were as follows. Capacitance of the dc-link capacitor CCH , CCL was 250 μF, inductance
of the filter inductor Lg was 14 mH, resistance of the load Ro and the additional load were 540 Ω,
the switching frequency fSW was 10 kHz, the grid side voltage vg was 943 V/60 Hz in the root mean
square (rms) value, and the controlled dc-link voltage reference VDC * was 1.8 kV.
Figure 9 shows the simulation results for the dc-link capacitor voltage balancing control with the
type of injection voltage under the same modulation index. In the simulation, the voltage difference
between the upper and lower capacitor of the dc-link was enforced at about 334 V. Figure 9a shows
the simulation results of the dc-link capacitor voltage balancing control using distribution factor
μ. From the simulation results, each capacitor voltage VCH and VCL reached a balanced point at
t = 0.4941 s. Figure 9b shows the simulation results when injecting a second-order harmonic signal
into the modulation signal. In this case, each capacitor voltage VCH and VCL reached a balanced point
at t = 0.4249 s. Figure 9c shows the simulation result when injecting the half-wave of a second-order
harmonic signal into the modulation signal. In this case, the upper and lower capacitor voltage reached
a balanced point at 0.3875 s. From the simulation results, the half-wave of the second-order harmonic
signal injection method was better than other offset voltage injection methods.
(a)
(b)
Figure 9. Cont.
32
Energies 2018, 11, 1886
(c)
Figure 9. Simulation results for the single-phase NPC inverter with VDC , VCH , VCL and ig : (a) using
distribution factor μ; (b) using second-order harmonic component; and (c) using half-wave of second-order
harmonic component.
Figure 10 shows a photograph of the experimental setup for a single-phase three-level NPC
inverter used to verify the proposed method. The NPC inverter module consisted of two NPC
half-bridges, a series filter inductor, and two electrolytic capacitors. For the test, a 6 kW resistive load
was connected to the dc-link capacitor of the NPC inverter. The same system parameters for the NPC
inverter were applied as in the previous simulation. A 1:6 transformer was connected to the output of
the variac to obtain 943 V AC voltage. Each leg of the NPC inverter consisted of four MOSFETs and two
clamping diodes. SiC MOSFETs, Cree’s C2M0040120D, and a SiC Schottky diode, Cree’s C4D20120D,
were utilized for each leg. By adapting silicon carbide devices, the switching frequency can be higher
than for silicon-based devices. When using a higher switching frequency, the physical size of the
magnetic component for the NPC inverter can be reduced. Furthermore, a lower switching loss is
expected than with silicon-based devices. Component specifications of the NPC inverter are shown
in Table 2. In order to measure the dc-link capacitor voltage and input current, a differential probe
and a current probe were used. For each probe of the dc-link capacitor, PINTEK’s high voltage
differential probe DP-50 was used. In addition, for input current, Lecroy’s current probe CP150 was
used. The control structure of the NPC inverter contained a current controller for input current,
a voltage controller for the dc-link capacitor voltage, and a voltage balance controller for the dc-ink
capacitor voltage balance. For these controllers, a digital control board based on Texas Instruments’
TMS320F28335 was used, which was made in-laboratory. The phase voltage reference signal for the
NPC inverter was generated by measuring the dc-link capacitor voltage and input current, and the
injection signal for the dc-link capacitor voltage balance was calculated from the measured dc-link
capacitor voltage and the phase angle of the grid. The NPC inverter regulated the AC voltage to
DC voltage without the dc-link capacitor voltage imbalance caused by the generated phase voltage
reference signal and injection signal.
33
Energies 2018, 11, 1886
In the above experimental setup, the experimental process was as follows: first, the AC input
voltage was increased to 943 V under dc-link voltage control conditions for 1.8 kV dc-link voltage.
Second, the dc-link capacitor voltage imbalance was enforced at about 100 V by operating an additional
resistive load circuit, which was attached on the upper capacitor. At this time, the voltage difference
should be suppressed by the voltage rating of the electrolytic capacitor. In addition, then, the adopting
proposed method, dc-link voltage, separated capacitor voltage, and current distortion were observed
intensively under unbalanced dc-link capacitor voltage.
Figure 10. Hardware configuration for the dc-link capacitor voltage balancing test.
The experimental results when adopting the proposed method for dc-link capacitor voltage
balance are presented in Figure 11. As shown in Figure 11a,b, the capacitor voltage difference
was enforced at about 100 V. Before adopting the balancing control in Figure 11a, the upper and
lower capacitor voltage levels were measured as 828 V and 924 V, respectively. After adopting the
proposed second-order harmonic injection method, the upper capacitor voltage level increased from
828 V to 869 V, and the lower capacitor voltage level decreased from 924 V to 887 V. In Figure 11b,
the other experimental result, the capacitor voltage difference was measured as 106 V. After adopting
the proposed half-wave rectified second-order harmonic injection, the capacitor voltage difference
decreased from 106 V to 9 V. At the beginning of the capacitor voltage balancing control, the line
current ig was instantaneously distorted, but this distortion disappeared within 50 ms as the upper
and the lower capacitor voltage level became equal.
(a)
34
Energies 2018, 11, 1886
(b)
Figure 11. Experimental results for the single-phase NPC inverter with VDC , VCH , VCL and ig
(a) using second-order harmonic component; and (b) using subdivided wave of second-order
harmonic component.
From the simulations and experimental results, the proposed capacitor voltage balancing control
strategies of injecting the second-order harmonic signal and the half-wave of the second-order harmonic
signal were effective for dc-link capacitor voltage balancing. Among these balancing methods,
the method of injecting the half-wave signal into the modulation signal was faster, at about 50 ms,
at achieving capacitor voltage balance than the injection of the full-wave signal of the second-order
harmonic. However, in the case of input current ig , the full-wave injection method of the second-order
harmonic had a lower distortion than the half-wave signal injection method as it seems that the
synthesized pole voltage reference signal was distorted when the half cycle of the second-order
harmonic signal had a negative polarity.
5. Conclusions
This paper described an offset voltage injection method for dc-link capacitor voltage balance on
a single-phase three-level NPC inverter. The operations and the balancing strategies were explained.
The proposed offset voltage consisted of double the frequency of the grid and the voltage difference
between the upper and lower capacitors of the dc-link. In addition, the partial offset voltage
injection method of the second-order harmonic signal was proposed to achieve dc-link voltage balance.
The proposed method does not require hard calculations and additional hardware setup for dc-link
balancing control; it is simpler and more intuitive to implement than the conventional offset voltage
injection method. However, the proposed method can operate only in a narrower voltage difference
than the conventional method. This limitation is caused by the maximum and minimum values of
the offset voltage, which consists of the capacitor voltage difference and the phase angle of the grid.
Simulations and experiments were performed at 60% load of the NPC inverter. In addition, the results
based on a single-phase NPC inverter application verified the validity and feasibility of the proposed
method. The proposed method of reducing dc-link capacitor voltage difference can be adopted for
other topologies that have separated-dc link capacitors. Furthermore, it seems that using a variable
weight factor on the offset voltage for the dc-link balance could be possible.
Author Contributions: K.-P.K. implemented the system, and performed the experiments. Y.C. managed the
project. M.-H.R. and J.-W.B. assisted with the idea development and paper writing.
Funding: This research was funded by the Human Resources Program in Energy Technology of the Korea Institute
of Energy Technology Evaluation and Planning (KETEP), granted financial resources from the Ministry of Trade,
Industry & Energy, Republic of Korea (No. 20174030201660), and by the Korea Electric Power Corporation
35
Energies 2018, 11, 1886
(KEPCO) under project entitled Demonstration study for Low Voltage Direct Current Distribution Network in
Island (D3080).
Acknowledgments: This research was funded by the Human Resources Program in Energy Technology of the
Korea Institute of Energy Technology Evaluation and Planning (KETEP), granted financial resource from the
Ministry of Trade, Industry & Energy, Republic of Korea (No. 20174030201660), and by the Korea Electric Power
Corporation (KEPCO) under project entitled Demonstration study for Low Voltage Direct Current Distribution
Network in Island (D3080).
Conflicts of Interest: The authors declare no conflict no interest.
References
1. Olivares, D.E.; Mehrizi-Sani, A.; Etemadi, A.H.; Cañizares, C.A.; Iravani, R.; Kazerani, M.; Hajimiragha, A.H.;
Gomis-Bellmunt, O.; Saeedifard, M.; Palma-Behnke, R.; et al. Trends in Microgrid Control. IEEE Trans.
Smart Grid 2014, 5, 1905–1919. [CrossRef]
2. Asmus, P. Microgrids, virtual power plants and our distributed energy future. Electr. J. 2010, 23, 72–82.
[CrossRef]
3. She, X.; Burgos, R.; Wang, G.; Wang, F.; Huang, A.Q. Review of solid state transformer in the distribution
system: From components to field application. In Proceedings of the 2012 IEEE Energy Conversion Congress
and Exposition (ECCE), Raleigh, NC, USA, 15–20 September 2012; pp. 4077–4084.
4. Kolar, J.W.; Ortiz, G. Solid-state-transformers: Key components of future traction and smart grid systems.
In Proceedings of the International Power Electronics Conference (IPEC), Hiroshima, Japan, 18–21 May 2014.
5. Huber, J.E.; Kolar, J.W. Optimum number of cascaded cells for high-power medium-voltage multilevel
converters. In Proceedings of the 2013 IEEE Energy Conversion Congress and Exposition (ECCE),
Denver, CO, USA, 15–19 September 2013; pp. 359–366.
6. Guillod, T.; Huber, J.E.; Ortiz, G.; De, A.; Franck, C.M.; Kolar, J.W. Characterization of the voltage and electric
field stresses in multi-cell solid-state transformers. In Proceedings of the 2014 IEEE Energy Conversion
Congress and Exposition (ECCE), Pittsburgh, PA, USA, 14–18 September 2014; pp. 4726–4734.
7. Huber, J.E.; Kolar, J.W. Volume/weight/cost comparison of a 1MVA 10 kV/400 V solid-state against
a conventional low-frequency distribution transformer. In Proceedings of the 2014 IEEE Energy Conversion
Congress and Exposition (ECCE), Pittsburgh, PA, USA, 14–18 September 2014; pp. 4545–4552.
8. Jih-Sheng, L.; Zheng, P.F. Multilevel converters-a new breed of power converters. IEEE Trans. Ind. Appl. 1996,
32, 509–517. [CrossRef]
9. Rodriguez, J.; Jih-Sheng, L.; Zheng, P.F. Multilevel inverters: A survey of topologies, controls, and applications.
IEEE Trans. Ind. Electron. 2002, 49, 724–738. [CrossRef]
10. Nabae, A.; Takahashi, I.; Akagi, H. A New Neutral-Point-Clamped PWM Inverter. IEEE Trans. Ind. Appl
1981, IA-17, 518–523. [CrossRef]
11. Schweizer, M.; Friedli, T.; Kolar, J.W. Comparative Evaluation of Advanced Three-Phase Three-Level
Inverter/Converter Topologies Against Two-Level Systems. IEEE Trans. Ind. Electron. 2013, 60, 5515–5527.
[CrossRef]
12. Stala, R. Application of Balancing Circuit for DC-Link Voltages Balance in a Single-Phase Diode-Clamped
Inverter with Two Three-Level Legs. IEEE Trans. Ind. Electron. 2011, 58, 4185–4195. [CrossRef]
13. Boora, A.; Nami, A.; Zare, F.; Ghosh, A.; Balaabjerg, F. Voltage-sharing converter to supply single-phase
asymmetrical four-level diode-clamped inverter with high power factor loads. IEEE Trans. Power Electorn.
2010, 25, 2507–2520. [CrossRef]
14. Song, W.; Feng, X.; Smedley, K.M. A Carrier-Based PWM Strategy with the Offset Voltage Injection for
Single-Phase Three-Level Neutral-Point-Clamped Converters. IEEE Trans. Power Electron. 2013, 28, 1083–1095.
[CrossRef]
15. De Freitas, I.S.; Bandeira, M.M.; Barros, L.D.M.; Jacobina, C.B.; dos Santos, E.C.; Salvadori, F.;
de Silva, S.A. A Carrier-Based PWM Technique for Capacitor Voltage Balancing of Single-Phase Three-Level
Neutral-Point-Clamped Converters. IEEE Trans. Ind. Appl. 2015, 51, 3227–3235. [CrossRef]
16. Kang, K.-P.; Ryu, M.-H.; Baek, J.-W.; Kim, J.-Y.; Cho, Y. A carrier-based pwm method with the double
frequency voltage injection for three-level neutral-point clamped (NPC) converters. In Proceedings of
the 2017 Asian Conference on Energy, Power and Transportation Electrification (ACEPT), Singapore,
24–26 October 2017; pp. 1–6.
36
Energies 2018, 11, 1886
17. Du, Z.; Tolbert, L.M.; Ozpineci, B.; Chiasson, J.N. Fundamental Frequency Switching Strategies of
a Seven-Level Hybrid Cascaded H-Bridge Multilevel Inverter. IEEE Trans. Power Electron. 2009, 24, 25–33.
[CrossRef]
18. Ye, Z.; Xu, Y.; Wu, X.; Tan, G.; Deng, X.; Wang, Z. A Simplified PWM Strategy for a Neutral-Point-Clamped
(NPC) Three-Level Converter with Unbalanced DC Links. IEEE Trans. Power Electron. 2016, 31, 3227–3238.
[CrossRef]
19. Kou, L.; Wang, H.; Liu, Y.F.; Sen, P.C. DC-link capacitor voltage balancing technique for phase-shifted
PWM-based seven-switch five-level ANPC inverter. In Proceedings of the 2017 IEEE Applied Power
Electronics Conference and Exposition (APEC), Tampa, FL, USA, 26–30 March 2017; pp. 671–678.
20. WenSheng, S.; XiaoYun, F.; Chenglin, X. A neutral point voltage regulation method with SVPWM control for
single-phase three-level NPC converters. In Proceedings of the 2008 IEEE Vehicle Power and Propulsion
Conference, Harbin, China, 3–5 September 2008; pp. 1–4.
21. Celanovic, N.; Boroyevich, D. A comprehensive study of neutral-point voltage balancing problem in three-level
neutral-point-clamped voltage source PWM inverters. IEEE Trans. Power Electron. 2000, 15, 242–249. [CrossRef]
22. Hong-Seok, S.; Keil, R.; Mutschler, P.; Weem, J.v.d.; Kwanghee, N. Advanced control scheme for a single-phase
PWM rectifier in traction applications. In Proceedings of the 38th IAS Annual Meeting on Conference Record
of the Industry Applications Conference 2003, Salt Lake City, UT, USA, 12–16 October 2003; pp. 1558–1565.
23. Abdelsalam, M.; Marei, M.; Tennakoon, S.; Griffiths, A. Capacitor voltage balancing strategy based on
sub-module capacitor voltage estimation for modular multilevel converters. CSEE J. Power Energy Syst. 2016,
2, 65–73. [CrossRef]
24. Ghias, A.M.Y.M.; Pou, J.; Acuna, P.; Ceballos, S.; Heidari, A.; Agelidis, V.G.; Merabet, A. Elimination of
Low-Frequency Ripples and Regulation of Neutral-Point Voltage in Stacked Multicell Converters. IEEE Trans.
Power Electron. 2017, 32, 164–175. [CrossRef]
25. Yang, R.; Li, B.; Wang, G.; Cecati, C.; Zhou, S.; Xu, D. Asymmetric Mode Control of MMC to Suppress Capacitor
Voltage Ripples in Low-Frequency, Low-Voltage Conditions. IEEE Trans. Power Electron. 2017, 32, 4219–4230.
[CrossRef]
© 2018 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access
article distributed under the terms and conditions of the Creative Commons Attribution
(CC BY) license (http://creativecommons.org/licenses/by/4.0/).
37
energies
Article
A Highly Efficient Single-Phase Three-Level Neutral
Point Clamped (NPC) Converter Based on Predictive
Control with Reduced Number of Commutations
Eun-Su Jun and Sangshin Kwak *
School of Electrical and Electronics Engineering, Chung-ang University, Seoul 06974, Korea;
[email protected]
* Correspondence: [email protected]; Tel.: +82-2-820-5346
Abstract: This paper proposes a highly efficient single-phase three-level neutral point clamped (NPC)
converter operated by a model predictive control (MPC) method with reduced commutations of
switches. The proposed method only allows switching states with none or a single commutation at
the next step as candidates for future switching states for the MPC method. Because the proposed
method preselects switching states with reduced commutations when selecting an optimal state at
a future step, the proposed method can reduce the number of switchings and the corresponding
switching losses. Although the proposed method slightly increases the peak-to-peak variations of the
two dc capacitor voltages, the developed method does not deteriorate the input current quality and
input power factor despite the reduced number of switching numbers and losses. Thus, the proposed
method can reduce the number of switching losses and lead to high efficiency, in comparison with
the conventional MPC method.
1. Introduction
Recently, multilevel converters have become popular in a variety of high-power systems owing to
their low voltage stress, improved waveform qualities, and low electromagnetic interference (EMI)
compared to two-level converters [1,2]. Among several kinds of multilevel converters, three-level
neutral point clamped (NPC) converters with relatively simple configurations have been realized for
many application areas. In addition to three-phase NPC converters, single-phase three-level NPC
converters have been employed for high-speed traction systems as well. In order to control single-phase
three-level NPC converters, traditional carrier-based pulse width modulation (CBPWM) methods
combined with linear proportional and integral (PI) controllers have been investigated to synthesize ac
sinusoidal current waveforms with three-level NPC converters. Aside from their adjustable ac voltage
and current synthesis, the NPC converters require balancing of the two dc capacitor voltages because
of their structure, which has two split dc capacitors in the dc link. As a result, CBPWM methods with
offset voltage injection to remove imbalance of neutral point (NP) voltage in the NPC converters have
been often used [3–7].
Recently, model predictive control (MPC) methods have been studied for numerous power
converters including three-level NPC converters [8–10]. There have been several studies on MPC
algorithms for single-phase NPC converters as well as three-phase NPC converters [11–13]. In the
MPC methods for single-phase NPC converters, a cost function to determine an optimal switching
state generally consists of two terms combined with a weighting factor not only to control both the
ac sinusoidal currents but also to balance the two capacitor voltages. The ac sinusoidal current is
controlled by changing the converter voltage levels, whereas the NP voltage balance is adjusted by
using redundant switching states that yield the same voltage level.
The conventional MPC method selects an optimal switching state among nine switching states
allowed by the single-phase three-level NPC converter on the basis of a cost function considering
the ac source current and the NP voltage balance. Consideration of all possible switching states
in the conventional method can choose a switching state involved in many commutations as an
optimal switching state for the next step, which can lead to an increased number of switchings
and corresponding switching losses [14–18]. In addition, the conventional MPC method changes the
optimal switching state by evaluating the capacitor voltage balance term using the redundant switching
states to equal the two capacitor voltages [19,20] owing to a slight voltage difference even when the
converter does not require a change in the voltage level. Thus, this operation can increase the number
of switchings and switching losses as well [21,22]. Several trials to reduce switching losses based
on the model predictive control methods have been addressed for a variety of power converters in
literatures. In [23,24], approaches to reduce switching losses of matrix converters have been addressed.
Ref. [23] proposed a switching loss reduction technique by adding an additional term related with a
number of future commutations to a cost function used to control the matrix converter. In [24], a trial
to decrease switching losses of the matrix converter has been presented, where a cost function includes
an extra term directly representing switching losses at next step by calculating switch currents and
switch voltages. In [25], a model predictive control method for modular multilevel converters (MMCs)
has been developed with a cost function which is aimed at the elimination of the MMC circulating
currents, regulating the arm voltages, and controlling the ac-side currents. In addition, this strategy
tried to reduce power losses by decreasing the submodule switching frequency. In [26,27], reduction
techniques of switching losses for two-level voltage source inverters have been presented. Ref. [26]
proposed a switching strategy based on the model predictive control method to clamp one phase with
the largest load current among the three legs in the voltage source inverter every sampling period,
which can successfully reduce switching losses of the voltage source inverter. In addition, a model
predictive control method for the voltage source inverter has been developed to reduce switching
losses by injecting future zero-sequence voltage [27]. This approach decreased the switching losses by
implementing optimal discontinuous pulse patterns to stop switching operations at vicinity of peak
values of load currents. However, there has not been, to the authors’ best knowledge, tried to reduce
switching losses, using a trade-off between switching losses and capacitor voltage balancing in the
three-level NPC converters, although several trials to reduce switching losses based on the model
predictive control methods have been addressed for a variety of power converters.
In this paper, a highly efficient algorithm with a reduced number of switching and low
switching losses for single-phase three-level neutral point clamped (NPC) converters is proposed
based on a model predictive control (MPC) method with a decreased number of commutations of
switches. The proposed method pre-excludes, from the candidates for possible future switching
states, the switching states that yield more than two commutations in the next sampling period. As a
result, the proposed technique can reduce the number of switchings and switching losses by utilizing
switching states involving no commutation or only one commutation during every sampling instant
for single-phase three-level NPC converters. In addition, the developed method does not deteriorate
the input current quality or input power factor despite the reduced switching numbers and losses.
Although the proposed method slightly increases the peak-to-peak variations of the two dc capacitor
voltages at the expense of reduced commutation, the increased voltage variation is not high. Thus, the
proposed method can obtain high efficiency and low switching losses at the expense of a slightly
increased peak-to-peak variation of the NP voltage. The performance of the proposed method with
a reduced number of switchings and higher efficiency is evaluated in terms of the total harmonic
distortion (THD) and peak-to-peak variations of the capacitor voltages. Simulations and experimental
results are presented to verify the effectiveness of the proposed method.
39
Energies 2018, 11, 3524
The two switches Sx1 and Sx3 operate complementarily. Similarly, Sx2 and Sx4 work in a
complementary manner. As a result, the switching status of the two lower devices is automatically
determined by the upper switches. Owing to possible combinations of the switching states of (1) in the
a and b phases, a total of nine operating states can be generated by the single-phase three-level NPC
converter. On the basis of nine operating states, the phase switching state, upper device switching
status, and converter input voltage vab are listed in Table 1. The nine operating states yield five
voltage levels for the converter input voltage vab , which provides the single-phase NPC converter
with redundancy.
As shown in Table 1, the two states (1, 0) and (0, −1) for (Sa , Sb ) are redundant switching states
that apply the same voltage level to the converter input terminal of the single-phase three-level NPC
converter by assuming that the two capacitor voltages are well balanced. Likewise, the states (0, 1)
and (−1, 0) for (Sa , Sb ) are also redundant because they yield the equal converter input voltage vab .
These redundancies can be utilized to balance the two capacitor voltages vc1 and vc2 . The currents iu
and il shown in Figure 1 can be expressed using the switching status and the source current is as in (2)
and (3). Thus, they can be obtained without additional measurements [16]:
S a ( S a + 1) − Sb ( Sb + 1)
iu = is (2)
2
S a ( S a − 1) − Sb ( Sb − 1)
il = − is (3)
2
40
Energies 2018, 11, 3524
Table 1. Nine operating states, phase switching state, upper device switching status, and converter
input voltage of single-phase three-level NPC converter.
Operating Status Phase Switching State Converter input Voltage Capacitor Voltage
#
Sa Sb Sa1 Sa2 Sb1 Sb2 vab vc1 vc2
1 0 0 OFF ON OFF ON 0 - -
2 1 1 ON ON ON ON 0 - -
3 −1 −1 OFF OFF OFF OFF 0 - -
4 1 −1 ON ON OFF OFF Vdc ↑ ↑
5 1 0 ON ON OFF ON Vdc /2 ↑ ↓
6 0 −1 OFF ON OFF OFF Vdc /2 ↓ ↑
7 0 1 OFF ON ON ON −Vdc /2 ↑ ↓
8 −1 0 OFF OFF OFF ON −Vdc /2 ↓ ↑
9 −1 1 OFF OFF ON ON −Vdc ↓ ↓
The capacitor voltage dynamics of the dc link are calculated by using differential equations:
dvc1 1
= iu (4)
dt C1
dvc2 1
= i (5)
dt C2 l
Using a constant sampling period Ts , the capacitor voltage dynamics in the discrete-time domain
are described as:
dvcm vcm (k + 1) − vcm (k)
≈ (m = 1, 2) (6)
dt Ts
Using (6), Equations (4) and (5) can be expressed in the discrete time domain as:
Ts S a ( S a + 1) − Sb ( Sb + 1)
vc1 (k + 1) = vc1 (k ) + is (7)
C1 2
Ts S a ( S a − 1) − Sb ( Sb − 1)
vc2 (k + 1) = vc2 (k ) − is (8)
C2 2
The input current of the ac side shown in Figure 1 is expressed in the continuous time domain as:
dis
vs = Ris + L + v ab (9)
dt
Equation (9) is expressed in the discrete time domain as:
RTs Ts
i s ( k + 1) = 1− is (k ) + (vs (k ) − v ab (k)) (10)
L L
The ac source current at the next step, is (k + 1), in (10) can have five possible movements owing to
the five possible voltage levels for vab (k). The single-phase three-level NPC converter needs to balance
the two capacitor voltages by manipulating the phase switching states Sa (k) and Sb (k) shown in (7) and
(8) as well as control the source current by changing the converter input voltage vab (k) in (10). As a
result, the cost function with two terms for the ac source current control part and the neutral point
(NP) voltage control part of the two capacitor voltages is:
where λc represents the weighting factor of the capacitor voltage balancing term in the cost function.
Moreover, the future ac reference current can be expressed with past and present currents from a
Lagrange extrapolation as [28–31]:
41
Energies 2018, 11, 3524
where is∗ (k ) is the present current, and is∗ (k − 1) and is∗ (k − 2) are the reference value of the one-step
and two-step past ac source currents, respectively. The ac sinusoidal current is controlled by changing
the converter voltage levels, whereas the NP voltage balance is adjusted by using redundant switching
states that yield the same voltage level. As a result, the conventional MPC method changes the optimal
switching state by evaluating the capacitor voltage balance term using the redundant switching states
to equal the two capacitor voltages owing to a slight voltage difference even when the converter does
not require a change in the voltage level. Thus, this operation can increase the number of switchings
and the switching losses as well.
Table 2. Number of commutations involved in switch transitions from current step to next step in
conventional MPC method.
A switching operation with a number of commutations equal to that shown in Table 2, for example,
implies that one switch turns off and another switch turns on at a switching instant. Likewise, two
switches are off and two are on at a switching moment when the switching operation corresponds to a
number of commutations equal to two in Table 2. The conventional method, which selects a next-step
switching state depending on the cost function, does not consider the number of commutations.
42
Energies 2018, 11, 3524
Thus, the number of switchings can increases in a case where an optimal switching state with many
commutations is chosen at the next step. Figure 2 shows simulation waveforms obtained by the
conventional MPC method for a single-phase three-level NPC converter.
(a) (b)
Figure 2. Simulation waveforms of conventional MPC method (a) during period with converter voltage
vab fixed to Vdc /2 and (b) during period with converter input voltage vab fixed to −Vdc /2.
It is seen from Figure 2a that the conventional method, during the period with the converter
voltage vab fixed to Vdc /2, repeatedly changes the switching states corresponding to an operating status
between (1, 0) and (0, −1). This is the redundant state with respect to each other, although the switch
transitions do not be required in terms of the ac source current control. These switching operations
involve two commutations at every switching instant, as shown in Table 2. As a result, the number
of switching operations substantially increases, whereas the two capacitor voltages perfectly match.
Similarly, the simulation waveforms obtained by the conventional MPC method, especially during
the period with the converter input voltage vab fixed to −Vdc /2, are depicted in Figure 2b. It is seen
43
Energies 2018, 11, 3524
that the switch transition repeatedly occurs between (0, 1) and (−1, 0) in terms of the operating status,
which also involves two commutations at every switching instant, as shown in Table 2. Therefore,
it is noted that the two capacitor voltages are tightly balanced by repeatedly using the redundant
switching states, at the expense of an increased number of switchings in the conventional MPC
method. The proposed method pre-excludes, from the candidates for possible future switching states,
the switching states that yield more than two commutations in the next sampling period. As a result,
the proposed technique can reduce the number of switchings and the switching losses by utilizing
switching states involving no commutation or only one commutation at every sampling instant for
single-phase three-level NPC converters. Table 3 shows the switching states allowed in the proposed
method, which are states with the number of commutations restricted to zero or one
Figure 3 shows simulation waveforms obtained by the proposed MPC method for a single-phase
three-level NPC converter. It is seen from Figure 3a that the proposed method, during the period
with the converter voltage vab fixed to Vdc /2, does not change the switching states. This is because the
operating status (0, −1) corresponding to the redundant status of (1, 0) is not a possible state for the
next state when the current operating status is (0, −1). Similarly, simulation waveforms obtained by
the proposed MPC method, especially during the period with the converter input voltage vab fixed
to −Vdc /2, are depicted in Figure 3b. It is also seen that there is no switch transition because the
operating status (−1, 0) corresponding to the redundant status of (0, 1) is not a possible state for the
next state when the current operating status is (−1, 0). As a result, the proposed method can reduce
the number of switchings and the corresponding switching losses, whereas an NP voltage imbalance
between the two capacitor voltages occurs. The NP voltage imbalance that occurs when the periods of
the converter voltage are fixed at Vdc /2 or −Vdc /2 is resolved by selecting switching states to eliminate
the imbalance afterward. Figure 4 depicts simulation waveforms obtained by the proposed MPC
method during the period when the converter voltage vab oscillates between Vdc /2 and Vdc . It is seen
that the NP voltage imbalance is solved by the proposed algorithm, where the optimal states are 5, 4, 6,
4, 5, and so on, as shown in Figure 4. Figure 5 shows the capacitor voltage behavior in the switching
states. Because switching states 4, 5, and 6 can increase or decrease the upper and lower capacitor
voltages, the proposed method can successfully eliminate the NP voltage imbalance quickly.
44
Energies 2018, 11, 3524
(a) (b)
Figure 3. Simulation waveforms of proposed MPC method (a) during period with converter voltage
vab fixed to Vdc /2 and (b) during period with converter input voltage vab fixed to −Vdc /2.
45
Energies 2018, 11, 3524
Figure 4. Simulation waveforms of proposed MPC method during period with converter voltage vab
between Vdc /2 and Vdc .
Figure 5. Number of operating status and capacitor voltage behavior of proposed MPC method during
period with converter voltage vab between Vdc /2 and Vdc .
The performance of the MPC methods owing to its inherent operational principle is strongly
influenced by the sampling frequency. The number of switchings by the conventional MPC and
proposed methods as functions of the sampling periods are shown in Figure 6. It is seen that the
46
Energies 2018, 11, 3524
number of switchings of the proposed method is lower than that of the conventional MPC method
for all considered sampling periods. Increasing the sampling frequency increases the number of
switchings, leading to an increasing difference in the number of switchings obtained from the two
methods. The conventional MPC and the proposed methods are compared in terms of the THDs of the
source current and the peak-to-peak capacitor voltages vs. the sampling periods shown in Figure 6.
It is observed that the proposed method results in almost the same THDs in the source current as those
in the conventional MPC method. In addition, the peak-to-peak capacitor voltages of the proposed
method are slightly higher than those of the conventional method, at the expense of a decreased
number of switchings. Thus, it can be concluded that compared to the conventional MPC method,
the proposed method can lead to a reduced number of switchings, which can lead to lower switching
losses and a nearly equal THD of the source currents.
ϮϱϬ
ϳ
7+'2)/,1(&855(17>@
ϮϬϬ ϲ
ϱ
ϭϱϬ
ϰ
ϵϴ͘Ϭϴ
ϭϬϬ ϴϯ͘ϵϲ ϯ
ϳϯ͘ϱ
ϱϴ͘ϱϰ
ϰϴ͘ϲϳ Ϯ
ϱϬ ϯϱ͘ϰϲ
Ϯϰ͘ϰϮ
ϭϭ͘ϴϯ ϭ
Ϭ Ϭ
ϭϬ ϮϬ ϯϬ ϰϬ ϱϬ ϲϬ ϳϬ ϴϬ ϭϬ ϮϬ ϯϬ ϰϬ ϱϬ ϲϬ ϳϬ ϴϬ
(a) (b)
3($.723($.9$/8(2)&$3$&,725
5,33/(92/7$*(>9@
Ϭ͘Ϯ ϱ
ϰ
Ϭ͘ϭϱ
ϯ
Ϭ͘ϭ
Ϯ
Ϭ͘Ϭϱ
ϭ
Ϭ Ϭ
ϭϬ ϮϬ ϯϬ ϰϬ ϱϬ ϲϬ ϳϬ ϴϬ ϭϬ ϮϬ ϯϬ ϰϬ ϱϬ ϲϬ ϳϬ ϴϬ
(c) (d)
Figure 6. Comparison results obtained by conventional MPC method and proposed method vs.
sampling frequency: (a) number of switchings; (b) THD values of source currents; (c) current errors;
and (d) peak-to-peak values of capacitor ripple voltages.
Loss analysis and stress distribution among the switching devices were further conducted on
conditions with vs = 730 V, Vdc = 1000 V, and Pin = 10 kW. Losses resulted in each switching component
by the conventional and the proposed methods are depicted in Figure 7. The proposed method
yields reduced losses in all the switching component, including the IGBTs and the clamping diodes,
in comparison with the conventional method. By comparing the conduction loss and the switching
loss in Figure 7, the conduction losses generated by the two methods are almost the same. On the other
hand, the switching losses of the proposed method are lower than those of the conventional method
for all the components. Total efficiency of the conventional and the proposed method was 98% and
47
Energies 2018, 11, 3524
98. 7%, respectively. Regarding loss distribution shown in Figure 7, the two methods lead to more
losses in the inner switches, Sa2 and Sb2 , than the outer switches, which is general in the three-level
NPC converters. However, it is seen that the losses by the proposed method are less concentrated on
the inner switches than the conventional method, as shown in Figure 7.
ŽŶǀĞŶƚŝŽŶĂůŵĞƚŚŽĚ
ŽŶĚƵĐƚŝŽŶůŽƐƐ ^ǁŝƚĐŚŝŶŐůŽƐƐ
Ϯϱ
ϮϬ
ϴ͘ϵϲ ϴ͘ϵϱ
dŽƚĂůůŽƐƐĞƐt
ϭϱ
ϭϬ ϲ͘ϮϮ ϲ͘Ϯϱ
ϲ͘ϯϳ ϲ͘ϯϳ
ϭϰ͘ϯϴ ϭϰ͘ϯϴ
ϱ
ϲ͘ϵϯ ϲ͘ϵϰ
ϱ͘ϭϴ ϱ͘ϭϳ
Ϭ
^Ăϭ ^ĂϮ ^ďϭ ^ďϮ Ăϭ ďϭ
(a)
WƌŽƉŽƐĞĚŵĞƚŚŽĚ
ŽŶĚƵĐƚŝŽŶůŽƐƐ ^ǁŝƚĐŚŝŶŐůŽƐƐ
Ϯϱ
ϮϬ
dŽƚĂůůŽƐƐĞƐt
ϭϱ Ϯ͘ϲϮ Ϯ͘ϭϲ
ϭϬ Ϯ͘ϭϲ ϯ͘ϵϮ
ϭϯ͘ϳϵ ϭϰ͘ϱϭ
ϭ͘ϰϳ
ϱ ϴ͘ϯϵ Ϯ͘ϬϮ
ϳ͘ϯϱ
ϯ͘ϴϯ ϰ͘ϵϲ
Ϭ
^Ăϭ ^ĂϮ ^ďϭ ^ďϮ Ăϭ ďϭ
(b)
48
Energies 2018, 11, 3524
conventional method because of the reduced number of switchings. It is seen that the pole voltage of
the proposed method has a lower number of commutations than the conventional method owing to
the reduced switching operations of the proposed method. From the frequency spectrum waveforms,
it can be shown that the two methods represent almost the same current THD values. Therefore, the
proposed method can reduce the number of switchings and the switching losses without deteriorating
the quality of the ac current waveform in comparison with the conventional method.
(a) (b)
Figure 8. Simulation results of ac source current (is ), source voltage (vs ), converter line-to-line voltage
(vab ), pole voltages (vaN, vbN ), and frequency spectrum of input current (is ) obtained by (a) conventional
and (b) proposed methods.
Figure 9 shows simulation waveforms of the upper and the lower capacitor voltages (vc1 and vc2 )
and switching patterns of the four upper switches (Sa1 , Sa2 , Sb1 , and Sb2 ) during the steady state as
obtained by the conventional and proposed methods. In Figure 9a, obtained by the conventional MPC
method using all possible switching states, the two capacitor voltages with the NP voltage controlled
by the redundant switching states are almost equal with an avoidable oscillation at a certain voltage
boundary ΔVC .
49
Energies 2018, 11, 3524
In the proposed method, as shown in Figure 9b, the converter is operated with only a consideration
of the reduced number of commutations. It is clearly seen from the switching patterns that the proposed
method yields a reduced number of switchings compared with the conventional method. This can lead
to a decreased number of switching losses and higher efficiency. In addition, in the proposed method
of Figure 9b, the NP voltage balance is well regulated without a continuous increase or decrease in the
capacitor voltages, whereas the peak-to-peak ripple voltages of the two capacitors obtained by the
proposed method are slightly increased compared with those of the conventional method. The number
of switchings and switching losses of the proposed method were reduced by almost half in comparison
with the conventional method.
(a) (b)
Figure 9. Simulation results of upper and lower capacitor voltages (vc1 , vc2 ) and switching patterns
of four upper switches (Sa1 , Sa2 , Sb1 , Sb2 ) during steady state in (a) conventional MPC method and
(b) proposed MPC method.
50
Energies 2018, 11, 3524
Figure 10 shows simulation waveforms of the two methods when imbalance conditions of the
capacitor voltages, which were intentionally generated, occur. Both the conventional and proposed
methods can balance the capacitor voltages, as shown in Figure 10. It is seen that the proposed method,
using a reduced number of possible switching states for a reduced number of commutations, can yield
an NP voltage balance at almost the same speed as the conventional method.
(a)
(b)
Figure 10. Simulation results of capacitor voltages (vc1 , vc2 ) and source current during imbalanced NP
voltage conditions obtained by (a) conventional method and (b) proposed method.
Figures 11 and 12 show simulation waveforms of step changes of the load resistance and the dc
load voltage obtained by the two methods. It is seen that the proposed method achieves dynamic
responses as quickly as the conventional method despite the reduced number of possible switching
states to decrease the number of switching losses.
51
Energies 2018, 11, 3524
(a)
(b)
Figure 11. Simulation results of capacitor voltages (vc1 , vc2 ) and source current with step change of
load resistor from 200 Ω to 100 Ω obtained by (a) conventional method and (b) proposed method.
52
Energies 2018, 11, 3524
(a)
(b)
Figure 12. Simulation results of capacitor voltages (vc1 , vc2 ) and source current with step change of dc
voltage from 150 V to 120 V obtained by (a) conventional method and (b) proposed method.
Effects of the control parameter λc on performance were investigated, where Figure 13 shows the
average number of switching, the THD values of line current, and the peak-to-peak values of capacitor
ripple voltage of the conventional and the proposed methods, as a function of the weighting factor λc
varying from 0.05 to 2. It is shown from Figure 13 that the proposed method results in much lower
average number of switching and almost same THD values of the line currents in comparison with the
conventional method, over the range of the varying weighting factor. Figure 14. depicts simulation
results of ac source current, frequency spectrum of source current, and two capacitor voltages obtained
by the conventional and the proposed methods with weighting factor λc = 0.05, λc = 0.5, and λc = 2,
respectively. The peak-to-peak value of the two capacitor ripple voltages of the proposed method is
slightly increased compared with that of the conventional method, with the trade-off with the reduced
number of switching and the consequently decreased switching losses. It is seen that the proposed
method with the three different weighting factors regulates the sinusoidal input current well and
maintains the two capacitor voltage balancing, even with the lower switching operations than the
conventional method.
53
Energies 2018, 11, 3524
(a) (b)
ĐŽŶǀĞŶƚŝŽŶĂů ƉƌŽƉŽƐĞĚ
ϯ͘ϱ
ϯ
Ϯ͘ϱ
Ϯ
ϭ͘ϱ
ϭ
Ϭ͘ϱ
Ϭ
Ϯ ϭ͘ϱ ϭ Ϭ͘ϳ Ϭ͘ϱ Ϭ͘ϯ Ϭ͘ϭ Ϭ͘Ϭϱ
(c)
Figure 13. Effects of weighting factor λc varying from 0.05 to 2 on (a) average number of switching
(b) THD of line current (c) peak-to-peak value of capacitor ripple voltage of the conventional and the
proposed methods.
(a)
54
Energies 2018, 11, 3524
(b)
(c)
Figure 14. Simulation results of ac source current (is ), frequency spectrum of input current (is ),
and capacitor voltages (vaN, vbN ) obtained by the conventional and the proposed methods with
weighting factor (a) λc = 0.05, (b) λc = 0.5, and (c) λc = 2.
Performances with larger input resistance and input inductance were investigated. Figure 15
shows the average number of switching, the THD values of line current, and the peak-to-peak values
of capacitor ripple voltage of the conventional and the proposed methods, for several values of the
input resistance and the input inductance. It is shown from Figure 15 that the proposed method results
55
Energies 2018, 11, 3524
in much lower average number of switching and almost same THD values of the line currents in
comparison with the conventional method, for the different input parameters. Figure 16. depicts
simulation results of ac source current, frequency spectrum of source current, and two capacitor
voltages obtained by the conventional and the proposed methods with the three different input
resistances and input inductances. The peak-to-peak value of the two capacitor ripple voltages of
the proposed method is slightly increased compared with that of the conventional method, with the
trade-off with the reduced number of switching and the consequently decreased switching losses.
It is seen that the proposed method with the three different input parameters regulates the sinusoidal
input current well and maintains the two capacitor voltage balancing, even with the lower switching
operations than the conventional method.
(a) (b)
(c)
Figure 15. Effects of input resistance and input inductance on (a) average number of switching
(b) THD of line current (c) peak-to-peak value of capacitor ripple voltage of the conventional and the
proposed methods.
56
Energies 2018, 11, 3524
(a)
(b)
57
Energies 2018, 11, 3524
(c)
Figure 16. Simulation results of ac source current (is ), frequency spectrum of input current (is ), and
capacitor voltages (vaN, vbN ) obtained by the conventional and the proposed methods with input
parameters (a) Rs = 1 Ω and Ls = 10 mH (b) Rs = 2 Ω and Ls = 20 mH, and (c) Rs = 3 Ω and Ls = 30 mH.
The single-phase three-level NPC converter operated with the proposed method was tested with
a nonlinear load, which is a three-phase voltage source inverter with a fundamental frequency of
80 Hz as shown in Figure 17. For the purpose of comparison, the simulation results obtained by the
conventional method were also included. It is seen from Figure 18 that the single-phase three-level
NPC converter with the proposed method well regulates the sinusoidal source current in phase with
the source voltage with a low THD value, even with a nonlinear load. In addition, the two capacitor
voltages of the proposed method are balanced in a case of the nonlinear load as the same as the linear
load, as shown in Figure 18.
S
iS
6D 6E
& vF
6D 'D 6E 'E
iD RLQY LLQY
R L iV
vD iE
vV vDE D R 9GF
vE iF
E
6D 'D 6E 'E
v
& F
6D 6E
iQ Q
Figure 17. Schematic with a three-phase voltage source inverter as a nonlinear load.
58
Energies 2018, 11, 3524
(a) (b)
Figure 18. Simulation results with the three-phase voltage source inverter as a nonlinear load: ac source
current (is ), frequency spectrum of input current (is ), line to line source voltages (vab ), capacitor voltages
(vc1, vc2 ), and three-phase load currents of the voltage source inverter (from top to bottom) obtained by
(a) the conventional method (b) the proposed methods.
A prototype of a single-phase three-level NPC converter, shown in Figure 19, was fabricated in a
laboratory to prove the proposed method. The conventional and proposed methods were implemented
using a DSP board (TMS320F28335). To compare the performance of the two methods, experiments
were conducted under the same conditions as the simulation. Figure 20 shows experimental waveforms
of the source voltage/current, converter input voltage, each pole voltage, and an FFT analysis of the
source current for the conventional method and the proposed method during steady-state conditions.
59
Energies 2018, 11, 3524
Figure 19. Photograph of prototype setup for single-phase three-level NPC converter.
&RQYHQWLRQDO0HWKRG
iV >$GLY@
vV >9GLY@
>PVGLY@
vDE >9GLY@
>PVGLY@
vD1>9GLY@
>PVGLY@
vE1>9GLY@
>PVGLY@
iV
>+]GLY@
(a) (b)
Figure 20. Experimental results of ac source current (is ) and source voltage (vs ), converter input
voltage (vab ), pole voltage (vaN , vbN ), and FFT analysis of source current (is ) in (a) conventional and
(b) proposed methods.
60
Energies 2018, 11, 3524
As in the simulation, the proposed method shows almost the same source current and converter
input voltage waveforms as the conventional method. In addition, the proposed method through
the FFT analysis shows performance that is very similar to that of the conventional method. On the
other hand, as shown in Figure 20, the proposed method has a quite different pole voltage from the
conventional method owing to the reduced number of switchings.
Figure 21 shows the upper and lower capacitor voltages, source current, and switching state in
the steady state. As shown in Figure 21, the proposed method reduces the number of switchings
in comparison with the conventional method. In addition, the NP voltage balance in the proposed
method is well regulated without a continuous increase or decrease in the capacitor voltages, whereas
the peak-to-peak ripple voltages of the two capacitors obtained by the proposed method is slightly
increased compared with the conventional method.
3URSRVHG0HWKRG
iV >$GLY@
>PVGLY@
6D
6D
>PVGLY@
(a) (b)
Figure 21. Experimental results of capacitor voltages (vc1 , vc2 ), source current (is ), and upper switch of
a leg (Sa1 , Sa2 ) during steady state in (a) conventional method and (b) proposed method.
In Figure 22, experimental waveforms of the two methods are shown when imbalanced NP voltage
conditions of the capacitor voltages, which are intentionally generated, occur. Both the conventional
and proposed methods can balance the capacitor voltages, as shown in Figure 22. This is the same as
the simulation results of Figure 10. It is seen that the proposed method, using a reduced number of
possible switching states for a reduced number of commutations, can yield an NP voltage balance at
almost the same speed as the conventional method. Figures 23 and 24 show experimental waveforms
of step changes of the load resistance and the dc load voltage obtained by the two methods. It is seen
that the proposed method achieves dynamic responses as quickly as the conventional method despite
the reduced number of possible switching states to decrease the number of switching losses.
61
Energies 2018, 11, 3524
&RQYHQWLRQDO0HWKRG 3URSRVHG0HWKRG
>PVGLY@ >PVGLY@
(a) (b)
Figure 22. Experimental results of capacitor voltages (vc1 , vc2 ) and source current during imbalanced
NP voltage conditions obtained by (a) conventional method and (b) proposed method.
&RQYHQWLRQDO0HWKRG
vF >9GLY@
vF >9GLY@
iV >$GLY@
>PVGLY@
(a) (b)
Figure 23. Experimental results of capacitor voltages (vc1 , vc2 ) and source current with step change of
load resistor from 200 Ω to 100 Ω obtained by (a) conventional method and (b) proposed method.
&RQYHQWLRQDO0HWKRG
vF >9GLY@
vF >9GLY@
iV >$GLY@
>PVGLY@
(a) (b)
Figure 24. Experimental results of capacitor voltages (vc1 , vc2 ) and source current with step change of
dc voltage from 150 V to 120 V obtained by (a) conventional method and (b) proposed method.
5. Conclusions
This paper proposed a highly efficient algorithm with a reduced number of switchings and
low switching losses for single-phase three-level NPC converters based on an MPC method with
a decreased number of commutations of switches. The proposed method pre-excludes, from the
candidates for possible future switching states, the switching states that yield more than two
commutations in the next sampling period. As a result, the proposed technique can reduce the
number of switchings and the switching losses by utilizing switching states involving no commutation
or only one commutation at every sampling instant for single-phase three-level NPC converters.
In addition, the developed method does not deteriorate the input current quality or input power
62
Energies 2018, 11, 3524
factor despite the reduced switching numbers and losses. Although the proposed method slightly
increases the peak-to-peak variations of the two dc capacitor voltages at the expense of reduced
commutation, the increased voltage variation is not high. Thus, the proposed method can obtain high
efficiency and low switching losses at the expense of slightly increased peak-to-peak variations of the
NP voltage. Simulations and experimental results were presented to verify the effectiveness of the
proposed method.
Nomenclature
Abbreviations
EMI Electromagnetic interference
NPC Neutral point clamped
CBPWM Carrier-based pulse width modulation
PI Proportional and integral
NP Neutral point
MPC Model predictive control
THD Total harmonic distortion
IGBT Insulated gate bipolar transistor
Variables
Sa Operating status of a-phase
Sb Operating status of b-phase
va Source voltage
ia Source current
i∗a Reference source current
Rs Input resistance
Ls Input inductance
v ab Line-to-line source voltage
v aN Phase voltage of a-phase
vbN Phase voltage of b-phase
C1 Output capacitance in upper capacitor
C2 Output capacitance in lower capacitor
iu Current of upper dc-bus bar
il Current of lower dc-bus bar
RL Output load resistance
Vdc Output dc voltage
g Cost function
λc Weighting factor
Ts Sampling period
References
1. Portillo, R.; Prats, M.M.; Leon, J.I.; Sanchez, J.A.; Carrasco, J.M.; Galvan, E.; Franquelo, L.G. Modeling strategy
for back-to-back three-level converters applied to high-power wind turbines. IEEE Trans. Ind. Electron. 2006,
53, 1483–1491. [CrossRef]
2. Alepuz, S.; Busquets-Monge, S.; Bordonau, J.; Gago, J.; Gonzalez, D.; Balcells, J. Interfacing renewable
energy sources to the utility grid using a three-level inverter. IEEE Trans. Ind. Electron. 2006, 53, 1504–1511.
[CrossRef]
63
Energies 2018, 11, 3524
3. Stala, R. Application of balancing circuit for DC-link voltages balance in a single-phase diode-clamped
inverter with two three-level legs. IEEE Trans. Ind. Electron. 2011, 58, 4185–4195. [CrossRef]
4. Song, W.; Feng, X.; Smedley, K. A carrier-based PWM strategy with the offset voltage injection for
single-phase three-level neutral-point-clamped converters. IEEE Trans. Power Electron. 2013, 28, 1083–1095.
[CrossRef]
5. Choi, U.-M.; Lee, H.-H.; Lee, K.-B. Simple neutral-point voltage control for three-level inverters using a
discontinuous pulse width modulation. IEEE Trans. Energy Convers. 2013, 28, 434–443. [CrossRef]
6. Song, W.; Wang, S.; Xiong, C.; Ge, X.; Feng, X. Single-phase three-level space vector pulse width
modulation algorithm for grid-side railway tractionconverter and its relationship of carrier-based pulse
width modulation. IET Electr. Syst. Transp. 2014, 14, 78–87. [CrossRef]
7. Freitas, I.S.D.; Bandeira, M.M.; Barros, L.D.M.; Jacobina, C.B.; Santos, E.C.D.; Salvadori, F.; Silva, S.A.D.
A carrier-based PWM technique for capacitor voltage balancing of single-phase three-level neutral-point-
clamped converters. IEEE Trans. Ind. Appl. 2015, 51, 3227–3235. [CrossRef]
8. Habibullah, M.; Lu, D.D.; Xiao, D.; Fletcher, J.E.; Rahman, M.F. Predictive torque control of induction motor
sensorless drive fed by a 3L-NPC inverter. IEEE Trans. Ind. Inf. 2017, 13, 60–70. [CrossRef]
9. Yaramasu, V.; Wu, B. Predictive control of a three-level boost converter and an NPC inverter for high-power
PMSG-based medium voltage wind energy conversion systems. IEEE Trans. Power Electron. 2014, 29, 5308–5322.
[CrossRef]
10. Acuna, P.; Moran, L.; Rivera, M.; Aguilera, R.; Burgos, R.; Agelidis, V.G. A single-objective predictive control
method for a multivariable single-phase three-level NPC converter-based active power filter. IEEE Trans.
Ind. Electron. 2015, 62, 4598–4607. [CrossRef]
11. Song, W.; Ma, J.; Zhou, L.; Feng, X. Deadbeat predictive power control of single-phase three-level
neutral-point-clamped converters using space-vector modulation for electric railway traction. IEEE Trans.
Power Electron. 2016, 31, 1083–1095. [CrossRef]
12. Acuna, P.; Aguilera, R.P.; Ghias, A.M.Y.M.; Rivera, M.; Baier, C.R.; Agelidis, V.G. Cascade-free model
predictive control for single-phase grid-connected power converters. IEEE Trans. Ind. Electron. 2017,
64, 721–732. [CrossRef]
13. Deng, Y.; Li, J.; Shin, K.H.; Viitanen, T.; Saeedifard, M.; Harley, R.G. Improved modulation scheme for loss
balancing of three-level active NPC converters. IEEE Trans. Power Electron. 2017, 32, 2521–2532. [CrossRef]
14. Jing, X.; He, J.; Demerdash, N.A.O. Loss balancing SVPWM for active NPC converters. In Proceedings of
the 2014 IEEE Applied Power Electronics Conference and Exposition—APEC 2014, Fort Worth, TX, USA,
16–20 March 2014.
15. Pulikanti, S.; Dahidah, M.S.A.; Agelidis, V. Voltage balancing control of three-level active NPC converter
using SHE-PWM. IEEE Trans. Power Deliv. 2011, 26, 258–267. [CrossRef]
16. Bruckner, T.; Bernet, S.; Guldner, H. The active NPC converter and its loss-balancing control. IEEE Trans.
Ind. Electron. 2005, 52, 855–868. [CrossRef]
17. Floricau, D.; Gateau, G.; Leredde, A.; Teodorescu, R. The efficiency of three-level active NPC converter for
different PWM strategies. In Proceedings of the 2009 13th European Conference on Power Electronics and
Applications, Barcelona, Spain, 8–10 September 2009.
18. Bruckner, T.; Bernet, S.; Steimer, P. Feedforward loss control of three-level active NPC converters. IEEE Trans.
Ind. Appl. 2007, 43, 1588–1596. [CrossRef]
19. Brückner, T.; Bernet, S. Loss balancing in three-level voltage source inverters applying active NPC switches.
In Proceedings of the IEEE Power Electronics Specialists Conference (PESC), Vancouver, BC, Canada,
17–21 June 2001; pp. 1135–1140.
20. Ma, L.; Kerekes, T.; Rodriguez, P.; Jin, X.; Teodorescu, R.; Liserre, M. A new PWM strategy for grid-connected
half-bridge active NPC converters with losses distribution balancing mechanism. IEEE Trans. Power Electron.
2015, 30, 5331–5340. [CrossRef]
21. Jiao, Y.; Lee, F.C. New modulation scheme for three-level active neutral-point-clamped converter with loss
and stress reduction. IEEE Trans. Ind. Electron. 2015, 62, 5468–5479. [CrossRef]
22. Habibullah, M.; Lu, D.D.; Xiao, D.; Rahman, M.F. Finite-state predictive torque control of induction motor
supplied from a three-level NPC voltage source inverter. IEEE Trans. Power Electron. 2017, 32, 479–489.
[CrossRef]
64
Energies 2018, 11, 3524
23. Vargas, R.; Ammann, U.; Rodriguez, J. Predictive approach to increase efficiency and reduce switching losses
on matrix converters. IEEE Trans. Power Electron. 2009, 24, 894–902. [CrossRef]
24. Vargas, R.; Rodriguez, J.; Rojas, C.A.; Rivera, M. Predictive control of an induction machine fed by a matrix
converter with increased efficiency and reduced common-mode voltage. IEEE Trans. Energy Convers. 2014,
29, 473–485.
25. Vatani, M.; Bahrani, B.; Saeedifard, M.; Hovd, M. Indirect finite control set model predictive control of
modular multilevel converters. IEEE Trans. Smart Grid 2015, 6, 1520–1529. [CrossRef]
26. Kwak, S.; Park, J. Switching strategy based on model predictive control of VSI to obtain high efficiency and
balanced loss distribution. IEEE Trans. Power Electron. 2014, 29, 4551–4567. [CrossRef]
27. Kwak, S.; Park, J. Predictive control method with future zero-sequence voltage to reduce switching losses in
three-phase voltage source inverters. IEEE Trans. Power Electron. 2015, 30, 1558–1566. [CrossRef]
28. Kukrer, O. Discrete-time current control of voltage-fed three-phase PWM inverters. IEEE Trans. Power Electron.
1996, 11, 260–269. [CrossRef]
29. Hildetirand, F.B. Introduction to Numerical Analysis; McGraw-Hill: New York, NY, USA, 1956.
30. Venkatraman, K.; Selvan, M.P.; Moorthi, S. Predictive current control of distribution static compensator for
load compensation in distribution system. IET Gener. Transm. Distrib. 2016, 10, 2410–2423. [CrossRef]
31. Kumar, C.; Mishra, M.K. Operation and control of an improved performance interactive DSTATCOM.
IEEE Trans. Ind. Electron. 2015, 62, 6024–6034. [CrossRef]
© 2018 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access
article distributed under the terms and conditions of the Creative Commons Attribution
(CC BY) license (http://creativecommons.org/licenses/by/4.0/).
65
energies
Article
A Method for the Simultaneous Suppression of DC
Capacitor Fluctuations and Common-Mode Voltage
in a Five-Level NPC/H Bridge Inverter
Ming Wu 1 , Zhenhao Song 1, *, Zhipeng Lv 1 , Kai Zhou 2 and Qi Cui 2
1 China Electric Power Research Institute, Haidian District, Beijing 100192, China;
[email protected] (M.W.); [email protected] (Z.L.)
2 Jiangsu Province Laboratory of Mining Electric and Automation, China University of Mining and
Technology, Xuzhou 221008, China; [email protected] (K.Z.); [email protected] (Q.C.)
* Correspondence: [email protected]; Tel.: +86-1821-054-0873
Abstract: To suppress the direct current (DC) capacitor voltage fluctuations and the common-mode
voltage (CMV) in a three-phase, five-level, neutral-point-clamped (NPC)/H-bridge inverter, this
paper analyzes the influence of all voltage vectors on the neutral point potential of each phase under
different pulse mappings in detail with an explanation of the CMV distribution. Then, based on
the traditional space vector pulse width modulation (SVPWM) algorithm, a dual-pulse-mapping
algorithm is proposed to suppress the DC capacitor fluctuations and the CMV simultaneously. In the
algorithm, the reference voltage synthesis selects the voltage vector that has the smallest CMV value
as the priority. In addition, the two kinds of pulse mappings that have opposite effects on the neutral
point potential are switched to output. At the same time, regulating factors are introduced to adjust
the working time of each voltage vector under the two pulse mappings; then, the capacitor voltages
can be balanced. Both the simulation and experiment demonstrate the algorithm’s effectiveness.
Keywords: NPC/H Bridge; five-level; Balance of capacitor voltage; Suppression of CMV; SVPWM
1. Introduction
In the past several decades, multilevel power topologies have increasingly been used in high-power,
medium-voltage drives [1,2]. Due to the advantages of a higher voltage capability, lower switching
frequencies, better power quality, and smaller voltage jumps (dv/dt), multilevel converters have
become more popular and are applied to high-voltage variable frequencies, flexible alternating current
(AC) transmissions, high-voltage direct current (HVDC), and so on [3]. Several strategies have been
proposed for multilevel converters, such as sinusoidal pulse width modulation (SPWM), selective
harmonic elimination pulse width modulation (SHEPWM), and space vector pulse width modulation
(SVPWM). Compared to SPWM, SVPWM has lower total harmonic distortion (THD) and a high
utilization of direct current (DC)-side voltage [4]. SHEPWM is kind of offline strategy that requires
excellent storage performance [5]. Moreover, various multilevel converter topologies have been studied,
such as neutral-point-clamped (NPC) [6], cascaded H-Bridge (CHB) [7], modular multilevel converter
(MMC) [8], and Matrix converter [9]. Among all of the topologies, the neutral-point-clamped and the
cascaded H-Bridge are the two most widely used, and they are suitable for medium-voltage, high-power
drives [10,11]. By combining the NPC and H-bridge topologies, a five-level NPC/H-bridge topology
was proposed in 1990 [12] and since then has been applied in industrial drive applications. Figure 1
shows a schematic diagram of a three-phase, five-level NPC/H bridge inverter’s main circuit with RL
(resistance and inductance) load. Each phase has an independent DC power Vdc , and the DC-side is
connected by two capacitors in series. Under ideal conditions, the voltage of each is Vdc /2.
However, the NPC/H bridge topology has two crucial problems: an imbalance in capacitor
voltages in three phases and a requirement that the common-mode voltage be suppressed. In fact,
there are some reports about solving the imbalance in capacitor voltages of the NPC/H bridge topology.
Most use two six-pulse rectifying devices to obtain two independent DC powers to supply each phase,
which not only increases the complexity of the topology, but also increases the cost of the system
circuit [13,14].
The best way to solve the problem is to utilize software balancing techniques because of the cost. In
other five-level topologies, the object function optimization, zero sequence voltage injection, and virtual
space-vector PWM methods are common techniques that mainly utilize the redundant vectors with a
different combination of switching sequences [15,16]. In [15], for a five-level, diode-clamped converter
(DCC), the duty cycles are calculated for the redundant states and adjusted between two zero vectors
to control the capacitor voltages. This method is not suitable for the NPC/H bridge topology because
the redundant states have the same influences on the neutral potential of capacitors. In [16], the authors
propose to solve the capacitor voltage balancing issue of the five-level DCC based on a Model Predictive
Control strategy. Although this strategy balances the capacitor voltages, it causes voltage jumps that
could damage the switches.
In addition, the common-mode voltage in the NPC/H topology also deserves more attention.
High common-mode voltage and its common-mode current will produce electromagnetic interference
that will damage the motor. There are many methods to solve the problem. In [17], a five-level NPC/H
inverter is considered to be equivalent to two three-level NPC inverters. One equivalent inverter
always operates with zero common-mode voltage to suppress CMV, and the other one operates with
the conventional three-level SVPWM. This measure can inhibit the CMV to V dc /3. Another author
proposes a strategy called hierarchical model predictive voltage control (HMPVC) [18], which can
suppress CMV effectively.
In this paper, a dual-pulse-mapping algorithm is proposed for the simultaneous suppression
of DC-side capacitor midpoint potentials and CMV in five-level NPC/H bridge inverter. In fact,
the algorithm is suitable for NPC/H-Bridge converters with any number of voltage levels. In the
analysis in Section 2, each voltage vector is found to correspond to a variety of pulse mappings, so the
two pulse mappings (A) and (C), which have completely opposite effects on the midpoint potential of
capacitors in each phase, are selected. In the proposed algorithm, the first step is to select the voltage
vectors with the smallest CMV based on a line-voltage coordinate system. In order to ensure the
output performance, the target of the algorithm is to suppress the CMV to V dc /6. The second step
is to synthesize the reference voltage based on space vector modulation (SVM) with six segments.
The first three segments work under pulse mapping (A) and the other three segments work under
pulse mapping (C). The key of the algorithm is to choose regulating factor for each vector. The value of
the factor decides the working time of each vector that influences the charge or discharge of capacitors
under the two pulse mappings. So, adjusting the regulating factor can balance the capacitor voltages
effectively. The algorithm proposed in this paper can perfectly solve the two crucial problems of the
67
Energies 2019, 12, 779
NPC/H bridge topology, which makes the NPC/H bridge topology play a better role in high-voltage
and high-power applications.
Switching State Sx Pulse Mapping Number Sx1 , Sx2 , Sx3 , Sx4 , Sx5 , Sx6 , Sx7 , Sx8 Phase Voltage uxo
2 1 11000011 V dc
2 11000110
1 V dc /2
3 01100011
4 11001100
0 5 01100110 0
6 00110011
7 01101100
−1 −V dc /2
8 00110110
−2 9 00111100 −V dc
Based on the main circuit diagram of the system shown in Figure 1 and the corresponding
switching states in Table 1, the output voltage of each phase of the inverter is
⎧
⎪
⎨ uao = Vdc ∗ Sa /2
ubo = Vdc ∗ Sb /2 (1)
⎪
⎩ u = V ∗ S /2
co dc c
&$ SD S D
S D SD
$
V GF SD SD
&$
SD SD
1
Figure 3 shows the circuit of pulse mapping 2. Assuming that the direction of phase current ia is
the same as in Figure 3, the current flows through Sa1 , Sa2 , Sa7 , and Da4 and then arrives at the midpoint
68
Energies 2019, 12, 779
potential. Due to the effect of ia , the midpoint potential increases and the voltage of capacitor CA1
decreases. If the current direction is opposite to that shown in Figure 3, the current flows through Da3 ,
Sa6 and the freewheeling diodes of Sa2 , Sa1 , then arrives at the positive pole. At this time, the midpoint
potential decreases and the voltage of capacitor CA1 increases. In these two situations, the current has
an opposite influence on the midpoint potential. Figure 4 shows the circuit of pulse mapping 3. If the
current direction is same as the definition of Figure 4, the current flows through Da1 , Sa2 ’s freewheeling
diode, Sa7 and Sa8 , then arrives at the negative pole. The midpoint potential decreases and the voltage
of capacitor CA1 increases. If the current direction is opposite to the definition, the current flows
through the freewheeling diodes of Sa8 and Sa7 , Sa3 , and Da2 . At this time, the midpoint potential
increases and the voltage of capacitor CA1 decreases. We can conclude that different directions of ia
have different effects on the midpoint potential. The changes caused by pulse mapping 7 and 8 are
same as those caused by pulse mapping 2 and 3. Table 2 shows the changes in midpoint potential
when using pulse mapping 2, 3, 7, and 8 with opposite direction currents.
iD
& $ SD SD
& $ SD S D
'D S D ' D S D
iD $
VGF
SD S D
'D ' D
&$
SD SD
1
Table 2. Changes in midpoint potential in pulse mapping 2, 3, 7, and 8 with different direction currents.
69
Energies 2019, 12, 779
As shown in Table 2, the changes caused by pulse mapping 2 are the total opposite of those caused
by pulse mapping 3. This situation also exists between pulse mapping 7 and 8. So, we select pulse
mapping 2 and 7, which have the same influence on the midpoint potential, to form pulse mapping (A),
and pulse mapping 3 and 8 constitute pulse mapping (B), as listed in Table 3.
Based on the analysis of Tables 2 and 3, we know that pulse mapping (A) and (B) have a completely
opposite effect on the midpoint potential whatever the direction of ia is. If the pulse mapping (A)
and (B) are used properly, the midpoint potential can be balanced.
(a) (b)
Figure 5a shows the traditional common-mode voltage distribution of the five-level NPC/H
bridge inverter. In order to suppress the common-mode voltage of the system while not affecting the
output performance of the inverter, this paper retains the vector that has the smallest common-mode
voltage among all the redundant vectors. Additionally, the six vertex vectors of the outer hexagon
are eliminated. So, the common-mode voltage distribution in Figure 5a can be simplified as shown
in Figure 5b.
70
Energies 2019, 12, 779
When the reference voltage is located in the shaded quadrangle of Figure 5b, the closest three
voltage vectors are utilized in the synthesis. Thus, the common-mode voltage of the five-level NPC/H
bridge inverter is suppressed to ±V dc /6 and 0 while the output performance of the inverter is ensured.
The per unit values of components are rounded up and down to an integer. In the equation,
“floor” means rounding down to an integer and “ceil” represents rounding up to an integer.
⎧
⎪
⎨ Fab = f loor (Uab ), Cab = ceil (Uab ) ;
Fbc = f loor (Ubc ), Cbc = ceil (Ubc ) ; (4)
⎪
⎩ F = f loor (U ), C = ceil (U ) ;
ca ca ca ca
All of the triangles can be separated into regular and inverted ones. If Fab + Fbc + Fca = −1, the
end of the reference voltage vector is located in the regular triangle, and the coordinates of the three
triangle vertexes (UA , UB , and UC ) and the time duty ratio of three basic vectors are as follows.
⎧
⎪
⎨ UA = (Cab , Fbc , Cca ), dA = Uab − Fab ;
UB = ( Fab , Cbc , Fca ), dB = Ubc − Fbc ; (5)
⎪
⎩ U = ( F , F , C ), d = U − F ;
C ab bc ca C ca ca
If Fab + Fbc +Fca = −1, the end of the reference voltage vector is located in the inverted triangle.
The coordinates and the time duty ratio are as follows.
⎧
⎪
⎨ UA = (Cab , Fbc , Cca ), dA = Cab − Uab ;
UB = ( Fab , Cbc , Cca ), dB = Cbc − Ubc ; (6)
⎪
⎩ U = ( C , C , F ), d = C − U ;
C ab bc ca C ca ca
After selecting the three basic vectors, it is essential to find all the switching states corresponding
to each basic vector. (Sa , Sb , Sc ) represents the switching states of basic vectors in the α − β coordinate
71
Energies 2019, 12, 779
system. UX = (a, b, c) represents the coordinates of triangle-vertex vectors in the line-voltage coordinate
system (where X = A, B, or C). ⎧
⎪
⎪ Sa = Sa
⎪
⎨ Sb = Sa − a
(7)
⎪
⎪ Sc = Sa + c
⎪
⎩
0 ≤ Sa , Sb , Sc ≤ 4
Equations (5)–(7) can quickly determine the triangle-vertex vectors and their time duty ratios.
The relationship between common-mode voltage and switching states is obtained by Equations (1)
and (2) as the following:
Sa + Sb + Sc
UCMV = Vdc (8)
6
The dual-pulse-mapping algorithm proposed in this paper utilizes Equation (8) to select the
vectors that have the smallest CMV among redundant vectors.
Figure 6. The vectors with the minimum common-mode voltage (CMV) in Sector I.
We take the 13th triangle in Figure 6 as an example to explain how the dual-pulse mapping works.
Because the reference voltage is in the 13th triangle, the vector synthesizing sequence is showing
as Figure 7.
ĺĺĺĺĺ
0DSSLQJ˄$˅ 0DSSLQJ˄%˅
Figure 7. The vector synthesizing sequence of dual-pulse mapping strategy.
As shown in Tables 2 and 3, the pulse mappings (A) and (B) have the opposite effect on the
midpoint potential. Based on this, the regulating factors ka and kc are adopted. Assuming that the
working time of the three vectors are T1 , T2 , and T3 , the working time of the six segments is assigned
as Figure 8.
72
Energies 2019, 12, 779
0DSSLQJ˄$˅ 0DSSLQJ˄%˅
If the midpoint potential of phase A is equal to V dc /2, then ka is 0.5. If the midpoint potential of
phase A is higher than V dc /2, we only need to reduce the value of ka to <0.5, for example 0.4, in order
to increase the working time of 10-2 under mapping (B) (because the time if the follow current’s state is
much smaller than the sampling time and a follow current also exists when using pulse mapping (B),
so this state will not be taken into consideration). It is all the same when the midpoint potential of
phase A is lower than V dc /2. By adjusting the operating time of 10-2 under the two kinds of pulse
mappings, the midpoint potential of phase A will be balanced.
U$2U%2U&2
tV
(a)
tV
(b)
Figure 9. The inverter without capacitor voltage control. (a) Midpoint Potential of three phases; and (b)
Line voltage and common mode voltage.
73
Energies 2019, 12, 779
The line voltage between phase A and phase B is degraded to five-level from the original
nine-level. The imbalanced DC-side voltages inject harmonics into the output voltage of the inverter,
thereby distorting the output voltage waveform. If the inverter continues to work in an unbalanced
capacitor voltage state, the power electronics in the system will be unevenly pressed or will even break
down, and eventually the entire system will not work properly.
&XUUHQW $
&XUUHQW $
U$ 2 U%2
U$ 2 U%2 U&2 U&2
9ROWDJH 9
9ROWDJH 9
U$% U&0 9 U$% U&0 9
9ROWDJH 9
9ROWDJH 9
7LPH V 7LPH V
Figure 10. The simulation waveforms under the algorithm. (a) The three-phase current, midpoint
potentials, line voltage between phase A and phase B, and common-mode voltage when m is 0.4;
and (b) The three-phase current, midpoint potentials, line voltage between phase A and phase B,
and common-mode voltage when m is 0.9.
According to the Figure 10, under the modulation index of 0.4 and 0.9, the proposed
dual-pulse-mapping strategy could control the operation of the inverter stably. The midpoint potentials
of the three-phase DC-side capacitors fluctuate within ±3 V, which indicates that the proposed
algorithm can effectively balance the midpoint potentials of DC-side capacitors. The largest ripple in
the common voltage is 1/6V dc , which means that the common voltage has effectively been suppressed.
74
Energies 2019, 12, 779
capacitor voltages of phase A change from 0 V and 100 V to 50 V. These simulation results show that
the proposed algorithm has intelligent dynamic performance.
6. Experimental Results
In order to further verify the effectiveness of the proposed control algorithm for balancing DC-side
(Direct Current) capacitor voltages and the suppression of the common-mode voltage and its dynamic
response capability, a three-phase, five-level NPC/H Bridge inverter with an RL load experimental
platform was built as shown in Figure 12. The structure is composed of a 12-pulse uncontrolled rectifier
and a five-level NPC/H-bridge-type inverter. The basic parameters of the experiment are shown
in Table 4.
Parameters Values
DC-side voltage V dc 100 V
Output voltage frequency f AC 50 Hz
DC-side capacitance C 3300 μF
RL load 26 Ω + 15 mH
Modulation index m 0.9 and 0.4
Switching frequency f s 800 Hz
Figure 12. The experimental platform.
75
Energies 2019, 12, 779
In Figure 13a,b, the DC-side capacitor voltages’ fluctuations are very small regardless of whether
the reference voltage locates in the high- or low-modulation index region, and the common-mode
voltage of the system is suppressed at the −V dc /6, 0, V dc /6. This proves that the dual-pulse-mapping
algorithm controls the stable operation of the three-phase, five-level NPC/H-bridge inverter.
Figure 13c,d show the harmonic analysis of the line voltage. It can be seen that, when the modulation
index m is 0.9 and 0.4, the THD is 17.8% and 35.0%, respectively, which means that the output
performance of the algorithm is the same as that of traditional SVPWM.
The pulse-width modulations (PWMs) of Sa1 , Sa2 , Sa3 , and Sa4 in phase A are shown in Figure 14.
The switching frequencies of the four switches in phase A were calculated approximately during
250~350 Hz, with a modulation index m of 0.4 and 0.9. The higher the modulation index is, the lower
the switching frequency of each switch is. Phase B and C are both the same. Compared with the
traditional SVPWM, the switching frequency of each switch just a little higher.
Figure 15a,b show the experimental waveforms of the dynamic response when the reference
voltage modulation index suddenly decreases. The modulation index changes from m = 0.9 to m = 0.4.
The line voltage and phase currents respond immediately during a very short time. The capacitor
voltage is still balanced but has a little increase because of the uncontrolled rectifier.
In order to verify the strong self-balancing property of the algorithm, the conditions were set as
follows: in the beginning, the modulation index was m = 0.9, and the values of regulating factors were
all 0.5, which means that the dual-pulse-mapping algorithm was equivalent to a common six-segment
SVPWM. Under the mapping (A), the midpoint potentials V AO , V BO , and V CO rise quickly and
achieve the maximum V dc /2 after some time. The line voltage also degenerates to five-level from
nine-level. The inverter works under an unstable condition. Then, the dual-pulse-mapping algorithm
was adopted. In Figure 15c, the midpoint potentials of the three-phase capacitors return to a balanced
state after a short time. The line voltage also returns to nine-level. The two capacitor voltages in phase
A change from 0 V and 100 V to 50 V in Figure 15d.
Figure 13. The experimental results of steady-state operation. (a) The DC-side voltage, the capacitance
voltage of phase A, line voltage between phase A and phase B, and common-mode voltage when m is
0.9; (b) The DC-side voltage, the capacitance voltage of phase A, line voltage between phase A and
phase B, and common-mode voltage when m is 0.4; (c) The harmonic analysis of the line voltage when
m is 0.9; and (d) The harmonic analysis of the line voltage when m is 0.4.
76
Energies 2019, 12, 779
Figure 14. The pulse width modulations (PWMs) of phase A when m = 0.4 and m = 0.9.
V$ 9GLY VGF 9GLY
U$%ˈU&09 9GLY
VGF
U$% VGF
V$
VGF 9GLY
IDEF $GLY
U&09
PVGLY PVGLY
D E
U$2U%2U&2 V$
V$2ˈV%2ˈV&2 9GLY
V$ˈV$ 9GLY
U$% 9GLY
U$% 9GLY
PVGLY PVGLY
F G
Figure 15. The experimental results of dynamic performance. (a) The DC-side voltage, the capacitance
voltage of phase A, line voltage between phase A and phase B, and common-mode voltage with
changing m; (b) The DC-side voltage and the currents of three-phase with changing m; (c) The midpoint
potentials of three-phase and the line voltage between phase A and phase B after dual-pulse mapping
strategy started to work; and (d) The two capacitor voltages in phase A after dual-pulse mapping
strategy started to work.
7. Conclusions
In this paper, the balance of the midpoint potentials of three-phase DC-side capacitors and
the suppression of common-mode voltage were studied in a three-phase, five-level NPC/H-bridge
inverter. A dual-pulse-mapping algorithm was proposed based on the characteristics of this topology.
In combination with the traditional six-segment SVPWM, the proposed algorithm selectively uses
the two pulse mappings that have the opposite effects on the midpoint potentials of the capacitors.
The simulation and experimental results show that the proposed algorithm can balance the midpoint
potentials perfectly and can suppress the common-mode voltage effectively. Based on the dynamic
experiments, we can conclude that the proposed algorithm has a good capability to respond and the
output performance is as good as that of the traditional SVPWM. Compared with the hardware
balancing method, the volume and the cost of the system are both reduced. So, the proposed
algorithm has a certain significance for cascaded NPC/H-bridge multilevel topology research.
In high-voltage and high-power applications, the NPC/H bridge topology will be more suitable
with the proposed algorithm.
Author Contributions: Z.S. put forward the main idea of this paper. K.Z. and Q.C. performed the data analysis
and the simulations/experiments. M.W. and Z.L. assisted with the idea’s development and the paper’s writing.
Funding: This research was funded by National Key R&D Program of China, grant number is 2016YFB 0900400.
Conflicts of Interest: The authors declare no conflict of interest.
77
Energies 2019, 12, 779
References
1. Wu, B. High Power Converters and AC Drives; IEEE Press/Wiley: New York, NY, USA, 2006.
2. Rodgriguez, J.; Lai, J.S.; Peng, F.Z. Multilevel inverters: A survey of topologies, controls and applications.
IEEE Trans. Ind. Appl. 2002, 49, 724–738.
3. Saeedifard, M.; Barbosa, P.M.; Steimer, P.K. Operation and control of a hybrid seven-level converter.
IEEE Trans. Power Electron. 2012, 27, 652–660. [CrossRef]
4. Kokila, A.; Kumar, V.S. Comparison of SPWM and SVPWM control techniques for diode clamped multilevel
inverter with photovoltaic system. In Proceedings of the 2018 4th International Conference on Electrical
Energy Systems (ICEES), Chennai, India, 7–9 February 2018; pp. 234–241.
5. Yang, P.; Li, C.; Lan, Z. Investigation on the subsection synchronous modulation strategy for high power
NPC/H-bridge inverter. In Proceedings of the IEEE 8th International Power Electronics and Motion Control
Conference (IPEMC-ECCE Asia), Hefei, China, 22–26 May 2016.
6. Chang, H.; Wei, R.; Ge, Q.; Wang, X.; Zhu, H. Comparison of SVPWM for five level NPC/H-Bridge inverter
and traditional five level NPC inverter based on line-voltage coordinate system. In Proceedings of the
International Conference on Electrical Machines and Systems, Pattaya, Thailand, 25–28 October 2015;
pp. 574–577.
7. Gong, Z.; Wu, X.; Dai, P.; Zhu, R. Modulated model predictive control for MMC-based active frontend
rectifiers under unbalanced grid conditions. IEEE Trans. Ind. Electron. 2019, 66, 2398–2409. [CrossRef]
8. Rendusara, D.A.; Cengelci, E.; Enjeti, P.N.; Stefanovic, V.R.; Victor, R.; Gray, J.W. Analysis of common mode
voltage — neutral shift in medium voltage PWM adjustable speed drive (MV-ASD) systems. IEEE Trans.
Power Electron. 2014, 29, 6281–6292.
9. Gong, Z.; Zhang, H.; Dai, P.; Sun, N.; Li, M. A low-cost phase-angle compensation method for the indirect
matrix converters operating at the unity grid power factor. IEEE Trans. Power Electron. 2019. [CrossRef]
10. Sun, L.; Wu, L.Z.; Ma, W.; Fei, X.; Cai, X.; Zhou, L. Analysis of the DC-link capacitor current of power cells
in cascaded H-Bridge inverters for high-voltage drives. IEEE Trans. Power Electron. 2014, 29, 6281–6292.
[CrossRef]
11. Wu, C.M.; Lau, W.H.; Chung, H. A five-level neutral-point-clamped H-bridge PWM inverter with superior
harmonic suppression: A theoretical analysis. In Proceedings of the 1999 IEEE International Symposium on
Cirsuits and Systems, Orlando, FL, USA, 30 May–2 June 1999; Volume 5, pp. 198–201.
12. Chen, Z.Y.; Wu, B. A Novel Switching Sequence Design for Five-Level NPC/H-Bridge Inverters With
Improved Output Voltage Spectrum and Minimized Device Switching Frequency. IEEE Trans. Power Electron.
2017, 22, 2138–2145. [CrossRef]
13. Shen, J.; Schroder, S.; Gao, J.P.; Qu, B. Impact of DC-Link Voltage Ripples on the Machine-Side Performance
in NPC H-Bridge Topology. IEEE Trans. Ind. Appl. 2016, 52, 3212–3223. [CrossRef]
14. Rojas, C.A.; Kouro, S.; Edwards, D.; Wu, B. Five-level H-bridge NPC central photovoltaic inverter with
open-end winding grid connection. In Proceedings of the 40th Annual Conference of the IEEE Industrial
Electronics Society (IECON), Dallas, TX, USA, 30 October–1 November 2014; pp. 4622–4627.
15. Hotait, H.A.; Massoud, A.M.; Finney, S.J.; Williams, B.W. Capacitor Voltage Balancing Using Redundant
States of Space Vector Modulation for Five-level Diode Clamped Inverter. IET Power Electron. 2010, 3,
292–313. [CrossRef]
16. Qin, J.C.; Saeedifard, M. Capacitor Voltage Balancing of a Five-level Diode-Clamped Converter Based on a
Predictive Current Control Strategy. In Proceedings of the 26th Annual IEEE Applied Power Electronics
Conference and Exposition, Fort Worth, TX, USA, 6–10 March 2011; pp. 1656–1660.
78
Energies 2019, 12, 779
17. Long, L.Z.; Zhang, Y.G.; Kuang, G.J. A Modified Space Vector Modulation Scheme to Reduce Common
Mode Voltage for Cascaded NPC/H-bridge Inverter. In Proceedings of the IEEE 7th International Power
Electronics and Motion Control Conference (ECCE), Harbin, China, 25 June 2012; pp. 1837–1841.
18. Gong, Z.; Dai, P.; Wu, X.J.; Deng, F.J.; Liu, D.; Chen, Z. A Hierarchical Model Predictive Voltage Control
for NPC/H-Bridge Converters with a Reduced Computational Burden. J. Power Electron. 2017, 17, 136–148.
[CrossRef]
© 2019 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access
article distributed under the terms and conditions of the Creative Commons Attribution
(CC BY) license (http://creativecommons.org/licenses/by/4.0/).
79
energies
Article
A Novel Fault-Tolerant Control of Modular
Multilevel Converter under Sub-Module Faults
Based on Phase Disposition PWM
Jingyuan Yin 1, *, Wen Wu 2 , Tongzhen Wei 1 , Xuezhi Wu 2 and Qunhai Huo 1
1 Institute of Electrical Engineering, Chinese Academy of Sciences, Beijing 100044, China;
[email protected] (T.W.); [email protected] (Q.H.)
2 National Active Distribution Network Technology Research Center, Beijing Jiaotong University,
Beijing 100044, China; [email protected] (W.W.); [email protected] (X.W.)
* Correspondence: [email protected]; Tel.: +86-138-1151-8632
Abstract: Each arm of modular multilevel converter (MMC) consists of a large number of sub-module
(SM) units. However, it also increases the probability of SM failure during the long-term system operation.
Focusing on the fault-tolerant operation issue for the MMC under SM faults, the traditional zero-sequence
voltage injection fault-tolerant control algorithm is analyzed detailed and its disadvantages are concluded.
Based on this, a novel fault-tolerant control strategy based on phase disposition pulse-width modulation
(PD-PWM) is proposed in this paper, which has three main benefits: (i) it has carrier and modulation
wave dual correction mechanism, which control ability is more higher and flexible; (ii) it only needs to
inject zero-sequence voltage in half a cycle of the modulation wave, which simplifies the complexity
of traditional zero-sequence voltage injection control algorithms and much easier for implement;
(iii) furthermore, the zero-sequence voltage can even be avoided injecting under the symmetrical fault
conditions. Finally, the effectiveness of the proposed control strategy is verified with the simulation
and experiment studies under different fault conditions.
Keywords: modular multilevel converter (MMC); Sub-module (SM) fault; fault-tolerant control;
Phase Disposition PWM
PACS: J0101
1. Introduction
Compared with the traditional two-level converter, modular multilevel converter (MMC) enjoys
the advantage of modular design [1,2], which allows MMC good scalability and facilitates the
improvement of voltage level, as well as other advantages as many output levels and good harmonic
characteristics. Therefore, in recent years, MMC topology converters have been widely studied
and applied in high-voltage direct current transmission (HVDC), staticsynchronous compensator
(STATCOM), and medium-voltage motor drive [3–6].
In actual transmission projects, in order to adapt to higher transmission voltage level, a large
number of sub-modules (SMs) are often cascaded. For example, Trans Bay Cable Project is reported
to have 216 SMs per arm [7], and the Zhou Shan multi-terminal flexible HVDC transmission project
completed in 2014 in China is larger cascaded reach 250 SMs per arm [8].
As the number of cascaded SMs increasing, the security risks of MMC converters become larger,
where the SM faults are prone to occur. When a SM fault occurs and is not processed in time,
it may cause system shutdown and even endanger the security of the power grid [9,10]. Therefore,
fault-tolerant control approach under SM faults is a problem that needs to be studied.
Generally, the common fault-tolerant control strategies are often designed based on equipping
redundant SMs [8]. According to the operation state of the redundant SMs, two main schemes are
developed, which are cold-reserve mode and hot-reserve mode, respectively. For the cold-reserve
scheme [11,12], it means that the redundant SMs are all in bypassed state when the system operating
normally and will replace the same number of faulty SMs when SMs malfunction. For the hot-reserve
scheme [13–15], it means that the redundant SMs are all operating identically as the rated SMs.
However, there are two further detailed modes under this scheme. We call it hot-reserve mode-a,
b, respectively, where hot-reserve mode-a means that simultaneously bypass the same number of
faulty SMs in each arm to keep the system strictly symmetrical [13]; and hot-reserve mode-b means
that only bypass the faulty SMs [14,15]. Compared to the mode-a, the hot-reserve mode-b scheme
can ensure full utilizing of all SMs during normal operation period and can avoid the long changing
time for redundant SM capacitors to rated values. Furthermore, some extra healthy SMs may need be
bypassed in hot-reserve mode-a, which might induce a greater transient impact on the system when
large number of SMs are simultaneously bypassed. Therefore, hot-reserve mode-b is a more preferable
redundant option for the MMC since its economic and reliability. However, this scheme also has a
potential problem, where the system may operate asymmetric under asymmetrical faults. For ensuring
the subsequent stable operation, the corresponding fault-tolerant control approach should be further
considered, and this is also what this paper deals with.
Based on the background of hot-reserve mode-b, an energy-balancing-based fault-tolerant control
strategy is proposed in [16]. Its main control idea is to increase the SM capacitor voltages on the faulty
arms to ensure the energy equalization of each arm, thereby achieving the subsequent balance operation
of the system. However, the reference command of the SM capacitor voltage needs to be calculated,
and the increased value of SM capacitor voltage will become larger as the number of malfunction SMs
increases. The neutral-point shift control method has been applied in the H-bridge cascaded multilevel
converter system, which can well solve the problems caused by the module faults [17–20]. Inspired by
this idea, the corresponding neutral-point shift control approaches suitable for the MMC system are
researched in [15,21]. With injecting the zero-sequence voltage to modify the modulation waves, the
converter line-voltages in the grid side are ensured balanced to maintain the system stable operation
under SM faults. The advantage of these methods in [15,21] is that they do not need to adjust the SM
capacitor voltages in fault arms. Similar to the methods in [15,21], an improved zero-sequence voltage
injection fault-tolerant control strategy is proposed in [22]. It simplifies the calculation process of the
required zero-sequence voltage. However, the common shortcoming in [15–22] is that they main only
consider one arm occurs SM faults. When the upper and lower arm occur SM faults simultaneously,
multiple zero-sequence voltages need to be calculated, which increase the complexity of the control
method. It should be further improved.
Aiming at this problem and for better deal with the multiple SM fault conditions, also under
the background of the redundant SMs equipped with hot reserve scheme and only bypassing the
faulty SMs when SMs malfunction, a novel fault-tolerant control strategy is proposed in this paper.
Compared to the current approaches, it has three main benefits: (i) it has carrier and modulation wave
dual correction mechanism, which control ability is more higher and flexible; (ii) it only needs to
inject zero-sequence voltage in half a cycle of the modulation wave, which simplifies the complexity
of traditional zero-sequence voltage injection control algorithms and more easier for implement;
(iii) furthermore, the zero-sequence voltage can even be avoided injecting under the symmetrical fault
conditions. Finally, the effectiveness of the proposed control strategy is verified with the simulation
and experiment studies under different fault conditions.
81
Energies 2019, 12, 20
Among them, the internal structure of the SM unit has various forms [23–25], and the more
common half-bridge SM structure is selected as the research object. Specifically, it is composed of an
insulated gate bipolar transistor (IGBT) half bridge, a DC capacitor C, and a bypass switch K. In the
normal working state of the system, the SM capacitor voltage USM has two levels of output states of 0
and DC capacitor voltage UC . When T1 is turned on and T2 is off, the SM is inserted and outputs UC .
When T1 is turned off and T2 is on, the SM is bypassed and output zero. Thus, the AC side multi-level
output of the MMC converter can be realized by properly controlling the on-off state of the SM.
82
Energies 2019, 12, 20
it is equal to N if no SM faults occur). njp is the number of the SMs need to be inserted in the upper
arm of phase j, which is obtained from the PD-PWM modulation. njl is the number of the SMs need to
be inserted in the lower arm of phase j, which can be obtained directly by calculating Njsum − njp .
Figure 2. Schematic diagram basic control: (a) Diagram of the pulse-width modulation (PD-PWM);
(b) Diagram of the capacitor voltage sorting algorithm.
When the system is operating, the numbers of the SMs need to be inserted in the upper arm
njp and the lower arm njl are obtained according to the PD-PWM modulation firstly, and then the
voltage of each SM in the arm is sorted by the capacitor voltage sorting algorithm. According to the
direction of the arm current, the SM with lower capacitor voltage is preferentially charged, and the SM
with higher capacitor voltage is preferentially bypassed and discharged, thereby ensuring a relatively
balanced voltage of each module during the whole dynamic operation.
83
Energies 2019, 12, 20
the stable operation of MMC system and flexibly deal with the multiple possible arms faulty states
after SMs malfunction, this paper improves the traditional zero-sequence voltage injection control
method, and proposes a new fault-tolerant control strategy based on PD-PWM.
Figure 3. Diagram of zero sequence voltage injection modulation: (a) Schematic diagram of fault
modulation wave of upper arm; (b) Schematic diagram of fault modulation wave of upper arm and
lower arm.
Figure 4 shows the overall control flow chart of the fault-tolerant control strategy proposed in this
paper. It can be divided into three main parts in the process of implementation:
1. Sub module fault handling. Its main task is to block the trigger pulse of the faulty SMs and isolate
the faulty SMs through closing the bypass switch.
2. Correction of the modulation state. The main task of this part is that with combining the faulty SM
numbers of the fault phase, achieving the correction of the original carrier and modulation waves
by adopting the proposed correction algorithm (where its specific implementation method will
be discussed in detail in Section 4.2, thereby obtaining the SM numbers that need to be inserted in
84
Energies 2019, 12, 20
each arms after SMs malfunction. In addition, it should be note that this step is the also core part
of the fault-tolerant control strategy. In the traditional zero-sequence voltage injection control
method, it only with correcting the modulation waves to help achieve the SM fault-crossing.
Compared to it, we add the correction algorithm of the carrier waves on the basis of the correction
algorithm of the modulation waves, and realized their combination. This effectively simplifies the
complexity of traditional control algorithm when deal with multiple arms occurring SM faults.
3. Generation of the SM drive pulses. In this part, with combining the SM numbers that need to
be inserted in each arms obtained from the step (2), the drive pulses of the remained healthy
SMs are generated by using SM voltage sorting control algorithm, and finally completes the
fault-tolerant control.
4.2. Specific Implementation Method of the Correction of the Carrier and Modulation Waves
When the system is operation under the normal state, we can depict the modulation diagram of
one phase as Figure 5.
As shown in Figure 5, when the MMC system is operating normally, the carrier waves of the N
SMs in the upper arm equally distributed in the interval [0, 2] according to the ratio of γ, where it is
easy to know:
2
γ= (2)
N
However, if the SMs occurring faults, the number of SMs that can normally be switched in
the faulty phase will be change as the faulty SMs are bypassed. Therefore, the original modulation
link must be revised and divided into two parts: ‘Correction algorithm of the carrier waves’ and
‘Correction algorithm of the modulation waves’. We will describe the implementation method detailed
in Sections 4.2.1 and 4.2.2, respectively.
85
Energies 2019, 12, 20
In order to ensure the maximum utilization of the remained healthy SMs, the number of SMs that
need to participate in switching operation in the two arms of the fault phase should respectively be:
Njχ = N − χj (5)
Njτ = N − τj (6)
Then, for correcting carrier wave conveniently, the correction coefficient Kjc (Kjc ≥ 1) about the
amplitude of the carrier waves is introduced. Simultaneously, combing the smaller faulty SM number
χj , we establish a relationship between them, where:
2
Kjc · γ = (7)
N − χj
86
Energies 2019, 12, 20
Figure 6. Modulation diagram of the faulty phase under carrier wave correction.
Therefore, through the correction algorithm of the carrier waves, we firstly guarantee the SMs on
the smaller faulty SM numbers arm can all normally participate in the switching operation. In other
words, we can equivalently consider that the MMC is under the ‘signal arm fault’ state, and its
rated SM number is Nj χ = N − χj ; its faulty SM number is τ j − χj . Especially, we can found that
when the τ j − χj = 0 (e.g., the faulty SM numbers in the upper and the lower arm are equal), the SM
fault-crossing can be achieved only with the carrier wave correction algorithm.
In addition, if the influence of the different faulty SM numbers τ j − χj is not considered at present,
it can be considered that the fault phase will operate normally according to the newly rated total
number of the inserted SMs of phase Njsum = Njχ . Under the control of sorting algorithm, the SM
capacitor voltage of the fault phase will automatically be average raised and operating stable [16,28].
N − τj
x = Kjc · γ · ( N − τj ) = 2 · (9)
N − χj
Then, according the traditional zero-sequence voltage injection control method [23], the zero
sequence voltage that needed to be injected into the initial modulation wave vj * of each phase can be
obtained by (9):
kjm (t) = −vj ∗ + ( x − 1) (10)
Based on the Figure 6, injecting the zero-sequence voltage kjm (t) in the interval [t1 , t2 ], we can
obtain the final corrected modulation diagram of the faulty phase as shown in Figure 7.
87
Energies 2019, 12, 20
Figure 7. Final modulation diagram of the faulty phase under fault-tolerant control.
In addition, assuming the sampled phase voltage of phase j after the standard is:
vj ∗ = m sin(ωt + ϕj ) (12)
where, ϕj denotes the initial phase angle of the phase voltage. Combining Equations (9) and (11), the
corresponding times t1 and t2 in one modulation period can be calculated respectively:
⎧ N −τj
⎪
⎪
⎨ t = arcsin[(1−2· N −χj )/m]− ϕj
1 ω
N −τj (13)
⎪
⎪ arcsin[(1−2· N −χ )/m]− ϕj
⎩ t = π− j
2 ω
Based on the above analysis, the overall implementation block diagram of the fault-tolerant
control strategy in the MMC system can be obtained as shown in Figure 8.
88
Energies 2019, 12, 20
Therefore, to ensure that the system does not appear over modulation after the SM fault, it is
necessary to ensure that:
√ τj − χj
0 ≤ 1 − 3m − 2 · ≤2 (18)
N − χj
with
√ √
1 − 3m 1 + 3m
max njp_fau , njl_fau ≤ N− χj (19)
2 2
5. Simulation Studies
A three-phase MMC simulation model is built in MATLAB/Simulink simulation software as
shown in Figure 1. The main parameters of the simulation system are shown in Table 1. In the
simulation process, the circulating current suppression strategy is always put into operation when the
grid is connected [29].
Parameters Value
Ac system nominal voltage 10 kV
Ac System inductance Ls 5 mH
Fundamental frequency 50 Hz
Ac system power losses Rs 0.03 Ω
Arm inductance Lm 5 mH
Series arm resistance Rm 0.01 Ω
Dc bus voltage Udc 20 kV
Number of SMs per arm N 20
Number of redundant SMs per arm 5
Sub-module capacitor C 2000 μF
Transformer ratio 1:1 (Y/Δ)
89
Energies 2019, 12, 20
5.1. Case 1
Fault condition 1: Single arm fault to symmetrical arm fault. When the system operates to t = 0.4 s,
five SMs in the upper arm of phase a occur fault; at t = 0.5 s, the fault-tolerant control strategy is
enabled; at t = 0.9 s, five SMs in the lower arm of phase a are failed again. Figure 9 is the related
simulation results.
Figure 9. Simulation results of fault condition 1: (a) Capacitor voltage of phase a; (b) Capacitor voltage
of phase b; (c) Capacitor voltage of phase c; (d) Arm current of phase j (j = a,b,c); (e) Circulating current
of phase j (j = a,b,c); (f) AC current; (g) DC-link current.
From Figure 9a–g, it can be seen that: (1) When the system is in normal operation, the voltage
and current of the system are stable. (2) When the SMs fail at t = 0.4 s, the SM capacitor voltage of
each phase begins to oscillate irregularly, the arm current and AC grid-connected current show an
asymmetric state, and the DC current and circulating current of the system also appear relatively
fluctuant. (3) When fault-tolerant control strategy is enabled at t = 0.5 s, the system SM voltage
immediately starts to return to normal value, the fluctuation of circulating current and DC current
is obviously suppressed, and the arm current and AC grid-connected current are quickly restored to
symmetry and stable operation. (4) When the SMs occur fault again at t = 0.9 s, through the control of
90
Energies 2019, 12, 20
the increasing carrier wave amplitude, the SM voltage of fault phase is in the boost operation (up to
about 1.3 kV) and the SM voltage of the non-fault phase continues to maintain the stable operation of
the original rated value (1.0 kV), and all the current can continue to maintain stable operation through
rapid transient regulation.
The above results show that the proposed fault-tolerant control strategy can quickly realize
fault-tolerant operation after the SM fault, and can respond quickly when the single arm SM fault
transforms to symmetrical fault.
5.2. Case 2
Fault condition 2: Single arm fault to arm asymmetric fault. When the system operates to t = 0.4
s, five SMs in the upper arm of phase a occur fault; at t = 0.5 s, the fault-tolerant control strategy is
enabled; at t = 0.9 s, three SMs in the lower arm of phase a are failed again. Figures 10 and A1 are the
related simulation results.
Figure 10. Simulation results of fault condition 2: (a) Capacitor voltage of phase a; (b) Capacitor voltage
of phase b; (c) Capacitor voltage of phase c; (d) Arm current of phase a; (e) Circulating current of phase
a; (f) AC current; (g) DC-link current.
It can be seen that: (1) Since the operation conditions of the system before t = 0.9 s are the same as
the fault condition 1, the simulation of the system in 0~0.9 s is basically the same as the fault condition
1. (2) When the SMs occur fault again at t = 0.9 s, the system is operating asymmetrically in the
upper and lower arms. The SM voltage of the fault phase is increased to about 1.2 kV by increasing
carrier wave amplitude, while the SM voltage of the non-fault phase keeps the stable operation with
the original rated value, and all the current can continue to maintain stable operation through rapid
transient regulation.
Because the χa (the smaller number of faulty SMs of phase a) is smaller than the fault condition 1,
the boosting amplitude of SM voltage of the fault phase is smaller than the fault condition 1, and the
impact of the AC and DC current of the system is relatively small at t = 0.9 s. The above results also
show that the proposed fault-tolerant control strategy can effectively achieve fault-tolerant operation
after the SM fault, and can also respond quickly when the single arm fault transforms to the asymmetric
arm fault.
91
Energies 2019, 12, 20
5.3. Case 3
Fault condition 3: Arm symmetrical fault to arm asymmetric fault. When the system operates to
t = 0.4 s, three SMs in the upper arm and lower arm of phase occur fault simultaneously; at t = 0.5 s,
the fault-tolerant control strategy is enabled; at t = 0.9 s, two SMs in the upper arm of phase a are failed
again. Figures 11 and A2 are the related simulation results.
Figure 11. Simulation results of fault condition 3: (a) Capacitor voltage of phase a; (b) Capacitor voltage
of phase b; (c) Capacitor voltage of phase c; (d) AC current; (e) DC-link current.
It can be seen that: (1) When the system is in normal operation, the voltage and current of the
system are stable. (2) When the SMs fail at t = 0.4 s, the capacitor voltage of each phase SM begins to
oscillate irregularly, the arm current and AC grid-connected current show an asymmetric state. But
at this time, the arm structure is still in symmetrical state and the number of faulty SMs is smaller
than fault conditions 1 and 2, so the oscillation amplitude of voltage and current is slight compared
with the fault conditions 1 and 2. (3) When fault-tolerant control strategy is enabled at t = 0.5 s, the
SM voltage of the fault phase is increased to about 1.2 kV, while the SM voltage of the non-fault phase
keeps the stable operation with the original rated value, and all the current can continue to maintain
stable operation rapidly. (4) When the SMs occur fault again at t = 0.9 s, through the control of the
limiting modulation wave amplitude, the system can continue to operate stably.
Based on the simulation results of fault conditions 1–3, it can be seen that the fault-tolerant control
strategy of the SM proposed in this paper can effectively realize the fault-tolerant operation control of
the system after the SM fault, and can respond flexibly to different fault conditions of the arm, and can
respond quickly when the fault state of the arm changes.
6. Experimental Studies
In order to verify the fault-tolerant control strategy, a 2-terminal MMC-based experimental
platform is built in the laboratory. The experimental platform is shown in Figure 12. Among them,
MMC1 is the DC voltage source and MMC2 is to verify the control strategy. The basic parameters of
MMC prototype are shown in Table 2.
92
Energies 2019, 12, 20
In the course of the experiment, the SM1 in the upper arm of phase a occurs fault at t1,
fault-tolerant control strategy is enabled at t2 and the SM4 in the lower arm of phase a occurs fault
again at t3. Figure 13 shows the relevant experimental waveform.
Figure 12. The photograph of MMC experiment prototype.
Table 2. Experimental parameters of the MMC prototype.
Parameters Value
AC System inductance Ls 5 mH
Arm inductance Lm 5 mH
DC bus voltage Udc 20 kV
Number of SMs per arm N 4
Number of redundant SMs per arm 1
Sub-module capacitor C 2000 μF
Transformer ratio 380 V/380 V (Y/Δ)
Figure 13. Waveforms of experiment: (a) Capacitor voltage of phase a; (b) Capacitor voltage of phase
b; (c) Circulating current of phase a; (d) Circulating current of phase b; (e) AC current and DC current
from t1 to t3; (f) AC current and DC current after t3.
93
Energies 2019, 12, 20
It can be seen from Figure 13 that: (1) Before the fault, the system operates steadily. When the
SM1 fails at t1, the capacitor voltage of SM1 begins to oscillate irregularly, the arm current and AC
grid-connected current show an asymmetric state, and the DC current and circulating current of the
system also appear relatively fluctuant. (2) When the fault-tolerant control strategy is put into operation
at t2, SM1 voltage starts to return to normal value and the arm current and AC grid-connected current
are restored to symmetry and stable operation. (3) When the SM4 occurs fault again at t3, the SM4
voltage of the fault phase is increased to 80 V, while the SM voltage of the non-fault phase keeps the
stable operation with the original rated value (60 V). There is no major impact on the system in the
process, and the system current is still in a stable state.
Limited by the number of SMs of the experimental platform, the experiment only validates the
fault condition 1, but the experimental results are basically consistent with the simulation. The results
of simulation and experiment show that the design of fault-tolerant control strategy proposed in this
paper is reasonable and effective, and it is helpful to realize fault-crossing of SMs under different
operating conditions.
7. Conclusions
The fault-tolerant operation issue of MMC under SM faults is studied in this paper. The main
works and contributions can be summarized as:
(1) The traditional zero-sequence voltage injection fault-tolerant control algorithm is analyzed
detailed. It reveals that the traditional method is easy to implement under the signal arm
faulty state. However, if the SM simultaneously occurring faults in the upper and lower arms or
appearing multiple arm failures, the required zero-sequence voltages will be calculated difficult.
The SM fault-crossing is complicated to realize.
(2) A novel fault-tolerant control strategy based on PD-PWM is proposed, which has three main
benefits: (i) it has carrier and modulation wave dual correction mechanism, which control ability
is more higher and flexible; (ii) it only needs to inject zero-sequence voltage in half a cycle of the
modulation wave, which simplifies the complexity of traditional zero-sequence voltage injection
control algorithms and much easier for implement; (iii) furthermore, the zero-sequence voltage
can even be avoided injecting under the symmetrical fault conditions.
(3) The simulations in the MATLAB/SIMULINK and experiments with 2-terminal a MMC-based
prototype are all studied with the proposed control strategy under different fault conditions.
The results confirm the efficiency of the control strategy.
Author Contributions: Conceptualization, W.W., T.W. and Q.H.; Formal analysis, J.Y.; Writing—original draft,
J.Y.; Writing—review & editing, J.Y.
Acknowledgments: This research work was supported by National Key R&D Program of China
(2016YFB0900900), National Natural Science Foundation of China (51607171), Chinese Academy of Sciences
Youth Innovation Association (2017180).
Conflicts of Interest: The authors declare no conflict of interest.
94
Energies 2019, 12, 20
Appendix A
Figure A1. Simulation results of fault condition 2: (a) Arm current of phase b; (b) Arm current of phase
c; (c) Circulating current of phase b; (d) Circulating current of phase c.
Figure A2. Simulation results of fault condition 3: (a) Arm current of phase j (j = a,b,c); (b) Circulating
current of phase j (j = a,b,c).
References
1. Popova, L.; Pyrhonen, J.; Ma, K.; Blaabjerg, F. Device loading of modular multilevel converter MMC in wind
power application. In Proceedings of the 2014 International Power Electronics Conference (IPEC-Hiroshima
2014—ECCE-ASIA), Hiroshima, Japan, 18–21 May 2014; pp. 548–554.
2. Gowaid, I.A.; Adam, G.P.; Ahmed, S.; Holliday, D.; Williams, B.W. Analysis and design of a modular
multilevel converter with trapezoidal modulation for medium and high voltage DC-DC transformers.
IEEE Trans. Power Electron. 2015, 30, 5439–5457. [CrossRef]
3. Perez, M.A.; Bernet, S.; Rodriguez, J.; Kouro, S.; Lizana, R. Circuit topologies, modeling, control schemes,
and applications of modular multilevel converters. IEEE Trans. Power Electron. 2018, 30, 4–17. [CrossRef]
4. Nami, A.; Liang, J.; Dijkhuizen, F.; Demetriades, G. Modular multilevel converters for HVDC applications:
Review on converter cells and functionalities. IEEE Trans. Power Electron. 2015, 30, 18–36. [CrossRef]
5. Lesnicar, A.; Marquardt, R. An innovative modular multilevel converter topology suitable for a wide
power range. In Proceedings of the IEEE Bologna Power Tech Conference Proceedings, Bologna, Italy,
23–26 June 2003; pp. 23–26.
6. Debnath, S.; Saeedifard, M. Simulation-based gradient-descent optimization of modular multilevel converter
controller parameters. IEEE Trans Ind. Electron. 2016, 63, 102–112. [CrossRef]
7. Li, Y.; Jiang, W.; Yu, S.; Zou, X. Design of zhoushan multi-terminal VSC-HVDC transmission project.
High Voltage Eng. 2014, 40, 2490–2496.
8. Wu, W.; Wu, X.; Yin, J.; Jing, L.; Wang, S.; Li, J. Characteristic analysis and fault-tolerant control of circulating
current for modular multilevel converters under SM faults. Energies 2017, 10, 1827. [CrossRef]
95
Energies 2019, 12, 20
9. Abdelsalam, M.; Tennakoon, S.; Griffiths, A.L.; Marei, M. Investigation of sub-module fault types of
modular multi-level converters in HVDC networks. In Proceedings of the International Universities Power
Engineering Conference (UPEC), Stoke, UK, 1–4 September 2015; pp. 1–6.
10. Jiang, W.; Wang, C.; Wang, M. Fault detection and remedy of multilevel inverter based on BP neural network.
In Proceedings of the Asia-Pacific Power and Energy Engineering Conference (APPEEC), Shanghai, China,
27–29 March 2012; pp. 1–4.
11. Moon, J.W.; Kim, C.S.; Park, J.W. Circulating current control in MMC under the unbalanced voltage.
IEEE Trans. Power Deliv. 2013, 28, 1952–1959. [CrossRef]
12. Son, G.; Lee, H.J.; Nam, T. Design and control of a modular multilevel HVDC converter with redundant
power modules for noninterruptible energy transfer. IEEE Trans. Power Deliv. 2012, 27, 1611–1619.
13. Konstantinou, G.; Pou, J.; Ceballos, S. Active redundant sub-module configuration in modular multilevel
converters. IEEE Trans. Power Deliv. 2013, 28, 2333–2341. [CrossRef]
14. Liu, G.; Xu, Z.; Xue, Y. Optimized control strategy based on dynamic redundancy for the modular multilevel
converter. IEEE Trans. Power Electron. 2015, 30, 339–348. [CrossRef]
15. Li, S.; Wang, Z.; Wang, G. Fluctuation volt age control and fault-tolerant operation of modular multilevel
converters with zero-sequence injection. Int. Trans. Electr. Energy Syst. 2014, 24, 944–959. [CrossRef]
16. Hu, P.; Jiang, D.; Zhou, Y. Energy-balancing control strategy for modular multilevel converters under
submodule Fault Conditions. IEEE Trans. Power Electron. 2014, 29, 5021–5029. [CrossRef]
17. Peter, W. Enhancing the reliability of modular medium-voltage drives. IEEE Trans Ind. Electron. 2002, 49,
948–954.
18. Jose, R.; Peter, W.; Jorge, P.; Rodrigo, M.; Maria, J. Operation of a medium-voltage drive under faulty
conditions. IEEE Trans Ind. Electron. 2005, 52, 1080–1085.
19. Pablo, L.; Gabriel, O. Extended operation of cascade multicell converters under fault condition. IEEE Trans
Ind. Electron. 2009, 56, 2697–2703.
20. Fernanda, C.; Humberto, P.; Cassiano, R. Generalized carrier-based modulation strategy for cascaded
multilevel converters operating under fault conditions. IEEE Trans. Ind. Electron. 2012, 59, 679–689.
21. Yang, Q.; Qin, J. A post-fault strategy to control the modular multilevel converter under submodule failure.
IEEE Trans. Power Deliv. 2012, 27, 1538–1547.
22. Shen, K.; Xiao, B.; Mei, J. A modulation reconfiguration based fault-tolerant control scheme for modular
multilevel converters. In Proceedings of the IEEE Applied Power Electronics Conference and Exposition
(APEC), Long Beach, CA, USA, 17–31 March 2013; pp. 3251–3255.
23. Yang, W.; Song, Q.; Xu, S.; Rao, H.; Liu, W. An MMC topology Based on unidirectional current H-bridge
submodule with active circulating current injection. IEEE Trans. Power Electron. 2018, 33, 3870–3883. [CrossRef]
24. Ning, L.; Venkata, D. Dynamic electro-magnetic-thermal modeling of MMC-based DC–DC converter for
real-time simulation of MTDC grid. IEEE Trans. Power Deliv. 2018, 33, 1337–1347.
25. Xu, J.; Penghao, Z.; Zhao, C. Reliability analysis and redundancy configuration of MMC with hybrid
submodule topologies. IEEE Trans. Power Electron. 2016, 31, 2720–2729. [CrossRef]
26. Lu, C. Research on the Control Strategy of Modular Multilevel Converter; China University of Ming and Technology:
Beijing, China, 2014.
27. Wang, D.; Yang, J.; Chen, Z.; Mao, C.; Lu, J. A Transformerless medium voltage multiphase motor drive
system. Energies 2016, 9, 323. [CrossRef]
28. Meshram, P.M.; Borghate, V.B. A Novel Voltage Balancing Method of Modular Multilevel Converter (MMC).
In Proceedings of the International Conference on Energy, Automation and Signal, Bhubaneswar, Odisha,
India, 28–30 December 2011; pp. 1–5.
29. Li, J.; Jin, X.; Wu, X. Analysis of Fault Circulating current without redundant SM and its suppression strategy.
Power Syst. Technol. 2016, 40, 32–39.
© 2018 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access
article distributed under the terms and conditions of the Creative Commons Attribution
(CC BY) license (http://creativecommons.org/licenses/by/4.0/).
96
energies
Article
A Novel Multilevel Bidirectional Topology for
On-Board EV Battery Chargers in Smart Grids
Rafael S. Leite, João L. Afonso and Vítor Monteiro *
Industrial Electronics Department, School of Engineering, University of Minho, 4800-058 Guimarães, Portugal;
[email protected] (R.S.L.); [email protected] (J.L.A.)
* Correspondence: [email protected]; Tel.: +351-253-510-392
Abstract: This paper proposes a novel on-board electric vehicle (EV) battery charger (EVBC)
based on a bidirectional multilevel topology. The proposed topology is formed by an AC-DC
converter for the grid-side interface and by a DC-DC converter for the battery-side interface.
Both converters are interfaced by a split DC-link used to achieve distinct voltage levels in both
converters. Characteristically, the proposed EVBC operates with sinusoidal grid-side current,
unitary power factor, controlled battery-side current or voltage, and controlled DC-link voltages.
The grid-side converter operates with five voltage levels, while the battery-side operates with
three voltage levels. An assessment, for comparison with classical multilevel converters for EVBCs
is considered along the paper, illustrating the key benefits of the proposed topology. As the
proposed EVBC is controlled in bidirectional mode, targeting the EV incorporation into smart grids,
the grid-to-vehicle (G2V) and vehicle-to-grid (V2G) operation modes are discussed and evaluated.
Both converters of the proposed EVBC use discrete-time predictive control algorithms, which are
described in the paper. An experimental validation was performed under real operating conditions,
employing a developed laboratory prototype.
Keywords: multilevel converter; electric vehicle; on-board battery charger; power factor correction;
power quality; smart grid
1. Introduction
The electric vehicle (EV) is considered as the central element to support electric mobility in
smart grids, serving to help to address major energy concerns. From a global perspective, different
options of EVs can be considered distinguished by the energy storage system, as battery EVs (BEVs)
or fuel cell EVs (FCEVs), and by the external interface for the charging process, as plug-in EVs
(PHEV) [1–3]. Within the scope of this paper, the final application is for EVs using batteries as the energy
storage system, where the main advantage is the capacity of the energy storage system and the main
drawback is the required charging time. The relevance of the EV for this purpose is carefully addressed
and evaluated in [4–6] in terms of power electronics and control methodologies for the grid-side.
As demonstrated in [7,8], since the EV batteries are charged from the power grid (independently
of the on-board or off-board technology), power quality is an imperative feature for assuring the
grid stability. In this perspective, advanced contributions for the EV controlled action in smart grids,
and bearing in mind power quality issues, are presented in [9]. Additionally, the opportunity to
operate in bidirectional mode, as well as to operate in the four quadrants in terms of power quality
will also be decisive for contributing to establish energy management strategies in a smart grid
perspective. These new contributions for the EV operation in four-quadrants and framed in smart
grids, are examined in [10,11]. The flexible incorporation of an EV into the energy management of
a smart home is presented in [12], perspective an advanced communication toward to control the
charging and discharging processes.
Classically, on-board EV battery chargers (EVBC) are projected with two- or three-level topologies
for the grid-side coupling converter [13], however, by increasing the levels, the size of the passive
filters can be reduced, as demonstrated in [14,15] for other types of applications, different from EVBC.
Nonetheless, the levels cannot be augmented indeterminately. By establishing a tradeoff between
power density and required hardware and software, five-level topologies are identified as interesting
solutions for different purposes. For instance, considering the grid-side converter, a five-level topology
with reduced switching devices and based on the active neutral point clamped in presented in [16]
for grid-tied solar photovoltaic applications; a five-level Vienna-type structure is proposed in [17]
for active rectifiers; a unidirectional five-level based on the T-rectifier topology is analyzed in [18]
for high-speed gen-set applications; an improved five-level topology is presented in [19] for active
rectifiers or grid-tied applications; a unidirectional five-level topology is proposed in [20] for power
factor correction converters, including applications of EVBC; a symmetric cascade five-level topology
is proposed in [21] for grid-tied inverters; based on the previous structure, a bidirectional five-level
topology is proposed in [19], allowing the operation as active converter or as grid-tied converter;
a modular unidirectional five-level topology is offered in [22] for applications of renewable energy
sources; a five-level topology for renewables applications is proposed in [23]; a five-level topology
based on the neutral point clamped arrangement is presented in [24] for motor drivers; a novel
five-level topology is proposed in [25] for unidirectional EVBC; and a five-level topology with reduced
switching devices is proposed in [20] for active rectifier applications.
In terms of the battery-side converter, two-level topologies are usually employed for the
battery-side coupling converter. However, it should be noted that DC-DC multi-level topologies
can be applied for other applications, for instance, in [26] is presented a novel multilevel boost
converter for applications of photovoltaics or fuel cell generation systems, in [27] a review of DC-DC
four- and three-level topologies is presented, and in [28] a two-level interleaved and intercoupled
boost converter for high power applications is analyzed. The three-level topology is presented in [29],
however, the application is for the voltage balancing of series connected batteries. On the other hand,
in this paper, the split DC-link is used as interface for the grid-side converter, where the voltage of
the capacitors is always controlled by the grid-side power converter. Moreover, the control algorithm
is completely different, in order to obtain a reduced current ripple, where the proposed approach
consists in using the converter controlled by current controlling only two switching devices during
each operation mode. It should be noted that in [29] are controlled four switching devices, therefore,
controlling only two it is possible to reduce the switching losses and the control complexity (e.g., it is
not necessary to deal with any type of dead-time for the switching devices).
The above-mentioned five-level topologies for the grid-side converter were validated in the scope
of diverse applications, but not all were validated neither compared in the scope of an EVBC. The same
occurs with the battery-side converter. Moreover, no EVBC was validated employing multilevel
topologies in the grid-side and the battery-side converters. In this sense, this paper proposes an
on-board EVBC multilevel topology. The internal constitution of a conventional on-board EVBC is
presented in Figure 1, where is highlighted the bidirectional power flow, between the batteries and
the grid, in order to accomplish with the grid-to-vehicle and vehicle-to-grid operations in smart grids.
The key contributions of this paper are: (a) a novel EVBC based on a multilevel topology; (b) an analysis
of the proposed EVBC in terms of operation targeting smart grids; and (c) an experimental validation
using a dedicated developed on-board EVBC.
The paper is outlined as follows: A description of the hardware topology of the proposed EVBC is
presented in Section 2. The discrete-time predictive control algorithms used for the grid-side converter
and for the battery-side converter are presented in Section 3. The foremost experimental results
considering diverse operating states for smart grids are presented in Section 4. The main conclusions
are discussed in Section 5.
98
Energies 2018, 11, 3453
ŽŶͲďŽĂƌĚsďĂƚƚĞƌLJĐŚĂƌŐĞƌ
;ŝŶƚĞƌŶĂůĐŽŶƐƚŝƚƵƚŝŽŶͿ
ŽŶƚƌŽůůŐŽƌŝƚŚŵƐ
ŝŐŝƚĂůĐŽŶƚƌŽůƐLJƐƚĞŵŽĨƚŚĞ
ĐŽŶǀĞƌƚĞƌƐĨŽƌƚŚĞŐƌŝĚŝŶƚĞƌĨĂĐĞĂŶĚ
ĨŽƌƚŚĞďĂƚƚĞƌLJŝŶƚĞƌĨĂĐĞ͘
Figure 1. Internal constitution of a conventional on-board electric vehicle battery charger (EVBC).
vL3
L3
S9
ibat
vL1 S1 S3 S5 S7 C1 vdc vcv_DC1
iev S11
L1 2
C3
vg vcv_AC vbat
L2
C2 vdc S12 vcv_DC2
vL2 S 2
2 S4 S6 S8 S10
L4
vL4
ĂĐͲĚĐŐƌŝĚͲƐŝĚĞĐŽŶǀĞƌƚĞƌ ĚĐͲĚĐďĂƚƚĞƌLJͲƐŝĚĞĐŽŶǀĞƌƚĞƌ
Figure 2. Topology of the proposed on-board electric vehicle battery charger (EVBC).
The values of the parameters constituting the on-board EVBC, as well as the specifications of the
system that was taken into account when choosing components, are given in Table 1.
99
Energies 2018, 11, 3453
100
Energies 2018, 11, 3453
Figure 3. Operation stages for the grid-side converter during the operation as active rectifier: (a) vcv_AC
= 0; (b) vcv_AC = +vdc /2; (c) vcv_AC = +vdc ; (d) vcv_AC = 0; (e) vcv_AC = −vdc /2; (f) vcv_AC = −vdc .
Figure 4. Operation stages for the grid-side converter during the operation as grid-tied inverter:
(a) vcv_AC = 0; (b) vcv_AC = +vdc /2; (c) vcv_AC = +vdc ; (d) vcv_AC = 0; (e) vcv_AC = −vdc /2; (f) vcv_AC = −vdc .
A predictive current control technique, with a fixed switching frequency of 20 kHz, was applied
to obtain a sinusoidal EVBC current and in phase with the grid voltage (or phase opposition in
vehicle-to-grid mode). Since this current control is identified as a linear current control, the modulation
technique is applied individually. In this sense, Figure 5 shows the pulse-width modulation (PWM)
modulation technique arrangement used for the grid-side converter. The proposed PWM modulation
technique requires only one carrier signal and two reference signals to control eight IGBTs. This figure
shows the adapted voltage reference (ref 1 , ref 2 ), the triangular carrier signal (vcarrier ), the PWM signals
of the IGBTs, the voltage levels produced by the converter (vcv_AC ) and the power grid voltage (vg ).
The pulses signal of the IGBTs (S1 , S2 , S3 , S4 ) are exclusively dependent of the instantaneous value of
the power grid voltage. During the operation as grid-tied inverter, the IGBTs (S7 , S8 ) have an opposite a
command signal as the IGBTs (S5 , S6 ), respectively. In the modulation strategy, the voltages references
(ref 1 , ref 2 ) are adapted, based on a digital codification, from the modulating signal sM established by
the Equation (1), where vcv_AC are the voltage levels produced by the converter and ma the amplitude
modulation index. The voltage levels produced by the converter are obtained in the control algorithm,
explained in Section 3.1.
s M = 2vcv_AC m a . (1)
101
Energies 2018, 11, 3453
# "
# !
'
!
( )
- .
*+ *,
Figure 5. Modified pulse-width modulation (PWM) strategy for the grid-side converter during the
operation as active rectifier or as grid-tied inverter.
102
Energies 2018, 11, 3453
Figure 6. Operation stages for the battery-side converter during the operation as a buck-type converter:
(a) The stored energy in L3 , L4 is released to the batteries; (b) L3 , L4 and the batteries stores energy from
C1 ; (c) L3 , L4 and the batteries stores energy from C2 ; (d) L3 , L4 and the batteries store energy from C1 , C2 .
Figure 7. Operation stages for the battery-side converter during the operation as a boost-type converter:
(a) L3 , L4 stores energy from the batteries; (b) C2 stores energy from the batteries and L3 , L4 ; (c) C1
stores energy from the batteries and L3 , L4 ; (d) C1 , C2 stores energy from the batteries and L3 , L4 .
Similar to the algorithm applied in the grid-side converter, in the battery-side converter was also
applied a predictive current control technique and a modulation technique with a fixed switching
frequency of 20 kHz, to control the current and voltage in the batteries during the charging or
discharging processes. In the modulation technique, two 180◦ phase-shifted carriers were used,
in order to reduce the ripple of the EV battery current and, hence, the frequency EV battery current is
held twice of the switching frequency.
103
Energies 2018, 11, 3453
v g = vcv_AC + v L1 + v L2 . (2)
It should be noted that, as represented in Figure 2, it was used a mutual coupling inductance.
Therefore, replacing the inductance voltage by its intrinsic equation, and rewriting the equation as
a function of the voltage produced by the converter, it is obtained:
diev diev
vcv_AC = v g − L1 − L2 . (3)
dt dt
Applying the progressive Euler method, illustrated in Equation (4), the derivative component of
the current can be approximated by considering a very low Δt in order to obtain a good prediction of
the system behavior:
diev (t) iev (t + Δt) − iev (t)
= . (4)
dt Δt
Applying the Equation (4) in the Equation (3), and assuming a sampling frequency of fs = 1/Ts ,
results in the digital control Equation (5), where the term k represents the current sample and [k + 1]
represents the next sample:
iev [k + 1] − iev [k ]
vcv_AC [k] = v g [k ] − ( L1 + L2 ) . (5)
Ts
Since the law of predictive control consists of a closed-loop control and, if the reference current
at time [k + 1] is to be equal to the current produced by the converter at time [k], the equation that
translates the current control implemented can be defined by:
Since, the EVBC is proposed to operate with a sinusoidal current and unitary power factor in the
grid-side converter, the instantaneous value of the power grid voltage is directly proportional to the
EVBC current. However, aiming to prevent the inclusion of the harmonic distortion of the grid voltage
into the current, it is used a phase-locked loop (PLL). Thus, instead of the grid voltage, it is used the
output signal from the PLL, resulting in:
where vpll is in phase with the power grid voltage and Gev represents the equivalent conductance of
the EVBC from the grid-side point of view, which can be defined according to the mean value of active
power (Pev ) and the rms value of the power grid voltage (Vg ):
104
Energies 2018, 11, 3453
Applying the Equation (8) in the Equation (7), the reference of the EVBC current is obtained
according to:
iev ∗ = Pev VG −2 v pll . (9)
The active power of the EVBC can be divided in two parts, namely the power to regulate the
DC-link voltage and the power to regulate the batteries. Furthermore, because of the split DC-link,
two proportional-integral (PI) are used to regulate the DC-link voltage independently in both capacitors
(pdc1 , pdc2 ). Therefore, during the G2V operation mode, the reference of the EVBC current can be
defined as:
iev ∗ = ( pdc1 + pdc1 + pbat )v pll VG −2 . (10)
On the other hand, during the V2G operation mode, the reference of the EVBC current is
established according to Equation (11), where ibat * represent the reference of current to discharge
the batteries.
iev ∗ = ( pdc1 + pdc1 + ibat ∗ vbat )v pll VG −2 . (11)
Since the current in the inductance L3 is the same as that in the inductance L4 , the Equation (12)
can be rewritten, replacing the voltage in the inductance by its intrinsic equation:
di L3,L4
vcv_DC = vbat + ( L3 + L4 ) . (13)
dt
Applying the progressive Euler method, the Equation (13) can be established in discrete time as:
Since it is desired that the reference current at time [k + 1] should be equal to the current produced
by the converter at time [k], it is obtained:
When the same converter operates as buck converter, but controlling the charging voltage of the
batteries, the reference voltage is established as:
The aforementioned equations were defined for the battery-side converter operating as buck
converter, i.e., charging the batteries from the grid (G2V mode). On the other hand, a set of equations
should also be defined for the battery-side converter operating as boost converter, i.e., discharging the
batteries to the grid (V2G mode). Based on the representations of the currents and voltages in Figure 2,
105
Energies 2018, 11, 3453
when the converter intends to discharge the batteries with a constant current, the following relation
can be established:
vcv_DC = vbat − v L3 − v L4 . (17)
From Equation (18), it is important to note that it is necessary to identify the positive direction
of the current in the batteries (Figure 2), which is why the negative signal −iL3,L4 *[k + 1] is applied
to the digital implementation of this equation. The obtained signal (vcv_DC [k]) is compared with two
carriers in order to obtain the duty-cycle of the gate signals for S9 and S10 , which is the same, but two
carriers, delayed by 180 degrees, are employed. Applying this strategy, the frequency of the resultant
ripple is the double of the switching frequency. The duty-cycle is determined according to the current
control algorithm, e.g., in the previous equations is defined the a voltage that is compared with the
carriers in order to obtain a current in the EV battery i(L3,L4) [k] equal to the reference current i(L3,L4) *[k].
Applying this strategy, the current ripple in the EV battery can be reduced when compared with
a traditional buck or boost converter. In circumstances where the battery-side converter is responsible
for controlling the voltage on the DC-link, the Equation (19) is implemented, where δcv_DC represents
the duty-cycle that the converter must produce, vdc * represents the reference voltage for the DC-link,
and vbat represents the battery voltage:
vdc ∗ [k ] − vbat [k ]
δcv_DC [k ] = . (19)
vdc ∗ [k ]
106
Energies 2018, 11, 3453
The converters of the developed prototype were sized to meet the key requirements of the
proposed on-board EVBC in terms of power quality, and the specifications given in Table 1. In this
sense, the choice of components was mainly based on their operational characteristics, such as the
maximum operating frequency and the rated current and voltage. In addition to the electrical aspects
of the concerned application, mechanical and thermal aspects, such as dimensions, encapsulation
and thermal dissipation of components, have also been taken into account, since the entire system
is integrated in a metal box (Bernstein CA 380 (Porta Westfalica, Germany)), with dimensions of
330 × 230 × 110 mm. As it can be seen, two heatsinks were used, one for each converter, which were
fixed on each side of the metal box. In order to prevent electrical noise, it was decided to place
the gate driver boards as close as possible to the power semiconductors, each one responsible for
a power electronics converter. In the control system, electrical noise was also taken into account in
order to optimize the signal-to-noise ratio, i.e., to minimize undesired signals superimposed on a
measured signal. Based on the developed three-dimensional modeling and the implemented prototype,
an estimation of the internal volume distribution associated to the different main parts of the on-board
EVBC was established, which is presented in Figure 10.
107
Energies 2018, 11, 3453
Figure 11. Laboratory setup used to obtain the experimental results.
108
Energies 2018, 11, 3453
Figure 12. Experimental results during the initial stage of the electric vehicle (EV) battery charging
process: EV battery current (ibat : 1 A/div); DC-link voltages of both capacitors (vdc1 : 20 V/div, vdc2 : 20
V/div); EVBC current (iev : 2 A/div).
Figure 13. Experimental results in grid-to-vehicle (G2V) mode showing the EVBC current (iev : 5 A/div),
the grid voltage (vg : 100 V/div), a detail of zero crossing between the current and the voltage (iev , vg ),
and the DC-link voltages ripple in both capacitors (Δvdc1 : 5 V/div, Δvdc2 : 5 V/div).
The PWM technique developed for the battery-side converter consists in two carriers with a 180◦
phase-shifting. With this phase-shifting strategy, one of the gate signals is applied to IGBT S9 while the
other is applied to the IGBT S10 , to reduce the ripple of the EV battery current. Thus, as it can be seen
in Figure 15, the frequency of the current ripple in the inductor L3 (iL3 ) is 40 kHz, which is twice of the
switching frequency. This experimental result shows the relation of the current in the inductor and
the gate-emitter voltage, vge_S9 and vge_S10 , of the IGTBs S9 and S10 . During this result, the registered
value of the ripple current in the inductor was 0.16 A.
109
Energies 2018, 11, 3453
Figure 14. Experimental results during the G2V operation mode: Gate-emitter voltage of the grid-side
insulated-gate bipolar transistors (IGBTs) (S1 , S2 , S3 , S4 , S5, S6 : 5 V/div); Output digital signal of the
phase-locked loop (PLL) (vPLL : 150 V/div).
Figure 15. Experimental results showing the current in the inductor L3 (iL3 : 0.1 A/div) and the
gate-emitter voltage of the IGBTs S9 and S10 (vge_s9 : 5 V/div and vge_10 : 5 V/div) during a time interval
of 100 μs.
For further details on the relationship between the grid voltage and the EVBC grid-side current,
it was used the x-y mode of the oscilloscope, as shown in Figure 16. Channel 4 is used in the x-axis
and the channel 2 is used in the y-axis, representing the grid voltage and EVBC grid-side current,
respectively. Thus, for the grid-side, this result shows the EVBC current in function of the grid voltage.
It is relevant to highlight that this variation is not linear due to the harmonic distortion present in the
grid voltage.
The experimental result shown in Figure 17 was obtained in x-y mode in order to identify the
DC-link voltage regulation and to clearly identify the five distinct voltage levels (+vdc , +vdc/2 , 0, −vdc/2 ,
−vdc ) produced by the grid-side converter. Thus, the DC-link voltage ripple (Δvdc1 , Δvdc2 ) and the
voltage levels (vcv_AC ), used in the y-axis, are a function of the grid voltage (vg ), used in the x-axis.
In order to keep the DC-link regulated and balanced, during the positive half-cycle of the grid voltage,
the voltage of the capacitor C1 is regulated, and during the negative half-cycle of the grid voltage,
the voltage of the capacitor C2 is regulated.
110
Energies 2018, 11, 3453
Figure 16. Experimental results in x-y mode showing the EVBC current (iev : 5 A/div) in function of the
power grid voltage (vg : 100 V/div).
Figure 17. Experimental results in x-y mode showing the DC-link voltage ripple (Δvdc1 : 5 V/div, Δvdc2 :
5 V/div) (y-axis) and the voltage levels produced by the grid-side converter (vcv_AC : 50 V/div) (y-axis),
both in function of the power grid voltage (vg : 100 V/div) (x-axis).
Using the Fluke power quality analyzer, in Figure 18a,b shows the harmonic spectrum of the
power grid voltage and the EVBC current, measured total harmonic distortion (THD%) of 3.5% and
2.8%, respectively. In power electronics systems, the thermal characteristic is a factor that directly
affects the performance of it. So, to analyse the thermal conditions of the EVBC, the experimental
results of temperature measurements during the G2V operation mode are presented in Figure 19.
Figure 19a shows the overall thermal distribution of the implemented EVBC, Figure 19b shows the
measured temperature of IGBT S9 (switched at a fixed frequency of 20 kHz), where was registered a
temperature value of 47.8 ◦ C, and Figure 19c shows the measured temperature of the IGBT S11 (only the
antiparallel diode is used in this context), where was registered a temperature value of 36.8 ◦ C.
111
Energies 2018, 11, 3453
Figure 18. Experimental results in G2V mode of the total harmonic distortion and spectral analysis:
(a) power grid voltage (vg ); and (b) EVBC current (iev ).
Figure 19. Experimental results of the temperature measurements during G2V operation mode:
(a) overall thermal distribution of the developed EVBC prototype; (b) temperature at the IGBT S9 ;
and (c) temperature at the IGBT S11 .
112
Energies 2018, 11, 3453
Figure 20. Experimental results showing the modulation technique applied to the IGBTs S7 and S8 ,
namely, the reference signals adopted for the modulation (refs7 : 1 V/div, refs8 : 1 V/div) and the voltage
gate-emitter of the respective IGBT (vge_s7 : 5 V/div and vge_s8 : 5 V/div).
Figure 21. Experimental results during vehicle-to-grid (V2G) operation mode: Gate-emitter voltage
of the grid-side IGBTs (S1 , S2 , S3 , S4 , S7 , S8 : 5 V/div), and output digital signal of the PLL (vPLL :
150 V/div).
For further details, Figure 23 presents an experimental result, during a time interval of 50 ms,
of the EVBC grid-side current (iev ), the grid voltage (vg ), and the DC-link voltage ripple in both
capacitors (Δvdc1 , Δvdc2 ). With the detail of the current zero-crossing, it is possible to state that during
these results the EVBC operates with unitary power factor. As aforementioned, during the positive
half-cycle of the power grid voltage, the voltage of the capacitor C1 is regulated and during the negative
half-cycle of the power gird voltage, the voltage of the capacitor C2 is regulated, which are controlled
by the grid-side converter. Moreover, as it can be seen in this figure, the DC-link voltage has a voltage
ripple of 3%.
113
Energies 2018, 11, 3453
Figure 22. Experimental results in V2G operation mode showing the EVBC current (iev : 5 A/div),
the power grid voltage (vg : 50 V/div), the voltage levels produced by the grid-side converter (vcv_AC :
100 V/div) and the DC-link voltage of both capacitors (vdc1 : 20 V/div, vdc2 : 20 V/div).
Figure 23. Experimental results in V2G operation mode showing the EVBC current (iev : 5 A/div),
the grid voltage (vg : 50 V/div), a detail of zero crossing between the current and the voltage (iev , vg ),
and the DC-link voltages ripple in both capacitors (Δvdc1 : 2 V/div, Δvdc2 : 2 V/div).
Regarding the battery-side converter, the same modulation technique implemented in the G2V
operation mode was used, namely the application of two 180◦ phase-shifted carrier signal. This strategy
was adopted to reduce the ripple amplitude of the batteries current. In this sense, Figure 24 shows
the current ripple in the inductor L3 according to the gate-emitter voltages, vge_S11 and vge_S12 , of the
IGBTs S11 , S12 . It is important to note that during this operation mode, the IGBTs S9 and S10 are always
off, reason why they are not shown in the figure. As it can be seen, the measured current ripple
in the inductor L3 was 0.13 A for a frequency of 40 kHz, which is twice of the switching frequency.
According to this result, when the IGBT S9 or the IGBT S10 is on, the inductor stores energy and
during the state transition of one the IGBTs, the inductor releases this energy. Using the power quality
analyzer, in Figure 25a,b, the harmonic spectrum of the power grid voltage and the EVBC current
is shown, measured THD% of 4.2% and 3.5%, respectively. These figures were obtained employing
a Fluke 435 power quality analyzer, and the high value of THD in the power grid voltage is caused by
distorted voltage drop in the line impedance, which is produced by distorted current consumed by
several nonlinear loads connected to the electrical installation.
114
Energies 2018, 11, 3453
Figure 24. Experimental results showing the current in the inductor L3 (iL3 : 0.1 A/div) and the
gate-emitter voltage of the IGBTs S11 and S12 (vge_s11 : 5 V/div and vge_12 : 5 V/div) during a time
interval of 100 μs.
Figure 25. Experimental results in V2G operation mode of the total harmonic distortion and spectral
analysis: (a) Power grid voltage (vg ); and (b) EVBC current (iev ).
5. Conclusions
A novel on-board bidirectional EV battery charger (EVBC) was presented. It is constituted by
a grid-side converter capable to operate with five voltage levels, and by a battery-side converter capable
to operate with three voltage levels. The distinct voltage levels for both converters are obtained using
a split DC-link. In order to ensure power quality features, the proposed EVBC operates with grid-side
current controlled to improve power factor, and to preserve the battery lifetime the EVBC operates
with battery-side controlled current or voltage. Throughout the paper is described the proposed
hardware topology, the discrete-time predictive control algorithms used for the grid-side converter
and for the battery-side converter, the developed full-scale laboratorial prototype of the EVBC, and the
foremost experimental results considering operating modes for smart grids. The obtained results allow
validating the key contributions of the paper, mainly, in terms of the bidirectional operation of the
novel EVBC based on a multilevel topology. As the EVBC is controlled targeting the EV incorporation
into smart grids, the grid-to-vehicle (G2V) and vehicle-to-grid (V2G) operation modes are discussed
and evaluated.
Author Contributions: All authors contributed equally to the conceptualization and writing of the paper.
Funding: This work has been supported by COMPETE: POCI-01-0145-FEDER-007043 and FCT—Fundação
para a Ciência e Tecnologia within the Project Scope: UID/CEC/00319/2013. This work is financed by the
ERDF—European Regional Development Fund through the Operational Programme for Competitiveness and
Internationalisation—COMPETE 2020 Programme, and by National Funds through the Portuguese funding agency,
FCT—Fundação para a Ciência e a Tecnologia, within project SAICTPAC/0004/2015—POCI—01-0145-FEDER-016434.
This work is part of the FCT project 0302836 NORTE-01-0145-FEDER-030283.
115
Energies 2018, 11, 3453
References
1. Idaho National Laboratory. Charging and Driving Behavior of Nissan Leaf Drivers in the EV Project with Access to
Workplace Charging; EV Project; Idaho National Laboratory: Idaho Falls, ID, USA, 2014; pp. 1–4.
2. Matthé, R.; Eberle, U. The Voltec System—Energy Storage and Electric Propulsion. In Lithium-Ion
Batteries—Advances and Applications; Elsevier: Amsterdam, The Netherlands, 2014; pp. 151–176.
3. Robledo, C.B.; Oldenbroek, V.; Abbruzzese, F.; van Wijk, A.J.M. Integrating a hydrogen fuel cell electric
vehicle with vehicle-to-grid technology, photovoltaic power and a residential building. Appl. Energy
2018, 215, 615–629. [CrossRef]
4. Boulanger, A.G.; Chu, A.C.; Maxx, S.; Waltz, D.L. Vehicle Electrification: Status and Issues. Proc. IEEE
2011, 99, 1116–1138. [CrossRef]
5. Rajashekara, K. Present Status and Future Trends in Electric Vehicle Propulsion Technologies. IEEE J. Emerg.
Sel. Top. Power Electron. 2013, 1, 3–10. [CrossRef]
6. Milberg, J.; Schlenker, A. Plug into the Future. IEEE Power Energy Mag. 2011, 9, 56–65. [CrossRef]
7. Monteiro, V.; Ferreira, J.C.; Melendez, A.A.N.; Couto, C.; Afonso, J.L. Experimental Validation of a Novel
Architecture Based on a Dual-Stage Converter for Off-Board Fast Battery Chargers of Electric Vehicles.
IEEE Trans. Veh. Technol. 2018, 67, 1000–1011. [CrossRef]
8. Basu, M.; Gaughan, K.; Coyle, E. Harmonic distortion caused by EV battery chargers in the distribution
systems network and its remedy. In Proceedings of the International Conference UPEC—Universities Power
Engineering Conference, Bristol, UK, 6–8 September 2004; pp. 869–873.
9. Monteiro, V.; Pinto, J.G.; Afonso, J.L. Operation Modes for the Electric Vehicle in Smart Grids and Smart
Homes: Present and Proposed Modes. IEEE Trans. Veh. Technol. 2016, 65, 1007–1020. [CrossRef]
10. Kisacikoglu, M.C.; Ozpineci, B.; Tolbert, L.M. Examination of a PHEV Bidirectional Charger System for V2G
Reactive Power Compensation. In Proceedings of the IEEE APEC Applied Power Electronics Conference
and Exposition, Palm Springs, CA, USA, 21–25 February 2010; pp. 458–465.
11. Monteiro, V.; Ferreira, J.C.; Meléndez, A.A.N.; Afonso, J.L. Electric Vehicles On-Board Battery Charger for
the Future Smart Grids. In Technological Innovation for the Internet of Things, 1st ed.; Camarinha-Matos, L.M.,
Tomic, S., Graça, P., Eds.; Springer: Berlin, Germany, 2013; Chapter 38; pp. 351–358.
12. Multin, M.; Allerding, F.; Schmeck, H. Integration of Electric Vehicles in Smart Homes—An ICT-based
Solution for V2G Scenarios. In Proceedings of the IEEE ISGT PES Innovative Smart Grid Technologies,
Washington, DC, USA, 16–20 January 2012; pp. 1–8.
13. Wong, N.; Kazerani, M. A Review of Bidirectional On-Board Charger Topologies for Plug-In Vehicles.
In Proceedings of the IEEE CCECE Canadian Conference on Electrical and Computer Engineering, Montreal,
QC, Canada, 29 April–2 May 2012; pp. 1–6.
14. Mei, J.; Xiao, B.; Shen, K.; Tolbert, L.M.; Zheng, J.Y. Modular Multilevel Inverter with new Modulation
Method and its Application to Photovoltaic Grid-Connected Generator. IEEE Trans. Power Electron.
2013, 28, 5063–5073. [CrossRef]
15. Tolbert, L.M.; Peng, F.Z.; Habetler, T.G. Multilevel Converters for Large Electric Drives. IEEE Trans. Ind. Appl.
1999, 35, 36–44. [CrossRef]
16. Wang, H.; Kou, L.; Liu, Y.-F.; Sen, P.C. A New Six-Switch Five-Level Active Neutral Point Clamped Inverter
for PV Applications. IEEE Trans. Power Electron. 2017, 32, 6700–6715. [CrossRef]
17. Monteiro, V.; Meléndez, A.A.N.; Afonso, J.L. Novel Single-Phase Five-Level VIENNA-Type Rectifier with
Model Predictive Current Control. In Proceedings of the IEEE IECON Industrial Electronics Conference,
Beijing, China, 29 October–1 November 2017; pp. 6413–6418.
18. Grbovic, P.; Lidozzi, A.; Solero, L.; Crescimbini, F. Five-Level Unidirectional T-Rectifier for High Speed
Gen-Set Applications. IEEE Trans. Ind. Appl. 2016, 52, 1642–1651. [CrossRef]
19. Monteiro, V.; Ferreira, J.C.; Meléndez, A.A.N.; Afonso, J.L. Model Predictive Control Applied to an Improved
Five-Level Bidirectional Converter. IEEE Trans. Ind. Electron. 2016, 63, 5879–5890. [CrossRef]
20. Monteiro, V.; Meléndez, A.A.N.; Ferreira, J.C.; Couto, C.; Afonso, J.L. Experimental Validation of a Proposed
Single-Phase Five-Level Active Rectifier Operating with Model Predictive Current Control. In Proceedings of
the IEEE IECON Industrial Electronics Conference, Yokohama, Japan, 9–12 November 2015; pp. 3939–3944.
116
Energies 2018, 11, 3453
21. Mokhberdoran, A.; Ajami, A. Symmetric and Asymmetric Design and Implementation of New Cascaded
Multilevel Inverter Topology. IEEE Trans. Power Electron. 2014, 29, 6712–6724. [CrossRef]
22. Elsheikh, M.G.; Ahmed, M.E.; Abdelkarem, E.; Orabi, M. Single-Phase Five-Level Inverter with Less
Number of Power Elements. In Proceedings of the IEEE INTELEC International Telecommunications Energy
Conference, Orlando, FL, USA, 5–9 February 2012; pp. 1–8.
23. Loukriz, A.H.; Dudley, S.; Quinlan, T.; Walker, S.D. Experimental Realization of a Single-Phase Five Level
Inverter for PV Applications. In Proceedings of the IEEE COMPEL Control and Modeling for Power
Electronics, Trondheim, Norway, 27–30 June 2016; pp. 1–6.
24. Wang, K.; Xu, L.; Zheng, Z.; Li, Y. Capacitor Voltage Balancing of a Five-Level ANPC Converter Using
Phase-Shifted PWM. IEEE Trans. Power Electron. 2015, 30, 1147–1156. [CrossRef]
25. Monteiro, V.; Pinto, J.G.; Sousa, T.J.C.; Meléndez, A.A.N.; Afonso, J.L. A Novel Single-Phase Five-Level
Active Rectifier for On-Board EV Battery Chargers. In Proceedings of the IEEE ISIE International Symposium
on Industrial Electronics, Edinburgh, UK, 19–21 June 2017; Volume 4, pp. 582–587.
26. Rosas-Caro, J.C.; Ramírez, J.M.; García-Vite, P.M. Novel DC-DC Multilevel Boost Converter. In Proceedings
of the IEEE Power Electronics Specialists Conference, Rhodes, Greece, 15–19 June 2008; pp. 2146–2151.
27. Zhang, F.; Peng, F.Z.; Qian, Z. Study of the Multilevel Converters in DC-DC Applications. In Proceedings of
the IEEE Annual Power Electronics Specialists Conference, Aachen, Germany, 20–25 June 2004.
28. Lee, P.; Lee, Y.; Cheng, D.K.W. Steady-state analysis of an interleaved boost converter with coupled inductors.
IEEE Trans. Ind. Electron. 2000, 47, 787–795. [CrossRef]
29. Jiang, W.; Fahimi, B. Phase-Shift Controlled Multilevel Bidirectional DC/DC Converter: A Novel Solution to
Battery Charge Equalization in Fuel Cell Vehicle. In Proceedings of the IEEE Vehicle Power and Propulsion
Conference, Arlington, TX, USA, 9–12 September 2007; pp. 587–590.
© 2018 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access
article distributed under the terms and conditions of the Creative Commons Attribution
(CC BY) license (http://creativecommons.org/licenses/by/4.0/).
117
energies
Article
A Novel Phase Current Reconstruction Method for
a Three-Level Neutral Point Clamped Inverter (NPCI)
with a Neutral Shunt Resistor
Yungdeug Son 1 and Jangmok Kim 2, *
1 Department of Mechanical Facility Control Engineering, Korea University of Technology and Education;
Cheonan, Chungnam 31253, Korea; [email protected]
2 Department of Electrical and Computer Engineering, Pusan National University, Busan 46241, Korea
* Correspondence: [email protected]; Tel.: +82-51-510-2366
Abstract: This paper presents three phase current reconstruction methods for a three-level neutral
point clamped inverter (NPCI) by measuring the voltage of a shunt resistor placed in the neutral point
of the inverter. In order to accurately acquire the phase currents from the shunt resister, the dwell time
of the active voltage vectors need to exceed the minimum time. On the other hand, if the time of active
voltage is shorter than the minimum time, the current measurement becomes impossible. In this
paper, unmeasurable regions for current are classified into three areas. Area 1 is a region in which both
phase currents can be measure. Therefore, it is not necessary to restore the current. In Area 2, only one
phase current can be measured. Thus, an estimation or restoration method is needed to measure
another phase current. In this paper, the current estimation method using an electrical model of the
motor is proposed. Area 3 is the region in which both phase currents can not be measured. In this
case, it is necessary to move the voltage vector to the current measurable area by injecting the voltage.
In this paper, Area 3 is divided into 36 sectors to inject optimal voltage. The proposed methods have
the advantages of high current measurement accuracy and low THD (total harmonic distortion).
The effectiveness of the proposed methods are verified through experimental results.
Keywords: alternating current (AC) motor drive; current estimation; current reconstruction method;
current unmeasurable areas; total harmonic distortion (THD); single shunt resistor; space vector pulse
width modulation (SVPWM); shift method; minimum voltage injection (MVI) method; three-level
neutral point clamped inverter (NPCI)
1. Introduction
Two-level inverters are used in most home appliances, such as washing machines, refrigerators,
and air conditioners, due to their simple structure, and high reliability and performance.
However, in order to overcome the limitations of the efficiency and harmonics of the two-level
inverter, three-level inverters have been recently investigated. The three-level neutral point clamped
inverter (NPCI) has a structure characteristic of having a neutral point in the direct current (DC)
stage, and thus has excellent electro magnetic interference (EMI) and electro magnetic compatibility
(EMC) characteristics, due to a low voltage variation rate when switching [1–4]. Unlike a two-level
inverter, each arm of a three-level NPCI consists of four switches and two clamping diodes, as shown
in Figure 1. When the DC-link voltage is Vdc , the voltage of each capacitor is Vdc /2. The neutral point is
connected to each phase output node by the clamp diodes and switches. Due to this structural feature,
the three-level NPCI can output either Vdc /2 or −Vdc /2 by turning on the two switches located in the
upper or lower side of a phase. When the switches of Sx3 and Sx4 are turned on, the node voltage of
the x phase is 0 due to the connection with the neutral point through the diodes and switches, where x
represents A, B, and C.
AC Motor
SA3 SB3 SC3
Vdc
2
SA4 SB4 SC4
For controlling the AC motor, the controller of the inverter requires the values of the three phase
currents, which can be acquired through current sensors or a shunt resistor. A phase current sensing
inverter (PCSI), as shown in Figure 2a, is a typical three-phase voltage source inverter with two phase
current sensors. It requires at least two current sensors and sensing circuits, which raise the cost of
the appliances [5]. For this reason, a DC link shunt resistor Rshunt can be used to measure the phase
current, as shown in Figure 2b,c. A multi-shunt inverter (MSI) obtains the phase current from the
shunt resistor located in the neutral and bottom of the DC link [6]. Measurement of the currents
through the shunt resistors is possible when the current flows into the shunt resistor. Since the
shunt resistors are located between the neutral and bottom of the DC link, it is possible to measure
the phase current only if the active voltage vectors are combined with “O” or “N” switching states.
However, although the active vectors are combined with “O” or “N” switching states, the phase
current cannot be measured due to the short dwell time of the active vectors. The portion in the
space vector diagram where the dwell time of the active vectors is not large enough to measure the
current is called the current-unmeasurable area (CUA) [7–24]. A shunt resistor at the neutral point
of the three-level NPCI can be used to measure the phase current, as shown in Figure 2c. This is
similar to MSI, but a phase current is only obtainable when applying the state of “O” in the switching
combination of the effective voltage vector. NPCI is effective in terms of volume and cost as compared
to PCSI and MSI. It also has one current sensing circuit, which reduces the ripples caused by current
sensor offset and scaling errors [6,7]. However, it has a limited time to sample the phase current in
the shunt resistor over one period compared to the PCSI and MSI, so that the unmeasurable areas are
widened in the output voltage hexagon. In order to overcome the limitations, some researchers have
been interested in NPCI topology for phase current reconstruction.
Vdc
SA1 SB1 SC1
Current Vdc
RShunt
SA1 SB1 SC1
Vdc
SA1 SB1 SC1
2 2 2
SA2 SB2 SC2 sensor SA2 SB2 SC2 SA2 SB2 SC2
RShunt
R Shunt
Vdc Z
Vdc Z
Vdc Z
119
Energies 2018, 11, 2616
Previous research has established the effective voltage time by shifting the pulse width modulation
(PWM) or injecting the voltage to restore the current [6–24]. However, these methods cause
a high total harmonic distortion (THD) by injecting relatively large voltages. In [6], the minimum
voltage injection (MVI) method minimizes voltage distortion and operating noise through THD
reduction, but this method does not completely reconstruct the phase current at very high modulation
index (MI). In addition, the PWM shifting method of [7] also generates harmonics due to asymmetric
voltage modulation.
In this paper, the phase current unmeasurable region is classified into three areas, and the current
reconstruction methods are proposed according to each area. First, two phase currents can be measured
in Area 1, and the normal operation is executed in this area. On the other hand, only 1 phase current
can be acquired in Area 2. In this case, the other phase current can be estimated by combining the
q-axis current reference obtained from the speed controller and the electrical model of the motor [10].
Lastly, Area 3 is defined as an area where no current can be measured. For measuring the current in
this area, the optimal voltage injection method is proposed [12]. To realize this, the hexagon of SVPWM
is divided into 36 sectors, and the optimum injection voltage according to the sector is calculated.
In addition, the current accuracy and THD are compared with the conventional method [6] in various
MI conditions. The proposed method is verified through experimental results.
AC Motor
ia SA3 SB3 SC3
Vdc
2
SA4 SB4 SC4
Figure 3. Current path of neutral shunt resistor when effective vector “O”, “N”, and “N” is applied to
the inverter.
120
Energies 2018, 11, 2616
8 8 8
020 : 120 ia 220 :
8 8 8 8
021 ic 121 ib 221 ic 210 ib
010 ib 110 ic
Vref
8 8 8 8 8
022 : 122 ia 222 : 211 ia 200 :
011 ia 111 : 100 ia
000 :
8 8 8 8
012 ib 112 ic 212 ib 201 ic
001 ic 101 ib
8 8 8
002 : 102 ia 202 :
Table 1. Switching states and acquiring the phase current from the shunt resistor.
Acquiring Current
Space Vector Switching State Vector Classification
from the Shunt Resistor
V0 [PPP], [OOO], [NNN] X Zero vector
P-type N-type P-type N-type
V 13 [POO] [ONN] −ia ia
V 14 [PPO] [OON] ic −ic
V 15 [OPO] [NON] −ib ib Effective vector
V 16 [OPP] [NOO] ia − ia (Small vector)
V 17 [OOP] [NNO] − ic ic
V 18 [POP] [ONO] ib −ib
V7 , V8 [PON], [OPN] ib , ia
Effective vector
V 9 , V 10 [NPO], [NOP] ic , ib
(Medium vector)
V 11 , V 12 [ONP], [PNO] ia , i c
V1 , V2 [PNN], [PPN] X, X
Effective vector
V3 , V4 [NPN], [NPP] X, X
(Large vector)
V5 , V6 [NNP], [PNP] X, X
In one period of the three-level SVPWM, the sampling point and measurable phase current are
expressed as shown in Figure 5. In this case, the “a” phase current can be measured in the “ONN”
switching state and the “c” phase current can be measured in the “OON” switching state. The other
phase current is calculated using Equation (1):
i a + ib + ic = 0 (1)
SA O O O P P O O O
SB N O O O O O O N
SC N N O O O O N N
ia -ic -ia
Figure 5. One period of the SVPWM method and sampling point.
121
Energies 2018, 11, 2616
where Tdead is the dead time to avoid arm-short of the inverter, Tsettling is the settling time of the
neutral-point current, and Tad is the sample and hold time of the A/D converter. Thus, in order
to acquire the phase current properly, the switching time should be greater than Tmin . Figure 6b
shows switching state when the voltage modulation index is changed from Figure 5. In the case of
“ONN”, since the switching time Ta in the “O” state is larger than Tmin , accurate “a” phase current can
be obtained. However, in the case of “OON”, since the switching time Tc of the “O” state is shorter
than Tmin , it is impossible to obtain current on the “c” phase in this state. The areas where the effective
voltage dwell time is less than Tmin are defined as CUAs (current unmeasurable areas). The CUAs in
sector 1 of the three level SVPWM hexagon are shown in Figure 7a. In Figure 7a, Area 1 is a region
where all phase currents are measurable, Area 2 is a region where only one phase current is measurable,
and Area 3 is defined as a current unmeasurable region. The CUAs in all areas of the SVPWM are
shown in Figure 7b.
Ts
Ta Tc
Sa O O O P P O O O
Sb N O O O O O O N
Tmin Tmin
Sc N N O O O O N N
Tdead Tsettling Ta/d
Tmin Ta > Tmin , Tc < Tmin
(a) (b)
Figure 6. Tmin and Ts of the SVPWM method. (a) Minimum time (Tmin ); (b) one PWM period (Ts ).
V3 V8 V2
V14 (T14, ic) Area 1 :
Area 2 :
Area 3 :
V9 V7
˭V V15 V14
Tmin
V4 V1
V16 V0 V13
(a) (b)
Figure 7. Current-unmeasurable areas (CUAs). (a) Sector 1; (b) reference-voltage vector hexagon.
Ts V
Tmin : = ΔV : √dc
2 3
2T
ΔV = √ min Vdc (3)
3Ts
where Vdc is the voltage of the DC link capacitor.
122
Energies 2018, 11, 2616
Sector 1 of the output voltage hexagon is divided into four regions composed of effective voltage
vectors for the reference voltage vector Vre f duration, as shown in Figure 8. When the reference voltage
vector is located as shown in Figure 8, the effective voltage vector and the duration time are expressed
as follows:
V13 Ta + V7 Tb + V14 Tc = Vre f Ts
Ta + Tb + Tc = Ts (4)
2V
V2= 3 dc e , Ta
jɉ/3
From Equation (4), the duration time of the effective voltage vectors Ta , Tb , and Tc in each region
can be obtained through the equations given in Table 2. When Ta , Tb , and Tc are shorter than Tmin ,
phase current cannot be obtained from the shunt resistor accurately. Therefore, it is a CUA.
Region Ta Tb Tc
√ V π √ V π √ V
1 Ts (2 3 Vredcf
sin −θ ) Ts (1 − 2 sin +θ ) Ts (2 3 Vredcf sin θ )
3 Vredcf
√ Vre f 3 √ Vre f π 3 √ V
2 Ts (1 − 2 3 Vdc sin θ ) Ts (2 3 Vdc sin 3 + θ − 1) Ts (1 − 2 3 Vredcf sin π3 − θ )
√ Vre f π √ Vre f √ Vre f π
3 Ts (2 − 2 3 Vdc sin 3 + θ ) Ts (2 3 Vdc sin θ ) Ts (2 3 Vdc sin 3 − θ − 1)
√ V √ V √ V
4 Ts (2 3 Vredcf sin θ − 1) Ts (2 3 Vredcf sin π3 − θ ) Ts (2 − 2 3 Vredcf sin π3 + θ )
123
Energies 2018, 11, 2616
(a) (b)
Figure 9. Duration of the reference voltage vector in CUAs. (a) Area 2; (b) Area 3.
Ts Ts
Sa O O O P O O O Sa N O O O N
Tmin Tmin
Sb N O O O O O N Sb N N O N N
Sc N N O O O N N Sc O N N N O
Ta Tc Tb Ta Tb Tc Ta Tb Ta 2 Tc Tb Ta Tb
4 2 2 2 2 2 4 4 2 2 2 4
Figure 10. Switching sequences in conventional SVPWM and modified voltage modulation method.
(Area 2).
V14[O,O,N]
Im Ts
Area2
Vm Vc
Ta Tc
Sa O O O P P O O O
Vm
Area3
Sb N O O O O O O N
Area2 Tmin Tmin
Vref
Sc N N O O O O N N
Vc
Original voltage
V0[O,O,O]
Re V13[O,N,N]
ia -ic Injected voltage
(a) (b)
Figure 11. Minimum voltage injection method. (a) Voltage injection method in Area 3; (b) PWM
switching patterns.
However, it is difficult to reconstruct the phase current using the MVI method in the high MI region
shown in Figure 12. At this time, the compensation voltage Vc exceeds the linear modulation area.
Therefore, it is impossible to reconstruct the phase current near the outermost edge of the hexagon.
124
Energies 2018, 11, 2616
Area2
Area1
Vm
Area3
Vref
V1
Vc
Figure 12. Voltage injection method in Area 3 beside a vertex of the hexagon.
where La is the stator inductance, Ra is the stator resistance, and ω cc is the bandwidth of the PI regulator.
Then, the closed-loop transfer function Gc (s) of the block diagram is given by Equation (6):
e (s)
idq ωcc
G0 (s) ωcc
Gc (s) = = = s
= (6)
e∗ ( s )
idq 1 + G0 (s) 1 + ωscc 1 + ωcc
According to Equations (5) and (6), the combination of the PI controller and model of the motor
is equivalent to a first low-pass filter whose cutoff frequency is ω cc . In this case, the real d–q axis
current can be estimated using the current reference and low pass filter, as shown in Figures 13 and 14.
Finally, the estimated three phase currents (îabc ) can be obtained from reverse transformation of the
estimated d–q axis currents (îdq e ). This estimated current is used to replace the unmeasurable current
when the voltage command lies inside Area 2, where only one phase current is acquired. This current
estimation method does not need PWM shift or voltage injection for current reconstruction.
Figure 13. Block diagram of the PI controller and electrical model of the motor system.
125
Energies 2018, 11, 2616
e* dq
i dq
abc
q-axis
1 2 3 6 4 7 5 8 9 10
11
16 17
12
Vqss Vref
Vdss d-axis
13
14
18
15
For simple injection voltage calculation, the reference voltage vector Vre f (Vdss ,V s ) that rotates
qs
the output voltage hexagon with electrical angle θe , is transformed as shown in Figure 16. Vre f is
t (V t ,V t ) in sector 0 by Equation (8).
transformed to the shifted reference voltage vector Vdqs ds qs
t
Vds cos θn − sin θn s
Vds
= (8)
t
Vqs sin θn cos θn s
Vqs
where θn = n·π/3.
The range of the shifted sector 0 is from −π/6 to π/6. As a result, the injected voltage is only
calculated in the shifted sector 0.
As shown in Figure 17a, the shifted sector is symmetrical with respect to the d-axis.
Therefore, when calculating the injection voltage, only the positive part needs to be calculated. In the
negative region, the negative sign can be added to the magnitude of the q component.
i
Vdqs i , Vi
Vds t
are the vector components for moving Vdqs to the measurable region.
qs
After calculating the injection voltage, Vdqs i is added to V t , and reverse-transformation is executed.
dqs
This voltage vector is defined as the measurement voltage vector Vms . Vms is induced during the first half
period of the modulation, and the compensation voltage Vcs is induced during the other half period.
The relation between Vre f , Vms , and Vcs is given by Equation (9).
1 s
Vre f = (V + Vcs ) → Vcs = 2 Vre f − Vms (9)
2 m
126
Energies 2018, 11, 2616
q-axis q-axis
1
2 Transform
Vref șe 0 d-axis
Shifted se ctor
Vref
șe
0 d-axis
3
șn= nś 3
5
4 ( n : Shifted se ctor numbe r )
(a) (b)
Figure 16. Transform shifted sector. (a) Shifted sectors (0–5); (b) shifted sector (0).
q-axis
Positive part
q-axis
1
Inve rse
2
Transformation Vref șe 0 d-axis
d-axis
3
șn= nś 3 5
4
(a) (b)
Figure 17. Inverse transformation shifted sector. (a) Shifted sector (0); (b) shifted sectors (0–5).
In order to recover the phase current by injecting the optimal voltage, the shifted sector 0 for the
positive q-axis is divided into different parts, as shown in Figure 18a, according to the MI. As shown in
Figure 18b, each part is more finely divided to restore the phase current by injecting the optimal voltage.
Part.1 is further divided into Part.1_1 and Part.1_2, and Part.2 is divided into Part.2_1, Part.2_2, Part.2_3,
and Part.2_4. Part.3 and Part.4 are also divided into two parts and four parts, respectively.
Part. 3 Part. 3
2
1
Part. 2 Part. 2
Part. 1 Part. 4 Part. 1 Part. 4
2 4 3 4
1 1 2 3
1 2
d-axis d-axis
(a) (b)
Figure 18. Detailed view of the parts of the positive shifted sector 0. (a) Part1–Part4; (b) segmentation
of Parts.
When the reference voltage vector Vre f is located in Part.1_1, as shown in Figure 19, the optimal
voltage is injected, and the measurement voltage vector Vms is pushed to the measurement point.
At this time, the measurement point is on the boarder of Area 2. The magnitude of the injected
i (V i , V i ) can be calculated by using both the measurement point and V t , as shown
voltage Vdqs ds qs dqs
in Equation (10).
Part.1_1 √
i
Vds = 2ΔV/ 3 − Vds t
, Vqsi
= −Vqst (10)
When the reference voltage vector is located in Part.1_2, as shown in Figure 20, the measurement
voltage vector is moved to the measurement line by the optimal
√ voltage
√ injection. The measurement
line is defined by Equation (11), with two points (2ΔV/ 3, 0) and ( 3ΔV, ΔV), as the boarder of
Area 2. The magnitude of the injected voltage is obtained by Equation (12), which gives the minimum
127
Energies 2018, 11, 2616
distance from the point to the measurement line through the Pythagorean theorem, as shown in
Equation (13). The optimal voltage injection method is used to classify each part of Area 3 in more
detail, and then bring Vms to the closest measurement line or measurement point for reconstructing
the phase currents. At this time, the measurement line or measurement point is at the boarder of
Area 1 or Area 2. Each part of Area 3 has a different type of optimal voltage injection, as shown in
Equations (10) and (13)–(23), and in Figure 21.
√ √
y= 3 x− 3ΔV + ΔV (11)
1 √ t
d= 3Vds − Vqs
t
− 2ΔV (12)
2
Part.1_2 √
3 √ √ t
i
Vds = d = 3 × 0.25 3Vds − Vqst
− 2ΔV ,
2 (13)
1 √
i
Vqs = − d = −0.25 3Vds t
− Vqst − 2ΔV
2
Part.2_1
√ √ t V √ √ t V
i
Vds = − 3 × 0.25 3Vds + Vqs
t
− √dc , i
Vqs = − 3 × 0.25 3Vds + Vqs
t
− √dc (14)
3 3
Part.2_2
√ √ V √ V
i
Vds = 3 × 0.25 t
3Vds − Vqst − √dc , i
Vqs = −0.25 t
3Vds − Vqst − √dc (15)
3 3
(a) (b)
Figure 19. Optimal voltage injection method in Part.1_1. (a) Reference voltage vector on Part.1_1;
(b) detailed view of the left one.
(a) (b)
Figure 20. Optimal voltage injection method in Part.1_2. (a) Reference voltage vector on Part.1_2;
(b) detailed view of the left one.
128
Energies 2018, 11, 2616
Part.2_3
√ √ V √ V
i
Vds = 3 × 0.25 t
3Vds + Vqst − √dc − 2ΔV i
, Vqs = 0.25 t
3Vds + Vqst − √dc − 2ΔV (16)
3 3
Part.2_4
√ √ t V √ V
i
Vds = − 3 × 0.25 3Vds − Vqs
t
− √dc + 2ΔV i
, Vqs = 0.25 t
3Vds − Vqst − √dc + 2ΔV (17)
3 3
Part.3_1 √
3Vdc
i
Vds = 0 , Vqsi = ( − ΔV ) − Vqst (18)
6
Part.3_2
√ √ V √ t V
i
Vds = 3·0.25 t
3Vds − Vqst − √dc , i
Vqs = −0.25( 3Vds − Vqst − √dc ) (19)
3 3
Part.4_1
√ √ t 2V
i
Vds = − 3·0.25 3Vds + Vqst
− √dc + 2ΔV ,
3
√ t (20)
2Vdc
Vqs = −0.25( 3Vds + Vqs − √ + 2ΔV )
t t
3
Part.4_2
2Vdc 2ΔV
i
Vds = − √ − Vds
t i
, Vqs = −Vqst (21)
3 3
Part.4_3
2Vdc ΔV
i
Vds = −√ − Vds
t i
, Vqs = ΔV − Vqst (22)
3 3
Part.4_4
i
Vds = 0, i
Vqs = ΔV − Vqst (23)
ܸௗ ܸௗ
Measurement V ȟ)
( ͵ ȟ, V ሺ ǡ ሻ Measurement
͵ ͵
line line
ܸௗ ȟ
V ௗ ܸ
ሺ െ ǡ െ ȟሻ
V
͵ ͵ ͵
Measurement
point
ଶ ܸௗ ȟ
( ଷ, 0) V ܸௗ
ሺ ǡ െ ȟሻ
V
͵ ͵ ͵
ܸௗ ܸௗ
ሺ ǡ െ ʹȟሻ
V
͵ ͵
(a) (b)
ܸௗ ͵ܸௗ Measurement Measurement
ሺ ǡ ሻ point ʹܸௗ ȟV
ܸௗ ͵ܸௗ ʹ
ʹܸௗ
line ሺ െ ǡ ȟሻ
V
ሺ െ ͵ȟǡ
V െ ȟሻ
V ሺ െ ͵ȟǡ
V ȟሻ
V ͵ ͵
ʹ ͵
ʹܸௗ
ሺ ǡ Ͳሻ
͵
Measurement
ʹܸௗ ʹȟ
V
line ሺ െ ǡ Ͳሻ
V ͵ܸௗ
ܸௗ ȟ
͵ ͵ Measurement
ሺ െ ǡ െ ȟሻ
V point
ʹ ͵
(c) (d)
Figure 21. Optimal voltage injection method in Area 3 for each part. (a) Optimal voltage injection
method in Part.1; (b) optimal voltage injection method in Part.2; (c) optimal voltage injection method
in Part.3; (d) optimal voltage injection method in Part.4.
129
Energies 2018, 11, 2616
V9 V7
V15 V14 0.1 V0 V0
V4 V1
V16 V0 V13
V8 V8
V10 V12
V17 V18
0.97
V5 V11 V6
Figure 22. Comparison of conventional method and proposed method at MI = 0.1 and MI = 0.97.
As shown in Table 3, when the proposed method is applied, it can be seen that the area of the
non-measurable region in the output voltage hexagon is reduced by about 93.7 % in comparison with
the case in the MVI method.
3-Level NPCI One Shunt Unmeasurable Area Conventional Method Proposed Method
6. Experimental Results
Figure 23 describes the system configuration of the experimental setup for the verification of the
proposed current reconstruction method. The system was composed of the three-level NPC inverter,
including the shunt resistor, connected to the neutral point, the control system based on the digital
signal processor (DSP, TMS320C28346), and the resistive-inductive load. The upper and lower DC
capacitors were connected with the 30 V power source.
130
Energies 2018, 11, 2616
A resistor of 10 Ω and inductor of 5 mH were used as the load. The resistance of the shunt resistor
was 0.2 Ω and its power capacity was 3 W. In addition, the minimum time Tmin needed to acquire the
precise phase current from the shunt resistor was set to be 4.5 μs. The reconstructed current from the
shunt resistor using the proposed algorithm was compared with an actual current measured using
two current sensors in order to verify its precision.
%WTTGPV
UGPUQT
6TCPUHQTOGT
5JWPVTGUKUVQT
%QPVTQNNGT
&%NKPM
In the experiment, the inverter system was operated by the V/F open-loop control algorithm.
The system was controlled with a fixed operating frequency of 12 Hz and variable output voltage to
change the MI. The experimental results were classified in 6 cases to compare with the conventional
MVI method. Figure 24a,b shows the experimental results with the condition of MI = 0.1 (Vre f = 3.56 V).
In this case, the inverter was operated in Area 3 where the two currents cannot be measured from the
shunt resistor. As presented in Figure 24b, the injected d–q voltage for the current reconstruction is
smaller than the voltage in Figure 24a. The experimental results of Figure 24c,d was measured when the
inverter was operated in Area 1 and 2 with MI of 0.4 (Vre f = 13.86 V). In Area 1, it is possible to obtain the
two phase currents from the shunt resistor, and only one current can be acquired in Area 2. As shown
in Figure 24c, the conventional method injects the q-axis voltage to reconstruct the phase current.
In contrast, the proposed method can reconstruct the phase current without the voltage injection,
as presented in Figure 24d, because the phase current is reconstructed using the estimated current.
In Figure 24e,f, Vre f is passed through Area 1 and 3 when the MI is 0.6 (Vre f = 20.78 V). As shown in
Figure 24f, a smaller voltage is injected to reconstruct the phase current in the proposed method in
comparison with the conventional method. The waveforms presented in Figure 25e,f was measured
when the MI was 0.97 (Vre f = 33.6 V). In this case, the trajectory of the voltage reference is near the
inscribed circle of the space vector hexagon. In the case of the conventional method, the phase current
cannot be reconstructed even if the voltage injection method is used, because the compensated voltage
reference exceeds the hexagon. On the other hand, the proposed method can reconstruct the phase
current, as presented in Figure 25f, because the voltage reference can be compensated on the boundary
of the hexagon.
The accuracy of the phase currents reconstructed using the conventional and proposed methods
were calculated to show the superiority of the proposed algorithm. The equation for the accuracy of
the phase current is expressed in Equation (24).
131
Energies 2018, 11, 2616
5 5 5
Shifted_sector Shifted_sector Shifted_sector
0 0 0
i a_shunt i a_shunt i a_shunt
0.5 1.5 2
(A) (A) (A)
-0.5 -1.5 -2
Vd_injection Vd_injection Vd_injection
5 0 0
3 -3 V q_injection
Vq_injection 5 Vq_injection 5
4
(V) (V) (V)
-4 -5 -5
0.5 ia_shunt 1.5 ia_shunt 2
ia_shunt
(A) (A) (A)
-0.5 -1.5 -2
0.5 ia_sensor 1.5 ia_sensor 2
ia_sensor
(A) (A) (A)
20[ms] 20[ms] 20[ms]
-0.5 -1.5 -2
0 0 0
ia_shunt ia_shunt
i a_shunt
0.5 1.5 2
(A) (A) (A)
-0.5 -1.5 -2
Vd_injection Vd_injection Vd_injection
0 0
4 -2
0 (V) Vq_injection Vq_injection
Vq_injection (V)
2.5 1
(V) 0 -1
-2.5
0.5 ia_shunt 1.5 2
ia_shunt ia_shunt
(A) (A) (A)
-0.5 -1.5 -2
0.5 ia_sensor 1.5 ia_sensor 2 ia_sensor
(A) (A) (A)
20[ms] 20[ms] 20[ms]
-0.5 -1.5 -2
0 0 0
ia_shunt i a_shunt ia_shunt
2.5 3 3
(A) (A) (A)
-2.5 -3 -3
Vd_injection Vd_injection Vd_injection
0 0 0
-1.5
Vq_injection 5 Vq_injection Vq_injection
5 5
(V) (V) (V)
-5 -5 -5 ia_reconstructed
2.5 3 ia_shunt 3
ia_shunt
(A) (A) (A)
-2.5 -3 -3
2.5 3 ia_sensor
ia_sensor ia_sensor 3
(A) (A) (A)
20[ms] 20[ms] 20[ms]
-2.5 -3 -3
0 0 0
i a_shunt ia_shunt ia_shunt
2.5 3 3
(A) (A) (A)
-2.5 -3 -3
Vd_injection Vd_injection 1 Vd_injection
0 0 0
(V) Vq_injection Vq_injection (V) Vq_injection
2 0.7
0 (V)
-2 -0.7
2.5
3 3 ia_reconstructed
ia_shunt ia_shunt
(A) (A) (A)
-2.5 -3 -3
2.5 3 3 ia_sensor
ia_sensor ia_sensor
(A) [A] (A)
20[ms] 20[ms] 20[ms]
-2.5 -3 -3
As the difference between the current measured by the sensor and the reconstructed current is
increased, the variance of the calculated results increases. This means the accuracy of the reconstruction
is low. The difference in accuracy between the conventional method and the proposed method is
132
Energies 2018, 11, 2616
compared according to the MI, and shown in Figure 26a. The accuracy of the proposed method is
higher than the conventional method in the whole range of the MI.
The comparison results for the THD of the phase current between the conventional method and
the proposed method are presented in Figure 26b.
The THD result for the proposed method is lower than the result for the conventional method in
the whole range of the MI, because the THD of the phase current is proportional to the injected voltage.
On average the THD of the proposed method is improved by 44.5 % compared with that of the
conventional method.
7. Conclusions
This paper proposed a phase current reconstruction method using a neutral shunt resistor,
which lowers both the cost and volume of a three-level inverter system.
First, the paper proposes the method for dividing the switching sectors, the rotated sectors,
and the region. Each region is separated by the equation of a straight line.
In addition, in Area 2 where there is only one measurable phase current, the remaining phase
current is reconstructed by the estimation method. The electrical model of the motor and PI current
controller are used to estimate the current.
Finally, the optimal voltage injection method is used in Area 3, where no current is acquired
through the shunt resistor (CUAs). Area 3 is divided and defined as parts in more detail. When the
reference is located on Area 3 of the hexagon, the phase currents are reconstructed by moving the
reference vector to the border of Area 1 or Area 2.
The proposed method utilized a small magnitude injection voltage compared to the conventional
method, and hence results in better performance in terms of THD and accuracy of the
estimated currents. The validity of the proposed algorithm is proven by the experiments.
Author Contributions: Y.S. contributed to the research activity and to manuscript writing. J.K. provided technical
feedback and did supervision of the overall work.
Funding: This research received no external funding.
Acknowledgments: This research was supported by the Basic Science Research Program through the National
Research Foundation of Korea (NRF) funded by the Ministry of Education (NRF-2018R1D1A1B07048954).
Conflicts of Interest: The authors declare no conflict of interest.
133
Energies 2018, 11, 2616
References
1. De, S.; Banerjee, D.; Gopakumar, K.; Ramchand, R.; Patel, C. Multilevel inverters for low-power application.
IET Power Electron. 2010, 4, 382–392. [CrossRef]
2. Lipo, T.A.; Manjrekar, M.D. Hybrid Topology for Multilevel Power Conversion. U.S. Patent 06,005,788,
21 December 1999.
3. Lai, R.; Wang, F.; Burgos, R.; Pei, Y.; Boroyevich, D.; Wang, B.; Lipo, T.A.; Immanuel, V.D.; Karimi, K.J.
A systematic topology evaluation methodology for high-density three-phase PWM AC-AC converters.
IEEE Trans. Power Electron. 2008, 23, 2665–2680.
4. Heldwein, M.L.; Kolar, J.W. Impact of EMC filters on the power density of modern three-phase
PWM converters. IEEE Trans. Power Electron. 2009, 24, 1577–1588. [CrossRef]
5. Jarzebowicz, L. Error Analysis of Calculating Average d-q Current Components using Regular Sampling
and Park Transformation in FOC Drives. In Proceedings of the 2014 International Conference and Exposition
on Electrical and Power Engineering (EPE 2014), Iasi, Romania, 16–18 October 2014; pp. 901–905.
6. Shin, H.; Ha, J.I. Phase Current Reconstructions from DC-Link Currents in Three-Phase Three-Level
PWM Inverters. IEEE Trans. Power Electron. 2014, 29, 582–593. [CrossRef]
7. Li, X.; Dusmez, S.; Akin, B.; Rajashekara, K. A New SVPWM for the Phase Current Reconstruction of
Three-Phase Three-level T-type Converters. IEEE Trans. Power Electron. 2015, 62, 2627–2637.
8. Blaabjerg, F.; Pedersen, J.K. An ideal PWM-VSI inverter using only one current sensor in the DC-link.
In Proceedings of the 1994 Fifth International Conference on Power Electronics and Variable-Speed Drives,
London, UK, 26–28 October 1994; pp. 458–464.
9. Lee, W.C.; Hyun, D.S.; Lee, T.K. A Novel Control Method for Three-Phase PWM Rectifiers Using a Single
Current Sensor. IEEE Trans. Power Electron. 2000, 15, 861–870.
10. Yeom, H.B.; Ku, H.K.; Kim, J.M. Current reconstruction method for PMSM drive system with a DC link
shunt resistor. In Proceedings of the 2016 IEEE Energy Conversion Congress and Exposition (ECCE),
Milwaukee, WI, USA, 18–22 September 2016; pp. 18–22.
11. Ha, J.I. Voltage Injection Method for Three-Phase Current Reconstruction in PWM Inverters Using
a Single Sensor. IEEE Trans. Power Electron. 2009, 24, 767–775.
12. You, J.J.; Jung, J.H.; Park, C.H.; Kim, J.M. Phase current reconstruction of three-level Neutral-Point-Clamped
(NPC) inverter with a neutral shunt resistor. In Proceedings of the 2017 IEEE Applied Power Electronics
Conference and Exposition (APEC), Tampa, FL, USA, 26–30 March 2017; pp. 2598–2604.
13. Gu, Y.; Ni, F.; Yang, D.; Liu, H. Switching-State Phase Shift Method for Three-Phase-Current Reconstruction
with a Single DC-Link Current Sensor. IEEE Trans. Ind. Electron. 2011, 58, 5186–5194.
14. Lin, Y.K.; Lai, Y.S. PWM Technique to Extend Current Reconstruction Range and Reduce Common-Mode
Voltage for Three-Phase Inverter using DC-link Current Sensor Only. In Proceedings of the 2011 IEEE Energy
Conversion Congress and Exposition, 12–16 September 2011; pp. 1978–1985.
15. Lai, Y.S.; Lin, Y.K.; Chen, C.W. New Hybrid Pulse width Modulation Technique to Reduce Current Distortion
and Extend Current Reconstruction Range for a Three-Phase Inverter Using Only DC-link Sensor. IEEE Trans.
Power Electron. 2013, 28, 1331–1337. [CrossRef]
16. Lu, H.; Cheng, X.; Qu, W.; Sheng, S.; Li, Y.; Wang, Z. A Three-Phase Current Reconstruction Technique Using
Single DC Current Sensor Based on TSPWM. IEEE Trans. Power Electron. 2014, 29, 1542–1550.
17. Ying, L.; Ertugrul, N. An Observer-Based Three-Phase Current Reconstruction using DC Link Measurement
in PMAC Motors. In Proceedings of the 2006 CES/IEEE 5th International Power Electronics and Motion
Control Conference, Shanghai, China, 14–16 August 2006; pp. 1–5.
18. Saritha, B.; Janakiraman, P.A. Sinusoidal Three-Phase Current Reconstruction and Control Using a DC-Link
Current Sensor and a Curve-Fitting Observer. IEEE Trans. Ind. Electron. 2007, 54, 2657–2664. [CrossRef]
19. Kim, K.; Yeom, H.; Ku, H.; Kim, J. Current reconstruction method with single DC-link. In Proceedings of the
2014 IEEE Energy Conversion Congress and Exposition, 14–18 September 2014; pp. 250–256.
20. Tomigashi, Y.; Hida, H.; Ueyama, K. Voltage vector correction based on a novel coordinate transformation for
motor current detection using a single shunt resistor. In Proceedings of the 2009 13th European Conference
on Power Electronics and Applications, 8–10 September 2009; pp. 1–8.
134
Energies 2018, 11, 2616
21. Kim, H.; Jahns, T.M. Integration of the Measurement Vector insertion Method (MVIM) with Discontinuous
PWM for Enhanced Single Current Sensor Operation. In Proceedings of the 2006 IEEE Industry Applications
Conference Forty-First IAS Annual Meeting, 8–12 October 2006; Volume 5, pp. 2459–2465.
22. Carpaneto, M.; Marchesoni, M.; Parodi, G. A Sensorless PMSM Drive Operating in the Field Weakening
Region Using Only One Current Sensor. In Proceedings of the 2010 IEEE International Symposium on
Industrial Electronics (ISIE), 4–7 July 2010; pp. 1199–1204.
23. Bing, Z.; Du, X.; Sun, J. Control of three-phase PWM rectifiers using a single DC current sensor. IEEE Trans.
Power Electron. 2011, 26, 1800–1808. [CrossRef]
24. Sun, K.; Wei, Q.; Huang, L.; Matsuse, K. An overmodulation method for PWM-inverter-fed IPMSM drive
with single current sensor. IEEE Trans. Ind. Electron. 2010, 57, 3395–3404. [CrossRef]
© 2018 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access
article distributed under the terms and conditions of the Creative Commons Attribution
(CC BY) license (http://creativecommons.org/licenses/by/4.0/).
135
energies
Article
A Novel Three-Level Voltage Source Converter for
AC–DC–AC Conversion
Zongbin Ye 1,2, *, Anni Chen 1,2 , Shiqi Mao 1,2 , Tingting Wang 1,2 , Dongsheng Yu 1,2
and Xianming Deng 1,2
1 Jiangsu Province Laboratory of Mining Electric and Automation, China University of Mining
and Technology, Xuzhou 221008, China; [email protected] (A.C.); [email protected] (S.M.);
[email protected] (T.W.); [email protected] (D.Y.); [email protected] (X.D.)
2 School of Electrical and Power Engineering, China University of Mining and Technology,
Xuzhou 221008, China
* Correspondence: [email protected] or [email protected]; Tel./Fax: +86-516-8359-2000
Abstract: This paper presents a novel three-level voltage source converter for AC–DC–AC conversion.
The proposed converter based on H-bridge structure is studied in detail. The control method with
traditional double-closed-loop control strategy and voltage balancing algorithm is applied to the
rectifier side. Correspondingly, a simplified modulation algorithm is applied to the inverter side,
and the voltage balancing of inverter side is realized through the optimal selection of switching
combination. Then, the application of the proposed topology is assessed in general and ideal operation
conditions. Furthermore, the proposed topology with a variable voltage variable frequency (VVVF) is
verified in experimental conditions. The performance of the proposed converter and control strategy
is evaluated by experimental and simulation results.
1. Introduction
With the development of the multilevel converter (MC), it has become a cost-effective solution
of medium-voltage AC drives [1]. Due to its merits compared with a conventional two-level voltage
source converter—such as lower voltage stress on switches, improved output waveforms, reduced
common mode voltage, and high voltage capability—MC has been applied to more emerging
fields [2–4]. The areas of applications include renewable energy generation, electric vehicle traction [5],
high-power energy storage system [6], micro-grids [7], high-voltage ac or dc transmission [8–10],
and some newly-developing fields.
In general, there are two conventional types of AC–DC–AC multilevel converters in view
of whether it has common dc-links. The diode-clamped MC (DCMC) [11] and fly-capacitor MC
(FCMC) [12] are widespread adopted structures with common dc-links, which can operate in four
quadrants and be supplied by single rectifier. Besides, there are some other topologies, such as
five-level active neutral-point-clamped MC (5L-ANPC) [13], modular MC (MMC) [9,10], and some
newly-developed MC [14–16]. However, these kinds of MCs, except MMC, are hard to extend towards
higher output voltage levels and power grades because of the complicated structures. The other
drawback of these types is the poor ability to deal with some special systems which have different
voltage grades, e.g., connection of two grids with different voltage grades [16–18]. Separated dc-links
are the features of the other types of MCs, including cascaded H-bridge MC (CHBMC) [17], five-level
H-bridge NPC (5L-HNPC) [18], and some hybrid and asymmetrical cascaded H-bridge MCs with
different sub-modules [19] or dc-link voltages [20]. It has the advantage of flexible extending of the
output levels and power rating. However, the bulky and expensive phase-shifting transformers for
isolated dc sources make it hard to increase the power density. A back-to-back CHB converter without
any isolating device [21] can avoid these problems. However, short-circuits caused by the hardware
topology are difficult to solve and the proposed topology cannot be expanded to a three phase system.
In this paper, a new three-level voltage source converter for AC–DC–AC conversion is proposed.
It can be used in three-phase system and more easily to extend to higher voltage level than a
back-to-back NPC converter. Compared to the back-to-back CHB converter proposed in [21], a half
H-bridge cell used in the new topology provides more redundant vectors and makes it overcome
the short-circuit problem, which simplifies the control method. In addition, the proposed topology
utilizes fewer switches at the cost of increasing the number of dc-link capacitors, the separated dc links
will decrease the total dc voltage of the system, which is beneficial for the insulation design in many
fields [22].
The rest of the paper is organized as follows. In Section 2, the circuit configuration, characteristics
and working principles of the proposed topology are studied in detail. The overall control strategy
and pulse-width modulation strategy considering the voltage balance control is given in Section 3.
In Section 4, two operation conditions are analyzed, and the simulation and experimental results
demonstrate the effectiveness of the proposed control strategies. Section 5 concludes the paper.
Phase C Phase C
Phase B Phase B
Phase A Phase A
Rectifier Common Inverter Inverter
Side Part Side I Side II
S2 S3 S4 S5 RL load
S1
eC C
n eB LC C B
LB B 2 CX_rec 3 2 CX_inv 1 A O
eA 1
LA A iX_inv
S1 S2 S3 S4 S5
For convenience, the rectifier side, common part, inverter side I, and inverter side II can be defined
as shown in Figure 1. The rectifier side connects in series with three-phase inductors and the grid
through three phase electrical terminals A, B, and C. The three electrical terminals A, B, and C of
inverter side connect with the three-phase load.
137
Energies 2018, 11, 1147
138
Energies 2018, 11, 1147
quantity in the Table, but it must be equipped with a transformer and PWM rectifier for four-quadrant
applications. In the rest of the topologies, CMC topology, without clamping diodes and capacitors,
has a lower number of components than other topologies with the improvement of voltage level.
Table 2. Comparison of different topologies (Vll_rms = 3 kV, Iph_rms = 115.5 A, P = 600 kW).
Level 3L 5L
Topology NPC FC CHB CMC NPC FC CHB CMC
Rated device voltage (IGBT) 4.5 kV 4.5 kV 4.5 kV 4.5 kV 3.3 kV 3.3 kV 3.3 kV 3.3 kV
Rated device current (IGBT) 450 A 450 A 450 A 450 A 450 A 450 A 450 A 450 A
IGBTs 24 24 24 30 48 48 48 54
Diodes 12 --- --- --- 36 --- --- ---
Capacitors 2+0 2+6 3+0 6+0 4+0 4 + 18 6+0 12 + 0
Total Components 38 32 23 36 88 70 54 66
To compare with the B2B 3L-NPC, the switching losses for both topologies are calculated and
normalized according to the method proposed in [26] and the datasheet of IGBT. The result is shown
in Figure 2 where the modulation index of the inverter side ranges from 0.5 to 1.15 and the power
factor of the load ranges from 0.7 to 1.
139
Energies 2018, 11, 1147
ed_grid
Udc ref_rec u
+ id* + −+ d *
PI PI + uA_rec
− id − dq
ωL *
+ +
uB_rec
Udc_ave_rec iq ωL Modulation
*
uC_rec + + Algorithm
iq* + − − − uq abc
0 PI
+ +
+
eS Digital θ eq_grid
uz_rec
PLL U dcA/B/C_rec
Voltage
iA/B/C_rec Balancing
Algorithm
eS LA/B/C
RL-load
S1 Switching
* Switch Optimal States of
uX_inv S2
States Selection of Rectifier
Modulation S3
Algorithm Udc ref_inv Switching S4 Side
Combination S5
iX_inv
UdcX_inv
S=3 S=2
NPN OPN
PPN
NPP
OPP POO PNN S=1
NOO ONN
S=4
POP PNO
NOP NNO ONO
S=5 S=6
Figure 4. Sectors for the proposed three-level converter with the simplified PWM.
140
Energies 2018, 11, 1147
When S = 1, the voltage-second balancing principle can be represented by Equation (4), where
uz represents the equivalent zero-sequence voltage. The general solutions of (4) can be obtained as
Equation (5). ⎧
∗
Ts Ts
⎪
⎨ uA_inv · Ts = 0 uAN (t)dt + 0 uz (t)dt
∗
uB_inv
T T
· Ts = 0 s uBN (t)dt + 0 s uz (t)dt , (4)
⎪
⎩ ∗ Ts Ts
uC_inv · Ts = 0 uCN (t)dt + 0 uz (t)dt
⎧
⎪ ∗
TA_inv = (uA_inv − uz ) · Ts /UdcA_inv
⎨
∗
TB_inv = Ts + (uB_inv − uz ) · Ts /UdcB_inv , (5)
⎪
⎩ T ∗
C_inv = Ts + ( u C_inv − u z ) · Ts /UdcC_inv
TX_inv stands for the duration time of switching state P when (u* X_inv − uz > 0) otherwise stands for
the duration time of O.
If UdcX_rec is imbalanced, uz_rec should be calculated to adjust the reference voltage u* X_rec . As an
example, if voltage values of CX_rec satisfy UdcA_rec > UdcB_rec > UdcC_rec , it means that the magnitude
of charge change within Ts should be QA < QB < QC . uz_rec can be changed to adjust QX . Calculation
of uz_rec is as follows:
1. QX , u* X_rec , and iX_rec are sorted according to UdcX_rec . In order to realize the voltage balancing,
QX should satisfy Equation (7).
Qmax < Qmid < Qmin , (7)
u∗X_rec − uz_rec
Q X = i X_rec · · Ts , (8)
UdcX_rec
If iX_rec > 0 and (u* X_rec − uz_rec ) > 0, uX_rec consists of P/O. The current paths of S1S2 are shown
in Figure 5. Obviously, QX > 0 and CX_rec is charged in this case. CX_rec is discharged within Ts
when iX_rec < 0 and (u* X_rec − uz_rec ) > 0.
2. Substituting (8) into (7) gives (9).
∗ ∗ −uz_rec ∗ −uz_rec
umax_rec −uz_rec umid_rec umin_rec
imax_rec · Udcmax_rec · Ts < imid_rec · Udcmid_rec · Ts < imin_rec · Udcmin_rec · Ts , (9)
⎧
⎪
⎪ a1 = imax_rec · Udcmid_rec − imid_rec · Udcmax_rec
⎪
⎨ b1 = i ∗ ∗
max_rec · umid_rec · Udcmid_rec − imid_rec · umid_rec · Udcmax_rec
, (10)
⎪ a2 = imid_rec · Udcmin_rec − imin_rec · Udcmid_rec
⎪
⎪
⎩ ∗ ∗
b2 = imid_rec · umid_rec · Udcmin_rec − imin_rec · umin_rec · Udcmid_rec
utemp1 = b1/a1, and utemp2 = b2/a2.
141
Energies 2018, 11, 1147
3. The range of uz_rec can be obtained from Equation (9), and uz_rec can take any value within the
range. However, it should satisfy Equation (11) to acquire a linear modulation.
⎧
⎪ ∗
⎨ −Udcmax_rec ≤ umax_rec − uz_rec ≤ Udcmax_rec
∗
−Udcmid_rec ≤ umid_rec − uz_rec ≤ Udcmid_rec , (11)
⎪
⎩ −U ∗
dcmin_rec ≤ u min_rec − uz_rec ≤ Udcmin_rec
4. Calculating the limit value of uz_rec : the corresponding limitations of the injected zero-sequence
voltages are given in (12).
⎧
⎪ ∗
uzmax = max(umax_rec ∗
− Udcmax_rec , umid_rec − Udcmid_rec ,
⎪
⎪
⎨ u∗ − U )
min_rec dcmin_rec
∗ ∗ , (12)
⎪
⎪ uzmin = min(umax_rec + Udcmax_rec , umid_rec + Udcmid_rec ,
⎪
⎩ ∗
umin_rec + Udcmin_rec )
Finally, uz_rec can be obtained to realize the targets of voltage balancing as shown in Table 3.
The voltage balancing algorithm is shown in Figure 6 in detail.
Swithing state P
Swithing state O S1 S2
iX_rec 1 CX_rec 2
S1 S2
Obtaining uz_rec
Figure 6. Current paths of S1S2 when iX_rec > 0 and (u* X_rec − uz_rec ) > 0.
142
Energies 2018, 11, 1147
S2 S3 S4 S5
C 3 2 iX_inv >0
2 X_rec CX_inv 1
S2 S3 S4 S5
143
Energies 2018, 11, 1147
Rectifier N O N Rectifier N O N
TA_rec TA_rec
State State
Inverter P Inverter O P O
O O TA_inv
State TA_inv State
Inverter Inverter P O
O O O
Side I O P P P O Side I
Inverter Inverter O P O P O
O N O N O Side II
Side II
S1 0 0 0 S1 0 0 0
S2 1 0 1 S2 1 0 1
S3 1 1 1 S3 1 1 1
S4 0 1 0 S4 0 1 0
S5 0 1 0 S5 0 1 0
Figure 8. Converter state and switching commands. (a) (u* A_rec − uz_rec ) < 0, (u* A_inv − uz ) > 0,
and UdcA_inv > Udcref_inv ; iX_inv > 0, TA_rec > TA_inv ; (b) (u* A_rec − uz_rec ) < 0, (u* A_inv − uz ) > 0,
and UdcA_inv > Udcref_inv ; iX_inv < 0, TA_rec < TA_inv .
144
Energies 2018, 11, 1147
u* A_rec − uz_rec u* A_inv − uz U dcA_inv iA_inv tS1 tS2 tS3 tS4 tS5
>0 TA_rec 0 0 0 TA_inv
UdcA_inv > Udcref_inv
>0 ≤0
TA_rec 0 Ts Ts TA_inv
>0
>0 UdcA_inv ≤ Udcref_inv
≤0 TA_rec 0 0 0 TA_inv
>0 Ts TA_rec 0 TA_rec TA_inv
UdcA_inv > Udcref_inv
≤0 ≤0
TA_rec 0 TA_inv Ts 0
>0
UdcA_inv ≤ Udcref_inv
≤0 Ts TA_rec 0 TA_rec TA_inv
>0 TA_rec Ts TA_inv 0 Ts
UdcA_inv > Udcref_inv
>0 ≤0 TA_rec Ts TA_rec TA_inv
0
>0
UdcA_inv ≤ Udcref_inv
≤0 ≤0 TA_rec Ts TA_inv 0 Ts
>0 TA_rec Ts 0 0 TA_inv
UdcA_inv > Udcref_inv
≤0 ≤0
TA_rec Ts Ts Ts TA_inv
>0
UdcA_inv ≤ Udcref_inv
≤0 TA_rec Ts 0 0 TA_inv
tS1~S5 is the duration time of each switch, S1~S5.
there will be no uncontrollable cases based on the above analyses in this operation condition. That is,
the voltage deviation of CX_inv will be kept under control completely. Although this condition can
balance the capacitor voltages well, the use of this structure is restricted in some applications such as
power electronic transformers and AC regulators.
145
Energies 2018, 11, 1147
Magnitude Magnitude
iA_inv t iA_inv t
(u*A_inv-uz) (u*A_inv -uz)
udcref_inv
udcref_inv
udcA_inv udcA_inv
TA_rec&& Ts TA_inv
TA_inv
TA_rec TA_inv TA_rec
t
TA_inv>TA_rec t
TA_rec>TA_inv
(a) (b)
Figure 9. Analysis of voltage deviation with CA_inv . (a) When Sgn|(u* A_rec − uz_rec )| = −Sgn|(u* A_inv
− uz )|; (b) when minv < 1 − mrec .
Including this special case, the uncontrollable states can be eliminated absolutely when Sgn(u* X_rec
− uz_rec ) = Sgn(u* X_inv − uz ) and minv ≤ 1 − mrec as shown in Figure 9b. Although the time of
uncontrollable state can be quantified as shown in Figure 9b when minv ≥ 1 − mrec , the voltage
deviation of CX_inv still cannot be improved without efficient measures. Hence, the magnitude of
output voltage will be limited. DC voltage deviation and low-frequency fluctuation will exist in the
whole system.
146
Energies 2018, 11, 1147
Parameter Value
Source voltage, eX_rec 55 V
DC-link voltage 100 V
DC-link capacitor 1200 μF
Filter-inductive 2.2 mH
Resistive-inductive load 20 Ω, 2.2 mH
Switching frequency 5 kHz
The experimental results obtained in Figure 11 show the voltage–current waveforms of the rectifier
side and inverter side at different modulation indexes minv and switching frequency f during the whole
working process. Figure 11a,c shows that the three-phase current iX_rec rectifier side and iX_inv inverter
side increase with the increase of modulation index and frequency. In Figure 11c, the waveforms of
line-to-line voltage uAB_inv have three-levels when f = 20 Hz, minv = 0.4 and f = 30 Hz, minv = 0.6, while
it changes to five-levels when f = 40 Hz, minv = 0.8 and f = 50 Hz, minv = 0.9. UdcX_rec and UdcX_inv are
shown in Figure 11b,d are the waveforms of three-phase capacity of CX_rec and CX_inv . It can be seen
that UdcX_rec and UdcX_inv do not change with the modulation index and frequency after the system is
working. Capacitor voltages can be balanced well, and better performance of the proposed multilevel
converter is verified in this process. Figure 12 shows the performance of the converter in transient-state
condition with the modulation index minv changing from 0.4 to 0.6 and output frequency f changing
from 20 Hz to 30 Hz. Figure 12a,b shows the input voltage–current waveforms and voltage waveforms
of CX_rec . Figure 12c show the waveforms of line-to-line voltage uAB_inv and three-phase currents
iX_inv . The capacitor voltages of CX_inv , UdcX_rec are shown in Figure 12d.
Cont roll able f=20Hz f=30Hz f=40Hz f=50Hz Uncont roll able Cont roll able f=20Hz f=30Hz f=40Hz f=50Hz
Precharge m=0.4 m=0.6 m=0.8 m=0.9 Precharge Precharge min v=0.4 min v=0.6 min v=0.8 min v=0.9
Precharge
Udc A_rec
UdcX_rec (80V/div)
Udc B_rec
iX_rec (4A/div)
Udc C_rec
(a) (b)
INV-Si de f=20Hz f=30Hz f=40Hz f=50Hz INV-Si de f=20Hz f=30Hz f=40Hz f=50Hz
Without Worki ng m=0.4 m=0.6 m=0.8 m=0.9 Without Worki ng min v=0.4 min v=0.6 min v=0.8 min v=0.9
UAB-inv (100V/div)
UdcX_inv (80V/div)
Udc A_inv
Udc B_inv
iX_inv (4A/div)
Udc C_inv
(c) (d)
Figure 11. Experimental results of the whole working-process in transient-state condition; (a) Input
voltage–current waveforms, eA_rec and iX_rec ; (b) voltages of CX_rec ; (c) output voltage–current
waveforms, uAB_inv and iX_inv ; (d) voltages of CX_inv .
147
Energies 2018, 11, 1147
eA_rec (62V/div) f=20Hz,minv =0.4 f=30Hz,minv =0.6 f=20Hz,minv =0.4 f=30Hz,minv =0.6
eA_rec
Udc A_rec
UdcX_rec (80V/div)
iA_rec iB_rec iC_rec Udc B_rec
iX_rec (4A/div)
Udc C_rec
( )
(a) (b)
f=20Hz,minv =0.4 f=30Hz,minv =0.6 f=20Hz,minv =0.4 f=30Hz,minv =0.6
uAB_inv (80V/div)
UdcX_inv (80V/div)
Udc A_inv
Udc C_inv
iA_inv iB_inv iC_inv
(c) (d)
Figure 12. Experimental results of the whole working process in transient-state conditions; (a) Input
voltage–current waveforms, eA_rec and iX_rec ; (b) voltages of CX_rec ; (c) output voltage–current
waveforms, uAB_inv and iX_inv ; (d) voltages of CX_inv .
As can be seen from Figure 11a, when the output frequency f and modulation index minv are
20 Hz and 0.4, the peak value of three-phases on the rectifier side current iX_rec has low-frequency
fluctuations, and the sine effect is not ideal; when switching to f = 20Hz and minv = 0.4, the three-phase
current iX_rec stabilizes rapidly after about 25 ms, the sine is good, and the amplitude is basically the
same. In the process of switching, the entire control system can achieve a balanced three-phase current
and unity power factor control, and show good robust performance. UdcX_rec and UdcX_inv shown in
Figure 11b,d have almost no change when the frequency and modulation index switching. They are
constantly maintained at a fixed value, showing strong anti-interference performance. As shown in
Figure 11c, after switching, the inverter side line-to-line voltage uAB_inv and three-phase currents iX_inv
are rapidly stabilized, and the three-phase current change trend remains the same.
Obviously, the inverter side of the converter performs well in this case. Figure 13 shows the
experimental results in transient-state conditions with the modulation index set at 0.8 and 0.9 and
the output frequency f set from 40 Hz to 50 Hz. Figure 13a,c shows the same results as Figure 12 and
will not be repeated here. According to Figure 13b,d, voltages of rectifier side and inverter side are
maintained at their given values. At the same time, it becomes more stable after switching. Thus, the
effectiveness of the proposed three-level converter to capacitor voltage equalization control is verified.
148
Energies 2018, 11, 1147
(a) (b)
UdcX_inv(80V/div˅
UdcA_inv
uAB_inv UdcB_inv
UdcC_inv
iA_in v iB_in v iC_in v
(c) (d)
Figure 13. Experimental results of the multilevel converter in transient-state conditions; minv changes
from 0.8 to 0.9; (a) Input voltage-current waveforms, eA_rec and iX_rec ; (b) voltages of CX_rec ; (c) output
voltage–current waveforms, uAB_inv and iX_inv ; (d) voltages of CX_inv .
WTHD/%
fswitch/Hz
m
Figure 14. Harmonic characteristic results of WTHD curves of uAB_inv with f switch and minv .
WTHD is defined in Equation (16), where V 1 and Vn mean the fundamental and n order
harmonic components in line-to-line voltage respectively. As shown in Figure 14, WTHD of uAB _inv
increases with the decrease of switching frequency f switch and modulation index minv . It shows better
performance when minv > 0.4, while WTHD becomes taller when minv < 0.4 in some areas. In general,
the performance of the proposed converter can operate well.
∞ Vn2
WTHD = ∑ 2
/V1 , (16)
n =2 n
149
Energies 2018, 11, 1147
of 5/3 level converter has shown in Figure 15. Due to the similar structure, the control methods of 5/3
level voltage source converter are as same as the aforementioned methods of the three-level converter.
Phase C
Phase C
Phase B Phase B
Phase A Phase A
Rectifier Common Inverter Inverter
LC SIde Part Side I Side II RL load
eC C
S1 S2 S3 S4 S5 S6 S7
n eB ˳ B
LB ˲ 3 CX_inv A O
eA CA2
LA U CA1 CA3 iX_inv
The simulation result is shown in Figure 16. The whole working process shown in Figure 16a,
is divided into three sections: uncontrollable precharge, controllable precharge, and inverter side
working. In the uncontrollable precharge section, uncontrollable full wave rectification is achieved only
by diodes with anti-parallel device. Then the rectifier side starts in Power Unit II, and the voltages of
modules SMX1 and SMX2 are selected as 50 V and 100 V, respectively. Figure 16b,c shows line-to-line
voltages and three-phase currents of the rectifier side under the modulation index set at 1. Obviously,
the voltage reaches nine levels and the currents are undistorted sinusoidal waveforms.
100
0
-100
-200
10
iX (5A/div)
-10
uXX (100V/div)
100
100
0
0
-100
-100
-200
-200
15
15
10
10
iX (5A/div)
iX (5A/div)
5
5
0
0
-5
-5
-10
-10
-15
0.24 0.25 0.26 0.27 0.28 0.29 0.3 -15
0.8 0.81 0.82 0.83 0.84 0.85
t (0.1s/div)
t (0.1s/div)
(b) (c)
Figure 16. Simulation results of the whole working process; (a) Output voltage–current waveforms,
uxx and iX ; (b) Output voltage–current waveforms, uxx and iX ; time from 0.24s to 0.3s;(c) Output
voltage–current waveforms, uxx and iX ; time from 0.8 s to 0.86 s.
150
Energies 2018, 11, 1147
5. Conclusions
In order to balance the voltage of flying-capacitors, a novel three-level voltage source converter
for AC–DC–AC conversion was proposed in this paper. The circuit configuration and work principle of
the proposed three-level voltage source converter were studied in detail. The dual double-closed-loop
control strategy and voltage balancing algorithm, especially the method of inverter capacitors with
OSSC, were introduced to elaborate the control method of a three-level converter. Then, two operation
conditions were analyzed to assess the operating characteristics of the proposed converter. Finally, the
balanced control capabilities of this new topology to the three-phase suspension capacitor voltage of
the rectifier side and inverter side was verified by simulations and experiments.
Author Contributions: Conceptualization, Z.Y. and X.D.; Methodology, A.C.; Software, S.M.; Validation, A.C., T.W.
and S.M.; Formal Analysis, D.Y.; Investigation, T.W.; Resources, Z.Y.; Data Curation, D.Y.; Writing-Original Draft
Preparation, A.C.; Writing-Review & Editing, T.W.; Visualization, S.M.; Supervision, S.M.; Project Administration,
Z.Y.; Funding Acquisition, X.D.
Funding: This work has been partially supported by the Fundamental Research Funds for the Central Universities
under Award 2015XKMS030 and the National Natural Science Foundation of China (U1610113).
Conflicts of Interest: The authors declare no conflict of interest.
References
1. Nguyen, L.V.; Tran, H.D.; Johnson, T.T. Virtual prototyping for distributed control of a fault-tolerant modular
multilevel inverter for photovoltaics. IEEE Trans. Energy Convers. 2014, 29, 841–850. [CrossRef]
2. Alishah, R.S.; Hosseini, S.H.; Babaei, E.; Sabahi, M. A New General Multilevel Converter Topology Based
on Cascaded Connection of Submultilevel Units With Reduced Switching Components, DC Sources,
and Blocked Voltage by Switches. IEEE Trans. Ind. Electron. 2016, 63, 7157–7164. [CrossRef]
3. Buccella, C.; Cecati, C.; Cimoroni, M.G.; Razi, K. Analytical method for pattern generation in five-level
cascaded H-bridge inverter using selective harmonic elimination. IEEE Trans. Ind. Electron. 2014, 61,
5811–5819. [CrossRef]
4. Zamiri, E.; Vosoughi, N.; Hosseini, S.H.; Barzegarkhoo, R.; Sabahi, M. A New Cascaded Switched-Capacitor
Multilevel Inverter Based on Improved Series–Parallel Conversion with Less Number of Components.
IEEE Trans. Ind. Electron. 2016, 63, 3582–3594. [CrossRef]
5. Tolbert, L.M.; Fang, Z.P.; Thomas, G.H. Multilevel Converters for Large Electric Drives. IEEE Trans. Ind. Appl.
1999, 35, 36–44. [CrossRef]
6. Teymour, H.R.; Sutanto, D.; Muttaqi, K.M. Solar PV and Battery Storage Integration using a New
Configuration of a Three-Level NPC Inverter With Advanced Control Strategy. IEEE Trans. Energy Convers.
2014, 29, 354–365.
7. Pouresmaeil, E.; Montesinos-Miracle, D.; Gomis-Bellmunt, O. Control scheme of three-level NPC inverter for
integration of renewable energy resources into AC grid. IEEE Syst. J. 2012, 6, 242–253. [CrossRef]
8. Peng, F.Z.; Lai, J.S.; McKeever, J.W. A multilevel voltage-source inverter with separate DC sources for static
var generation. IEEE Trans. Ind. Appl. 1996, 32, 1130–1138. [CrossRef]
9. Pou, J.; Ceballos, S.; Knstantinou, G. Circulating current injection methods based on instantaneous
information for the modular multilevel converter. IEEE Trans. Ind. Electron. 2015, 62, 777–788. [CrossRef]
10. Meshram, P.M.; Borghate, V.B. A simplified nearest level control (NLC) voltage balancing method for
modular multilevel converter (MMC). IEEE Trans. Power Electron. 2015, 30, 450–462. [CrossRef]
11. Hatti, N.; Hasegawa, K.; Akagi, H. A 6.6-kV transformerless motor drive using a five-level diode-clamped
PWM inverter for energy savings of pumps and blowers. IEEE Trans. Power Electron. 2009, 24, 796–803.
[CrossRef]
12. Ghias, A.M.Y.M.; Pou, J.; Agelidis, V.G.; Ciobotaru, M. Optimal switching transition-based voltage balancing
method for flying capacitor multilevel converters. IEEE Trans. Power Electron. 2015, 30, 1804–1817. [CrossRef]
13. Oikonomou, N.; Gutscher, C.; Karamanakos, P.; Kieferndorfand, F.D.; Geyer, T. Model predictive pulse
pattern control for the five-level active neutral-point-clamped inverter. IEEE Trans. Ind. Appl. 2013, 49,
2583–2592. [CrossRef]
151
Energies 2018, 11, 1147
14. Roshankumar, P.; Rajeevan, P.P.; Mathew, K.; Leon, J.I.; Franquelo, L.G. A five-level inverter topology with
single-DC supply by cascading a flying capacitor inverter and an H-bridge. IEEE Trans. Power Electron. 2012,
27, 3505–3512. [CrossRef]
15. Ooi, G.H.P.; Maswood, A.L.; Lim, Z. Five-level multiple-pole PWM AC-AC converters with reduced
components count. IEEE Trans. Ind. Electron. 2015, 62, 4739–4748. [CrossRef]
16. Narimani, M.; Wu, B.; Cheng, Z.; Zargari, N.R. A new nested neutral point-clamped (NNPC) converter for
medium-voltage (MV) power conversion. IEEE Trans. Power Electron. 2014, 29, 6375–6382. [CrossRef]
17. Cortes, P.; Wilson, A.; Kouro, S.; Rodriguez, J.; Abu-Rub, H. Model predictive control of multilevel cascaded
H-bridge inverters. IEEE Trans. Ind. Electron. 2010, 57, 2691–2699. [CrossRef]
18. Kouro, S.; Malinowski, M.; Gopakumar, K.; Pou, J.; Franquelo, L.G.; Wu, B.; Rodriguez, J.; Perez, M.A.;
Leon, J.I. Recent Advances and Industrial Applications of Multilevel Converters. IEEE Trans. Ind. Electron.
2010, 57, 2553–2580. [CrossRef]
19. Veenstra, M.; Rufer, A. Hybrid Cascaded Control of a Hybrid Asymmetric Multilevel Inverter for Competitive
Medium-Voltage Industrial Drives. IEEE Trans. Ind. Appl. 2005, 41, 655–664. [CrossRef]
20. Venugopal, J.; Subarnan, G.M. Hybrid cascaded MLI topology using ternary voltage progression technique
with multicarrier strategy. J. Electr. Eng. Technol. 2015, 10, 1610–1620. [CrossRef]
21. Miranbeigi, M.; Iman-Eini, H.; Asoodar, M. A new switching strategy for transformer-less back-to-back
cascaded H-bridge multilevel converter. IET Power Electron. 2014, 7, 1868–1877. [CrossRef]
22. Kongnun, W.; Sangswang, A.; Chotigo, S. Design of a cascaded H-bridge converter for insulation testing.
In Proceedings of the IEEE International Symposium on Industrial Electronics, Seoul, Korea, 5–8 July 2009;
pp. 859–863.
23. Blahnik, V.; Peroutka, Z.; Talla, J. Control of cascaded H-bridge active rectifier providing active voltage
balancing. In Proceedings of the 40th Annual Conference of the IEEE Industrial Electronics Society, IECON
2014, Dallas, TX, USA, October–1 November 2015; pp. 4589–4594.
24. Islam, M.R.; Guo, Y.; Zhu, J.G. Performance and cost Comparison of NPC, FC and SCHB Multilevel Converter
Topologies for High-voltage Applications. In Proceedings of the International Conference on Electrical
Machines and Systems, Beijing, China, 20–23 August 2011; pp. 1–6.
25. Fazel, S.S.; Bernet, S.; Krug, D.; Jalili, K. Design and Comparison of 4-kv Neutral-point-clamped,
Flying-capacitor, and Series-connected H-bridge Multilevel Converters. IEEE Tran. Ind. Appl. 2007, 43,
1032–1040. [CrossRef]
26. Minambres-Marcos, V.; Guerrero-Martinez, M.A.; Romero-Cadaval, E.; Milanes-Montero, M.I. Generic Losses
Model for Traditional Inverters and Neutral Point Clamped Inverters. Electron. Electr. Eng. 2014, 20, 84–88.
[CrossRef]
27. Ye, Z.B.; Xu, Y.M.; Li, F.; Deng, X.M.; Zhang, Y.Z. Simplified PWM Strategy for Neutral-Point-Clamped (NPC)
Three-Level Converter. J. Power Electron. 2014, 14, 519–530. [CrossRef]
© 2018 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access
article distributed under the terms and conditions of the Creative Commons Attribution
(CC BY) license (http://creativecommons.org/licenses/by/4.0/).
152
energies
Article
A Reverse Model Predictive Control Strategy for
a Modular Multilevel Converter
Weide Guan, Shoudao Huang, Derong Luo * and Fei Rong
College of Electrical and Information Engineering, Hunan University, Changsha 410082, China;
[email protected] (W.G.); [email protected] (S.H.); [email protected] (F.R.)
* Correspondence: [email protected]; Tel.: +86-731-8882-2461
Abstract: In recent years, modular multilevel converters (MMCs) have developed rapidly, and are
widely used in medium and high voltage applications. Model predictive control (MPC) has attracted
wide attention recently, and its advantages include straightforward implementation, fast dynamic
response, simple system design, and easy handling of multiple objectives. The main technical
challenge of the conventional MPC for MMC is the reduction of computational complexity of the
cost function without the reduction of control performance of the system. Some modified MPC scan
decrease the computational complexity by evaluating the number of on-state sub-modules (SMs)
rather than the number of switching states. However, the computational complexity is still too high
for an MMC with a huge number of SMs. A reverse MPC (R-MPC) strategy for MMC was proposed
in this paper to further reduce the computational burden by calculating the number of inserted
SMs directly, based on the reverse prediction of arm voltages. Thus, the computational burden was
independent of the number of SMs in the arm. The control performance of the proposed R-MPC
strategy was validated by Matlab/Simulink software and a down-scaled experimental prototype.
Keywords: model predictive control (MPC); computational burden; reverse prediction; modular
multilevel converter (MMC)
1. Introduction
Multilevel converters have been widely used in medium and high voltage applications in recent
years [1–3]. Among various multilevel converters, the modular multilevel converter (MMC) has become
more popular because of its scalability, modularity, and redundancy. An MMC can be used in many
high-power applications; for example, high-voltage direct current (HVDC) systems, static synchronous
compensators, grid-connected systems, and medium/high voltage motor drive systems [4–6].
There are some technical challenges for the control of an MMC, such as the balance of sub-module
(SM) capacitor voltages, the suppression of circulating currents, and the tracking of output currents.
Many control and modulation methods have been proposed to address these issues. Among them,
model predictive control (MPC) is an interesting control scheme for the MMC. Its advantages include
straightforward implementation, fast dynamic response, and suitability for dealing with multiple
objectives [7–9].
Reference [10] first applied the conventional MPC scheme to MMC, in which the output currents,
SM capacitor voltages, and circulating currents were controlled together by the evaluation for all
the possible switching states in a cost function. In Reference [11], the proportional integral (PI)
control method was experimentally compared with the conventional MPC scheme for MMC, and the
conclusion was that the MPC scheme had better control performance than PI method, either for
steady-state or dynamic performance. In Reference [12,13], similar methods based on conventional
MPCs were used to control the MMC by evaluating for all the possible switching states of SMs.
2. Mathematical Model
The topology of the MMC and the single-phase equivalent circuit are shown in Figure 1. The MMC
was comprised of three phase legs, and each leg contained an upper arm and a lower arm, which were
represented by the subscript “p” and “n”, respectively. Each arm included an arm inductor Lo and N
SMs. The arm inductor limited the di/dt of the circulating currents caused by instantaneous voltage
154
Energies 2019, 12, 297
differences within the arms. The SMs usually adopted half-bridge structure, which contained two
switches (T1 and T2 ) and one capacitor (CSM ). The SMs generally worked in two switching states,
namely, on-state and off-state. On-state: The SM output voltage was the capacitor voltage ucij (i = p, n,
j = 1, 2, . . . , N) when T1 was turned ON and T2 was OFF. Off-state: The output voltage of the SM is
zero when T1 was turned OFF and T2 was ON. The switching states of SMs could be written as follows:
1, T1 is ON, T2 is OFF
Sij = (1)
0, T1 is ON, T2 is OFF
iS uS
iGLII
iR
iQ uQ
(a) (b)
Figure 1. The illustrative diagram of a modular multilevel converter (MMC) (a) The topology and
(b) the single-phase equivalent circuit.
The capacitor voltage dynamic equation for each SM of the MMC is expressed as follows:
ducij
= icij /CSM (2)
dt
where icij is the capacitor current, which can be obtained from the switching state Sij and the arm
current ii as follows:
icij = Sij ii (3)
where idiff is the circulating current, io is the output current, and they can be calculated by:
io = ip − in
(5)
idiff = 12 (ip + in )
155
Energies 2019, 12, 297
Based on Equations (4)–(6), the dynamic equation of the MMC can be obtained as:
⎧
⎪
⎪ dio un − up − 2Rio − 2e
⎨ =
dt Lo + 2L (7)
⎪
⎪ didiff Udc − (un + up )
⎩ =
dt 2Lo
Equation (7) indicates that the output current and the circulating current can be regulated directly
by the voltage difference and voltage summation between the lower arm voltage un and upper arm
voltage up , respectively.
3. MPC Strategy
Sij ii (k ) Ts
ucij (k + 1) = ucij (k ) + (9)
CSM
where λ1 , λ2 , and λ3 are the function weighing factors, io∗ (k + 1), idiff∗ ( k + 1), U /N are the reference
dc
p p p
values of control objectives, and io (k + 1), idiff (k + 1), and ucij (k + 1) are the next-step predicted values
of control objectives, respectively.
The block diagram of conventional MPC is shown in Figure 2a. Within each sampling period of
MPC strategy, the cost function was evaluated one step ahead, and the switching state that minimized
the cost function was chosen and used to control the converter at next switching cycle by evaluating
for all the possible switching states of the converter.
Nevertheless, the number of all possible switching states for an MMC with N SMs in each bridge
N
is C2N . For example, an MMC used for HVDC usually has more than 100 SMs per arm, thus the
156
Energies 2019, 12, 297
number of all possible switching states in one phase is more than 9 × 1058 . Therefore, it is challenging
to implement the conventional MPC by the existing digital processors in practical applications due to
large computation load.
iGLII k iGLII k
iR k iR k
uFij k uFij k
iRS k + iRS k +
iR k + S
iGLII k + Sij k+ iR k + S
iGLII k +
Sij k+ iGLII k + uFSij k + iGLII k + uFSij k +
nS k+
nQ k+
() ()
iGLII k
iR k
uFij k
(c)
Figure 2. Control schemes of a model predictive control (MPC). (a) A conventional MPC, (b) an indirect
MPC, and (c) the proposed inverse MPC.
157
Energies 2019, 12, 297
The balancing of SM capacitor voltage is one of key issues in MMC. The modified MPC generally uses
the conventional sorting method (e.g., bubble sorting) to balance the SM capacitor voltages [16,18,20,22],
in which all of the SM capacitor voltages have to be sorted in ascending or descending order to
determine the inserted SMs with the highest or lowest voltages. However, the sorting algorithm
itself is not a trivial task when MMC has huge number of SMs. Therefore, many improved sorting
methods were presented to reduce the computational complexity, such as grouping sorting method [17],
fundamental-frequency sorting method [23], limited sorting method [24], etc. In general, as long as
several SMs with the highest or lowest voltages are selected, the voltage balance task can be completed
within an allowable range of voltages ripples, while the rest SMs need not be sorted to reduce the
computational burden. In addition, using the parallel computing method, FPGA (Field Programmable
Gate Array) can be used to complete the SM capacitor voltage balancing task more quickly, which does
not occupy CPU resources [9,16].
After the sorting task, assuming all of the capacitor voltages are balanced well, then the number
of on-state SMs for upper arm and lower arm at next-step can be calculated if the next-step arm voltage
can be predicted.
From Equation (7), the arm voltages can be written as follows:
Udc
up = 2 − Lo didtdiff − ( L2o + L) didto − Rio − e
Udc (13)
un = 2 − Lo didtdiff + ( L2o + L) didto + Rio + e
dx x ( k ) − x ( k − 1)
= (14)
dt Ts
The discrete-time dynamic models of the arm voltages of MMC can be written as follows:
Udc Lo Lo /2+ L Lo /2+ L
up ( k ) = 2 − Ts [idiff ( k ) − idiff ( k − 1)] − ( Ts + R ) io ( k ) + Ts io ( k − 1) − e ( k )
Udc Lo Lo /2+ L Lo /2+ L (15)
un ( k ) = 2 − Ts [idiff ( k ) − idiff ( k − 1)] + ( Ts + R ) io ( k ) − Ts io ( k − 1) + e ( k )
Assuming the next-step reference values of control objectives can be tracked without error, thus,
p p
the next-step predicted arm voltages up (k + 1) and un (k + 1) can be obtained by shifting forward
(Equation (15)), as follows:
p Lo ∗ Lo /2+ L Lo /2+ L
up ( k + 1) = Udc
2 − Ts [idiff ( k + 1) − idiff ( k )] − ( Ts + R)io∗ (k + 1) + Ts io ( k ) − e ∗ ( k + 1)
p Lo ∗ Lo /2+ L Lo /2+ L (16)
un ( k + 1) = Udc
2 − Ts [idiff ( k + 1) − idiff ( k )] + ( Ts + R)io∗ (k + 1) − Ts io ( k ) + e ∗ ( k + 1)
158
Energies 2019, 12, 297
where ucp_avg (k) and ucn_avg (k ) are the average arm voltages of the MMC (upper arm and lower arm).
The number of control options of the proposed R-MPC strategy was further reduced to one by
calculating the number of on-state SMs directly based on the reverse prediction of arm voltages. Thus,
the computational burden was independent of the number of SMs in the arm. This strategy was
especially suitable for the MMC which has huge number of SMs. The number of control options for
different MPC strategies are listed in Table 1. As can be seen from this table, fast MPC and proposed
R-MPC have the least computational complexity, especially for the MMC with hundreds of SMs.
It should be noted that the computational burden of R-MPC is independent of the number of SMs,
but the computational burden of sorting algorithm is still related to the number of SMs. However,
the sorting algorithm can be improved by other means [9,16,17,23,24] to reduce its computational load.
4. Simulation Results
As shown in Figure 1, a three-phase MMC system was investigated in MATLAB/Simulink
softwareto validate the control performance of the proposed R-MPC strategy. Table 2 lists the
parameters of the MMC.
159
Energies 2019, 12, 297
()
()
()
Figure 3. Simulation results of steady-state operation: (a) fast MPC, (b) indirect MPC, (c) proposed
R-MPC. Subplots: from top to bottom, capacitor voltages of phase a, three-phase output voltages,
three-phase output currents, arm currents of phase a, and circulating current of phase a.
Figure 4 shows the harmonic spectrums of the output voltages and currents with proposed R-MPC.
The THDs of output voltages and currents were only 1.88% and 2.02%, respectively. The results showed
that the low-order harmonics were very small and within acceptable range. Thus, the noises generated
by prediction did not affect the quality of the generated voltages/currents.
160
Energies 2019, 12, 297
Figure 4. Harmonic spectrums of the output voltages and currents with proposed reverse model
predictive control (R-MPC).
Figure 5 shows the comparison of output SM states between the traditional nearest level
modulation (NLM) method and the R-MPC strategy proposed in this paper. The NLM method just
obtains the nearest level state from the reference voltage, according to the tracking of output currents,
however, R-MPC strategy considers not only the tracking of output current but also the suppressing of
circulating current and the system delay compensation. Thus, the two methods generated different
SM states and switching sequences.
Figure 5. Comparison of output sub-module (SM) states between the traditional nearest level
modulation (NLM) method and the R-MPC strategy.
161
Energies 2019, 12, 297
()
()
()
Figure 6. Simulation results of dynamic operation: (a) a fast MPC, (b) an indirect MPC, and (c) the proposed
R-MPC. Subplots: from top to bottom, capacitor voltages of phase a, three-phase output voltages,
output current of phase a, arm currents of phase a, and circulating current of phase a.
The results showed that the indirect MPC and the proposed R-MPC both had better dynamic-state
performance than the fast MPC. However, for the MMC with hundreds of SMs, the R-MPC had more
advantages due to less computational burden.
162
Energies 2019, 12, 297
5. Experimental Results
Figure 7 shows a down-scaled experimental prototype of the MMC (2 kVA), setup to verify the
control performance of the proposed R-MPC.A DSP/FPGA-based central control board was chosen to
complete the control scheme. The DSP (TI TMS320F28335) was used for mathematical calculations
and the MPC algorithm. The FPGA (Altera EP2C8Q208C8) was used for Pulse-width modulation
(PWM) generation, the sorting algorithm of capacitor voltages, and fault protection. Table 2 lists the
parameters of the experimental prototype.
It should be noted that a larger load resistance than that of simulation was chosen because the
experimental prototype could only operate in the passive inversion state (limited by the experimental
conditions), but the simulation model operated in the active inversion state, which simulated the
working characteristics of HVDC. In addition, also limited by the experimental conditions, the SM
capacitance was also smaller than that of simulation, which would increase the capacitor voltage
ripple slightly. Despite the above differences in load and capacitor parameters, it would not affect the
performance comparison and analysis of different control strategies.
() ()
Figure 8. Cont.
163
Energies 2019, 12, 297
() ()
() ()
Figure 8. Experimental results of steady-state operation: (a,b) a fast MPC, (c,d) an indirect MPC,
(e,f) the proposed R-MPC. Scopes: from top to bottom, first capacitor voltage of phase a (25 V/div),
arm current of phase a (5 A/div), output voltage of phase a (100 V/div), and output current of phase
a (10 A/div). Time scale: 50 ms/div.
164
Energies 2019, 12, 297
(a) (b)
(c)
Figure 9. Experimental results of dynamic operation: (a) a fast MPC, (b) an indirect MPC,
(c) the proposed R-MPC. Scopes: from top to bottom, first capacitor voltage of phase a (25 V/div),
arm current of phase a (5 A/div), output voltage of phase a (100 V/div), and output current of phase
a (10 A/div). Time scale: 20 ms/div.
6. Conclusions
In order to reduce the computational complexity of MPC for MMC, this paper proposed a R-MPC
strategy. Compared with the fast MPC and indirect MPC, the number of control options to be
calculated of proposed R-MPC was greatly reduced to one by calculating the number of on-state SMs
directly based on the reverse prediction of arm voltages. The simulation and experimental results of
steady-state operation showed that the fast MPC, an indirect MPC, and the proposed R-MPC all had
good steady-state performance, but fast MPC and the proposed R-MPC had more advantages than
indirect MPC because of less computational burden. However, the simulation and experimental results
of dynamic operation showed that the proposed R-MPC had better dynamic-state performance than
the fast MPC. Therefore, the proposed R-MPC strategy would be especially suitable for an MMC with
hundreds of SMs because of less computational burden and good performance of both steady-state
and dynamic operation.
Author Contributions: W.G. and D.L. put forward the idea and designed the proposed strategy; W.G. and F.R.
completed the simulation and experiment; S.H. managed the project; and W.G. wrote the paper. All authors gave
advice for the manuscript.
Funding: This research was funded in part by the State Key Program of National Natural Science of China
(Grant number 51737004) and in part by the Natural Science Foundation of Hunan Province, China (Grant number
2018JJ2045).
Conflicts of Interest: The authors declare no conflict of interest.
165
Energies 2019, 12, 297
References
1. Dekka, A.; Wu, B.; Fuentes, L.R.; Perez, M.; Zargari, R.N. Evolution of Topologies, Modeling, Control
Schemes, and Applications of Modular Multilevel Converters. IEEE J. Emerg. Sel. Top. Power Electron. 2017,
5, 1631–1656. [CrossRef]
2. Grandi, G.; Loncarski, J.; Dordevic, O. Analysis and Comparison of Peak-to-Peak Current Ripple in Two-Level
and Multilevel PWM Inverters. IEEE Trans. Ind. Electron. 2015, 62, 2721–2730. [CrossRef]
3. Zhetessov, A.; Ruderman, A. Time-domain optimization of current THD for a single-phase three-level
inverter modulation. In Proceedings of the 19th International Conference on Electrical Drives and Power
Electronics (EDPE), Dubrovnik, Croatia, 4–6 October 2017; pp. 82–87. [CrossRef]
4. He, L.; Zhang, K.; Xiong, J.; Fan, S. A Repetitive Control Scheme for Harmonic Suppression of Circulating
Current in Modular Multilevel Converters. IEEE Trans. Power Electron. 2015, 30, 471–481. [CrossRef]
5. Zhang, M.; Huang, L.; Yao, W.; Lu, Z. Circulating Harmonic Current Elimination of a CPS-PWM-Based
Modular Multilevel Converter with a Plug-In Repetitive Controller. IEEE Trans. Power Electron. 2014,
29, 2083–2097. [CrossRef]
6. Zeng, R.; Xu, L.; Yao, L.; Finney, J.S.; Wang, Y. Hybrid HVDC for Integrating Wind Farms with Special
Consideration on Commutation Failure. IEEE Trans. Power Deliv. 2016, 31, 789–797. [CrossRef]
7. Dekka, A.; Wu, B.; Yaramasu, V.; Fuentes, L.R.; Zargari, R.N. Model Predictive Control of High-Power
Modular Multilevel Converters–An Overview. IEEE J. Emerg. Sel. Top. Power Electron. 2018, (Early Access).
[CrossRef]
8. Leuer, M.; Lönneker, M.; Böcker, J. Model predictive control strategy for multi-phase thyristor matrix
converters—Advantages, problems and solutions. In Proceedings of the 18th European Conference on
Power Electronics and Applications (EPE’16 ECCE Europe), Karlsruhe, Germany, 6–8 September 2016;
pp. 1–10. [CrossRef]
9. Guo, P.; He, Z.; Yue, Y.; Xu, Q.; Huang, X.; Chen, Y.; Luo, A. A Novel Two-Stage Model Predictive Control for
Modular Multilevel Converter with Reduced Computation. IEEE Trans. Ind. Electron. 2019, 66, 2410–2422.
[CrossRef]
10. Qin, J.; Saeedifard, M. Predictive Control of a Modular Multilevel Converter for a Back-to-Back HVDC
System. IEEE Trans. Power Deliv. 2012, 27, 1538–1547. [CrossRef]
11. Böcker, J.; Freudenberg, B.; The, A.; Dieckerhoff, S. Experimental Comparison of Model Predictive Control
and Cascaded Control of the Modular Multilevel Converter. IEEE Trans. Power Electron. 2015, 30, 422–430.
[CrossRef]
12. Dekka, A.; Wu, B.; Yaramasu, V.; Zargari, R.N. Model Predictive Control With Common-Mode Voltage
Injection for Modular Multilevel Converter. IEEE Trans. Power Electron. 2017, 32, 1767–1778. [CrossRef]
13. Zhou, D.; Yang, S.; Tang, Y. A Voltage-Based Open-Circuit Fault Detection and Isolation Approach for
Modular Multilevel Converters with Model-Predictive Control. IEEE Trans. Power Electron. 2018, 33, 9866–9874.
[CrossRef]
14. Perez, A.M.; Rodriguez, J.; Fuentes, J.E.; Kammerer, F. Predictive Control of AC–AC Modular Multilevel
Converters. IEEE Trans. Ind. Electron. 2012, 59, 2832–2839. [CrossRef]
15. Dekka, A.; Wu, B.; Yaramasu, V.; Zargari, R.N. Integrated model predictive control with reduced switching
frequency for modular multilevel converters. IET Electr. Power Appl. 2017, 11, 857–863. [CrossRef]
16. Vatani, M.; Bahrani, B.; Saeedifard, M.; Hovd, M. Indirect Finite Control Set Model Predictive Control of
Modular Multilevel Converters. IEEE Trans. Smart Grid 2015, 6, 1520–1529. [CrossRef]
17. Liu, P.; Wang, Y.; Cong, W.; Lei, W. Grouping-Sorting-Optimized Model Predictive Control for Modular
Multilevel Converter with Reduced Computational Load. IEEE Trans. Power Electron. 2016, 31, 1896–1907.
[CrossRef]
18. Gong, Z.; Dai, P.; Yuan, X.; Wu, X.; Guo, G. Design and Experimental Evaluation of Fast Model Predictive
Control for Modular Multilevel Converters. IEEE Trans. Ind. Electron. 2016, 63, 3845–3856. [CrossRef]
19. Dekka, A.; Wu, B.; Yaramasu, V.; Zargari, R.N. Dual-Stage Model Predictive Control with Improved Harmonic
Performance for Modular Multilevel Converter. IEEE Trans. Ind. Electron. 2016, 63, 6010–6019. [CrossRef]
20. Mahmoudi, H.; Aleenejad, M.; Ahmadi, R. Modulated Model Predictive Control of Modular Multilevel
Converters in VSC-HVDC Systems. IEEE Trans. Power Deliv. 2018, 33, 2115–2124. [CrossRef]
166
Energies 2019, 12, 297
21. Moon, J.; Gwon, J.; Park, J.; Kang, D.; Kim, J. Model Predictive Control with a Reduced Number of Considered
States in a Modular Multilevel Converter for HVDC System. IEEE Trans. Power Deliv. 2015, 30, 608–617.
[CrossRef]
22. Wang, Y.; Cong, W.; Li, M.; Li, N.; Cao, M.; Lei, W. Model predictive control of modular multilevel converter
with reduced computational load. In Proceedings of the IEEE Applied Power Electronics Conference and
Exposition–APEC, Fort Worth, TX, USA, 16–20 March 2014; pp. 1776–1779. [CrossRef]
23. Qin, J.; Saeedifard, M. Reduced Switching-Frequency Voltage-Balancing Strategies for Modular Multilevel
HVDC Converters. IEEE Trans. Power Deliv. 2013, 28, 2403–2410. [CrossRef]
24. Tu, Q.; Xu, Z.; Xu, L. Reduced Switching-Frequency Modulation and Circulating Current Suppression for
Modular Multilevel Converters. IEEE Trans. Power Deliv. 2011, 26, 2009–2017. [CrossRef]
25. Cortes, P.; Rodriguez, J.; Silva, C.; Flores, A. Delay Compensation in Model Predictive Current Control of
a Three-Phase Inverter. IEEE Trans. Ind. Electron. 2012, 59, 1323–1325. [CrossRef]
© 2019 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access
article distributed under the terms and conditions of the Creative Commons Attribution
(CC BY) license (http://creativecommons.org/licenses/by/4.0/).
167
energies
Article
A Simplified Model Predictive Control for T-Type
Inverter with Output LC Filter
Van-Quang-Binh Ngo 1,2, Minh-Khai Nguyen 3, Tan-Tai Tran 1, Young-Cheol Lim 1 and
Joon-Ho Choi 1,*
1 Department of Electrical Engineering, Chonnam National University, Gwangju 500-757, Korea;
[email protected] (V.-Q.-B.N.); [email protected] (T.-T.T.); [email protected] (Y.-C.L.)
2 Department of Physics, College of Education, Hue University, Thua Thien Hue 530000, Vietnam
3 Department of Electrical Engineering, Chosun University, Gwangju 61452, Korea; [email protected]
* Correspondence: [email protected]
Abstract: In this paper, a model predictive control scheme for the T-type inverter with an output LC
filter is presented. A simplified dynamics model is proposed to reduce the number of the measurement
and control variables, resulting in a decrease in the cost and complexity of the system. Furthermore,
the main contribution of the paper is the approach to evaluate the cost function. By employing the
selection of sector information distribution in the reference inverter voltage and capacitor voltage
balancing, the execution time of the proposed algorithm is significantly reduced by 36% compared
with conventional model predictive control without too much impact on control performance.
Simulation and experimental results are studied and compared with conventional finite control
set model predictive control to validate the effectiveness of the proposed method.
Keywords: finite control set model predictive control; T-type inverter; computational cost; LC filter;
DC-link capacitor voltage balancing
1. Introduction
Recently, the multilevel converter has been widely applied to various applications such as
renewable energy system, flexible AC transmission systems and electric drives thanks to its benefits:
increase the power capacity of the converter and improve the quality of the system [1–3]. In particular,
compared with the neutral-point-clamped (NPC) type, the T-type inverter topology has the advantage
in terms of the efficiency for medium switching frequency [4–6]. Thus, the T-type inverter is considered
to be an alternative solution for multilevel inverter. Like the NPC converter, the unbalance of
neutral-point potential is the drawback of this topology which causes the distortion of the output
voltage and current. However, several approaches have been introduced to solve this problem [7–10].
A linear controller with proportional-integral (PI) is typically applied to control the converter
because of its simplicity and stability [11,12]. However, this approach has a low dynamic response
and requires a complex modulation technique for balancing the DC-link capacitor voltage. Recently,
direct power control [13] which uses a switching look-up table for determining the switching state has
been introduced to improve the performance. Nonetheless, it requires a high sampling frequency to
achieve an acceptable steady-state and high dynamic performances. To deal with this disadvantage,
several control approaches have been proposed such as using direct power control with space vector
modulation [14], fuzzy control [15], sliding mode control [16], and predictive control [17–19].
In recent years, a finite control set model predictive control (FCS-MPC) is considered as an
attractive alternative control strategy for power converters due to its simple structure, facilitating
implementation, and fast dynamic response [20–25]. Furthermore, compared with classical control,
the FCS-MPC provides the advantages such as easy inclusion of nonlinearities and constraints in the
controller. However, at each sampling period, the prediction of control variables is 27, corresponding
to the three-level T-type inverter, leading to producing a high computational cost. In [26], a simplified
FCS-MPC for three-level voltage source converter is introduced. In order to reduce the computational
time, this approach used the two-level switching state group for prediction and optimization. Another
approach is presented in [27], which employs equivalent transformations in the cost function for the
optimization loop. Another approach is proposed in [28,29] based on using a modified sphere decoding
algorithm for multilevel converters. In [30], a sector distribution and non-zero voltage vectors are
exploited with the aim to reduce the computational burden for two-level converters. Nonetheless,
the main disadvantage of this method is the nonexistence of zero voltage leading to an increase of
the total harmonic distortion (THD) in the load current. In [31], the control approach is suggested
based on the candidate region that minimizes the sub-cost function to reduce the execution time. The
presented technique in [32] combined the conventional FCS-MPC, a look-up table, and steady-state
evaluation to reduce the computational burden. However, this algorithm can have a large amount of
computational cost like the conventional FCS-MPC in the worst case.
With a three-level T-type inverter, control variables are predicted by using the predictive model
and measured variables such as DC-link capacitor voltage, output voltage, filter current, and output
current. In order to reduce the cost and complexity of this system, a simplified dynamics model is
presented in this paper. Moreover, the highlight of this research is the significant computational cost
reduction without decreasing the quality of control by preselecting the required inverter output voltage.
The balance of DC-link capacitor voltage is guaranteed by determining the suitable small voltage
vectors resulting in the elimination of the weighting factor in the cost function. As a consequence,
the amount of predictive state for loop optimization is reduced from 27 to 6 compared with the
conventional FCS-MPC method. This means that it is easy to implement the proposed algorithm in a
real-time system with a low-cost processor and to extend with a long prediction horizon for improving
the control performance. The simulation and experimental results validate the effectiveness of the
proposed control strategy.
The rest of this paper is organized as follows: a reduced model predictive control for the three-level
T-type inverter is presented in Section 2. Next, the proposed algorithm is explained in Section 3 for
reducing the computational cost. In Section 4, a comparative study of the conventional FCS-MPC and
the proposed method is examined. Finally, the conclusions are given in Section 5.
2.1. Topology
A simple topology of the three-level T-type inverter (3L-T-type) is shown in Figure 1. The basic
principle of this configuration can be expressed by three switching states [P], [N] and [O] which
correspond to three inverter output voltages +Udc /2, −Udc /2 and 0. Consequently, 27 possible
switching configurations are considered for a 3L-T-type inverter. Table 1 presents the summary of the
operating principle for 3L-T-type.
169
Energies 2019, 12, 31
S2a S3a
iz B i fb iob
U dc Z
S2b S3b
i fc C ioc
uC1 C1
S2c S3c
uc Cf
iC1
S4a S4b S4c
2
uinv = u AZ + ku BZ + k2 uCZ , (1)
3
√
where u AZ , u BZ , and uCZ are the output phase voltages; k = e j2π/3 = − 12 + j 23 .
The phase voltage u xZ is calculated in terms of DC-link voltage Udc and switching state Sx
as [9,22]:
U
u xZ = Sx dc , (2)
2
where Sx represents the switching status and has three possible values: {−1, 0, 1} with the index
x ∈ { a, b, c}.
The dynamic behavior of LC filter can be described by the following:
di f
Lf = uinv − uc , (3)
dt
duc
Cf = i f − io ,
dt
where uinv and uc are the inverter and output capacitor voltage vectors; i f and io are the filter and
output load current vectors and L f , C f are the filter inductance and capacitance.
The control variables uc and i f are measured while uinv is obtained from Equations (1) and (2).
In general, io is measured or estimated by using an observer, leading to an increase in the cost and
complexity of the system. In this paper, to achieve a simple model, we assume that the output load
current is derived from output capacitor voltage. Thus, Equation (3) is rewritten as:
duc 1 uc
= if − , (4)
dt Cf R Load
di f 1
= (u − uc ) ,
dt L f inv
170
Energies 2019, 12, 31
In order to reduce the number of the control variable, the neutral-point voltage is taken into
account in the model instead of two capacitor voltages (uC1 , uC2 ). The neutral-point voltage (uz ) can
be expressed based on the assumption that the DC-link voltage is kept constant and C1 = C2 = C
as follows:
duz d uC1 − uC2 1 1
= = − iz = − (1 − | Sa |)i f a + (1 − | Sb |)i f b + (1 − | Sc |)i f c . (5)
dt dt C C
Consequently, we have a representation of the dynamics model based on Equations (4) and (5) as:
duc 1 uc
= if − , (6)
dt Cf R Load
di f 1
= (u − uc ) ,
dt L f inv
duz 1
=− (1 − | Sa |)i f a + (1 − | Sb |)i f b + (1 − | Sc |)i f c .
dt C
where u∗cα (k + 1), u∗cβ (k + 1) and ucα (k + 1), ucβ (k + 1) indicate the real and imaginary components of
p p
the reference and predicted output capacitor voltages at instant k + 1, respectively. λuz is the weighting
factors of the capacitor voltage balancing.
To achieve the discrete-time model, the first-order Euler approximation is used as:
dx x ( k ) − x ( k − 1)
= , (8)
dt Ts
Ts Rload C f Rload
uc (k ) = i (k) + u c ( k − 1). (9)
C f Rload + Ts f C f Rload + Ts
By shifting the output voltage in Equation (9) into one future sample, we have the predicted
output voltage at instant k + 1:
p Ts Rload p C f Rload
u c ( k + 1) = i ( k + 1) + u c ( k ). (10)
C f Rload + Ts f C f Rload + Ts
The discrete-time form for the filter current is given by using the forward Euler approximation as:
p Ts
i f ( k + 1) = i f ( k ) + (u (k) − uc (k)) . (11)
L f inv
171
Energies 2019, 12, 31
p Ts
u z ( k + 1) = u z ( k ) − (1 − |Sa |) i f a (k) + (1 − |Sb |) i f b (k) + (1 − |Sc |) i f c (k) . (12)
C
Substituting Equation (11) into Equation (10), the predicted output voltage is rewritten as:
p Ts Rload Ts2 Rload Rload T2
u c ( k + 1) = i (k) + uinv (k ) + Cf − s uc (k ). (13)
C f Rload + Ts f L f C f Rload + Ts C f load + Ts
R Lf
T
A control input is a sequential switch state S p = S pa S pb S pc , symbolized as a set of p vector
S p ∈ {1, ..., 27}. Furthermore, the switching inputs a finite set: S px ∈ {−1, 0, 1} with the index
x ∈ { a, b, c}. As a result, the optimal switching input Sopt is achieved as the result of Equation (14):
The space voltage vector of 3L-T-type inverter can be classified into four groups: zero vectors
(from u25 to u27 ), small vectors (from u13 to u24 ), medium vectors (u2 , u4 , u6 , u8 , u10 , and u12 ) and large
vectors (u1 , u3 , u5 , u7 and u9 ), wherein the small vectors are divided into two types: positive state (P)
and negative state (N) such as u14 and u13 , respectively. The neutral-point voltage is increased with
the positive state and decreased with the negative state, respectively [33]. The zero, medium and large
vectors do not affect the neutral-point voltage deviation. In the conventional FCS-MPC, the capacitor
voltage balancing can be solved by adjusting the weighting factor in the cost function. However, it is
not easy to obtain the optimal weighting factor value leading to affecting the THD of the load current.
In this study, the capacitor voltages are balanced by selecting the suitable small vectors that depend on
the predicted neutral-point voltage. Therefore, the proposed method is simple due to no requirement
of the weighting factor for balancing capacitor voltages in the cost function.
For the 3L-T-type inverter, 27 switching states are considered to evaluate the cost function.
Long prediction horizon can improve the control performance. However, the computational cost
is increased exponentially corresponding to the prediction horizon. Therefore, it leads to a large
computational cost which makes it difficult to implement the algorithm in common digital signal
processing. In this paper, the selection of sector distribution is employed with the aim to solve this
problem. The main idea of the proposed method is to determine the position of inverter reference
voltage which is obtained from the predictive model. In this case, the required inverter voltage
∗ ( k ) is achieved based on Equation (13) by replacing the predicted output voltage u p ( k + 1) with its
uinv c
reference. Then, the location of the reference voltage uinv ∗ ( k ) is determined by its components u∗
invα
∗ . In the proposed method, we divide the space vector of the 3L T-type inverter into six sectors
and uinvβ
as illustrated in Figure 2. For example, when the reference voltage uinv ∗ ( k ) is in sector I, there are only
10 voltage vectors which are selected for the evaluation of the cost function. As previously discussed,
the neutral-point voltage is predicted based on the previous optimal switching states and filter currents
by using Equation (5). In order to achieve the balance of capacitor voltages, two cases are considered:
the first one corresponds to uz ≤ 0 and the second one to uz > 0. The positive small vectors (u14 , u15 )
and negative small vectors (u13 , u16 ) are considered with the condition uz ≤ 0 and uz > 0, respectively.
Zero vectors can reduce from 3 to 1 due to the same value and without the effect of voltage imbalance.
In this case, the feasible voltage vectors are u1 , u2 , u3 , u14 , u15 , u25 for uz ≤ 0, whereas they are u1 , u2 ,
u3 , u13 , u16 , u25 for uz > 0, respectively. Table 2 illustrates the available inverter voltage vectors for a
3L-type inverter after obtaining the appropriate sector. Thus, the prediction of the control variable
for cost function loop optimization is decreased from 27 to 6 with the proposed method. As a result,
compared with the conventional FCS-MPC method, the computational cost is appreciably reduced by
about 77% in the proposed algorithm. It is obvious that this advantage is more attractive to real-time
172
Energies 2019, 12, 31
implementation with low-cost digital hardware and long prediction horizon. The overall control
strategy of the proposed method is shown in Figure 3. Then, the optimal switching state is applied to
the inverter by minimizing this cost function:
gmd f = u∗cα (k + 1) − ucα (k + 1) + u∗cβ (k + 1) − ucβ (k + 1) ,
p p
(15)
Sopt = arg{min gmd f }, p = 1, ..., 6.
Sector II
E
u5 [-1 1 -1] u4 [0 1 -1] u3 [1 1 -1]
Sector Sector I
u18 u17 u16 u15 u2
III u6
[0 1 0] [-1 0 -1] [0 0 -1] [1 1 0] [1 0 -1]
[-1 1 0]
*
uinv (k )
u19 [0 1 1] u25 u14 [1 0 0]
u7 [1 -1 -1]
[-1 1 1]
u20 [-1 0 0] u26 u27
u13 [0 -1- 1] u1 D
uC 2
U dc Z LC Load
uC1 Filter
3L-T-type
Sabc ( k )
Minimization of
uc* cost function g
n 1,..., 6
ucp (k 1)
if
uc*
Select Sector Predictive uc
uc
sector model uz
if
U dc
173
Energies 2019, 12, 31
Start
For j = 1 to 6
If g ( j ) g opt
g opt g ( j)
xopt j
No
j 6
Yes
174
Energies 2019, 12, 31
uc_ref uc_ref
Reference voltage
sector
uc u_c
Figure 6 shows the steady-state of the proposed method with the output voltage at 155 V.
As depicted in Figure 6, the proposed method obtains the sinusoidal output voltage and the balance
of DC-link capacitor voltage. The characteristic of the variable switching frequency is illustrated
in Figure 6c. This can increase the THD of the load current, but this does not affect the control
performance too much. The THD of the load current can receive further improvements by using
alternative methods. However, this is not the main focus of this paper and will not be developed here.
175
Energies 2019, 12, 31
200 310
uca ucb ucc
150 uC1
uC2
100 305
50
Voltage [V]
Voltage [V]
0 300
-50
-100 295
-150
-200 290
0.015 0.02 0.025 0.03 0.035 0.04 0.045 0.05 0.015 0.02 0.025 0.03 0.035 0.04 0.045 0.05
Time [s] Time [s]
800
600
400
200
Voltage [V]
-200
-400
-600
-800
0.015 0.02 0.025 0.03 0.035 0.04 0.045 0.05
Time [s]
In order to show the efficiency of the control strategy, a comparison between the proposed method
and the conventional FCS-MPC [23] were carried out under different operating conditions and the
same parameters. The amplitude of the reference voltage changed from 155 to 311 V in the first scenario
and stepped from 311 to 155 V at t = 0.03 s in the second scenario as illustrated in Figures 7 and 8.
The corresponding dynamic current response is shown in Figures 7b and 8b. As can be seen, it is
clear that the proposed method achieves sinusoidal current with the different reference amplitude.
In addition, one important issue associated with the T-type inverter is the balance of DC-link capacitor
voltage. Figures 7c and 8c indicate that the voltage of the DC-link capacitor is balanced despite the
change in reference. The maximum absolute error of this voltage at steady-state are about 1 and 3 V
for output voltage of 155 and 311 V, respectively. Figure 9 demonstrates single phase output voltage of
the proposed and conventional FCS-MPC methods. The simulation results indicate the ability of the
proposed method to accurately track and accomplish the steady-state with a fast dynamic response.
With the aim to evaluate the steady-state performance, the harmonic spectra of load current for
the conventional FCS-MPC and proposed methods are also examined in Figure 10a,b. These figures
show that the THD of the load current is increased slightly from 0.45% to 0.58% with the proposed
method. The comparison of two control methods is summarized in Table 4. Although the THD of the
load current is not perfect, we nevertheless believe that the slight increase does not affect the control
performance too much. Specifically, the computation time of the proposed algorithm is greatly reduced
compared with the conventional FCS-MPC as shown in Figure 11a. In fact, the minimum, average and
maximum computation times of the proposed algorithm are 3, 6 and 9 μs in a 2.0 GHz, i5 4310 CPU,
while their corresponding values are 4, 10 and 16 μs with conventional FCS-MPC. The performance
of FCS-MPC method is influenced by the sampling time which is improved by choosing the smaller
value. To investigate the effect of sampling time on the quality of the current, two controllers are
employed with different sampling times. Figure 11b shows that the quality of load current is the best
with sampling time 40 μs and the worst with 100 μs. However, there is a limitation of sampling time
due to the requirement of execution time such as computation time and measurement of the signal.
176
Energies 2019, 12, 31
Therefore, this method exhibits a valuable alternative to reduce the sampling time and extend with a
long prediction horizon, which improves the control performance.
400 20
uca i oa
300 ucb 15 i ob
ucc i oc
200 10
100 5
Voltage [V]
Current [A]
0 0
-100 -5
-200 -10
-300 -15
-400 -20
0.015 0.02 0.025 0.03 0.035 0.04 0.045 0.05 0.015 0.02 0.025 0.03 0.035 0.04 0.045 0.05
Time [s] Time [s]
310 800
uC1 600
uC2
305 400
300 0
-200
295 -400
-600
290 -800
0.015 0.02 0.025 0.03 0.035 0.04 0.045 0.05 0.015 0.02 0.025 0.03 0.035 0.04 0.045 0.05
Time [s] Time [s]
Figure 7. The dynamic response of the proposed method for step change from 311 to 155 V.
400 20
uca i oa
300 ucb 15 i ob
ucc i oc
200 10
100 5
Voltage [V]
Current [A]
0 0
-100 -5
-200 -10
-300 -15
-400 -20
0.015 0.02 0.025 0.03 0.035 0.04 0.045 0.05 0.015 0.02 0.025 0.03 0.035 0.04 0.045 0.05
Time [s] Time [s]
310 800
uC1 600
uC2
305 400
200
Voltage [V]
Voltage [V]
300 0
-200
295 -400
-600
290 -800
0.015 0.02 0.025 0.03 0.035 0.04 0.045 0.05 0.015 0.02 0.025 0.03 0.035 0.04 0.045 0.05
Time [s] Time [s]
Figure 8. The dynamic response of the proposed method for step change from 155 to 311 V.
177
Energies 2019, 12, 31
400 300
u cc_ref u cc_ref
ucc_convention ucc_convention
ucc_proposed ucc_proposed
200 250
Voltage [V]
Voltage [V]
0 200
-200 150
-400 100
0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.0396 0.04 0.0404 0.0408 0.0412 0.0416
Time [s] Time [s]
(a) Transient responses of single phase output voltage. (b) Zoom of output voltage response.
Figure 9. The dynamic response of the output voltage for the conventional FCS-MPC and
proposed methods.
0.3 0.3
Current magnitude (% of fundamental)
0.2 0.2
0.15 0.15
0.1 0.1
0.05 0.05
0 0
0 500 1000 1500 2000 2500 3000 0 500 1000 1500 2000 2500 3000
Frequency [Hz] Frequency [Hz]
(a) Current harmonic spectrum of conventional FCS-MPC. (b) Current harmonic spectrum of the proposed method.
Figure 10. The harmonic spectrum of the load current for the conventional FCS-MPC and
proposed methods.
20 1.4
1.2
Average computation time Conventional FCS-MPC
15 Maximum computation time Proposed method
1
Computation time [s]
0.8
10
0.6
5 0.4
0.2
40 50 60 70 80 90 100
0 Conventional FCS-MPC Proposed method Ts [μs]
The behavior of the system is also examined under time varying load step as illustrated in
Figure 12. At the initial state, the system operates at no load condition; then, the load is set to 20 Ω at
178
Energies 2019, 12, 31
t = 0.02 s. According to Figure 12, this change does not impact on the quality of the output voltages.
A resistive-inductive load is imposed for the same test as shown in Figure 13. The load resistance and
inductance are set to 40 Ω and 10 mH, respectively. It can be seen from Figure 13 that no deterioration
of output voltage is observed in this case.
400 20
uca ucb ucc
i oa
i ob
i oc
200 10
Voltage [V]
Current [A]
0 0
Start up
-200 -10
-400 -20
0.01 0.015 0.02 0.025 0.03 0.035 0.04 0.045 0.05 0.055 0.06 0.01 0.015 0.02 0.025 0.03 0.035 0.04 0.045 0.05 0.055 0.06
Time [s] Time [s]
Figure 12. Output voltage and current with the resistive load step at t = 0.02 s.
400 10
uca ucb ucc
i oa
i ob
i oc
200 5
Voltage [V]
Current [A]
0 0
Start up
-200 -5
-400 -10
0.01 0.015 0.02 0.025 0.03 0.035 0.04 0.045 0.05 0.055 0.06 0.01 0.015 0.02 0.025 0.03 0.035 0.04 0.045 0.05 0.055 0.06
Time [s] Time [s]
Figure 13. Output voltage and current with the resistive–inductive load step at t = 0.02 s.
To investigate the influence of frequency variations, a step change in the voltage from 60 Hz to
50 Hz at t = 0.03 s with Rload = 10 Ω is examined in this study. Figure 14 indicates that the proposed
method can achieve a reasonable reference tracking despite the sudden change in the frequency.
400 40
u cc_ref ioa iob ioc
300 ucc_proposed
200 20
500
Current [A]
Voltage [V]
0 0
-500
-200 -20
-300
-400 -40
0.001 0.05 0.051 0.02 0.021 0.03 0.031 0.04 0.041 0.01 0.011 0.06 0.001 0.05 0.051 0.02 0.021 0.03 0.031 0.04 0.041 0.01 0.011 0.06
Time [s] Time [s]
Figure 14. The output voltage and current responses under dynamic change in frequency.
179
Energies 2019, 12, 31
A nonlinear load test is also performed in this study with a diode rectifier and resistive-inductive
load (R = 60 Ω, Lnl = 10 mH) as shown in Figure 15c. Figure 15 illustrates that the output voltages
give a small distortion, but it still acquires sinusoidal in spite of the high distorted load currents.
400 15
uca ucb ucc
ioa iob ioc
300
10
200
5
100
Voltage [V]
Current [A]
0 0
-100
-5
-200
-10
-300
-400 -15
0.01 0.015 0.02 0.025 0.03 0.035 0.04 0.045 0.05 0.055 0.06 0.01 0.015 0.02 0.025 0.03 0.035 0.04 0.045 0.05 0.055 0.06
Time [s] Time [s]
A Lnl
B
C
R
To confirm the robustness of the controller against parameter variations, we have considered a
change of parameters with two cases. In the first case, the filter inductance and capacitance have been
decreased to 40% of their real values as illustrated in Figure 16a. On the other hand, the load resistance
has been increased to 50% of its value as shown in Figure 16b. It can be observed that the proposed
method is continued to obtain sinusoidal current with small deviations. The load current increases
from 0.58% to 1.5%, but it still meets within the limit required of the IEEE 519 standard.
60 10
i oa i ob i oc i oa i ob i oc
-5
-0 5
5
Ti mme[ s ]Cu
Current [A]
0 0
45
4- 0 -5
4- 5
460 -10
0.01 0.015 0.02 0.025 0.05 0.055 0.03 0.03 0.035 0.04 0.045 0.05 0.055 0.06
Time [s] r nt e ]Au
180
Energies 2019, 12, 31
block in the Matlab/Simulink with embedded coder tools [35]. Twelves modules FGH40T120SMD
for IGBT were applied in the three-phase inverter. Furthermore, two capacitors B43305A9108M 1000
μF-400 V were used for DC-link voltage. The parameters of the LC filter were maintained at 3 mH
and 40 μF. The LV 25-P and LA 25-P sensors were used to measure the output voltage, filter current
and capacitor voltages. The digital signal processing (DSP) generates the signals for 12 switches of
3L-T-type inverter via general-purpose input/output (GPIO) outputs.
DSP FPGA
Sensor
The DC input voltage is set at 180 V while the load resistance is kept at 30 Ω. The reference
of the peak phase output voltage is stepped from 90 to 60 V corresponding to the change in output
current from 3 to 2 A. Figure 18 indicates that the proposed method has a fast dynamic response and a
good balance of DC-link capacitor voltage. As illustrated in Figure 19, the steady-state of three-phase
sinusoidal load current confirms the control performance of the proposed method. Furthermore,
the execution time of the proposed and conventional FCS-MPC methods are 41 and 64 μs, respectively,
as shown in Figure 20. This highlights that the execution time is effectively reduced 36% by the
proposed method. Therefore, the sampling time of the conventional method is increased compared
with the proposed method resulting in a decrease in the quality of control performance. The load
current of the conventional FCS-MPC is depicted in Figure 21. In this case, the THD of the load current
of the proposed method is reduced from 1.6% to 1.0% compared with the conventional method as
illustrated in Figure 22. Thus, the better performance of the proposed algorithm can be obtained with
the low-cost processor.
t = [10 ms/div]
Figure 18. Experimental results for step change in the output voltage.
181
Energies 2019, 12, 31
t = [5 kHz/div]
t = [4 ms/div]
(a) Waveform and FFT of line to line voltage u ab . (b) Output voltage and three-phase load current.
t = 64 s
Ts = 50 s
Ts = 100 s
t = 41 s
t = 40 [ s/div] t = 20 [ s/div]
iob [2.5 A/div] ioa [2.5 A/div] ioc [2.5 A/div] ioa [2.5 A/div] ioc [2.5 A/div] iob``
[2.5 A/div]
182
Energies 2019, 12, 31
5. Conclusions
This paper presents a simplified model predictive control method for a three-level T-type
inverter. A reduced dynamics model is proposed to decrease the cost and the complexity of the
system. Moreover, the execution time is greatly reduced compared with the conventional FCS-MPC by
applying the preselection of reference inverter voltage and capacitor voltage balancing, allowing an
easy real-time implementation. In order to show the effectiveness of the control strategy, a comparative
study of the proposed method and conventional FCS-MPC is performed. Simulation and experimental
results prove the feasibility of the proposed approach.
Author Contributions: V.-Q.-B.N. established the major part of this paper which includes modeling, simulation
investigation, and original draft preparation. M.-K.N. contributed in review and editing. T.-T.T. contributed to
validating in the real system. Y.-C.L. provided resources and supervision. J.-H.C. provided resources and funding
acquisition.
Acknowledgments: This research was supported by Korea Electric Power Corporation (Grant number: R18XA04).
Conflicts of Interest: The authors declare no conflict of interest
References
1. Blaabjerg, F.; Liserre, M.; Ma, K. Power Electronics Converters for Wind Turbine Systems. IEEE Trans.
Ind. Appl. 2012, 48, 708–719. [CrossRef]
2. Portillo, R.C.; Prats, M.M.; Leon, J.I.; Sanchez, J.A.; Carrasco, J.M.; Galvan, E.; Franquelo, L.G. Modeling
Strategy for Back-to-Back Three-Level Converters Applied to High-Power Wind Turbines. IEEE Trans.
Ind. Electron. 2006, 53, 1483–1491. [CrossRef]
3. Kouro, S.; Malinowski, M.; Gopakumar, K.; Pou, J.; Franquelo, L.G.; Wu, B.; Rodriguez, J.; Perez, M.A.; Leon,
J.I. Recent Advances and Industrial Applications of Multilevel Converters. IEEE Trans. Ind. Electron. 2010,
57, 2553–2580. [CrossRef]
4. Schweizer, M.; Kolar, J.W. Design and Implementation of a Highly Efficient Three-Level T-Type Converter
for Low-Voltage Applications. IEEE Trans. Power Electron. 2013, 28, 899–907. [CrossRef]
5. Lee, K.; Shin, H.; Choi, J. Comparative analysis of power losses for 3-Level NPC and T-type inverter
modules. In Proceedings of the 2015 IEEE International Telecommunications Energy Conference (INTELEC),
Osaka, Japan, 18–22 October 2015; pp. 1–6.
6. Qin, C.; Zhang, C.; Chen, A.; Xing, X.; Zhang, G. A Space Vector Modulation Scheme of the Quasi-Z-Source
Three-Level T-Type Inverter for Common-Mode Voltage Reduction. IEEE Trans. Ind. Electron. 2018,
65, 8340–8350. [CrossRef]
7. Vahedi, H.; Labbe, P.A.; Al-Haddad, K. Balancing three-level NPC inverter DC bus using closed-loop SVM
Real time implementation and investigation. IET Power Electron. 2016, 9, 2076–2084. [CrossRef]
8. Xiang, C.; Shu, C.; Han, D.; Mao, B.; Wu, X.; Yu, T. Improved Virtual Space Vector Modulation for Three-Level
Neutral-Point-Clamped Converter With Feedback of Neutral-Point Voltage. IEEE Trans. Power Electron. 2018,
33, 5452–5464. [CrossRef]
9. Ngo, B.Q.V.; Ayerbe, P.R.; Olaru, S. Model Predictive Control with Two-step horizon for Three-level
Neutral-Point Clamped Inverter. In Proceedings of the 20th International Conference on Process Control,
Strbske Pleso, Slovakia, 9–12 June 2015; pp. 215–220.
10. In, H.C.; Kim, S.M.; Lee, K.B. Design and Control of Small DC-Link Capacitor-Based Three-Level Inverter
with Neutral-Point Voltage Balancing. Energies 2018, 11, 1435. [CrossRef]
11. Wilamowski, B.M.; Irwin, J.D. Power Electronics and Motor Drives; Taylor and Francis Group:
Boca Raton, FL, USA, 2011.
12. Zorig, A.; Belkheiri, M.; Barkat, S. Control of three-level T-type inverter based grid connected PV system.
In Proceedings of the 13th International Multi-Conference on Systems, Leipzig, Germany, 21–24 March 2016;
pp. 66–71.
13. Malinowski, M.; Kazmierkowski, M.P.; Hansen, S.; Blaabjerg, F.; Marques, G.D. Virtual-flux-based direct
power control of three-phase PWM rectifiers. IEEE Trans. Ind. Appl. 2001, 37, 1019–1027. [CrossRef]
183
Energies 2019, 12, 31
14. Malinowski, M.; Jasinski, M.; Kazmierkowski, M.P. Simple direct power control of three-phase PWM rectifier
using space-vector modulation (DPC-SVM). IEEE Trans. Ind. Electron. 2004, 51, 447–454. [CrossRef]
15. Farahani, H.F.; Rashidi, F. Direct power control of a grid-connected photovoltaic system using a fuzzy-logic
based controller. Simul.-Trans. Soc. Model. Simul. Int. 2017, 93, 213–223. [CrossRef]
16. Sebaaly, F.; Vahedi, H.; Kanaan, H.Y.; Moubayed, N.; Al-Haddad, K. Design and Implementation of
Space Vector Modulation-Based Sliding Mode Control for Grid-Connected 3L-NPC Inverter. IEEE Trans.
Ind. Electron. 2016, 63, 7854–7863. [CrossRef]
17. Donoso, F.; Mora, A.; Cárdenas, R.; Angulo, A.; Sáez, D.; Rivera, M. Finite-Set Model-Predictive Control
Strategies for a 3L-NPC Inverter Operating With Fixed Switching Frequency. IEEE Trans. Ind. Electron. 2018,
65, 3954–3965. [CrossRef]
18. Vazquez, S.; Mohan, C.; Franquelo, L.G.; Marquez, A.; Leon, J.I. A Generalized Predictive control for T-type
power inverters with output LC filter. In Proceedings of the 9th International Conference on Compatibility
and Power Electronics (CPE), Costa da Caparica, Portugal, 24–26 June 2015; pp. 20–24.
19. Nauman, M.; Hasan, A. Efficient Implicit Model-Predictive Control of a Three-Phase Inverter With an
Output LC Filter. IEEE Trans. Power Electron. 2016, 31, 6075–6078. [CrossRef]
20. Xing, X.; Chen, A.; Zhang, Z.; Chen, J.; Zhang, C. Model predictive control method to reduce common-mode
voltage and balance the neutral-point voltage in three-level T-type inverter. In Proceedings of the
IEEE Applied Power Electronics Conference and Exposition, Long Beach, CA, USA, 20–24 March 2016;
pp. 3453–3458.
21. Kouro, S.; Cortes, P.; Vargas, R.; Ammann, U.; Rodriguez, J. Model Predictive Control:A Simple and Powerful
Method to Control Power Converters. IEEE Trans. Ind. Electron. 2009, 56, 1826–1838. [CrossRef]
22. Rodriguez, J.; Kazmierkowski, M.P.; Espinoza, J.R.; Zanchetta, P.; Abu-Rub, H.; Young, H.A.; Rojas, C.A.
State of the Art of Finite Control Set Model Predictive Control in Power Electronics. IEEE Trans. Ind. Inf.
2013, 9, 1003–1016. [CrossRef]
23. Rodriguez, J.; Cortes, P. Predictive Control of Power Converters and Electrical Drives; John Wiley:
New York, NY, USA, 2012.
24. Ngo, B.Q.V.; Rodriguez-Ayerbe, P.; Olaru, S.; Niculescu, S.I. Model predictive power control based on virtual
flux for grid connected three-level neutral-point clamped inverter. In Proceedings of the 18th European
Conference on Power Electronics and Applications, Karlsruhe, Germany, 5–9 September 2016; pp. 1–10.
25. Singh, V.K.; Tripathi, R.N.; Hanamoto, T. HIL Co-Simulation of Finite Set-Model Predictive Control Using
FPGA for a Three-Phase VSI System. Energies 2018, 11, 909. [CrossRef]
26. Shi, T.; Zhang, C.; Geng, Q.; Xia, C. Improved model predictive control of three-level voltage source converter.
Electr. Power Compon. Syst. 2014, 42, 1029–1138. [CrossRef]
27. Xia, C.; Liu, T.; Shi, T.; Song, Z. A Simplified Finite-Control-Set Model-Predictive Control for Power
Converters. IEEE Trans. Ind. Inf. 2014, 10, 991–1002.
28. Geyer, T.; Quevedo, D.E. Performance of Multistep Finite Control Set Model Predictive Control for Power
Electronics. IEEE Trans. Power Electron. 2015, 30, 1633–1644. [CrossRef]
29. Aguilera, R.P.; Baidya, R.; Acuna, P.; Vazquez, S.; Mouton, T.; Agelidis, V.G. Model predictive control of
cascaded H-bridge inverters based on a fast-optimization algorithm. In Proceedings of the 41st Annual
Conference of the IEEE Industrial Electronics Society, Yokohama, Japan, 9–12 November 2015; pp. 4003–4008.
30. Liu, X.; Wang, D.; Peng, Z. Improved finite-control-set model predictive control for active front-end rectifiers
with simplified computational approach and on-line parameter identification. ISA Trans. 2017, 69, 51–64.
[CrossRef] [PubMed]
31. Zhang, Z.; Hackl, C.M.; Kennel, R. Computationally Efficient DMPC for Three-Level NPC Back-to-Back
Converters in Wind Turbine Systems With PMSG. IEEE Trans. Power Electron. 2017, 32, 8018–8034. [CrossRef]
32. Taheri, A.; Zhalebaghi, M.H. A new model predictive control algorithm by reducing the computing time
of cost function minimization for NPC inverter in three-phase power grids. ISA Trans. 2017, 71, 391–402.
[CrossRef] [PubMed]
33. Wu, B.; Narimani, M. High-Power Converters and AC Drives; Wiley-IEEE Press: New York, NY, USA, 2017.
184
Energies 2019, 12, 31
© 2018 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access
article distributed under the terms and conditions of the Creative Commons Attribution
(CC BY) license (http://creativecommons.org/licenses/by/4.0/).
185
energies
Article
An Averaged-Value Model of an Asymmetrical
Hybrid Multi-Level Rectifier
Salvatore Foti 1, *, Giacomo Scelba 2 , Antonio Testa 1 and Angelo Sciacca 3
1 DI, University of Messina, 98122 Messina, Italy; [email protected]
2 DIEEI, University of Catania, 95131 Catania, Italy; [email protected]
3 ST Microelectronics, I-95121 Catania, Italy; [email protected]
* Correspondence: [email protected]; Tel.: +39-3206487898
Keywords: electrical drives; energy saving; multilevel power converters; permanent magnet
synchronous generator; open-end winding configuration; voltage balancing; power factor
1. Introduction
Multi-level converters have proved in the last decades to be a viable alternative to conventional
topologies in medium-voltage, high-power, industrial applications, but today, their field of applications
is rapidly spreading toward low-power and low-voltage ranges. Main advantages of multi-level
converters are basically those of an improved harmonic content of AC voltages and currents and
of a reduction of power switch voltage ratings [1,2], the main drawback being a greater complexity.
Open-winding (OW) configurations, consisting of an AC machine fed by two power converters [3–6],
can be deemed as a special kind of multi-level converter [7]. Different configurations, control schemes,
and modulation techniques dealing with OW systems have been discussed in the literature [8–10].
Some OW configurations embedding multi-level converters have also been recently developed [11–13].
Among them, a high efficiency asymmetrical hybrid multilevel inverter for motor drives has been
presented and analyzed in [12] featuring a particular asymmetrical structure where two different
kinds of converters are connected at the two sides of an OW AC machine with different functions.
Specifically, a main multilevel converter supplies the load, and an auxiliary two-level inverter acts as
an active power filter. Such an approach has also been used in [13] to realize an asymmetrical hybrid
unidirectional T-type rectifier (AHUTR) for gen-set applications, tailored around an open-end winding
permanent magnet synchronous generator (PMSG), as shown in Figure 1. According to the AHUTR
topology, the open-end winding PMSG on one side supplies the electrical load through the main
converter, a T-type rectifier (TTR), also commonly known as a Vienna rectifier, and on the other side, it
is connected to an auxiliary two-level inverter (TLI). The main converter processes the whole power
delivered to the load, and thus, it is operated at the fundamental frequency in order to minimize the
switching power losses. The TLI is instead driven by a high switching frequency PWM technique to
suitably shape the phase currents. Therefore, a stable output DC voltage and almost sinusoidal input
currents are obtained, achieving a higher efficiency than comparable conventional PWM rectifiers [12].
The AHUTR structure is also of general applicability, being exploitable in grid-connected applications
by replacing the generator with a transformer featuring an open-end secondary winding, as shown
in Figure 1, but it is more complex than conventional rectifiers, requiring suitable mathematical
tools for control and optimization purposes. The aim of this work is thus to provide an essential
tool for the design of the control system of an AHUTR by developing an averaged-value model
(AVM) of the system. In general, averaged-value techniques approximate the model of a switching
converter to a continuous system by considering the values taken by the variables along a switching
period as constant. They are useful when designing and testing control algorithms, as well as to
develop efficiency optimization techniques, because a high frequency dynamic analysis is not required,
differently than power circuits and filters design. Specifically, an AHUTR AVM has been developed
with the aim to support the design of effective solutions to maximize system efficiency, to provide a
stable DC output voltage, to cancel low-order undesired harmonics from the phase currents, to equalize
the Vienna rectifier DC bus capacitor voltages, and to control the TLI DC bus voltage. Furthermore,
the developed model is valuable in tuning voltage and current regulators.
(a)
(b)
Figure 1. AHUTR for electrical power generation (a) and grid-connected (b) applications.
187
Energies 2019, 12, 589
li − 1 2l − 1
Vig = ViTTR − ViTLI − Vn n = VDC − i VDC − Vn n (3)
2 2
where VDC and VDC ” are the DC bus voltages of the Vienna rectifier and the TLI, respectively, and Vn n”
is the voltage between the mid points n and n” of the two DC buses, which can be expressed as
1 1
Vn n = (VaTTR + VbTTR + VcTTR ) − (VaTLI + VbTLI + VcTLI ). (4)
3 3
According to (2) and (3), the OW structure of Figure 1, featuring twelve power switches,
is equivalent to a six-level neutral point clamped (NPC) or flying capacitor (FC) converter, which would,
however, encompass thirty power switches [12]. As shown in Figure 2, the AHUTR requires a complex
control system to suitably coordinate the operations of the two converters in order to regulate the DC
output voltage, to cancel low-order harmonics from phase currents, to equalize the Vienna rectifier DC
bus capacitor voltages, and to control the TLI DC bus voltage [14,15].
188
Energies 2019, 12, 589
Load
Output DC voltage control
șe VDCΖ
VDC'* Į
PI Step Modulation Vienna
VDC'
PMSG current control VDCΖ in VC1 VC2 iDC PMSG Prime
ViTTR Mover
VjTLI*
VDC' șe PWM TLI șr
Vi1TTR pp
VDCΖΖ ijg
iDC' idg*
șe
PI dq
į (25)
iq* iqg* idg
Į
PI abc
șe
iqg șe
dq
ijg
abc
VDC'* 0
PI PI
VDC' in VC1-VC2
TLI DC Bus voltage control Vienna DC Bus voltages equalization
Figure 2. Block diagram of the control system of the AHUTR for electrical power
generation applications.
λqs = Ls iqs
(6)
λds = Ls ids + λ pm
189
Energies 2019, 12, 589
PMSG phase voltages can be expressed in a qd synchronous reference frame to the back-EMF
vector as a function of qd components of voltages V iTTR and V iTLI by:
cos(ω t) cos(ωre t − 23 π ) cos(ωre t + 23 π ) V
V 2
re aTTR
qTTR
= sin(ωre t) sin(ωre t − 23 π ) sin(ωre t + 23 π ) V bTTR (8)
V dTTR 3
1
2
1
2
1
2
V cTTR
cos(ω t) cos(ωre t − 23 π ) cos(ωre t + 23 π ) V
V 2
re aTLI
qTLI
= × sin(ωre t) sin(ωre t − 23 π ) sin(ωre t + 23 π ) × V bTLI (9)
V dTLI 3
1
2
1
2
1
2
V cTLI
Figure 3. Block scheme of the permanent magnet synchronous generator (PMSG) model.
190
Energies 2019, 12, 589
0 < θe < α
if iag > 0 => Sa1 ON Sa2 OFF
Phase a π − α < θe < π + α
if iag < 0 => Sa1 OFF Sa2 ON
2π − α < θ e < 2π
2/3π < θ e < α + 2/3π
if ibg > 0 => Sb1 ON Sb2 OFF
Phase b 5/3π − α < θ e < 5/3π + α
if ibg < 0 => Sb1 OFF Sb2 ON
2/3π − α < θ e < 2/3π
4/3π < θ e < α + 4/3π
if icg > 0 => Sc1 ON Sc2 OFF
Phase c 1/3π − α < θ e < 1/3π + α
if icg < 0 => Sc1 OFF Sc2 ON
4/3π − α < θ e < 4/3π
Assuming the output voltage VDC is constant, actual values of Vienna rectifier input phase
voltages ViTTR are thus given by:
To avoid improper operations leading to extra power losses and voltage distortion, the angular
displacement ϕTTR between the fundamental harmonics of voltage ViTTR and current must be set
lower than |α|. Dealing with an electrical power generation application, a vector diagram of AC
variables is shown in Figure 4a, where ϕ is the phase displacement between the PMSG back-EMF E g
and the current I. δ represents the angle between the voltage V TTR and the q axis, and is set to allow a
reactive power flow between the Vienna rectifier and PMSG, associated to the inductive elements of
the electrical machine.
(a) (b)
Figure 4. Vector diagram of AC variables: (a) considering VTLI , (b) neglecting VTLI .
Neglecting, for simplicity, the voltage VTLI generated by the auxiliary inverter, which is an
independent variable and whose amplitude is significantly lower than Vi1TTR , the amplitude of the
fundamental harmonic of the TTR input voltage Vi1TTR is obtained as a function of the switching angle
α and DC bus voltage VDC as follows:
2 |V |
|V i1TTR | = V cos(α), m TTR = i1TTR (15)
π DC VDC
191
Energies 2019, 12, 589
where mTTR is the modulation index of the Vienna rectifier. According to the vector diagram of
Figure 4b, qd components of the voltage can be written as:
V qTTR =V i1TTR cos(δ) iq = I cos( ϕ) Eqg = E g
, , ,
V dTTR =V i1TTR sin(δ) id = I sin( ϕ) Edg = 0
(16)
Xiq = − Xs I sin( ϕ) Riq = − RI cos( ϕ)
,
Xid = + Xs I cos( ϕ) Rid = − RI sin( ϕ)
where PTTR and QTTR are the active and reactive power, respectively, processed by the Vienna rectifier,
PR and QX are the active power wasted in the stator resistance R and the reactive power due to the
PMSG synchronous reactance Xs , respectively, while Pg and Qg are the active and reactive power
delivered by the PMSG, respectively.
Neglecting the rectifier power losses, the AC power generated by the PMSG is equal to the sum
of the power dissipated in the DC bus capacitor resistances RC1 and RC2 and the power delivered to
the load RL . In the Laplace domain, VDC and the capacitor voltages VC1 and VC2 are thus given by
⎧
⎪
⎪ 2 (s)
VC1 V 2 (s)
⎪
⎪
VDC (s) = R L PAC (s) − R − RC2C2
⎪
⎪
⎨ C1
sR (1+ R C )
⎪ VC1 (s) = VDC (s) R + R C1+sR RC2 (2C +C ) (18)
⎪
⎪
C1 C1 C1 C2 1 2
⎪
⎪
⎪ VC2 (s) = VDC (s) − VC1 (s)
⎩
PAC (s) = 32 VqTTR (s)iq (s) + VdTTR (s)id (s)
where in is mainly given by the difference between the currents flowing through the two DC bus
capacitors and it can be also computed as the sum of the currents flowing through the three branches
of the Vienna rectifier:
in = Saj i ag + Sbj ibg + Scj icg (19)
1
in = T i ag + TONbj ibg + TONcj icg = d aj i ag + dbj ibg + dcj icg (20)
T ONaj
where dij = TONij /T are the duty cycles of the bidirectional switches Sij , according to Table 2. Figure 5
shows some simulations dealing with balanced and unbalanced DC bus voltages operations, while a
block diagram of the Vienna rectifier mathematical model is shown in Figure 6.
192
Energies 2019, 12, 589
T T
I II III IV V VI I II III IV V VI I
' VaTTR VbTTR VbTTR '
VDC /2
VDC /2 VaTTR VbTTR VbTTR
șe șe
0 0
icg iag ibg icg iag ibg
-VDC'/2 -VDC'/2
iag+ibg+icg
in ș e șe
0 0 in
-VC1 -VC2 -VC1 -VC2
VDC'/2 șe VDC'/2
șe
0 0
(a) (b)
Figure 5. Averaged-value in , iabcg , Vc1 , Vc2 , and ViTTR . (a) Balanced DC bus voltages, and (b)
unbalanced DC bus voltages.
A non-null average in leads to unbalanced DC bus voltages [16–18]; moreover, the mean value of
fundamental voltages Va1TTR becomes negative if VC1 < VC2 or positive if VC2 < VC1 . This is included
in the TTR model by adding the term ΔVDC = VC1 − VC2 :
⎧
⎪
⎨ Va1TTR = |Va1TTR | sin(θe ) + ΔVDC
Vb1TTR = |Vb1TTR | sin(θe − 3 π ) + ΔVDC
2 (21)
⎪
⎩ V
c1TTR = |Vc1TTR | sin( θe + 3 π ) + ΔVDC
2
193
Energies 2019, 12, 589
phase voltage is equal to the difference between the AC side input voltage ViTTR and its fundamental
component Vi1TTR , as shown in Figure 7.
Figure 7. Two-level inverter (TLI) reference voltage for active power filtering.
Phase voltages ViTTR encompass some zero sequence components, such as the 3rd , 9th , 27th ,
and 81st , that will not result in corresponding currents in the PMSG because the considered open-end
winding topology is composed by two isolated converters. Hence, these harmonics can be neglected in
the TLI reference voltages ViTLI * . This leads to a reduction of TLI DC bus voltage and, accordingly, to a
positive impact on TLI losses. TLI reference voltages VabcTLI * are thus given by
⎧
⎪
⎪ VaTLI ∗ (n, θe ) = ∑ ban × sin(nθe − ϕn )
⎪
⎪ n=5,7,11,13
⎨
VbTLI ∗ (n, θe ) = ∑ bbn × sin(nθe − ϕn − 2π
3 ) (24)
⎪
⎪ n=5,7,11,13
⎪ V
⎪ ∗
⎩ cTLI (n, θe ) = bcn × sin(nθe − ϕn + 3 )
2π
∑
n=5,7,11,13
Figure 8 shows the VaTLI * waveform when considering a different set of zero sequence components.
For each case, the minimum VDC ”/VDC requirement has been computed as shown in Figure 9,
while current and voltage THDs are provided in Figure 10. At medium-high values of the modulation
index mTTR , a proper suppression of the effects of the low-order voltage harmonics produced by the
Vienna rectifier is simply achieved by compensating the 5th and 7th harmonics. However, at low mTTR ,
additional harmonics must be considered to keep the THDs suitably low.
(a) (b)
(c) (d)
Figure 8. TLI reference voltage approximation. (a) 3rd , 5th , 7th , 9th , 11th , 13th . (b) 5th , 7th , 11th , 13th .
(c) 5th , 7th , 11th . (d) 5th , 7th .
194
Energies 2019, 12, 589
Figure 9. Minimum VDC ”/VDC requirement vs. peak amplitude of PMSG phase voltage, mTTR , and α.
Figure 10. THDv and THDi vs. the peak amplitude of PMSG phase voltage.
As shown in Figure 2, a closed loop input current control system is added to the predictive filter
in order to cope with unmodeled non-linearities and improve the input current waveform as well as
the system dynamic response. By equaling the active power generated by the PMSG to the output
DC power, the reference q-axis current iq * is computed from actual values of α, δ and the output DC
current iDC as:
πi DC
iq∗ = , i∗ = 0 (25)
3 cos(α) cos(δ) d
The d-axis reference current id * can be simply set to zero or suitably determined in case of interior
permanent magnet structures in order to operate the PMSG according to a maximum power per
ampere strategy.
Another key function of the TLI is to balance the voltage across the DC bus capacitors of the
Vienna rectifier, making unnecessary additional circuits. As shown in Figure 2, this goal is obtained
by acting on the q-axis component of the TLI reference current in order to control the amplitude of in ,
which is given by the difference between the currents flowing through the two DC bus capacitors.
The DC side of the TLI is modeled by balancing the AC and DC side power, neglecting the power
switches losses (Equation (26)). The TLI DC-link includes the resistance RCT representing the floating
capacitor losses, while VqTLI and VdTLI are the voltage components of TLI VjTLI in the qd axis, as shown
in Figure 11.
PAC = PDC2 = 3
2 VqTLI iq + VdTLI id
VDC 2
VDC 2 (26)
PDC2 = VDC i DC + RCT = VDC CT sVDC + RCT = 3
2 VqTLI iq + VdTLI id
195
Energies 2019, 12, 589
4. Model Validation
An electric power generation application has been considered for validating the value-averaged
model. Specifically, the proposed model represented with the blocks scheme of Figure 12 has been
implemented in a Simulink environment and compared to a detailed model of the system developed
in the same environment exploiting the SimPower System Toolbox, which is a circuit-based modeling
platform widely used for the simulation of power electronic converters, electromechanical systems,
and their control systems. The last model includes both converter topologies. The control scheme
used on both models is shown in Figure 2, including low-order harmonic compensation and DC bus
capacitor voltages balancing [14]. Simulation settings are summarized in Table 3, where kPα and kIα are
the proportional and integral gains of the output DC voltage controller, while kPiq , kIiq, kPid , and kIid are
the proportional and integral gains of qd PMSG current regulators; kPin and kIin are the proportional
and integral gains of the Vienna rectifier DC bus voltage equalization system; and kPTLI and kITLI are
the proportional and integral gains of the TLI DC Bus voltage controller. Figures 13 and 14 show
simulation results obtained with the SimPower System model and the averaged-value model, showing
a purposely generated Vienna rectifier DC bus voltage unbalance with the balance system not activated.
Specifically, capacitor voltages VC1 and VC2 , which at the beginning are equal because RC1 and RC2
are both set to 1000 Ω, diverge after t = 3 s because RC2 is changed to 600Ω in order to generate the
voltage unbalance. The in current is zero when capacitor voltages are balanced and greater than zero
after t = 3 s, while DC bus voltages VDC and VDC ” do not vary. A zoomed-in view of the balanced and
unbalanced steady-state operations of Figures 13 and 14 are shown in Figures 15 and 16, confirming
a good matching between the results obtained with the two models. Figures 15d and 16d show the
instantaneous Vienna rectifier power losses PTTR , TLI power losses PTLI , and PMSG power losses PLg
during balanced DC bus capacitors. A one-time variation of the references of the output voltage and
the TLI DC bus voltage is considered in Figures 17 and 18, while a load variation is shown in Figures 19
and 20. The results achieved with the two models are very close, but using the averaged-value model,
the simulation time is roughly one third. In particular, all simulations have been accomplished on an
Intel®CoreTM i7 CPU with 2.60 GHz and 16 GB RAM running a 64-bit Windows 10 operating system.
Simulation results shown in Figures 13–20 required three minutes computing time using the SimPower
System model with a 10−6 s time step. A 10−5 s time step can be used with the averaged-value model,
because high frequency voltage and current harmonics are neglected, leading to only ten seconds to
accomplish the same simulation.
196
Energies 2019, 12, 589
ȱ ȱ
(a)ȱ (b)ȱ
ȱ ȱ
(c)ȱ (d)ȱ
Figure 13. SimPower System model. (a) DC bus capacitor voltages VC1 and VC2. (b) in = iC1 − iC2 .
(c) output voltage VDC . (d) TLI DC bus voltage VDC ”.
180 0.08
>9@ >$@
160
0.06
140 %DODQFHG
120 0.04
100
0.02
80
60 0
8QEDODQFHG
40 -0.02 2
2 2.5 3 3.5 4 4.5 5 2.5 3 3.5 4 4.5 5
9&9& >V@ LQ >V@
(a) (b)
226
>9@ 106
>9@
224 105
222 104
220 103
218 102
216 101
214 2 100
2.5 3 3.5 4 4.5 5 2 2.5 3 3.5 4 4.5 5
>V@ 9'&ƍƍ >V@
9'&ƍ
(c) (d)
Figure 14. Averaged-value model. (a) DC bus capacitor voltages VC1 and VC2. (b) in = iC1 − iC2 .
(c) output voltage VDC . (d) TLI DC bus voltage VDC ”.
197
Energies 2019, 12, 589
200 20
>9@ >$@ 200
>9@ >$@
20
100 10 100 10
0 0 0 0
Figure 15. SimPower System model. (a) Balanced DC bus capacitor voltage operations, VaTTR , Eag , and
iag . (b) Unbalanced DC bus capacitor voltage operations. (c) Current in , average value in , and AC input
Vienna voltages ViTTR . (d) TRR power losses PTTR , TLI power losses PTLI , and PMSG power losses PLg .
(a) (b)
(c) (d)
Figure 16. Averaged-value model. (a) Balanced DC bus capacitor voltage operations, VaTTR , Eag , and iag .
(b) Unbalanced DC bus capacitor voltage operations. (c) Current in , average value in , and AC input
Vienna voltages ViTTR . (d) TRR power losses PTTR , TLI power losses PTLI , and PMSG power losses PLg .
198
Energies 2019, 12, 589
(a) (b)
Figure 17. SimPower System model. One-time variation of VDC and VDC ” references. (a) TLI DC bus
voltage VDC ”. (b) Output voltage VDC .
(a) (b)
Figure 18. Averaged-value model. One-time variation of VDC and VDC ” references. (a) TLI DC bus
voltage VDC ”. (b) Output voltage VDC .
(a) (b)
Figure 19. SimPower System model. Load variation iDC *. (a) TLI DC bus voltage VDC ”. (b) Output
voltage VDC .
(a) (b)
Figure 20. Averaged-value model. Load variation iDC *. (a) TLI DC bus voltage VDC ” . (b) Output
voltage VDC .
Figure 21 displays the maximum errors between the quantities carried out by the two models,
confirming a good accuracy of the proposed average model in a wide range of load conditions.
199
Energies 2019, 12, 589
(a) (b)
Figure 21. Percentage error between SymPower System and averaged model vs. the power expressed
in per unit P/Pn . (a) Errors of VDC , VDC ”, ia , and in . (b) Errors of Vc1 , Vc2 , ω r and Te . Note: ω r = 200
rad/s, VDC = 400 V, and VDC ” = 100 V.
5. Experimental Assessment
The accuracy of the AHUTR analytical model has also been verified comparing the results
from the model with those from an experimental test rig consisting of 1kW AHUTR supplying an
open-end-winding PMSG, mechanically coupled to a 2.6 kW PM synchronous motor drive used as a
prime mover. Technical specifications of the PMSG are given in Table 4. This AHUTR supplied
DC loads at 400V through the Vienna rectifier equipped with insulated gate bipolar transistors
(IGBTs) whose technical data are listed in Table 5. The TLI was realized with low-voltage power
metal-oxide-semiconductor field-effect transistor (MOSFETs) and operated at 40 kHz, VDC ” = 100 V.
Technical data of the power MOSFETs are reported in Table 6. The TLI floating capacitor and both
capacitors C1 , C2 were equal to 470μF. The DC load was modified using a variable power resistor.
A single dSPACE DS1103 control board was used to control the Vienna rectifier and the TLI, while a
2048 ppr encoder was used to measure the rotor position θ r of the PMSG. The experimental setup is
shown in Figure 22. The currents and voltages were measured by using a dedicated sensing board
equipped with the current transducer LEM LA 55-P and voltage transducer LEM LV 25-P.
Pn (kW) Ls (mH) Vs (V) Rs (Ω) Is (A) λPM (Wb) ωr (krpm) Pole Pairs
1 20 565 4.8 6.5 1.53 2 3
Vce (V) V ce (on) (V) iRMS (A) trise (ns) tfall (ns)
600 2.1 30 27 160
200
Energies 2019, 12, 589
9LHQQD 7/,
5HFWLILHU
(a)
7RUTXH
'LVSOD\ 3ULPH0RYHU
,QYHUWHU
306*
306* 3RZHU
6XSSOLHV
&XUUHQWDQGYROWDJH 5/
DFTXLVLWLRQ
(b)
Figure 22. Experimental test bench. (a) Block scheme. (b) Experimental setup.
The experimental results shown in Figure 23 were obtained by imposing a transient voltage to
VDC from 400 V to 320 V by keeping a constant resistor value RL = 80 Ω and with the PMSG spinning at
ω r = 200 rad/s. Note a satisfying accuracy in the mechanical and electrical quantities estimated by the
model. The voltage VDC ” was properly modified by the control algorithm in order to keep the optimal
ratio between the DC bus voltages VDC and VDC ”. A different test is displayed in Figure 24 in which
a speed transient was forced by acting on the prime mover. More specifically, the rotational speed
ω r was changed from 200 rad/s to 260 rad/s while the resistive load was still kept constant. Even in
this case, the model accurately predicted the behavior of the drive, both at steady-state and transient.
The DC bus voltages were both affected by the speed variation, but the feedback control loops restored
the reference values. A step load variation was imposed in the test of Figure 25, where the DC load
was purposely doubled by switching from TL = 2 Nm to TL = 4 Nm. In this case, a more remarkable
difference was observed between the model and the experimental results. Finally, the effectiveness of
the model to predict the balancing of the voltages across the DC bus capacitors is shown in Figure 26.
Initially, the balancing algorithm described in the previous sections was inactive, and thus, the voltages
at the terminals of C1 and C2 were significantly different. At the instant t*, the voltage-balancing
approach was activated, nullifying VC1 − VC2 . The results of Figure 26 confirm the capability of
the model to accurately simulate even this critical issue of the AHUTR. Maximum percentage errors
between the outputs of the SimPower System and the averaged-value model are summarized in
201
Energies 2019, 12, 589
Table 7, where the quantities with the suffix Δ are the errors in estimating VDC , ω r , Te , VDC ” , in , Vc1 ,
and Vc2 .
(a) (b)
Figure 23. Voltage transient of VDC from 400 V to 320 V under a constant resistor value RL = 80 Ω.
Output voltage VDC , TLI DC bus voltage VDC ”, rotor speed ω r , electromagnetic torque Te .
(a) Experimental results. (b) Simulation results.
(a) (b)
Figure 24. Speed transient from ω r = 200 rad/s to ω r = 260 rad/s under a constant resistor value
RL = 80 Ω and VDC = 400 V, VDC ”= 100 V. Output voltage VDC , TLI DC bus voltage VDC ”, rotor speed
ω r , electromagnetic torque Te . (a) Experimental results. (b) Simulation results.
(a) (b)
Figure 25. Load transient from TL = 2 Nm to TL = 4 Nm at ω r = 200 rad/s and VDC = 400 V, VDC ”
= 100 V. Output voltage VDC , TLI DC bus voltage VDC ”, rotor speed ω r , electromagnetic torque Te .
(a) Experimental results. (b) Simulation results.
(a) (b)
Figure 26. DC bus voltage balancing: TL = 4 Nm, ω r = 200 rad/s and VDC = 400 V, VDC ” = 100 V. Vc1 ,
Vc2 and in . (a) Experimental results. (b) Simulation results.
202
Energies 2019, 12, 589
Table 7. Errors between experimental results and those obtained with the averaged-value model.
Test ΔVDC (%) Δωr (%) ΔTe (%) ΔVDC ” (%) Δin (%) ΔVC1 (%) ΔVC2 (%)
Figure 22 2.2 1.9 3.7 4.7 / / /
Figure 23 2.1 2.6 5 7.7 / / /
Figure 24 4.5 4.9 6 5 / / /
Figure 25 / / / / 6.6 10 4
6. Conclusions
The asymmetrical hybrid unidirectional T-type rectifier is more efficient than a conventional PWM
rectifier, mainly due to line frequency operation of the main converter, a T-type rectifier. However,
it features a more complex structure composed of three main components, namely a TTR, a TLI,
and an open winding electric machine, all interacting. The development of an accurate averaged-value
mathematical model of the AHUTR topology aimed to optimally design control and management
algorithms has been faced in the paper. Simulations and experimental results show that the proposed
model is able to reproduce the static and dynamic behavior of the AHUTR with good accuracy.
Furthermore, the obtained mathematical representation made a fast analysis of the system during TTR
DC bus voltage unbalance operations possible. This has been exploited to design an active balancing
system acting on the TLI side—a task which would be time-consuming with circuit-oriented simulator
models. Furthermore, the averaged-value model has been used to define the entire AHTUR control
and management system tasked to deal with efficiency maximization, input power factor control,
TTR DC bus capacitor voltage balance, and the control of TLI floating DC bus voltage.
Author Contributions: This work was carried out in collaboration between all authors. S.F., G.S. and A.T.
designed the study, wrote the manuscript and analyzed simulations and experimental results. A.S. undertook all
of the experimental measurements.
Conflicts of Interest: The authors declare no conflict of interest.
References
1. Kaarthik, R.S.; Gopakumar, K.; Mathey, J.; Underland, T. Medium Voltage Drive for Induction Machine with
Multilevel Dodecagon Voltage Space Vectors with Symmetric Triangles. IEEE Trans. Ind. Electron. 2015, 62,
79–87. [CrossRef]
2. Kouro, S.; Malinowski, M.; Gopakumar, K.; Pou, J.; Franquelo, L.G.; Wu, B.; Rodriguez, J.; Perez, M.A.;
Leon, J.I. Recent Advances and Industrial Applications of Multilevel Converters. IEEE Trans. Ind. Electron.
2010, 57, 2553–2580. [CrossRef]
3. De Caro, S.; Foti, S.; Scimone, T.; Testa, A.; Cacciato, M.; Scarcella, G.; Scelba, G. THD and efficiency
improvement in multi-level inverters through an open end winding configuration. In Proceedings of the
IEEE 2016 Energy Conversion Congress and Expo, Milwaukee, WI, USA, 18–22 September 2016; pp. 1–7.
4. Edpuganti, A.; Rathore, A. A Survey of Low Switching Frequency Modulation Techniques for
Medium-Voltage Multilevel Converters. IEEE Trans. Ind. Appl. 2015, 51, 4212–4228. [CrossRef]
5. Mondal, G.; Sivakumar, K.; Ramchand, R.; Gopakumar, K.; Levi, E. A Dual Seven-Level Inverter Supply for
an Open-End Winding Induction Motor Drive. IEEE Trans. Ind. Electron. 2009, 56, 1665–1673. [CrossRef]
6. Wang, Y.; Panda, D.; Lipo, T.A.; Pan, D. Open-Winding Power Conversion Systems Fed by Half-Controlled
Converters. IEEE Trans. on Power Electron. 2013, 28, 2427–2436. [CrossRef]
7. Mohapatra, K.K.; Gopakumar, K.; Somasekhar, V.T.; Umanand, L. A Harmonic Elimination and Suppression
Scheme for an Open-End Winding Induction Motor Drive. IEEE Trans. Ind. Electron. 2003, 50, 1187–1198.
[CrossRef]
8. Kawabata, Y.; Nasu, M.; Nomoto, T.; Ejiogu, E.C.; Kawabata, T. High-efficiency and low acoustic noise drive
system using open-winding AC motor and two space-vector-modulated inverters. IEEE Trans. Ind. Electron.
2002, 49, 783–789. [CrossRef]
9. Sivakumar, K.; Das, A.; Ramchand, R.; Patel, C.; Gopakumar, K. A hybrid multilevel inverter topology for an
open-end winding induction-motor drive using two-level inverters in series with a capacitor-fed H- bridge
cell. IEEE Trans. Ind. Electron. 2010, 57, 3707–3714. [CrossRef]
203
Energies 2019, 12, 589
10. Somasekhar, V.T.; Gopakumar, K.; Bajiu, M.R.; Mohapatra, K.K.; Umanand, L. A multilevel inverter system
for an inductor motor with open-end windings. IEEE Trans. Ind. Electron. 2015, 52, 824–836. [CrossRef]
11. Edpuganti, A.; Rathore, A.K. Optimal Pulsewidth Modulation for Common-Mode Voltage Elimination
Scheme of Medium-Voltage Modular Multilevel Converter-Fed Open-End Stator Winding Induction Motor
Drives. IEEE Trans. Ind. Electron. 2017, 64, 848–856. [CrossRef]
12. Foti, S.; Testa, A.; Scelba, G.; De Caro, S.; Cacciato, M.; Scarcella, G.; Scimone, T. An Open-End Winding
Motor Approach to Mitigate the Phase Voltage Distortion on Multilevel Inverters. IEEE Trans. Power Electron.
2018, 33, 2404–2416. [CrossRef]
13. Foti, S.; Testa, A.; Scelba, G.; Sabatini, V.; Lidozzi, A.; Solero, L. A symmetrical hybrid unidirectional T-type
rectifier for high-speed gen-set applications. In Proceedings of the IEEE Energy Conversion Congress and
Expo, Cincinnati, OH, USA, 1–5 October 2017; pp. 4887–4893.
14. Foti, S.; De Caro, S.; Scelba, G.; Scimone, T.; Testa, A.; Cacciato, M.; Scarcella, G. An Optimal Current
Control Strategy for Asymmetrical Hybrid Multilevel Inverters. IEEE Trans. Ind. Appl. 2018, 54, 4425–4436.
[CrossRef]
15. Mengoni, M.; Amerise, A.; Zarri, L.; Tani, A.; Serra, G.; Casadei, D. Control Scheme for Open-Ended
Induction Motor Drives with a Floating Capacitor Bridge Over a Wide Speed Range. Trans. Ind. Applications
2017, 53, 4504–4514. [CrossRef]
16. Pan, Z.; Peng, F.Z.; Corzine, K.A.; Stefanovic, V.R.; Leuthen, J.M.; Gataric, S. Voltage balancing control
of diode-clamped multilevel rectifier/inverter systems. IEEE Trans. Ind. Applications 2005, 41, 1698–1706.
[CrossRef]
17. Yan, G.; Duan, S.; Zhao, S.; Li, G.; Wu, W.; Li, H. Research on the mechanism of neutral-point voltage
fluctuation and capacitor voltage balancing control strategy of three-phase three-level T-type inverter.
J. Electr. Eng. Technol. 2017, 12, 2227–2236.
18. Zhang, Y.; Li, J.; Li, X.; Cao, Y.; Sumner, M.; Xia, C. A Method for the Suppression of Fluctuations in
the Neutral-Point Potential of a Three-Level NPC Inverter with a Capacitor-Voltage Loop. IEEE Trans.
Power Electron. 2017, 32, 825–836. [CrossRef]
© 2019 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access
article distributed under the terms and conditions of the Creative Commons Attribution
(CC BY) license (http://creativecommons.org/licenses/by/4.0/).
204
energies
Article
An Improved Imperialist Competitive Algorithm to
Solve the Selected Harmonic Elimination
Pulse-Width Modulation in Multilevel Converters
Zheng Gong 1 , Qi Cui 1 , Xi Zheng 1 , Peng Dai 1, * and Rongwu Zhu 2
1 Jiangsu Province Laboratory of Mining Electric and Automation, China University of Mining and
Technology, Xuzhou 221008, China; [email protected] (Z.G.); [email protected] (Q.C.);
[email protected] (X.Z.)
2 Chair of Power Electronics, Chritian-Albrechts- University of Kiel, 24118 Kiel, Germany; [email protected]
* Correspondence: [email protected]; Tel.: +86-150-0521-5026
Abstract: The traditional intelligent algorithms for the selected harmonic elimination pulse-width
modulation (SHEPWM) of multilevel converters provide low convergent rate and low accuracy of
solutions when solving quarter-wave symmetry nonlinear equations. To obviate this problem and
obtain a better modulating performance, an improved imperialist competition algorithm is proposed.
The proposed algorithm enhances the global search ability by using moving imperialists. Also,
a novel type of particles, named independent countries, are proposed to help the algorithm jump out
of the local optimum. These independent countries change their positions using swarm intelligence.
Compared with the existing particle swarm algorithm and genetic algorithm, the proposed algorithm
has significant advantages by improving the accuracy of solutions and the rate of convergence. Finally,
the correctness and effectiveness of the proposed algorithm are verified and evaluated by simulation
and experimental results.
1. Introduction
Multilevel converters have been widely applied in high-voltage and high-power applications
because of their advantages of effectively improving the quality of output voltage waveform, large
output capacity, and high inverting efficiency [1,2]. They have been employed for many industrial
applications, such as electrical motor drives [3], energy storage systems [4], and renewable power
generators [5]. Moreover, they are also considered as active power filters [6,7] to satisfy the urgent
grid-friendly requirements. There are several methods, such as sinusoidal pulse-width modulation
(SPWM), space vector pulse-width modulation (SVPWM), and selective harmonic elimination
pulse-width modulation (SHEPWM), that can be applied to multilevel converters. As shown in
Table 1, compared with the other two methods, the most attractive advantage of the SHEPWM is that
the low-order harmonics can be controlled. In addition, SHEPWM also keeps the advantages of a wide
modulation index and a high utilization of DC voltage [4]. It was also verified that SHEPWM could be
implemented with the objective of minimizing total harmonic distortion (THD) [8].
The key challenge for the SHEPWM technique is to solve nonlinear equations containing
trigonometric functions to obtain the right switching angles. A lot of contributions have been made
to address this issue in recent years. In a study [9], the Walsh functions are employed to transform
nonlinear equations into a series of linear algebraic equations, which can be easily calculated online,
providing various sets of solutions. Nevertheless, the transitions between the Walsh series and the
Fourier series requires an effective algorithm, and the high-accuracy requirement may cause an extra
heavy computation [10]. In reference [11], high-order equations are transferred to simple trigonometric
polynomials, and the calculation mass is greatly reduced by employing the resultant theory. However,
the increase of the switching angles enlarges the polynomial order and makes it very difficult to
be implemented; also, if there are several DC sources, the expression of the resultant polynomials
becomes more complicated [12]. The Homotopy algorithm is adopted to solve the equations in other
studies [13,14]. It features a rapid convergence and can be extended to the high-level converters
without any extra analytical calculations. Moreover, only one set of solutions can be obtained by
this algorithm. In references [15,16], the Newton–Raphson algorithm is applied to solve nonlinear
equations. This algorithm keeps a high accuracy and a low computation burden, but its implementation
strongly relies on the accuracy of the initial values. If the predictions of these initial values are not
around the right solution, the solving process would plunge into local optima. Meanwhile, there is still
only one sets of solutions that can be determined in each solving instant. A novel Groebner–Bases-based
method is presented in reference [17], which transforms the nonlinear equations into an equivalent
canonical system and improves the accuracy of the solutions. However, the transformation becomes
very complex when the order of the equations is high, making this method more complicated than the
previous methods.
On the basis of the review above, it is seen that the aforementioned solving methods for the
SHEPWM are commonly complex and not available for all sets of solutions. Actually, the problem of
solving the SHEPWM can be reformulated into a constraint optimization problem, and many intelligent
algorithms can also be adopted to solve this problem [18–22]. They not only can find all solutions, but
also can be expediently applied to the multilevel converters with equal or non-equal DC voltage sources.
The genetic algorithm (GA) has been used in SHEPWM for many years. It is an algorithm which
was inspired by natural biological evolution. This approach employs selection, crossover, and mutation
operators and starts by randomly generating the individuals of a population. The individuals represent
the properties of a solution and can be mutated and crossover to evolve toward better solutions. As we
can see, the GA is simple and easy to understand but, as the required switching angles increase,
the distortion of the output voltage gets worse. A new GA algorithm in reference [18] divided
a population into several independent populations whose individuals can migrate from one to another.
This improved algorithm, named multi-population genetic algorithm (MGA), can settle the problem of
precociousness efficiently, but the accuracy of solutions still demands improvement. Particle swarm
optimization (PSO), a common algorithm, simulates the predation behaviour of bird flocks and has
been proved very efficient in precision and convergent rate compared with GA. Each particle of PSO
has personal and global best positions which guide it towards to the optimal solution. The PSO in
reference [19] is used to solve a problem that reduces the computation. In reference [20], a constriction
factor was introduced, and a method to obtain proper constriction factor and acceleration coefficients
was described. The advanced algorithm improves the precociousness problem but still lacks global
search ability.
The imperialist competitive algorithm (ICA) is inspired by imperialistic competition and includes
two primary categories: imperialists and colonies. The major steps are colonies assimilation and
empires’ competition. The research presented in references [21,22] has proved the ascendency of the
206
Energies 2018, 11, 3080
ICA in rate and speed of convergence. The contribution described in reference [23] is the first attempt
to apply the ICA to solve the SHEPWM of power converters. It has been proved that this conventional
ICA algorithm can solve nonlinear equations when the dimension of the variable is low. However,
the convergent rate decreases, and the accuracy of solutions of the conventional ICA becomes worse
with the increasing dimension of multilevel converters. Hence, the solving execution time will be
longer, and the modulation accuracy will not be guaranteed.
To improve the ICA-based SHEPWM for multilevel converters, a novel kind of solving method
based on the particles named the independent countries is proposed in this paper. The optimized
design is conducted from two starting points: one is to increase the diversity and movements of the
imperialists, the other is to enhance the ability to jump out of the local optimal. This optimized design
is expected to obtain high convergent rates and high accuracy solutions when the converter’ dimension
increases. In addition, with taking the neutral-point-clamped H-Bridge (NPC/H-Bridge) five-level
converter [24] as a typical multilevel converter for the application, sufficient comparative analysis
and simulation research regarding various kind of solving methods for the multilevel SHEPWM are
carried out to present the characteristics and advantages of the proposed method. Finally, experimental
research is also conducted with a downscaled NPC/H-Bridge five-level converter prototype to validate
its practical applicability.
The rest of this paper is divided as follows. Section 2 introduces the topology of the NPC/H-Bridge
five-level converter and the basic principle for solving the SHEPWM. Section 3 presents the novel
intelligent algorithm and compares it to three existing algorithms in detail. Simulation results and
best solutions regarding the condition of two switching angles per quarter wave are described and
evaluated in Section 4. The experimental results are shown in Section 5, and Section 6 concludes
this paper.
207
Energies 2018, 11, 3080
Taking phase A as an example, it can be seen that the switching devices Sa1–Sa4 cascade the
right bridge, while the Sa5–Sa8 cascade the left bridge. Each bridge can generate three voltages, i.e.,
+1/2V dc , 0, and −1/2V dc by different switching angles, so the output voltages of phase A include
+V dc , +1/2V dc , 0, −1/2V dc , −V dc . Table 2 shows the switching states of the NPC/H bridge five-level
inverter. Sx1 -Sx8 represent the switching states of IGBTs. VXN is the value of output voltage. In this
paper, the switching states 1, 2, 5, 8, and 9 are chose to synthesize the output waveforms.
Figure 2. Pulse width modulation (PWM) waveforms definition of two switching angles according to
the quarter-wave SHEPWM techniques. (a) Waveform at low modulation width; (b) waveform at high
modulation width.
Equation (1) shows the Fourier series expansion of the full cycle.
∞
V ( t ) = a0 + ∑ (an cos nωt + bn sin nωt) (1)
n =1
where n = 1, 2, 3 . . .
208
Energies 2018, 11, 3080
Because of the characters of quarter-wave symmetry, the DC component a0 and the cosine
component an are equal to zero. The sine component is zero when n is even. Equation (1) is simplified
as follow: ⎧
⎪ an = 0,
⎪ ⎧
n = 0, 1, 2, 3 . . .
⎨
⎨ 0, n is even (2)
⎪ bn =
⎪ N
k +1
⎩ ⎩ nπ
4E
∑ (−1) cos nαk
k =1
Because all triple harmonics are removed in line voltage, only the 6k ± 1th harmonic should be
eliminated. Equation (3) is the simplified Equation (2):
⎧ N
⎪
⎪
⎨
2
π ∑ pk cos αk = M
k =1 (3)
⎪
⎪
N
⎩ ∑ pk cos nαk = 0 n = 5, 7, 11, . . . , 6k ± 1
k =1
where pk indicates the rising or falling edge of the output voltage, which is given by Equation (4):
1 rising edge
pk = (4)
−1 falling edge
According to the waveform of the five-level converter, the polynomial equations can be simplified
to Equation (5):
cos α1 + cos α2 − Mπ/2 = ε 1
(5)
cos 5α1 + cos 5α2 = ε 2
f (α) = ε 1 2 + ε 2 2 (6)
Equation (6) is the cost function of the intelligent algorithm, which is built on Equation (3).
Different switching angles can be calculated when the modulation index is changed.
Cn = cn − max{ci } (9)
i
209
Energies 2018, 11, 3080
C
n
pn = (10)
Nimp
∑ C
i
i =1
where cn is the cost of the nth imperialist, and Cn and pn are its normalized value and power. N.Cn in
Equation (11) represents the number of colonies of every imperialist.
(2) Assimilating colonies. Each imperialist improves its colonies by changing their positions.
All colonies move toward the imperialist according to Equations (12) and (13):
colniand colni−1
mean the current and previous positions of the nth colony, and r4 is the assimilation
coefficient. During this process, if the cost of any colony is less than the cost of the relative imperialist,
the imperialist position is updated.
(3) Imperialistic competition. The most powerful empire takes possession of the worst colony of
the weakest empire by two procedures.
(a) Calculating the total costs of empires.
N.C.n
∑ f (colm )
i=m
T.Cn = f (impn ) + ξ × (14)
N.Cn
In Equation (14), T.Cn means the total cost of the nth empire, and ξ is a positive number less
than 1.
(b) The empire which has the largest T.Cn is regarded as the weakest empire, and its worst colony
is captured by other empires, according to Equations (15) and (16):
where T.Cn and N.T.Cn indicate the total cost and normalized total cost, respectively. Rn is the
probability of the nth empire capturing the worst colony.
(4) Eliminating the worst empire. When an empire loses all its colonies, it is deleted.
(5) Reset colonies’ positions. When the total cost of the best empire does not change for a long
time, reset all colonies’ positions of each empire stochastically.
In this paper, not only the colony countries change positions, but also the imperialists move
their positions to improve their performance. Also, a type of particles called independent countries
is presented to improve the diversity of ICA, which change positions using swarm intelligence.
This new hybrid algorithm consists of both PSO and ICA and, thus, it is called PSOICA algorithm.
The implementation steps of the proposed PSOICA algorithm are as follows.
(a) Select the first (Nimp + 1~Nimp + Nind ) powerless countries as independent countries according
to Equations (7)–(9). Nind is the number of independent countries.
210
Energies 2018, 11, 3080
(b) Move imperialists and independent countries in line with the PSO procedures. In this step,
imperialists and independent countries may gain better positions. This step enhances the global search
ability of the algorithm.
impin = impin−1 + Vimp
i
(17)
i
Vimp = c1 ∗ r1 ∗ (bestimp − impin−1 ) (18)
Move the imperialists on the basis of Equations (17) and (18); impin and i
Vimp indicate the current
position and velocity of the nth imperialist, impin−1 means the previous position of the nth imperialist,
c1 is a positive number less than 1, and r1 is a random number between 0 and 1. If the cost of the
current position is less than that of the previous position, update the imperialist, otherwise, keep the
previous position.
Equations (19) and (20) show the movement of independent countries, where Pl and Pg are the
personal and global best positions of the nth independent countries, Vni is the current velocity, indin is
the current position of the nth independent country, ω is the inertia weight, c2 and c3 are acceleration
constants, and r2 and r3 are random numbers between 0 and 1. If the cost of Pg is better for the
imperialist, the imperialist moves to Pg , and vice versa if it is worse.
Figure 3 shows the moving steps of the ICA and the proposed PSOICA.
*&% %
D%
%%
<>
*&% %%
%
D%
%%
<*>
Figure 3. (a) Moving steps of the imperialist competitive algorithm (ICA); (b) moving steps of the
particle swarm optimization (PSO) ICA (PSOICA).
Figure 3a shows the moving steps of the conventional ICA [20,22] when all the colony countries
are assimilated by their imperialist, and the imperialist never moves. Figure 3b shows the moving steps
of the proposed PSOICA, with all the colony countries moving towards their imperialist. Meanwhile,
the imperialist changes its position and then it may move to a better position. The independent
countries move to their next positions on the basis of the swarm intelligence, and they may get new
better positions or stay in the former positions.
Figure 4 shows the flow chart of the proposed PSOICA.
211
Energies 2018, 11, 3080
E%%
%
("* D
%+
%+&V
T T
)*%%$%% I%%+
D
,%*
("
%
I%+$%%%+ D
'%V
T T
*%'U*
%
,%* %
D %
)%
D
)+"%
%V
%%
T
Table 3. Comparing the performance of the PSOICA to those of the multi-population genetic algorithm
(MGA), PSO, and ICA.
f (α)
m Switching Angles THD%
MGA PSO ICA PSOICA
1.1 6.715 42.72 18.34 2.95 × 10−11 4.93 × 10−32 4.93 × 10−32 4.93 × 10−32
1 16.33 52.33 19.27 9.80 × 10−11 4.93 × 10−32 4.93 × 10−32 4.93 × 10−32
0.9 23.99 59.99 26.58 1.02 × 10−11 4.93 × 10−32 4.93 × 10−32 2.77 × 10−32
0.8 30.65 66.65 35.21 5.06 × 10−17 0 0 0
0.7 36.7 72.68 43.95 1.08 × 10−8 0 0 0
0.6 42.3 78.3 52.64 8.53 × 10−10 1.233 × 10−32 1.23 × 10−32 1.11 × 10−31
0.5 47.61 83.61 60.7 3.62 × 10−11 4.93 × 10−32 4.93 × 10−32 1.97 × 10−31
0.4 52.71 88.71 65.51 1.64 × 10−11 4.93 × 10−32 4.93 × 10−32 4.93 × 10−32
0.3 57.69 86.31 88.04 1.01 × 10−6 3.081 × 10−33 3.08 × 10−33 0
0.2 62.5 81.5 128.72 5.04 × 10−8 1.233 × 10−32 1.23 × 10−32 1.77 × 10−30
0.1 67.26 76.74 205.63 5.12 × 10−8 7.704 × 10−34 7.70 × 10−34 7.70 × 10−34
212
Energies 2018, 11, 3080
It should be noticed that all four algorithms converge successfully, and all the THD under the
same modulation index unify, which means that all the algorithms can solve the nonlinear equations
efficiently when only two switching angles are included. The cost values show that the PSO, ICA, and
the proposed PSOICA are better than the MGA in local search. The cost of the MGA is about 1 × 10−10 ,
and those of the PSO, ICA, and PSOICA are about 1 × 10−30 .
At low modulation index, if more selected harmonics of output voltage have to be eliminated,
the switching angles per quarter wave should be increased. Table 4 shows the results of the four
algorithms when we compare the best costs of five computations. Each quarter wave includes
four angles.
Algorithms α1 α2 α3 α4 f (α)
MGA 51.219 57.315 73.357 84.342 0.001912
PSO 50.893 57.74 72.439 85.149 1.76 × 10−31
ICA 50.894 57.74 72.439 85.148 2.38 × 10−10
PSOICA 50.893 57.74 72.439 85.149 1.68 × 10−30
As can be seen, the switching angles of the MGA deteriorated, and the cost are bigger than
1 × 10−5 . Figure 5a shows the simulation results of the MGA. The output voltage distortion could not
be ignored. In contrast, the costs of the PSO, ICA, and the proposed PSOICA are much smaller than
1 × 10−5 . However, with the increasing switching angles, the accuracy of the solution could worsen.
Comparing Table 3 with Table 4, the accuracy of the solutions calculated by the ICA or the MGA
decreases rapidly with the increasing switching angles, while the costs of the PSO and the PSOICA have
no significant changes. Hence, the advantages of the PSO and PSOICA algorithms in local searching
ability are further confirmed. Figure 5b,c exhibits the phase voltages and corresponding spectra.
As shown in Figure 5, when the switching angles increase to 4, the MGA cannot eliminate the 5th
harmonic completely, and the phase voltage distortion raises to 9.2%. In contrast to the MGA, the 5th,
7th, and 11th harmonics are eliminated by the PSO, ICA, and proposed PSOICA. At the same time,
the phase voltages also meet the desired values.
The results show that the dimension of the variables has a large influence on the precision of
solutions. In Figure 6, the phase voltage distortion rates and the THDs of the four algorithms are plotted
with respect to the modulation degree in the situation of four switching angles per quarter wave.
As we can see, the phase voltage distortion rates (PVDR) of the MGA even reach 40%, which is
quite higher than the those of PSO, conventional ICA, and proposed PSOICA, whose PVDR ar on the
average, 1%. That means that the MGA performs worse in high variable optimization problems.
In contrast, the PSO, conventional ICA, and proposed PSOICA can output the desired voltage
effectively and eliminate the selective harmonics. However, there is a big difference between these
three algorithms. They have different THD of phase voltages. For PSO and ICA, the THDs decrease
with modulation increase but, in some situations, the THDs get higher. For the proposed PSOICA,
THD is an obvious attenuation curve. This is because in low modulation index, the nonlinear equations
with the four switching angles have three different solutions, and each of them has different THDs.
The PSOICA finds the best optimal solution that has the lowest THD each time. However, the ICA and
PSO frequently result in suboptimal solutions, with higher THDs due to the searching limitation.
213
Energies 2018, 11, 3080
Figure 5. Waveforms of phase voltage and spectrum analysis of four algorithms: (a,b) MGA; (c,d) PSO;
(e,f) ICA; (g,h) the proposed PSOICA. THD: total harmonic distortion.
A= A=1
-FI'+"%6X9
A1 A11
I%%'"%6X9
5= 5=1
51 (8) 511
0= (8)
0=1 E
01 *)
011 E *)
=
1 =1
E *)
= E *) 11
1 =1
11= 1 1 = 10 10= 15 11= 1 1 = 10 10= 15
Figure 6. Characteristic analysis: (a) voltage distortion rate; (b) THDs.
Therefore, we come to the conclusion that, when the dimension of the cost function increases,
the local search ability of the MGA decreases, and the PSO, ICA, and proposed PSOICA meet the
precision requirements. However, the results of the PSOICA include different solutions which always
contain the optimal solution. That means that the PSOICA may present the best global searching
ability among the four studied algorithms.
214
Energies 2018, 11, 3080
Table 5 is built to compare the global searching ability which is based on the data of 100 runnings
for every algorithm.
Compared to the proposed PSOICA, the conventional ICA has a lower convergent rate and a
higher possibility of getting one solution. It shows that the proposed PSOICA enhances the global
searching ability of the ICA. The PSOICA has a 54% chance of getting all three sets of solutions.
The MGA barely obtains three solutions, and the PSO only has one solution in each calculation
instant. Moreover, the convergent rate of PSOICA is also better than those of the MGA and PSO,
which demonstrates the superiority of the PSOICA in global search.
According to the comprehensive comparative analysis above, it can be seen that the
proposed PSOICA has advantages over the MGA, PSO, and ICA, regarding both global and local
searching abilities.
4. Simulation Analysis
To identify the correctness of solutions, we selected two different solutions, which are [20.3232,
56.3232] at 0.95 modulation index, and [62.4933, 81.5067] at 0.2 modulation index, and used
Matlab/Simulink for simulation and harmonic analysis. The simulation conditions consisted of
a fundamental output frequency of 50 Hz and a DC voltage of 1000 V.
In Figure 7, the phase voltage waveforms conform to the waveforms at low modulation shown
in Figure 1a, and the amplitude matches the desired values exactly. A spectrum analysis shows that
the selected 5th harmonic in phase voltage as well as the 5th and triple harmonics in line voltage are
completely eliminated.
In Figure 8, the phase voltage waveforms are five-level, as shown in Figure 1b. The output
voltages match the desired values exactly, and the selected 5th harmonic in phase voltage as well as
the 5th and triple harmonics in line voltage are equal to zero. This verifies the correctness of switching
angles and the effectiveness of the SHEPWM strategy.
Figure 7. Simulation results with a modulation index of 0.2: (a) waveforms of phase voltage and its
spectrum analysis; (b) waveforms of line voltage and its spectrum analysis.
215
Energies 2018, 11, 3080
111 0111
, =11 111
1 1
?=11 ? 111
? 111 ?0111
1 110 11A 114 1 110 11A 114
11 11
21 21
41 41
A1 A1
01 01
1 1
1 0 A 4 2 1 0 A 4 2 01 1 0 A 4 2 1 0 A 4 2 01
F F
<> <*>
Figure 8. Simulation and analysis with a 0.95 modulation index: (a) waveforms of phase voltage and
its spectrum analysis; (b) waveforms of line voltage and its spectrum analysis.
Figure 9a displays the trends of two switching angles, and second solutions are found in the
modulation index range of 0–0.605. The fact that the two solutions change regularly and work out at
all modulation indexes is convenient for building a look-up table. Both these solutions meet various
conditions of the five-level SHEPWM strategy and have different THDs. Figure 9b shows the THDs
of the two solutions. For the first solutions, low and high waveforms correspond to the modulation
index ranges 0–0.375 and 0.375–1.12, respectively. The second solutions merely work for waveforms
of low modulation index, between 0 and 0.605. Taking THD into consideration, for the situation of
two switching angles per quarter wave, we can conclude that, in the ranges of 0–0.551 and 0.605–1.12,
the first solutions are better, whereas, in the remaining range, the second solutions are more suitable.
Figure 9. Trends of two switching angles and second solutions with the varying of the modulation
index: (a) switching angles of the PSOICA; (b) THDs of the two different solutions.
5. Experimental Results
A downscaled three-phase NPC/H-Bridge five-level converter experimental prototype, shown in
Figure 10, is set up to validate the proposed PSOICA. The power devices of the experimental prototype
are insulated gate bipolar transistors (IGBT) modules (Infineon-BSM50GB120DLC). Meanwhile,
a high-speed digital control platform based on the digital signal processor (DSP) (TI-TMS320F28335)
and field programmable gate array (FPGA) (Xilinx-XC3S500E) is also adopted to implement the
proposed PSOICA. The experimental conditions consist of the fundamental output frequency of 50 Hz
and the DC voltage of 100 V.
216
Energies 2018, 11, 3080
I%*%
%'$
IE C 8)
"?"D *F?
$"%
+%
-+?+
%'I*
%
++'%
%'
Figure 10. Three-phase neutral-point-clamped (NPC)/H-Bridge five-level converter experimental prototype.
Figure 11a shows the phase voltage and line voltage and their spectrum analysis under 0.2
modulation index. The waveforms are the same as those of the simulation results, and the selected
5th harmonic and triple harmonics are totally eliminated. Figure 11b exhibits the phase voltage and
line voltage and their spectrum analysis under 0.95 modulation index. The phase voltage is five-level
and the line voltage is nine-level, which are similar to the simulation results. Moreover, the selected
harmonic and triple harmonics in line voltage are also removed. Hence, the analysis and simulation
results are validated by these experimental results.
%6 11"9
%6 11"9
+"% #"%
+"%
#"%
Figure 11. Experimental analysis of the waveforms: (a) waveforms of phase voltage and line voltage
and their spectrum analysis under a modulation index of 0.2; (b) waveforms of phase voltage and line
voltage and their spectrum analysis under a modulation index of 0.9.
217
Energies 2018, 11, 3080
As seen, a minor difference can be observed regarding the harmonic distribution characteristics
between the simulation results (see Figures 7 and 8) and the experimental results. We think that this is
mainly the result of two factors: one is the model difference between the simulation model and the
actual experimental prototype, the other is the dead-time effect. As known, the IGBT model in the
Matlab/Simulink is relatively ideal and can be regarded as a switch without the turn-on/turn-off time,
so the dead-time is not set in the simulation research in this paper. However, for the experimental setup,
the actual IGBT modules cannot switch as fast as the simulation models. Hence, for the experimental
research described above, the dead-time was set to 4 μs in order to prevent a short circuit in each
bridge arm. Considering that the SHEPWM is strongly associated with the switching time of the IGBTs,
the above factors may cause the aforementioned minor difference.
6. Conclusions
In this paper, an improved ICA algorithm named PSOICA has been proposed for solving the
multilevel SHEPWM. Two starting points were followed for designing the PSOICA: one was to increase
the diversity and movements of the imperialists, the other was to enhance the ability to jump out of
the local optimal. Hence, a novel type of particles, named independent countries, were brought into
the conventional ICA to solve the nonlinear equations for the multilevel SHEPWM, especially for the
situations with two and four switching angles per quarter wave. Compared to the existing MGA, PSO
algorithm, and conventional ICA, the proposed PSOICA shows better performances both in global
and local searching abilities, which verify the superiority of the proposed PSOICA. At the same time,
the switching angles at different modulation indexes were calculated more accurately by the proposed
PSOICA, which could help to obtain a more accurate modulating performance for various kinds of
multilevel converters. Moreover, since a higher convergent rate can be obtained by the proposed
algorithm, the execution time for solving the multilevel SHEPWM can also be reduced. Thus, the
proposed PSOICA could provide a more appropriate solving approach for the SHEPWM with a high
number of voltage levels.
Author Contributions: The individual contribution of each co-author with regards to the reported research and
writing of the paper is as follows. Z.G. and P.D. conceived the idea, Q.C. and X.Z. performed data analysis and
the simulation/experimental results, R.Z. analyzed the results and all authors wrote the paper. All authors have
read and approved the manuscript.
Funding: This research was funded by the Fundamental Research Funds for the Central Universities (China
University of Mining and Technology), grant number 2018QNB02.
Conflicts of Interest: The authors declare no conflict of interest.
References
1. Son, Y.; Kim, J. A novel phase current reconstruction method for a three-level neutral point clamped inverter
(NPCI) with a neutral shunt resistor. Energies 2018, 11, 2616. [CrossRef]
2. Gong, Z.; Wu, X.; Dai, P.; Zhu, R. Modulated model predictive control for MMC-based active front-end
rectifiers under unbalanced grid conditions. IEEE Trans. Ind. Electron. 2019, 66, 2398–2409. [CrossRef]
3. Rathore, R.; Holtz, H.; Boller, T. Generalized optimal pulse-width modulation of multilevel inverters for
low-switching-frequency control of medium-voltage high-power industrial AC drives. IEEE Trans. Ind. Electron.
2013, 60, 4215–4224. [CrossRef]
4. Wang, Q.S.; Cheng, M.; Jiang, Y.L.; Zuo, W.J.; Buja, G. A simple active and reactive power control for
applications of single-phase electric springs. IEEE Trans. Ind. Electron. 2018, 65, 6291–6300. [CrossRef]
5. Pouresmaeil, E.; Mehrasa, M.; Shokridehaki, M.A.; Rodrigues, E.M.G. Integration of renewable energy
for the harmonic current and reactive power compensation. In Proceedings of the 2015 IEEE 5th
International Conference on Power Engineering, Energy and Electrical Drives (POWERENG), Riga, Latvia,
11–13 May 2015; pp. 32–36.
6. Mehrasa, M.; Pouresmaeil, E.; Akorede, M.F. Multilevel converter control approach of active power filter for
harmonics elimination on electric grids. Energy 2015, 84, 722–731. [CrossRef]
218
Energies 2018, 11, 3080
7. Mehrasa, M.; Pouresmaeil, E.; Zabihi, S.; Rodrigues, E.M.G. A control strategy for the stable operation of the
shunt active power filters in power grids. Energy 2016, 96, 325–334. [CrossRef]
8. Srndovic, M.; Zhetessov, A.; Alizadeh, T.; Familiant, Y.L.; Grandi, G.; Ruderman, A. Simultaneous Selective
Harmonic Elimination and THD Minimization for a Single-Phase Multilevel Inverter with Staircase
Modulation. IEEE Trans. Ind. Appl. 2018, 54, 1532–1541. [CrossRef]
9. Zheng, C.H.; Zhang, B.; Qiu, D.Y. Solving switching angles for the inverter’s selected harmonic elimination
technique with walsh function. In Proceedings of the 2005 International Conference on Electrical Machines
and Systems, Nanjing, China, 27–29 September 2005; pp. 1366–1370.
10. Dahidah, M.S.A.; Konstantinou, G.; Agelidis, V.G. A review of multilevel selective harmonic elimination
PWM: Formulations, solving algorithms, implementation and applications. IEEE Trans. Power Electron. 2015,
30, 4091–4106. [CrossRef]
11. Chiasson, J.N.; Tolbert, L.M.; McKenzie, K.J.; Du, Z. Elimination of harmonics in a multilevel converter using
the theory of symmetric polynomials and resultants. IEEE Trans. Control Syst. Technol. 2005, 13, 216–223.
[CrossRef]
12. Jacob, T.; Suresh, L.P. A review paper on the elimination of harmonics in multilevel inverters using
bioinspired algorithms. In Proceedings of the 2016 International Conference on Circuit, Power and
Computing Technologies (ICCPCT), Nagercoil, India, 18–19 March 2016; pp. 1–8.
13. Guan, E.; Song, P.G.; Ye, M.Y.; Wu, B. Selective harmonic elimination techniques for multilevel cascaded
H-bridge inverters. In Proceedings of the International Conference on Power Electronics and Drives Systems,
Kuala Lumpur, Malaysia, 28 November–1 December 2005; pp. 1441–1446.
14. Aghdam, M.G.H.; Fathi, S.H.; Gharehpetian, G.B. Elimination of harmonics in a multi-level inverter with
unequal DC sources using the homotopy algorithm. IEEE Int. Symp. Ind. Electron. 2007, 578–583. [CrossRef]
15. Fei, W.M.; Du, X.L.; Wu, B. A Generalized half-wave symmetry SHE-PWM formulation for multilevel voltage
inverters. IEEE Trans. Ind. Electron. 2010, 57, 3030–3038. [CrossRef]
16. Kumar, A.; Chatterjee, D.; Dsagupta, A. Harmonic mitigation of cascaded multilevel inverter with non-equal
DC sources using hybrid newton raphson method. In Proceedings of the 2017 4th International Conference
on Power, Control & Embedded Systems (ICPCES), Allahabad, India, 9–11 March 2017; pp. 1–5.
17. Yang, K.H.; Zhang, Q.; Yu, W.S.; Yuan, H.X. Selective harmonic elimination with groebner bases and
symmetric polynomials. IEEE Trans. Power Electron. 2016, 31, 2742–2752. [CrossRef]
18. Ye, M.Y.; Zhou, Q.Q.; Hong, C.; Song, L. Multiple population genetic algorithm based on multi-band
SHEPWM control technology for multi-level inverter. Trans. China Electrontech. Soc. 2015, 30, 111–119.
[CrossRef]
19. Kumar, N.V.; Chinnaiyan, V.K.; Pradish, M.; Divekar, M.S. Enhanced power quality of MLI using PSO based
selective harmonic elimination. In Proceedings of the 2015 International Conference on Green Computing
and Internet of Things (ICGCIoT), Noida, India, 8–10 October 2015; pp. 42–47.
20. Kouzou, A.; Mahmoudi, M.O.; Boucherit, M.S. Application of SHE-PWM for seven-level inverter output
voltage enhancement based on particle swarm optimization. In Proceedings of the 2010 7th International
Multi- Conference on Systems, Signals and Devices, Amman, Jordan, 27–30 June 2010; pp. 1–6.
21. Atashpaz-Gargari, E.; Lucas, C. Imperialist competitive algorithm: An algorithm for optimization inspired
by imperialistic competition. In Proceedings of the 2007 IEEE Congress on Evolutionary Computation,
Singapore, 25–28 September 2007; pp. 4661–4667.
22. Mitras, B.A.; Sultan, J.A. A novel hybrid imperialist competitive algorithm for global optimization. Aust. J.
Basic Appl. Sci. 2013, 7, 330–341.
23. Etesami, M.H.; Farokhnia, N.; Fathi, S.H. A method based on imperialist competitive algorithm (ICA),
aiming to mitigate harmonics in multilevel inverters. In Proceedings of the 2011 2nd Power Electronics,
Drive Systems and Technologies Conference, Tehran, Iran, 16–17 February 2011; pp. 32–37.
24. Cheng, Z.; Wu, B. A Novel Switching Sequence Design for five-level NPC/H-bridge inverters with improved
output voltage spectrum and minimized device switching frequency. IEEE Trans. Power Electron. 2007, 22,
2138–2145. [CrossRef]
25. Chang, H.; Wei, R.; Ge, Q.; Wang, X.; Zhu, H. Comparison of SVPWM for five level NPC/H-Bridge
inverter and traditional five level NPC inverter based on line-voltage coordinate system. In Proceedings
of the 2015 18th International Conference on Electrical Machines and Systems (ICEMS), Pattaya, Thailand,
25–28 October 2015; pp. 574–577.
219
Energies 2018, 11, 3080
26. Taleb, R.; Helaimi, M.; Benyoucef, D.; Boudjema, Z. A comparative analysis of multicarrier SPWM strategies
for five-level flying capacitor inverter. In Proceedings of the 2016 8th International Conference on Modelling,
Identification and Control (ICMIC), Algiers, Algeria, 15–17 November 2016; pp. 608–611.
27. Mehrasa, M.; Pouresmaeil, E.; Akorede, M.F.; Zabihi, S.; Catalao, J.P.S. Function-based modulation control for
modular multilevel converters under varying loading and parameters conditions. IET Gener. Transm. Distrib.
2017, 11, 3222–3230. [CrossRef]
28. Ayyappa, P.N.V.S.; Srinivas, C.; Singh, T.R.S. A novel way to deal with harmonic elimination in multi-level
CHB inverter using without filtering technique. In Proceedings of the 2017 International conference of
Electronics, Communication and Aerospace Technology (ICECA), Coimbatore, India, 20–22 April 2017;
pp. 62–67.
29. Fei, W.; Wu, B.; Wu, Q. A novel SHE-PWM method for five level voltage inverters with quarter-wave
symmetry. In Proceedings of the 2009 Canadian Conference on Electrical and Computer Engineering, St.
John’s, NL, Canada, 3–6 May 2009; pp. 1034–1038.
30. Dahidah, M.S.A.; Agelidis, V.G.; Rao, M.V. On abolishing symmetry requirements in the formulation of a
five-level selective harmonic elimination pulse-width modulation technique. IEEE Trans. Power Electron.
2006, 21, 1833–1837. [CrossRef]
© 2018 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access
article distributed under the terms and conditions of the Creative Commons Attribution
(CC BY) license (http://creativecommons.org/licenses/by/4.0/).
220
energies
Article
An Input-Parallel-Output-Series Switched-Capacitor
Three-level Boost Converter with a Three-Loop
Control Strategy
Jianfei Chen 1, *, Caisheng Wang 2 and Jian Li 1
1 State Key Laboratory of Power Transmission Equipment & System Security and New Technology,
Chongqing University, Chongqing 400044, China; [email protected]
2 Department of Electrical and Computer Engineering, Wayne State University, Detroit, MI 48202, USA;
[email protected]
* Correspondence: [email protected]; Tel: +86-188-8387-6496
Abstract: There has been increasing interest for industry applications, such as solar power
generation, fuel cell systems, and dc microgrids, in step-up dc-dc converters with reduced number
of components, low component stress, small input ripples and high step-up ratios. In this paper,
an input-parallel-output-series three-level boost (IPOS-SC-TLB) converter is proposed. In addition
to achieving the required performance, the input and output terminals can share the same ground
and an automatic current balance function is also achieved in the IPOS-SC-TLB converter. Besides,
a capacitor voltage imbalance mechanism was revealed and a three-loop control strategy composed
of output voltage loop, input current loop and voltage-balance loop was proposed to address the
voltage imbalance issue. Finally both simulation and experiment studies have been conducted to
verify the effectiveness of the IPOS-SC-TLB converter and the three-loop control strategy.
1. Introduction
Multilevel step-up dc-dc converters are widely employed in wind farms [1–6], solar power
generation systems [7–11], fuel cell systems [12–15], high-power charging stations for electric cars [16,17],
and dc microgrids [18–20]. In these systems, a multilevel step-up dc-dc converter helps regulate a
varying low-level input voltage to a stable high-level voltage, which usually serves as the dc link
voltage of a grid-connected inverter. It is desirable to achieve both low voltage stress and low
current stress across components to reduce power losses and save cost. Besides, input current ripple
is another important issue that should be considered for these systems, especially for fuel cell or
battery storage systems. As multilevel conversion techniques have evolved, many multilevel step-up
dc-dc converters have been proposed. In terms of non-isolated multilevel step-up dc-dc converters,
the three-level boost converter was firstly proposed and then adopted to combine with a three-level
diode-clamped inverter to achieve medium voltage and high power [2,6]. The corresponding four-level
boost converter was subsequently proposed to output higher voltage level and higher power [4].
Owing to the interleaved scheme, small input current ripple and low component stress could be easily
realized in these multilevel boost converters. However, the input terminal and the output terminal
in the two converters do not share the same ground, which can bring in severe EMI problem [7].
One flying-capacitor-based three-level boost converter was proposed to address this problem and good
effect has been achieved [12]. However, all these multilevel boost converters face the same inherent
limitation, i.e., the voltage gain is limited to be 1/(1 − d), where d is the duty ratio. Unfortunately,
practical considerations limit its output voltage to approximately four times its input voltage. To supply
a high output voltage, it must operate at extremely high duty-cycle whereas extreme duty-cycles
impose inefficient small off times. Small off times will cause severe diode reverse-recovery currents,
increasing electromagnetic interference (EMI) levels [9].
Another flying-capacitor-based three-level boost converter with intrinsic voltage doubler was
proposed in [21,22]. In addition to the advantages of topology described in [8], the two input inductor
currents of this converter could be self-balanced due to the flying-capacitor. Moreover, the voltage
gain of this converter is 2/(1 − d) instead of 1/(1 − d). However, the voltage stresses across the
output diode and the output capacitor equals to the output voltage, which is a disadvantage. On the
other hand, the voltage stresses across the output diodes could be decreased by half of the output
voltage in the converter with two symmetrical flying-capacitors [23]. Nevertheless, one more diode
and one more capacitor are necessary, and voltage stress across the output capacitor is still very high.
These shortcomings are also presented in the topologies proposed in [24,25]. In general, a list of split
capacitors connected in series is a good solution to reducing voltage stress across the output capacitor.
One solution is the application of a diode-capacitor voltage multiplier on a classical non-isolated boost
converter, which also presents a high voltage gain and self-balanced function for capacitor voltages [26].
However, a large input current ripple and a high current stress across the single switch exist inevitably
as no interleaved scheme is adopted in these converters. Modular multilevel dc-dc converter is a good
choice for high voltage applications, such as high voltage direct current (HVDC) and high voltage
drive areas [27–31]. However, it is not a good choice for medium-voltage applications. Reference [32]
proposed a modular multilevel dc-dc converter composed of multiple buck-boost converter modules,
which is suitable for medium-voltage and high-power applications. However, the output voltage of
the lower module multiplying by d/(1 − d) serves as the input voltage of the upper module, to achieve
a high voltage gain. The voltage gain is smaller than 2/(1 − d) and all switches do not share the same
ground. Recently, a switched-capacitor technique has begun to be employed in medium-voltage and
high-power dc-dc converters with good performance [33–36].
To address the abovementioned issues and to achieve a reduced number of components,
low component stress, small input ripples and high step-up ratio, an input-parallel-output-series
switched-capacitor three-level boost (IPOS-SC-TLB) converter is proposed in this paper. In addition to
achieving the required performance target, the proposed IPOS-SC-TLB converter also has automatic
current balancing capability. Compared with the existing three-level boost converters, the proposed
converter has the advantages of high voltage gain at full duty cycle range, small component stress,
a reduced number of components, common ground for the input and output terminals, and automatic
current balancing. All capacitors, diodes, switches only endure half of the output voltage, enabling
components with less voltage rating used in the proposed IPOS-SC-TLB converter. Common ground
for the input and output terminals not only save power supplies for designing drivers, also helps
reduce EMI. Automatic current balancing capability avoid additional current-balance control strategy
that is required in a multi-converter system. To address the voltage imbalance issue, a three-loop
control strategy composed of an output voltage loop, an input current loop and a voltage-balance loop
is developed for the IPOS-SC-TLB converter.
The remainder of the paper is organized as follows: Section 2 introduces the topology derivation
and operating principle of the proposed IPOS-SC-TLB converter. Performance analysis is subsequently
presented in Section 3 and the three-loop control strategy is given in Section 4. Both simulation and
experimental verifications have been done in Section 5 and finally the conclusions of the paper are
drawn in Section 6.
2. IPOS-SC-TLB Converter
222
Energies 2018, 11, 2631
(Figure 1b). As it can be seen, the total components of the two topologies are equal except the numbers
of inductors and capacitors. One inductor is necessary in the SI structure while (n − 1) inductors
are employed in the PI structure. The SI structure needs (n − 1) capacitors, while one capacitor is
necessary in the PI structure.
A comparative analysis between the two techniques are presented in Table 1. On the one hand,
(n − 1) voltage levels U0 , U1 , . . . Un−1 , are achieved due to the (n − 1) split capacitors in the SI
structure while only one output voltage level Un−1 is achieved in the PI structure. On the other hand,
the total input current flow through (n − 1) split inductors in the PI structure while through only
one inductor in the SI structure. As a result, the SI structure has output voltage divider function
and voltage-balance control strategy is necessary to realize voltage balance. The PI structure has
input current shunt function and current-balance control strategy is necessary to balance all split
inductor currents. All the drive circuits of the switches must be isolated in the SI topology, i.e., (n − 1)
isolated drive sources are necessary in the SI structure. However, this drawback does not exist in the
PI structure because all the switches share the same ground.
D
U
• • • U
D E
The conventional three-level boost converter is based on the SI structure in Figure 2a.
To distinguish it from other topologies in this paper, the converter in Figure 2a is called SI-TLB.
The converter in Figure 2b is named as PIB as it is based on the PI topology. The input terminal and
the output terminal of SI-TLB do not share the same ground, which easily results in electromagnetic
interference (EMI) problems. Moreover, the voltage stresses across all the components in a PIB
converter are high since no multilevel technique is employed.
223
Energies 2018, 11, 2631
• • • • •
• •
• •
• • •
(a) (b)
• • • • • •
• • •
• • • • •
(c) (d)
• • •
•
• •
• • • •
• • • • •
• • • • •
(e) (f)
•
• • •
• • •
• •
• • •
• • •
(g) (h)
Figure 2. Development of TLB converters: (a) SI-TLB; (b) PIB; (c) SI-FC-TLB; (d) PI-FC-TLB;
(e) PI-SFC-TLB; (f) SC-TLB; (g) IPOS-TLB1; (h) IPOS-TLB2.
To avoid these shortcomings mentioned above, flying-capacitor technique has been introduced
into SI-TLB and PIB converters to develop new three-level boost converters. The converter called
SI-FC-TLB in Figure 2c is derived by employing one flying-capacitor. The input terminal and the output
terminal share the same ground and all switches and diodes are clamped at the half of the output
voltage by controlling the voltage of the flying-capacitor Cf to be half of the output voltage [21,22].
224
Energies 2018, 11, 2631
However, it can be seen that SI-TLB and SI-FC-TLB both have a limited voltage gain due to the SI
structure. Thus, the converter called PI-FC-TLB in Figure 2d was proposed based on PI structure
and one flying-capacitor [21,22]. The voltage gain of PI-FC-TLB is as two times as that of SI-TLB
and SI-FC-TLB. But the voltage stress across the output diode is high, equal to the output voltage.
Also, another converter PI-SFC-TLB based on the PI structure and two symmetrical flying-capacitors
in Figure 2e was proposed to reduce the voltage stresses across the output diodes [23]. However,
the voltage stress across the output capacitor is still equal to the output voltage and many capacitors
and diodes are necessary. As analyzed above, flying-capacitor technique introduced into multilevel
boost converters based on SI structure could help solve the problem that input and output terminals
do not share the same ground while flying-capacitor technique introduced into multilevel boost
converters based on PI structure could help enhance voltage gains. However, there is a common
disadvantage among SI-FC-TLB, PI-FC-TLB, and PI-SFC-TLB converters that the output terminal
is constructed by only one output capacitor, which not only bears a high voltage stress, but also
does not help reduce the voltage stress across output diodes and output capacitors. Additionally,
the voltage-balance control is not easy to realize as one or more flying-capacitor voltages should be
control independently. Even though the output capacitor can be replaced by two split capacitors in
series in the output terminal, the two split capacitors could not be self-balanced and could not be
controlled by voltage-balance control strategy either. On the other hand, a three-level boost converter
based on switched-capacitor network is proposed in [26]. For simplification, the converter is name as
SC-TLB, which not only has two split capacitors at the output terminal, but also has self-balancing
function for capacitor voltages. As a result, there is no need to employ any voltage-balance control
strategies to solve the voltage imbalance issue. However, as analyzed in Section 1, there is a big
disadvantage that SC-TLB has high input current and high input current ripple since no interleaved
structures are employed. As a result, high power losses are inevitable in the SC-TLB converter.
There are also two input-parallel-output-series (IPOS) boost converters shown in Figure 2g (called
by IPOS-TLB1) and Figure 2h (called by IPOS-TLB2) from references [24,25]. Like the ISOS-TLB
converter, the input terminal and the output terminal do not share the same ground and the voltage
stress across diode D1 is equal to the output voltage in the IPOS-TLB1 converter. Although the topology
IPOS-TLB2 is simple, its voltage gain is smaller than the other topologies and the input terminal and
the output terminal do not share the same ground, either.
According to the comparative analysis mentioned above, the SI structure is suitable for high input
voltage and high output voltage applications while the PI structure is suitable for high input current
and high output current applications. As shown in Figure 1, the input terminal, output terminal
and all switches share the same ground in the PI topology. The flying-capacitor technique helps
enhance the voltage gains of the converters based on the PI structure. Besides, the switched-capacitor
technique, which could be deemed as an extension of flying-capacitor technique, not only increases
the voltage gain, but also brings a self-balancing function for capacitor voltages. On the whole, there
are three techniques could be employed in multilevel dc/dc converters, i.e., interleaved technique,
flying-capacitor technique, and switched-capacitor technique. Until now, only one or two of the three
techniques were employed in a single power converter.
This paper proposes an IPOS-SC-TLB converter in Figure 3 and presents a detailed analysis of
the converter. IPOS-SC-TLB combines the parallel-interleaved technique, flying-capacitor technique,
and switched-capacitor technique together. In Figure 3, L1 , L2 , S1 , S2 formulate the PI structure,
while L1 , S1 , D1 , C1 form Boost I and L2 , S2 , D3 , C2 form Boost II. Besides, Cf , D2 and S2 , C1 formulate a
switched-capacitor network, which makes the two input terminals in parallel and the output terminals
in series for Boost I and Boost II.
225
Energies 2018, 11, 2631
• •
•
• •
• • •
C1 = C2 = C (2)
Considering the voltage drops of IGBT and diode, and the equivalent series resistor of inductor,
the equivalent circuits of the IPOS-SC-TLB converter are presented in Figure 4. In the interleaved
scheme, the operating stages of IPOS-SC-TLB could be divided into two modes according to duty
cycle: when d is greater than 0.5 and when d is smaller than 0.5.
(1) When the duty cycle d is greater than 0.5, the IPOS-SC-TLB operates at the periodic stages of I, II,
I, and III.
Stage I: Both switches S1 , S2 are turned on and the diode D2 is forward biased as the capacitor
voltage UC1 is still a little bigger than the capacitor voltage UCf after the stage III. During Stage I,
both the two inductors L1 , L2 are charged by the input source Uin . Thus, there are:
di L1 di
L1 = L2 L2 = Uin − IL1 r L − US (3)
dt dt
UC1 = UC f + US + UD (4)
As the two capacitor voltages UC1 , UCf are charged in parallel, the voltage differences between
UC1 and UCf are small but cannot be ignored. As a result, the current flowing through D2 caused by
the small voltage difference is labelled as I1 . The current flowing through S1 is equal to iL1 while the
current flowing through S2 is the sum of iL2 and I1 .
Stage II: When the switch S1 is turned on and the switch S2 is turned off, the diode D3 is forward.
The inductor L1 is still charged by the input source Uin , which also supplies energy to the load together
with the inductor L2 and the flying-capacitor Cf . Thus, there are:
di L1
L1 = Uin − IL1 r L − US (5)
dt
di L2
L2 = Uin + UC f − UD − UC2 − UC1 (6)
dt
According to (4) and (6), there is:
di L2
L2 = Uin − UC2 − US − 2UD (7)
dt
226
Energies 2018, 11, 2631
During Stage II, the capacitor voltage UCf decreases while the capacitor voltage UC1 increases.
As a result, the voltage difference between UC1 and UCf becomes bigger and bigger and finally reaches
its maximum at the end of Stage II. The current flowing through the switch S1 is still equal to iL1 while
no currents flows through the switch S2 and the diode D2 during this stage.
• •
• •
• • • •
• •
• • • •
• • • • • •
(a) (b)
• •
• •
• • • •
• •
• • • •
• • • • • •
(c) (d)
Figure 4. Equivalent circuits of the IPOS-SC-TLB converter: (a) stage I; (b) stage II; (c) stage III;
(d) stage IV.
Stage I: The converter repeats Stage I and the same output results could be achieved like (3) and (4).
However, as analyzed in Stage II, the voltage difference between UC1 and UCf reaches its maximum
value, the current flowing through the diode D2 reaches its maximum value, labelled as I2 . The current
flowing through S1 turns to be the same as iL1 again while the current flowing through S2 is the sum of
iL2 and I2 .
Stage III: When the switch S1 is turned off while the switch S2 is turned on, the diodes D1 , D2 are
both forward. The inductor L2 is charged by the input source Uin , which also supplies energy to C1
and Cf together with the inductor L1 . Thus, there are:
di L1
L1 = Uin − IL1 r L − UD − UC1 (8)
dt
di L2
L2 = Uin − IL1 r L − US (9)
dt
During Stage III, the two capacitors C1 , Cf are connected in parallel and thus the voltage difference
between them is small, which results in a small current flowing through the diode D2 . It has been
227
Energies 2018, 11, 2631
mentioned in the first Stage I, labelled as I1 . As a consequence, the current flowing through S1 turns to
be zero while the current flowing through S2 is the sum of iL2 and I1 .
(2) When the duty cycle d is smaller than 0.5, the IPOS-SC-TLB converter operates at the periodic
stages of IV, II, IV, and III.
Stage IV: Both switches S1 , S2 are turned off while D1 and D3 are on forward biased:
di L1
L1 = Uin − IL1 r L − UD − UC1 (10)
dt
di L2
L2 = Uin + UC f − UD − UC2 − UC1 = Uin − UC2 − US − 2UD (11)
dt
As the first Stage IV begins after Stage III, the capacitor voltage UCf decreases while the capacitor
voltage UC1 increases. During this stage, no currents pass through the two switches S1 , S2 and the
diode D2 as they are all switched off.
Stage II: The same results could be achieved like (5)–(7) and the voltage difference between UC1
and UCf continues increasing during this stage. The current flowing through the switch S1 is still equal
to iL1 while no currents flows through the switch S2 and the diode D2 during this stage.
Stage IV: The converter enters into another Stage IV, where the voltage difference between UC1
and UCf continues increasing and reach its maximum value at the end of the stage. And no currents no
currents pass through the two switches S1 , S2 and the diode D2 .
Stage III: At the beginning of the stage III, the current flowing through the diode D2 reaches its
maximum value I2 . But later becomes a smaller value I1 as the two capacitors C1 , Cf are charged in
parallel. Thus, the current flowing through the switch S1 is zero while the current flowing through the
switch S2 is the sum of iL2 and I2 and then the sum of iL2 and I1 during this stage. For any duty cycle d,
two equations can be attained based on Voltage-Second Balance Principle during one switching period:
During the switching period, the output voltage of the converter is always described by:
(2d−3)U −U
Uo 2+ Uin
D S
G= = r (1+d)
(16)
Uin 1 − d + RL(1−d)
228
Energies 2018, 11, 2631
3. Performance Analysis
1
US1 = US2 = UD1 = UD2 = UD3 = UC1 = UC2 = UC f = Uo (19)
2
S dTs S dTs
t t
S dTs S dTs
t t
uS Uo Uo Uo
uS
uS t t
Uo Uo uS Uo Uo
uD uD
t t
uD Uo Uo uD Uo Uo
t t
uD
uD Uo Uo Uo
t t
I II I III I II I III IV II IV III IV II IV III
(a) (b)
The current waveforms of the IPOS-SC-TLB converter are presented in Figure 6. From Figure 6,
whatever the duty cycle d is, the average current across S1 , S2 can be obtained as follows:
IS1 = dIL1
(20)
IS2 = IL2
The average currents across D1 , D2 , D3 identical with value equal to the average output current
are determined as follows:
Uo
ID1 = ID2 = ID3 = Io = (21)
R
When the duty cycle d is over 0.5, the operating period of Stage II in Figure 4b can be expressed
by (1 − d)Ts during one switching period. During Stage II, the capacitor C2 is charged with the current
expressed by:
Uo
iC2_charged = IL2 − (22)
R
229
Energies 2018, 11, 2631
S dTs S dTs
t t
S dTs S dTs
t t
t t
iL iL
ΔiL ΔiL
t t
iin iin
Δiin Δiin
t t
iS I L I L iS I L I L
t t
iS I L + I iS I L + I I L + I
I L + I I L + I
t t
iD I L I L iD I
L I L
t t
iD iD I
I
I I I
t t
iD I L iD I L
t t
I II I III I II I III IV II IV III IV II IV III
(a) (b)
Figure 6. Key current waveforms: (a) d > 0.5; (b) d ≤ 0.5.
During the remained operating period dTs , C2 is discharged with the current expressed by:
Uo
iC2_discharged = − (23)
R
According to Ampere-Second Balance Principle, there is:
Uo Uo
(1 − d) Ts ( IL2 − ) + dTs (− ) = 0 (24)
R R
We can obtain the average current of inductor L2 by simplifying (24) as below:
Uo
IL2 = (25)
R (1 − d )
When the duty cycle is smaller than 0.5, the same formula as (25) can be obtained. It should
be noted that the average current of inductor L2 could be also derived as below. During one whole
switching period, the average charging current flowing through Cf is the same as the average current
flowing through D2 . So the increased charges of Cf during one switching period is ID2 *Ts . In addition,
when d is over 0.5, the flying-capacitor Cf is only discharged during Stage II and the average discharging
current flowing through Cf is IL2 with the discharging time (1 − d)Ts . When d is smaller than 0.5,
230
Energies 2018, 11, 2631
the flying-capacitor Cf is discharged during Stage II and Stage IV with the average discharging current
IL2 and the total discharged time (1 − d)Ts . It can be seen that the decreased charges of Cf during
one switching period is IL2 *(1 − d)Ts no matter what the duty cycle d is. Therefore, by applying
Ampere-Second Balance Principle on Cf , we have:
According to (26), the same formula as (25) can be achieved. On the other hand, the average
current of L1 can be easily obtained as below:
ID1 Uo
IL1 = = (27)
1−d R (1 − d )
According to (20)–(27), the average currents across all switches and diodes are:
⎧
⎪
⎪ IL1 = IL2 = (1−Udo ) R
⎪
⎪
⎨ I = dUo
S1 (1− d ) R (28)
⎪
⎪ S2 = (1−do ) R
I U
⎪
⎪
⎩
ID1 = ID2 = ID3 = Uo
R
Uo d
ΔuC1 = ΔuC2 = (30)
RC f s
Uin d
Δi L1 = Δi L2 = (31)
L fs
231
Energies 2018, 11, 2631
UD and US are assumed to be the voltage drop of one diode and the voltage drop of one IGBT.
Figure 7 shows the equivalent circuit of the switched-capacitor network when S2 turns on.
UD US
C U C Cf U Cf
RC iD RCf
It can be seen that the output capacitor C1 is connected with the flying-capacitor Cf in parallel. RC1 ,
RCf means the equivalent serial resistors of C1 and Cf , respectively. The current iD2 flowing through
the diode D2 could be calculated by:
ΔU
i D2 = (34)
RC1 + RC f
In (34), the equivalent serial resistors RC1 , RCf are usually very small, which are in the range of
milliohms. As a result, although ΔU is small, it may bring in very high inrush current iD2 flowing
the switched-capacitor network when S2 is turned on and D2 is forward instantaneously. Moreover,
this will result in more conduction losses across the switch S2 and the diode D2 .
From (10), one way to suppress iD2 is to reduce the voltage difference ΔU is by using wide
bandgap semiconductors, such as SiC or GaN components that have smaller voltage drops compared
with Si-based components. However, ΔU cannot be reduced to zero and this may still bring in a certain
inrush current. Another method is to increase the impedance of the switched-capacitor network.
Placing a serial resistor with high resistance could increase the impedance but extra power losses are
produced. As shown in Figure 8, this paper proposes to put a small stray inductor Ls together with D2 .
In this way, the loop impedance is increased by 2πf s Ls and then the inrush current iD2 is reduced to:
ΔU
i D2 = (35)
2π f s Ls + RC1 + RC f
232
Energies 2018, 11, 2631
respectively. “Self-balance” means the input inductor currents could be self-balanced and “same
ground” means the input terminal and the output terminal share the same ground. In addition,
the voltage gain comparison curves are presented in Figure 9.
•
iD
D iC
io
• C UC
D
Cf U Cf Ls
L • •N R Uo
iL
• iD
D iC
iL L
• • C U C
iin
S S
U in
• • •
Figure 8. IPOS-SC-TLB with a small stray inductor Ls .
Among these seven TLB converters, the common performance parameters are the voltage stress
across switches and the input current ripple. The TLB converters based on SI structure need two
isolated drive power supplies and have a low voltage gain, while those TLB converters based on PI
structure need only one power supply and show a higher voltage gain. The SI-FC-TLB and PI-FC-TLB
are very similar except for different interleaved structures. From these two converters, it could be
seen that the voltage stresses across the output diodes are low in the SI structure while high in the
PI structure; and the average current stresses across switches are high in the SI structure while low
in the PI structure. The smaller average current stress across switches should be attributed to the PI
structure. Among the five converters, the quantity of components are not the most in the proposed
IPOS-SC-TLB, and high voltage gain, small voltage stress and small current stress are achieved.
Moreover, voltage-balance control could be easily achieved with the input terminal and the output
terminal sharing the same ground. In other words, the proposed IPOS-SC-TLB converter integrates
nearly all the merits of the other four TLB converters. However, there is also a disadvantage that the
imbalance current between the two power switches S1 , S2 . As analyzed in Equation (28), the average
current of S2 is Uo /R higher than the average current of S1 .
233
Table 2. Comparative analysis among SC-TLB, SI-TLB, SI-FC-TLB, PI-FC-TLB, SC-TLB and the proposed IPOS-SC-TLB.
G G Current Same
Topology L S D C DS U VPS U VPD U VPC IVPS1 IVPS2 IVPD Self-Balance
(d ≤ 0.5) (d > 0.5) Ripple Ground
SC-TLB 1 1 3 3 1 2/(1 − d) 0.5Uo 0.5Uo 0.5Uo dIin - Io Large Yes Yes
SI-TLB 2 2 2 2 2 1/(1 − d) 0.5Uo 0.5Uo 0.5Uo dIin dIin Io Small No No
SI-FC-TLB 2 2 2 2 2 1/(1 − d) 0.5Uo 0.5Uo 0.5Uo dIin dIin Io Small No Yes
Energies 2018, 11, 2631
PI-FC-TLB 2 2 2 2 1 1/(1 − d)2 2/(1 − d) 0.5Uo Uo Uo 0.5dIin 0.5dIin Io Small Yes Yes
PI-SFC-TLB 2 2 4 3 1 2/(1 − d) 0.5Uo Uo Uo (1 + d)Iin /4 (1 + d)Iin /4 0.5Io Small Yes Yes
IPOS-TLB1 2 2 2 2 1 1/(1 − d)2 2/(1 − d) 0.5Uo Uo 0.5Uo 0.5dIin 0.5dIin Io Small No Yes
IPOS-TLB2 2 2 2 2 2 (1 + d)/(1 − d) Uo /(1 + d) Uo /(1 + d) Uo /(1 + d) 0.5dIin 0.5dIin Io Small No No
Proposed 2 2 3 3 1 2/(1 − d) 0.5Uo 0.5Uo 0.5Uo 0.5dIin 0.5Iin Io Small Yes Yes
234
Energies 2018, 11, 2631
As the output terminals of Boost I and Boost II are connected in series, the two Boost modules
have the same output current. As the average currents across C1 and C2 are both equal to zero during
one switching period, there is:
ID1 = ID3 (37)
In addition, the power losses of D2 and S2 produced in the switched-capacitor network are small
but could not be ignored. But the power losses should be attributed to the Boost II as D2 and S2 help
formulate the Boost II. As a result, there is:
η1 > η2 (38)
As analyzed above, the two split inductor currents could be self-balanced, but the two output
capacitor voltages could not be self-balanced. Considering the voltage drops of IGBT and diode,
the voltage difference between C1 and C2 could be described by the sum of the voltage drop of one
IGBT and the voltage drop of one diode. Besides, the parasitic resistances of L1 and L2 are labelled as
rL and the parasitic resistance of Cf is labelled as rCf . As the average currents across L1 and L2 are high,
the voltage drops of parasitic resistances are large and could not be ignored. Under this condition,
the two output capacitor voltages could be rewritten as:
1
UC1 = (U − IL1 r L ) − UD (40)
1 − d in
1
UC2 = [U − IL2 (r L + rC f )] − ΔU − UD (41)
1 − d in
The two split inductors are designed to attain the same parameters. Owing to the automatic
balanced inductor currents, the voltage difference between C1 and C2 could be described by:
IL2 rC f
ΔU = UC1 − UC2 = + ΔU (42)
1−d
It can be seen from (43) that the voltage imbalance issue is related to the output characteristic and
the parasitic parameters, including the average input current Iin , the duty cycle d, the equivalent series
resistance rCf of the flying-capacitor, and the voltage drops of IGBTs and diodes. The capacitances of
the two output capacitors have no effect on the voltage imbalance issue, which is quite different from
the conventional three-level boost converter shown in Figure 2a.
235
Energies 2018, 11, 2631
In the IPOS-SC-TLB converter, the relationship of the input inductor currents and the output
current could be described by:
(1 − d1 ) IL1 = Io
(46)
(1 − d2 ) IL2 = Io
By substituting (44) and (45) into (46), there is:
(1 − d)ΔIL1 − Δd1 IL = ΔIo
(47)
(1 − d)ΔIL2 − Δd2 IL = ΔIo
When the output voltage is not disturbed, the output current variation ΔIo is equal to zero. Thus,
(47) could be simplified by:
Δd1 = 1− d
IL ΔIL1
1− d (48)
Δd2 = IL ΔIL2
When the IPOS-SC-TLB converter works at stable steady state, ΔIL1 and ΔIL2 indirectly reflect the
values of Δd1 , Δd2 . According to (38), it is not difficult to deduce the following formula:
IL
ΔIL1 + ΔIL2 = (Δd1 + Δd2 ) (49)
1−d
In the three-loop control strategy, to decouple the voltage loop and the voltage-balance loop,
the sum of Δd1 and Δd2 should be equal to zero. Thus, according to (49), there is:
Then, the reference inductor currents of Boost I and Boost II could be concluded as follows:
IL1 ∗ = IL + ΔIL1 = IL − ΔIL
(51)
IL2 ∗ = IL + ΔIL2 == IL + ΔIL
According to (51), the three-loop control strategy is presented in Figure 10. The regulators of the
output voltage loop and the voltage-balance loop adopt proportional-integral controller while the
regulator of the current loop adopts proportional controller. The controllers can be designed based on a
small-signal linearized model of the dc/dc converter, which can be developed according to the classic
236
Energies 2018, 11, 2631
average modeling method for power converters [35,36]. The inner current control loop is designed
to respond faster than the outer voltage control loop so that the two control loops can be designed
independently. As a result, when dealing with the inner loop, we take the outer loop as a constant input.
On the other hand, the inner current control loop can be approximated as a simple lag block when we
proceed with the voltage loop. The voltage-balance loop has the slowest response. When designing
the controller for the voltage-balance loop, the voltage and current control loop can be considered
being in steady state already. Classic Bode-plot and root-locus proportional-integral controller design
procedures [36] can be used to obtain the parameters for the controllers. Nevertheless, it should be
noted that due to the nonlinearity of power devices, the designed controller parameters need to be
further tuned for the actual circuit. Besides, the carrier signals Ca1 , Ca2 are with phase-shifted 180
degrees to realize interleaved scheme for the switches S1 and S2 .
,QWHUOHDYHG0RGXODWLRQ
9ROWDJH/RRS &XUUHQW/RRS
U& UR I/ CD
'HFRXSOH
S
U& I/ I/ d
3, • 3
9ROWDJH%DODQFH/RRS
The two sampled capacitor voltages UC1 , UC2 are added together and then compared with the
output voltage reference Uo * to output the average inductor current IL through the voltage loop
regulator. ΔIL is achieved through the voltage-balance loop regulator by comparing UC1 and UC2 . ΔIL2
equals to −ΔIL1 according to (50). The inductor current references IL1 *, IL2 * in (51) could be achieved
through the decoupled scheme. Then, IL1 * and IL2 * compares with IL1 and IL2 , and pass though the
two current loop regulators to output the duty cycles of Boost I and Boost II as follows:
d1 = d + Δd1 = d − Δd
(52)
d2 = d + Δd2 = d + Δd
When UC1 is bigger than UC2 , the voltage-balance process is: ΔIL becomes positive, which makes
IL1 * decrease and IL2 * increase. As a result, d1 decreases while d2 increases, i.e., the turn-on time of
S1 decreases while that of S2 increases. Thus, UC1 decreases while UC2 increases. Finally, UC1 equals
to UC2 after several switching periods. When UC1 is smaller than UC2 , UC1 and UC2 could be also
balanced according to a similar voltage-balance process.
237
Energies 2018, 11, 2631
Components Parameters
Input voltage Uin 48 V–120 V
Output voltage Uo 400 V
Switching frequency f s 25 kHz
Output power Po 400 W
Switches S1 , S2 G80N60, 2.4 V voltage drop
Diodes D1 , D2 DSEP30-06B, 2.0 V voltage drop
Inductors L1 , L2 915 μH, 895 μH, 0.1 ohm equivalent series resistance
Capacitors C1 , C2 , Cf 470 μF, 0.28 ohm equivalent series resistance
Driver A3120
The input voltage varies between 48 V and 120 V, and the output voltage is controlled to be stable
at 400 V. The switching frequency of the converter is set as 25 kHz. Two inductors are both chosen
as about 900 μH with 0.1 ohm equivalent series resistance. Three capacitors are all set as 470 μF with
0.28 ohm equivalent series resistance. Each of the two IGBT switches has a voltage drop of 2.4 V and
each of the three diodes has a voltage drop of 2.0 V. Figure 11 shows the simulation results when
the input voltage is 48 V and Figure 12 shows the simulation results when the input voltage is 120 V.
It can be seen that the IPOS-SC-TLB converter can output a stable dc voltage of 400 V under both the
two different input voltages. The voltage difference between UC1 and UC2 is about 20 V under the
input voltage 48 V and 10 V under the input voltage 120 V without voltage-balance control. However,
once the voltage-balance control loop is added, UC1 and UC2 are balanced with the same voltage 200 V.
Besides, in the whole experimental process, a small voltage difference between UC1 and UCf is about
4.4 V, which is the sum of the voltage drop of one IGBT and the voltage drop of one diode.
U&/9
UR/9
U&/9 U&I/9
t/s t/s
(a) (b)
Figure 11. Simulated voltage waveforms when Uin is 48 V: (a) Uo ; (b) UC1 , UC2 , and UCf .
U&/9
UR/9
U&/9 U&I/9
t/s t/s
(a) (b)
Figure 12. Simulated voltage waveforms when Uin is 120 V: (a) Uo ; (b) UC1 , UC2 , and UCf .
More importantly, Figure 13 shows the two split inductor current waveforms of the converter
without voltage-balance control and with voltage-balance control when the input voltage is 48 V.
Under the condition without voltage-balance control, the average values of the two inductor currents
are equal while a little different under the condition with voltage-balance control. Because the duty
cycle d1 and the duty cycle d2 are the same under the condition without voltage-balance control but d1
is a little smaller than d2 under the condition with voltage-balance control. Besides, the input current
ripple is smaller than the inductor current ripples, and input current ripple frequency is 50 kHz,
which is two times the switching frequency 25 kHz.
238
Energies 2018, 11, 2631
iLQ/$ iLQ/$
i//$ i//$ i//$ i//$
t/s t/s
(a) (b)
Figure 13. Simulated current waveforms when Uin is 48 V: (a) without voltage-balance control; (b) with
voltage-balance control.
The simulated voltage waveforms and current waveforms are presented in Figure 14. The voltage
stress across all power devices are half of the output voltage. The average current across every diode is
1 A, which is the same as the output current. Additionally, the average current across the switch S2
is bigger than S1 because the current across the diode D2 added on the current of S2 . These results
prove correctness of the theoretically derived results shown in (28). On the whole, the simulation
results basically verify the effectiveness of the IPOS-SC-TLB converter and the proposed three-loop
control strategy.
(a)
(b)
Figure 14. Simulated voltage and current waveforms: (a) Uin = 48 V; (b) Uin = 120 V.
239
Energies 2018, 11, 2631
C2 C1
Cf
L2 L1
Auxiliary
3RZHU
6XSSO\
'ULYHU
'ULYHU
The input current and capacitor voltages of the IPOS-SC-TLB converter under different input
voltages are presented in Figure 16, and the corresponding capacitor voltages are presented in Figure 17.
The inductor currents across L1 , L2 and the drive signals of S1 , S2 are presented in Figure 18. It can
be seen that the output voltage is stable at 400 V and the three capacitor voltages are stable with
200 V under different input voltages. The input current is continuous with a small current ripple
and the input current ripple frequency is 50 kHz, which is two times the switching frequency 25 kHz.
Moreover, it is easy to observe that as the duty cycle approaches 0.50, the input current ripple becomes
almost zero, which verifies (32).
To show voltage stresses across all the switches and diodes, the terminal voltage waveforms of
S1 , S2 , D1 , D2 , and D3 are presented in Figures 19–21. It should be noted that uS1 , uS2 are defined
to describe the voltage difference between the drain terminal and the source terminal of S1 and S2 ,
respectively. uD1 , uD2 , uD3 are the voltage differences between the cathode and the anode of D1 , D2 and
D3 . It can be seen that all the voltage stresses of the switches and diodes are 200 V, which is half of the
output voltage 400 V. It matches with (12). In addition, the current IS2 is the sum of IS1 and ID2 , which
matches with (20) and (21). For example, when the input voltage is 48 V, IS1 , IS2 , ID2 are 3.74 A, 4.78 A
and 1.13 A, respectively. It is not difficult to know that the switching state of D1 is complementary to
that of D2 , and the switching state of D1 is 180 degrees shifted from that of D3 . The switching state
of S1 is also 180 degrees shifted from that of S2 . All of these results can verify the correctness of the
operating principle of the IPOS-SC-TLB converter.
240
Energies 2018, 11, 2631
iLQ $GLY
iLQ $GLY
UR 9GLY UR 9GLY
XVGLY XVGLY
(a) (b)
(c) (d)
Figure 16. Input current and capacitor voltage waveforms: (a) Uin = 48 V; (b) Uin = 72 V; (c) Uin = 100 V;
(d) Uin = 120 V.
(a) (b)
Figure 17. Capacitor voltage waveforms: (a) Uin = 48 V; (b) Uin = 120 V.
(a) (b)
(c) (d)
Figure 18. Inductor current and drive signal waveforms: (a) Uin = 48 V; (b) Uin = 72 V; (c) Uin = 100 V;
(d) Uin = 120 V.
241
Energies 2018, 11, 2631
(a) (b)
Figure 19. Tested voltage and current waveforms of S1 , S2 : (a) Uin = 48 V; (b) Uin = 120 V.
(a) (b)
Figure 20. Tested voltage and current waveforms of D2 and current waveform of Cf : (a) Uin = 48 V;
(b) Uin = 120 V.
(a) (b)
Figure 21. Tested voltage and current waveforms of D1 , D3 : (a) Uin = 48 V; (b) Uin = 120 V.
More importantly, the voltage-balance experimental waveforms of the IPOS-SC-TLB converter are
presented in Figures 22 and 23. The experimental results indicate that when the voltage-balance loop
is not added, there is about 13.0 V voltage difference between UC1 and UC2 . For example, when the
input voltage is 48 V, the tested duty cycle is around 0.83. According to (43), the voltage difference
between UC1 and UC2 is 11.26 V under the input voltage of 48 V. The tested voltage difference of 13.00 V
basically matches the theoretical value 11.26 V with some voltage error. When the voltage-balance
loop is added, the voltage difference becomes nearly zero.
(a) (b)
Figure 22. Voltage balance process of C1 , C2 when Uin is 48 V: (a) from no voltage-balance control to
voltage-balance control; (b) from voltage-balance control to no voltage-balance control.
242
Energies 2018, 11, 2631
(a) (b)
Figure 23. Voltage balance process of C1 , C2 when Uin is 120 V: (a) from no voltage-balance control to
voltage-balance control; (b) from voltage-balance control to no voltage-balance control.
Figure 24 shows the theoretical voltage gain and the experimental voltage gain versus duty
cycle when Uin is 48 V. It can be seen that the theoretical voltage gain and the experimental voltage
gain have the same increasing trend though some deviations exist. The experimental voltage gain
basically matches the theoretical voltage gain when the duty cycle varies between 0.2 and 0.5. However,
when the duty cycle is over 0.50, the experimental theoretical voltage gain is less than the theoretical
voltage gain, and their difference increases with the duty-cycle increasing. This phenomenon may
be due to the non-linearity of power electronic components and the fact the true values of parasitic
parameters are hard to obtain.
The conversion efficiency curves versus output power for the IPOS-SC-TLB converter under
different input voltages are given in Figure 25. The minimum efficiency and the maximum efficiency
are 92.08% and 94.20%, respectively, at an input voltage of 48 V; 95.13% and 96.55% at the input voltage
of 72 V; 96.08% and 97.32% at the input voltage 100 V; 96.62% and 98.57% at an input voltage of
120 V. It can be seen that the proposed converter is not efficient in low voltage levels, such as 48 V in
the experiment. To make it efficient, the converter should be implemented with optimized design,
including component selection, coupling inductor design and applying soft switching technique.
For component selection, wide bandgap device (SiC, GaN) with much smaller parasitic parameters
should be a good solution, which could not only reduce conduction and switching losses, but also
enhance the switching frequency to reduce passive components’ size and parasitic parameters as well.
Coupling design for the two inductors L1 and L2 will help reduce size and improve efficiency of the
converter. Soft switching technique applied on this converter will help enhance conversion efficiency.
Figure 24. The theoretical voltage gain and the experimental voltage gain versus duty cycle when Uin is 48 V.
243
Energies 2018, 11, 2631
Based on all the experimental results, the theoretical analysis of the IPOS-SC-TLB converter is
correct and the three-loop control strategy is feasible. The effectiveness of the proposed IPOS-SC-TLB
converter has been verified.
6. Conclusions
This paper presents an input-parallel-output-series three-level Boost converter, which can step
up the input voltage to a high voltage level, as well as attaining low voltage stress, low current stress
and small input current ripple. Another advantage of the proposed topology is the automatic current
balancing function. There is also a disadvantage that the imbalance current between the two power
switches S1 , S2 . The average current of S2 is Uo /R higher than the average current of S1 .
Author Contributions: J.C. proposed the topology and control strategy, and built the simulation model and
experimental prototype. C.W. and J.L. helped do comparative analysis and wrote the paper.
Funding: This research was funded by China Postdoctoral Science Foundation, grant number 2017M612908.
Conflicts of Interest: The authors declare no conflict of interest.
Nomenclature
List of Abbreviations
IPOS-SC-TLB input-parallel-output-series switched-capacitor three-level boost
HVDC high voltage direct current
SI serial-interleaved
PI parallel-interleaved
SI-TLB serial-interleaved three-level boost
PIB parallel-interleaved boost
SI-FC-TLB serial-interleaved flying-capacitor three-level boost
PI-FC-TLB parallel-interleaved flying-capacitor three-level boost
PI-SFC-TLB parallel-interleaved symmetric flying-capacitor three-level boost
SC-TLB switched-capacitor three-level boost
IPOS-TLB1 input-parallel-output-series three-level boost 1
IPOS-TLB2 input-parallel-output-series three-level boost 2
List of Symbols
Uin average input voltage
Uo , Io average output voltage and average output current
Uo * output voltage reference
UC1 , UC2 , UCf average voltages of capacitors C1 , C2 , Cf
ΔU voltage difference between C1 and Cf ,
iL1 , iL2 currents of inductors L1 , L2
IL1 , IL2 average currents of inductors L1 , L2
IL1 *, IL2 * reference currents of inductors L1 , L2
ΔiL1 , ΔiL2 current ripples of inductors L1 , L2
Δiin input current ripple
ID1 , ID2 , ID3 average currents of diodes D1 , D2 , D3
IS1 , IS2 average currents of switches S1 , S2
d duty cycle
d1 duty cycle of boost 1
d2 duty cycle of boost 2
Δd duty cycle difference
244
Energies 2018, 11, 2631
References
1. Yaramasu, V.; Wu, B.; Sen, P.C.; Kouro, S.; Narimani, M. High-power Wind Energy Conversion Systems:
State-of-the-art and Emerging Technologies. Proc. IEEE 2015, 103, 740–788. [CrossRef]
2. Yaramasu, V.; Wu, B. Predictive Control of a Three-Level Boost Converter and an NPC Inverter for
High-Power PMSG-Based Medium Voltage Wind Energy Conversion Systems IEEE Trans. Power Electron.
2014, 29, 5308–5322. [CrossRef]
3. Parastar, A.; Seok, J.-K. High Power Step-Up Modular Resonant DC/DC Converter for Offshore Wind
Energy Systems. IEEE Energy Convers. Congr. Expos. (ECCE) 2014, 3341–3348. [CrossRef]
4. Yaramasu, V.; Wu, B.; Rivera, M.; Rodriguez, J. A New Power Conversion System for Megawatt PMSG Wind
Turbines Using Four-Level Converters and a Simple Control Scheme Based on Two-Step Model Predictive
Strategy-Part I: Modeling and Theoretical Analysis. IEEE J. Emerg. Sel. Top. Power Electron. 2014, 2, 3–13.
[CrossRef]
5. Paez, J.D.; Frey, D.; Maneiro, J.; Bacha, S.; Dworakowski, P. Overview of DC-DC Converters Dedicated to
HVDC Grids. IEEE Trans. Power Deliv. 2018. [CrossRef]
6. Xia, C.; Gu, X.; Shi, T.; Yan, Y. Neutral-Point Potential Balancing of Three-Level Inverters in Direct-Driven
Wind Energy Conversion System. IEEE Trans. Energy Convers. 2011, 26, 18–29. [CrossRef]
7. Chen, J.; Wang, C.; Li, J.; Jiang, C.; Duan, C. A Nonisolated Three-Level Bidirectional DC-DC Converter.
In Proceedings of the 2018 IEEE Applied Power Electronics Conference and Exposition (APEC), San Antonio,
TX, USA, 4–8 March 2018; pp. 1566–1570.
8. Hou, S.; Chen, J.; Sun, T.; Bi, X. Multi-input Step-Up Converters Based on the Switched-Diode-Capacitor
Voltage Accumulator. IEEE Trans. Power Electron. 2016, 31, 381–393. [CrossRef]
9. Zhou, H.; Zhou, J.; Hu, B.; Tong, C. A New Interleaved Three-level Boost Converter and Neutral-point
Potential Balancing. In Proceedings of the 2013 2nd International Symposium on Instrumentation and
Measurement, Sensor Network and Automation (IMSNA), Toronto, ON, Canada, 23–24 December 2013.
10. Zhang, Y.; Sun, J.-T.; Wang, Y.-F. Hybrid Boost Three-Level DC-DC Converter With High Voltage Gain for
Photovoltaic Generation Systems. IEEE Trans. Power Electron. 2013, 28, 3659–3664. [CrossRef]
11. Andrade, A.M.S.S.; Martins, M.L.D.S. Quadratic-Boost with Stacked Zeta Converter for High Voltage Gain
Applications. IEEE J. Emerg. Sel. Top. Power Electron. 2017, 5, 1787–1796. [CrossRef]
12. Jin, K.; Yang, M.; Ruan, X.; Xu, M. Three-Level Bidirectional Converter for Fuel-Cell/Battery Hybrid Power
System. IEEE Trans. Ind. Electron. 2010, 57, 1976–1986. [CrossRef]
13. Rahul, J.R.; Kirubakaran, A.; Vijayakumar, D. A New Multilevel DC-DC Boost Converter for Fuel Cell based
Power System. In Proceedings of the 2012 IEEE Students’ Conference on Electrical, Electronics and Computer
Science (SCEECS), Bhopal, India, 1–2 March 2012.
14. Hegazy, O.; Mierlo, J.V.; Lataire, P. Analysis, Modeling, and Implementation of A Multidevice Interleaved
DC/DC Converter for Fuel Cell Hybrid Electric Vehicles IEEE Trans. Power Electron. 2012, 27, 4445–4458.
[CrossRef]
15. Ni, L.; Patterson, D.J.; Hudgins, J.L. High Power Current Sensorless Bidirectional 16-Phase Interleaved
DC-DC Converter f or Hybrid Vehicle Application. IEEE Trans. Power Electron. 2012, 27, 1141–1151.
[CrossRef]
16. Rivera, S.; Wu, B.; Kouro, S.; Yaramasu, V.; Wang, J. Electric Vehicle Charging Station Using A Neutral-point
Clamped Converter with Bipolar DC Bus. IEEE Trans. Ind. Electron. 2015, 62, 1999–2009. [CrossRef]
17. Tan, L.; Wu, B.; Yaramasu, V.; Rivera, S.; Guo, X. Effective Voltage Balance Control for Bipolar-DC-Bus Fed
EV Charging Station with Three-Level DC-DC Fast Charger. IEEE Trans. Ind. Electron. 2016, 63, 4031–4041.
[CrossRef]
18. Adam, G.P.; Gowaid, I.A.; Finney, S.J.; Holliday, D.; Williams, B.W. Review of DC-DC Converters for
Multi-terminal HVDC Transmission Networks. IET Power Electron. 2016, 9, 281–296. [CrossRef]
19. Chen, J.; Hou, S.; Deng, F.; Chen, Z. An Interleaved Five-Level Boost Converter with Voltage-Balance Control.
J. Power Electron. 2016, 16, 1735–1742. [CrossRef]
20. Kakigano, H.; Miura, Y.; Ise, T. Distribution Voltage Control for DC Microgrids Using Fuzzy Control and
Gain-Scheduling Technique. IEEE Trans. Power Electron. 2013, 28, 2246–2258. [CrossRef]
21. Jang, Y.; Jovanovic, M.M. Interleaved Boost Converter with Intrinsic Voltage-Doubler Characteristic for
Universal-Line PFC Front End. IEEE Trans. Power Electron. 2007, 22, 1394–1401. [CrossRef]
245
Energies 2018, 11, 2631
22. Zhou, L.-W.; Zhu, B.-X.; Luo, Q.-M.; Chen, S. Interleaved Non-isolated High Step-up DC-DC Converter
Based on the Diode-capacitor Multiplier. IET Power Electron. 2014, 7, 390–397. [CrossRef]
23. Franco, L.C.; Pfitscher, L.L.; Gules, R. A New High Static Gain Nonisolated DC-DC Converter. In Proceedings
of the 34th Annual Power Electronics Specialist Conference IEEE, Acapulco, Mexico, 15–19 June 2003.
24. Kajangpan, K.; Neammenee, B. High Gain Double Interleave Technique with Maximum Peak Power
Tracking for Wind Turbine Converter. In Proceedings of the 2009 6th International Conference on Electrical
Engineering/Electronics, Computer, Telecommunications and Information Technology Pattaya, Chonburi,
Thailand, 6–9 May 2009.
25. Forest, F.; Huselstein, J.J.; Martiré, T.; Flumian, D.; Meynard, T.A.; Abdelli, Y.; Lienhardt, A.M.
A Nonreversible 10-kW High Step-Up Converter Using a Multicell Boost Topology. IEEE Trans. Power Electron.
2018, 33, 151–160. [CrossRef]
26. Rosas-Caro, J.C.; Ramirez, J.M.; Peng, F.Z.; Valderrabano, A. A DC-DC Multilevel Boost Converter.
IET Power Electron. 2010, 3, 129–137. [CrossRef]
27. Parastar, A.; Kang, Y.C.; Seok, J.-K. Multilevel Modular DC-DC Power Converter for High-Voltage
DC-Connected Offshore Wind Energy Applications. IEEE Trans. Ind. Electron. 2015, 62, 2879–2890. [CrossRef]
28. Zhang, X.; Green, T.C. The Modular Multilevel Converter for High Step-Up Ratio DC-DC Conversion.
IEEE Trans. Ind. Electron. 2015, 62, 4925–4936. [CrossRef]
29. Ferreira, J.A. The Multilevel Modular DC Converter. IEEE Trans. Power Electron. 2013, 28, 4460–4465.
[CrossRef]
30. Zhang, X.; Green, T.C. The New Family of High Step Ratio Modular Multilevel DC-DC Converters.
In Proceedings of the 2015 IEEE Applied Power Electronics Conference and Exposition (APEC), Charlotte,
NC, USA, 15–19 March 2015.
31. Hagar, A.A.; Lehn, P.W. Comparative Evaluation of a New Family of Transformerless Modular DC-DC
Converters for High-Power Applications. IEEE Trans. Power Deliv. 2014, 29, 444–452. [CrossRef]
32. Filsoof, K.; Lehn, P.W. A Bidirectional Modular Multilevel DC-DC Converter of Triangular Topology.
IEEE Trans. Power Electron. 2015, 30, 54–64. [CrossRef]
33. Athab, H.; Yazdani, A.; Wu, B. A Transformerless DC-DC Converter with Large Voltage Ratio for MV DC
Grids. IEEE Trans. Power Deliv. 2014, 29, 1877–1885. [CrossRef]
34. Chen, W.; Huang, A.Q.; Li, C.; Wang, G.; Gu, W. Analysis and Comparison of Medium Voltage High Power
DC-DC Converters for Offshore Wind Energy Systems. IEEE Trans. Power Electron. 2013, 28, 2014–2023.
[CrossRef]
35. Mohan, T.; Undeland, M.; Robbins, W.P. Power Electronics—Converters, Applications, and Design; John Wiley &
Sons Inc.: Hoboken, NJ, USA, 2003.
36. Erickson, R.W.; Maksimovic, D. Fundamentals of Power Electronics, 2nd ed.; Kluwer Academic Publisher:
Norwell, MA, USA, 2001.
© 2018 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access
article distributed under the terms and conditions of the Creative Commons Attribution
(CC BY) license (http://creativecommons.org/licenses/by/4.0/).
246
energies
Article
Capacitors Voltage Switching Ripple in Three-Phase
Three-Level Neutral Point Clamped Inverters with
Self-Balancing Carrier-Based Modulation
Manel Hammami, Gabriele Rizzoli *, Riccardo Mandrioli and Gabriele Grandi
Department of Electrical, Electronic, and Information Engineering, University of Bologna, 40136 Bologna, Italy;
[email protected] (M.H.); [email protected] (R.M.); [email protected] (G.G.)
* Correspondence: [email protected]; Tel.: +39-051-20-9-3585
Abstract: This paper provides a comprehensive analysis of the capacitors voltage switching
ripple for three-phase three-level neutral point clamped (NPC) inverter topologies. The voltage
ripple amplitudes of the two dc-link capacitors are theoretically estimated as a function of both
amplitude and phase angle of output current and the inverter modulation index. In particular,
peak-to-peak distribution and maximum amplitudes of the capacitor voltage switching ripple over
the fundamental period are obtained. A comparison is made considering different carrier-based
pulse-width modulations in the case of almost all sinusoidal load currents, representing either grid
connection or passive load with a negligible current ripple. Based on the voltage switching ripple
requirements of capacitors, a simple and effective original equation for a preliminary sizing of the
capacitors has been proposed. Numerical simulations and experimental tests have been carried out
in order to verify the analytical developments.
Keywords: voltage ripple; voltage source inverter; three-phase inverter; DC-link capacitor design
1. Introduction
In industrial applications, the most used switching inverter is the two-level converter. Due to
mass production, it is a relatively cheap and reliable configuration. Furthermore, as the number
of semiconductor devices is low, they can be simply controlled by different types of pulse-width
modulation (PWM) techniques. However, the main drawback of the two-level converter is the
high harmonic content of the output voltage, which makes the use of bulky output filter necessary,
increasing the cost of the system and the losses. The harmonic content can be reduced simply by
increasing the PWM switching frequency, which leads to an increase of the switching losses. The use
of power filters and high switching frequency has to be balanced to achieve reasonable converter costs
with acceptable efficiency.
During the last decades, the drawbacks of the two-level converter motivated researchers to
develop new converter topologies. A very promising inverter family, called multilevel inverters
(MLIs), offer better quality output voltage waveforms with a reduced harmonic content comparing to
the conventional two-level inverter topologies, increase the overall voltage and power rating of the
converter, and generally mitigate the electromagnetic interferences.
The penetration of multilevel inverters has been steadily increasing due to their widespread usage
in manufacturing, transport, energy, high-power drives and other industry applications. Several MLI
topologies have been introduced and extensively studied in the literature. Most currently used
multilevel topologies can be grouped: cascaded H-bridge (CHB), neutral point clamped (NPC),
and flying capacitors (FC).
Multilevel inverters were initiated by the invention of the so-called NPC inverter in 1981 by
Nabae et al. [1]. The NPC inverter uses a single DC bus subdivided into a number of voltage levels
by a series string of capacitors. The voltages across the individual switches are clamped by diodes
at the voltage level of only one capacitor of the series DC-link string. The major difficulty associated
with control of the diode-clamped inverter is the balancing of the capacitor voltages [2,3]. To achieve
that, many modulation techniques have been developed [4–8]. In particular, carrier-based modulation
and space vector modulation (SVM) strategies, similar to those employed for conventional two-level
three-phase inverters, can be readily modified and extended to fulfill the multilevel NPC requirements.
An essential part of MLI design is the selection of DC-link capacitors. The capacitors are a sensitive
element of the inverter and a common source of failures. So far, regarding two-level converter systems,
some papers have investigated the minimum DC-link capacitance and proposed methods for its size
reduction [9,10]. Recently, based on the DC-link voltage analysis and considering both low- and/or
high-frequency DC voltage components, simple and effective guidelines for designing the DC-link
capacitor have been presented in [11] for single-phase H-bridge inverter, and in [12] for three-phase
three-level flying capacitor inverter. Methods used to derive expressions for RMS value and harmonic
spectrum of the capacitor current in two-level inverters, are extended to the three-level inverters in [13].
An analytical expression for calculating RMS current through the DC-link capacitor in a three-level
NPC inverter is given in [14]. The analysis of the DC-link capacitor current in three-level NPC and
CHB inverters and a new numerical approach for calculating the RMS value of the capacitor current is
proposed in [15].
Evaluation of the low-frequency neutral-point voltage oscillations in the three-level NPC inverter
using space vector modulation (SVM) techniques has been analyzed in [16]. A novel modulation
strategy for the NPC inverter is proposed in [17] to overcome one of the main problems of this converter,
which is the low-frequency voltage oscillation that appears in the neutral point. The proposed
modulation strategy can completely remove this oscillation for all the operating conditions and for
any kind of loads, even unbalanced and nonlinear loads.
Nowadays, NPC inverters are the most widely used three-level inverter topologies in the
industrial applications, considering both the conventional and the T-type configurations (Figure 1).
In order to choose the most suitable topology and hereby increase power efficiency, the comparison
between of conventional NPC and T-type inverters has been investigated and reported in the
literature [18], also considering the loss evaluation. An efficiency comparison of both over-mentioned
topologies is presented in [19] and the result shows that the T-type inverter is generally more efficient
at lower switching frequencies.
/V
A B C A B C
5V LD LE LF
LV L 5V /V
LV L LD LE LF
iA
iA
6$ 6$
6$
v1
C1 v1 C1
6$ 6$
Vs Vdc Vs Vdc
C2 C2
v2 6$
v2
iA
iA
6$ 6$
L L
Figure 1. Circuit schemes of the three-phase three-level neutral point clamped (NPC) inverter:
conventional type (left side) and T-type (right side).
248
Energies 2018, 11, 3244
The analysis of inverter DC-link input current and voltage is essential for sizing and designing
the DC-link capacitor since it directly impacts the price, the lifetime and the failure rate of a converter
system. A DC-link capacitor has to deal with the harmonics of the inverter input current and to avoid
the high DC-link voltage ripple appearance. In general, the low-frequency voltage ripple component
is more important for the required capacitance design since it has a higher value comparing to the
switching frequency voltage ripple component. Although correctly sizing the DC-link capacitances is
important to control the magnitude of the low-frequency voltage ripple, it is not the only thing that
must be considered.
The calculation of low-frequency input current and input voltage ripples on DC-link capacitors
have been analyzed and presented in the literature by other authors [15,16]. The evaluation of voltage
switching ripple for the NPC converters has not been reported yet. The analysis of the voltage
switching ripple in DC-link capacitors of three-level three-phase NPC inverters, applicable to both
conventional and T-type configurations (Figure 1), is presented in this paper, with reference to different
carrier-based PWM techniques. The peak-to-peak capacitor voltage switching ripple amplitudes are
analytically determined as a function of modulation index and output phase angle. Based on the
limitation on the peak-to-peak capacitor voltage switching ripple amplitudes, simple and practical
expressions for sizing the capacitors have been proposed.
The paper is organized as follows. Section 2 introduces the system configuration and the
modulation principles. Section 3 presents the analysis of low-frequency and switching frequency input
current. Section 4 presents the analysis of the capacitor voltage switching ripple. Section 5 defines the
guidelines for a preliminary design of the DC-link capacitors. In Section 6 simulation and experimental
verifications have been reported, and Section 7 presents the conclusion.
where ϑ = ωt, ω is the fundamental angular frequency (ω = 2πf ), f is the fundamental frequency, m is
the inverter modulation index, ui∗ are the normalized reference output voltages of each phase (i = A, B
or C) and Cm represents the injected common mode signal.
The voltages across the two capacitors C1 and C2 can be spontaneously regulated to half
of the DC-link voltage by the use of proper modulation technique with self-balancing capability.
249
Energies 2018, 11, 3244
(1)
Correspondingly, the following averaged switching functions for the upper and lower switches Si
(4)
and Si can be written (averaging is denoted by overline):
(1)
Si = ui + | ui |
(4) . (2)
Si = − ui + | ui |
With reference to the modulation (1) and considering phase A, the averaged switching functions
of the upper and the lower switches, Equation (2), become:
(1)
SA = m sin(ϑ) + Cm + |m sin(ϑ) + Cm |
(4) . (3)
SA = −m sin(ϑ) + Cm + |m sin(ϑ) + Cm |
Due to the modulation symmetry among the three phases, the switching functions for the phases
B and C are readily obtained considering the phase displacement of the normalized output voltages
given in Equation (1).
In case of sinusoidal PWM (SPWM), the injected common-mode signal is zero:
Cm = 0. (4)
However, in case of centered PWM (CPWM), the injected common-mode signal is:
1 ∗
Cm = − (max(uA , uB∗ , uC
∗ ∗
) + min(uA , uB∗ , uC
∗
)). (5)
2
In this last case, Cm can be rewritten as:
⎧
⎪ sin ϑ, − π6 ≤ ϑ ≤ π6 , 5π
6 ≤ϑ≤ 6
7π
1 ⎨ π π 7π
Cm = m sin ϑ + 2π , ≤ ϑ ≤ , ≤ ϑ ≤ 3π . (6)
2 ⎪ ⎩ sinϑ − 2π , π ≤ ϑ ≤ 5π , 3π ≤ ϑ ≤ 11π
3 6 2 6 2
3 2 6 2 6
1 p p p p p p 1
Cm = − max(uA , uB , uC ) + min(uA , uB , uC ) − max(u2L
A , uB , uC ) + min( uA , uB , uC )
2L 2L 2L 2L 2L
(7)
2 2
being ⎧
⎪
⎪
p
u = 14 sign(uA ∗ ) − 1 sign ( u∗ ) + sign ( u∗ ) + sign ( u∗ )
⎪
⎨ A
3 A B C
uB = 14 sign(uB∗ ) − 13 sign(uA∗ ) + sign ( u∗ ) + sign ( u∗ )
p
(8)
⎪
⎪
B C
⎪
⎩ u p = 1 sign(u∗ ) − 1 sign(u∗ ) + sign(u∗ ) + sign(u∗ )
C 4 C 3 A B C
⎧
⎪ ∗ p
⎨ uA = uA − uA
2L
∗ p
⎪ B = uB − uB
u2L (9)
⎩ u2L = u∗ − u p
C C C
250
Energies 2018, 11, 3244
XL
6L 6L
6L 6L
Figure 2. Carrier-based PWM modulation logic for each leg (i) of NPC inverters: SPWM (red trace),
CPWM (blue trace), and OCPWM (green trace) in case of m = 0.4. Underline denotes complementary.
In case of balanced load and neglecting the output current ripple, the corresponding three-phase
output currents can be written as:
⎧
⎨ ia = Iac sin(ϑ − ϕ)
⎪
ib = Iac sin ϑ − 2π3 − ϕ) (11)
⎪
⎩ i = I sin ϑ − 4π − ϕ)
c ac 3
where Iac is the output current amplitude and ϕ is the power phase angle.
The averaged component (over the switching period) of each leg input current can be determined
by multiplying the switching function of upper or lower switch of each phase by the corresponding
output current. In the case of leg A it leads to:
+ (1)
i A = SA ia
− (4) (12)
iA = − SA ia
By introducing Equations (3) and (11) in Equation (12), the averaged currents of the upper and
lower switch of the leg A become:
+
iA = Iac sin(ϑ − ϕ)[m sin(ϑ) + Cm + |m sin(ϑ) + Cm |]
− (13)
iA = Iac sin(ϑ − ϕ)[−m sin ϑ − Cm + |m sin(ϑ) + Cm |]
+ −
The total input currents i and i can be calculated as the sum of the three leg currents as:
+ (1) (1) (1)
i = SA ia + SB ib + SC ic
− (4) (4) (4) (14)
i = − SA ia − SB ib − SC ic
Due to the three-phase symmetry of modulation and output currents within the fundamental
period T, both input currents have a periodicity of T/3. As a consequence, the analysis can be restricted
251
Energies 2018, 11, 3244
to an angle range of 2π/3, and all the input harmonics are multiple of 3. i.e., apart from the DC
component, the lowest harmonic order component is the 3rd.
With reference to the phase angle range 2π/3 ≤ ϑ ≤ 4π/3, two sub-ranges π/3 can be identified.
+ −
Considering Equations (2), (11) and (14), the input currents i and i can be expressed as:
(1) (1)
+ SA ia + SB ib , 2π
≤ϑ≤π
i = (1)
3 (15)
SB ib , π≤ϑ≤ 4π
3
(4)
− − SC ic , 2π
≤ϑ≤π
i = (4) (4)
3 (16)
− SA ia − SC ic , π≤ϑ≤ 4π
3
Introducing Equations (1), (2), and (11) in Equations (15) and (16), and setting Cm = 0 as in case of
SPWM, leads to:
+ mIac 2 cos(ϕ) + cos 2ϑ − 2π 3 −ϕ , 2π3 ≤ϑ≤π
i = (17)
mIac cos(ϕ) + cos 2ϑ − π3 − ϕ , π ≤ ϑ ≤ 4π 3
2π
− mIac cos(ϕ) − cos 2ϑ − 2π 3 − ϕ , 3 ≤ ϑ ≤ π
i = π (18)
mIac 2 cos(ϕ) − cos 2ϑ − 3 − ϕ , π ≤ ϑ ≤ 4π 3
+ −
Similarly, replacing Equation (6) in Equation (1) in case of CPWM, input currents i and i can be
expressed as
⎧ √
⎪ π
2 3 sin(2ϑ − ϕ) + sin 6 + ϕ + 4 cos(ϕ) , 3 ≤ ϑ ≤
mIac 2π 5π
⎪
⎪ 6
⎪
⎨ √
+
i =
mIac
3 sin 2ϑ − π3 − ϕ − sin ϕ − π6 + 4 cos(ϕ) , 5π ≤ϑ≤π (19)
⎪
2
√ 6
⎪ π
cos ϕ + π6 , π ≤ ϑ ≤ 7π
2 √3cos 2ϑ − 6 − ϕ +
mIac
⎪
⎪
⎩ 6
mIac
2 3 sin(2ϑ − ϕ) + sin ϕ + π3 , 7π 6 ≤ϑ≤ 3
4π
⎧ √
⎪ π
2 − 3 sin(2ϑ − ϕ) − sin 6 + ϕ + 2 cos(ϕ) , 3 ≤ ϑ ≤ 6
mIac 2π 5π
⎪
⎪
⎪
⎪ √
⎪
⎨ π π
2 − 3 sin 2ϑ − 3 − ϕ + sin ϕ − 6 + 2 cos(ϕ) , 6 ≤ ϑ ≤ π
mIac 5π
−
i = √ √ (20)
⎪ π π
2 − 3 cos 2ϑ − 6 − ϕ − 3 cos ϕ + 6 + 6 cos (ϕ) , π ≤ ϑ ≤ 7π
mIac
⎪
⎪
⎪
⎪ √ √ 6
⎪
⎩ π
mIac
2 − 3 sin ( 2ϑ − ϕ ) − 3 sin ϕ + 3 + 6 cos ( ϕ ) , 7π
6 ≤ ϑ ≤ 4π
3
Although the above analytical calculations are based on SPWM and CPWM, the analysis could be
readily extended to other PWM techniques, such as OCPWM, leading to more complex expressions
not presented in this paper.
Consequently, the low-frequency input current components are readily determined in case of
SPWM as:
3
Idc = mIac cos(ϕ) (21)
2
2π
i+ =
1
2 mIac cos (ϕ) + 2 cos 2ϑ − 2π 3 − ϕ , 3 ≤ϑ≤π
(22)
− 12 mIac cos(ϕ) − 2 cos 2ϑ − π3 − ϕ , π ≤ ϑ ≤ 4π 3
i− = − 12 mIac cos(ϕ) + 2 cos 2ϑ − 2π 3 −
ϕ , 2π 3 ≤ϑ≤π
π (23)
1
2 mI ac cos ( ϕ ) − 2 cos 2ϑ − 3 − ϕ , π ≤ ϑ ≤ 4π
3
252
Energies 2018, 11, 3244
In the case of CPWM, the low-frequency input currents are expressed as:
⎧ √
⎪ π
2 3 sin(2ϑ − ϕ) + sin 6 + ϕ + cos(ϕ) , 3 ≤ ϑ ≤ 6
mIac 2π 5π
⎪
⎪
⎪
⎨ √
i+ =
mIac
3 sin 2ϑ − π3 − ϕ − sin ϕ − π6 + cos(ϕ) , 5π ≤ϑ≤π (24)
⎪
2
√ 6
⎪
⎪
mIac
3 cos 2ϑ − π
− ϕ + cos ϕ + π
− 3 cos ( ϕ ) , π ≤ ϑ ≤ 7π
⎪
⎩ 2 √ 6 6 7π 6
π
mIac
2 3 sin(2ϑ − ϕ) + sin ϕ + 3 − 3 cos(ϕ) , 6 ≤ ϑ ≤ 4π 3
⎧ √
⎪ − mI2ac 3 sin(2ϑ − ϕ) + sin π6 + ϕ + cos(ϕ) , 2π3 ≤ ϑ ≤ 6
5π
⎪
⎪
⎪
⎪ √
⎪
⎨ − mIac π π
2 3 sin 2ϑ − 3 − ϕ − sin ϕ − 6 + cos(ϕ) , 6 ≤ϑ≤π
5π
i− = √ √ (25)
⎪ π π
⎪ − 2 3 cos 2ϑ − 6 − ϕ + 3 cos ϕ + 6 − 3 cos (ϕ) , π ≤ ϑ ≤
mI 7π
⎪ ac
⎪
⎪ √ √ 6
⎪
⎩ − mIac π
2 3 sin(2ϑ − ϕ) + 3 sin ϕ + 3 − 3 cos(ϕ) , 7π 6 ≤ϑ≤ 3
4π
where V 1 and V 2 are the DC components averaged over the fundamental period, v1 and v2 are the
alternating low-frequency ripple components, and Δv1 and Δv2 are the switching frequency ripple
components of the voltages across capacitors C1 and C2 , respectively. Being the low-frequency ripple
components widely studied in literature, the analysis is focused on the switching ripple component.
Δt1 Δt2
1 1
ΔV1 = Δi+ dt, ΔV2 = Δi− dt. (27)
C1 C2
0 0
being Δt1 and Δt2 specific switching time intervals. The instantaneous input current is considered
constant within each considered time interval.
Due to the periodicity of the input currents i+ and i– , the evaluation of peak-to-peak voltage
ripple is limited to the phase angle range 2π/3 ≤ ϑ ≤ 4π/3. Analyzing the voltage ripple, two cases
have been identified: the first case considering zero phase angle (ϕ = 0◦ ) and the second considering
ϕ = 60◦ . The peak-to-peak voltage switching ripple of capacitors has been analytically calculated as:
In case of ϕ = 0◦ : ⎧
(1) +
Tsw ⎨ 1 − SA i , 3 ≤ ϑ ≤ 6
2π 5π
ΔV1 = (28)
C1 ⎩ 1 − S(1) i+ , 5π ≤ ϑ ≤ 4π
B 6 3
253
Energies 2018, 11, 3244
⎧
(4) −
Tsw ⎨ 1 − SC ≤ϑ≤
2π 7π
i , 3 6
ΔV2 = (4) − (29)
C2 ⎩ 1 − SA i , 7π
≤ϑ≤ 4π
6 3
In case of ϕ = 60◦ :
⎧
⎪ (1) +
⎪
⎪ 1 − SA i , 2π
≤ϑ≤ 5π
Tsw ⎨ 3 6
+ (1)
ΔV1 = ia + ib − i SA , 5π
≤ϑ≤π (30)
C1 ⎪⎪
6
⎪
⎩ (1) +
1 − SB i , 5π
6 ≤ϑ≤ 4π
3
⎧
(4) −
Tsw ⎨ 1 − SC ≤ϑ≤
2π 7π
i , 3 6
ΔV2 = − (4) (31)
C2 ⎩ − ic − ia − i SC , 7π
≤ϑ≤ 4π
6 3
(1) (4)
being Si and Si the switching function for the upper and lower switches of phase i (being i = A,
+ −
B or C), given by Equation (2). The total averaged input currents i and i can be calculated by
Equations (17) and (18) in case of sinusoidal PWM, and by Equations (19) and (20) in case of centered
PWM. In case of optimized centered PWM the input currents can be calculated introducing Equations
(2), (7) and (11) in Equations (15) and (16), leading to more complex developments.
Equations (28)–(31) suggest normalization for ΔV 1 and ΔV 2 , as follow:
Iac Iac
ΔV1 = ΔU1 , ΔV2 = ΔU2 . (32)
f sw C1 f sw C2
being ΔU1 and ΔU2 the normalized peak-to-peak voltage switching ripple amplitude of capacitors.
Figure 3 shows the distribution of the normalized peak-to-peak voltage switching ripple calculated
based on Equations (28), (29), (30) and (31) over the period [0, 120◦ ]. Two modulation indices have
been selected, m = 0.3 and m = 0.5 and two output phase angles are considered, ϕ = 0 and ϕ = 60◦ .
M= 0 M= 60°
'8 '8
- 120°
- 120°
D E
'8 '8
- - 120°
120°
F G
Figure 3. Normalized peak-to-peak voltage ripple amplitude across the capacitors over the period
[0, 120◦ ] for two modulation indices m = 0.3 (a,b) and m = 0.5 (c,d) and output phase angles ϕ = 0 (a,c)
(left) and 60◦ (b,d) (right) in case of SPWM (red), CPWM (blue) and OCPWM (green).
Figure 3 presents the normalized peak-to-peak voltage ripple amplitude across the upper capacitor
since the normalized peak-to-peak voltage ripple amplitude across the lower capacitor has exactly the
same profile with a phase shift corresponding to 60◦ (1/2 of the considered period).
254
Energies 2018, 11, 3244
P P
੮сϬ ੮сϯϬ ੮сϲϬ ੮сϵϬ ੮сϬ ੮сϯϬ ੮сϲϬ ੮сϵϬ ੮сϬ ੮сϯϬ ੮сϲϬ ੮сϵϬ P
(a) (b) (c)
Figure 4. Maximum peak-to-peak value of the normalized voltage switching ripple vs. modulation
index m in case of (a) sinusoidal pulse-width modulation (SPWM), (b) centered PWM (CPWM) and (c)
optimized centered PWM (OCPWM) for different output phase angles.
1 Iac 1 Iac
C1 ≥ , C2 ≥ (34)
4 f sw ΔV1max 4 f sw ΔV2max
255
Energies 2018, 11, 3244
6. Results
In order to verify proposed theoretical developments valid for both the considered NPC multilevel
inverter configurations (Figure 1), numerical simulations and corresponding experimental tests are
carried out. Inverter is controlled by carrier-based multilevel PWM (Figure 2) with reference to the
three considered modulation techniques (SPWM, CPWM, and OCPWM). The switching frequency is
set 2.5 kHz to better emphasize the switching ripple components, and two different output phase angles
(0 and 60◦ ) are considered, as for the specific analytical developments. The main circuit parameters are
summarized in Table 1 for both simulations and experiments.
t (s) t (s) t (s)
Figure 5. One leg dc-link current (top) and total input current (bottom): instantaneous value
(blue trace), its averaged value over the switching period (red), and calculated value (green) in case of
SPWM, CPWM and OCPWM (from right to left) for m = 0.4, Iac = 1A and ϕ = 0◦ .
The top traces in Figures 5 and 6 show the simulation results comparing the instantaneous input
+ +
current of leg A iA (blue trace) with its averaged value over the switching period iA (red trace),
and the corresponding low-frequency current component calculated by Equation (13) (green trace)
in case of m = 0.4 and for two cases of output phase angles ϕ = 0◦ (Figure 5) and ϕ = 60◦ (Figure 6).
The bottom traces in Figures 5 and 6 show the total input current, with emphasis to instantaneous
+
value i+ (blue trace) and its averaged value over the switching period i (red trace). The low-frequency
current component (green trace) is determined analytically in both cases of SPWM and CPWM by
Equations (22) and (24), respectively, and is calculated by replacing Equations (2), (7), and (11) in
Equation (15), in the case of OCPWM.
256
Energies 2018, 11, 3244
The numerical results generally show a perfect matching with the theoretical values. The small
delay between averaged and theoretical currents (Tsw /2) is due to the averaging process itself.
The second group of simulation tests is concerning the switching voltage ripple across the two
DC-link capacitors. In this case, the load circuit model is corresponding to the real experimental setup,
made with the purpose to easily adapt the output phase angles to the considered cases (ϕ = 0 and
ϕ = 60◦ ), according to Figure 7. The corresponding circuit parameters are given in Table 2.
t (s) t (s) t (s)
Figure 6. One leg dc-link current (top) and total input current (bottom): instantaneous value
(blue trace), its averaged value over the switching period (red), and calculated value (green) in case of
SPWM, CPWM and OCPWM (from right to left) for m = 0.4, Iac = 1A and ϕ = 60◦ .
RL RL RL
LL LL LL
Co Ro Co Ro Co Ro
The voltage switching ripple is determined by filtering away the low-frequency components form
the instantaneous capacitor voltages.
Figure 8 presents the instantaneous voltage switching ripple across the capacitors (blue traces) in
case of sinusoidal PWM together with the theoretical envelopes ±ΔV 1 /2 (upper capacitor) and
±ΔV 2 /2 (lower capacitor), analytically evaluated by (28) and (29) (red traces) for two cases of
modulation index m = 0.3 (top) and 0.5 (bottom), considering the output phase angle ϕ = 0. The same
quantities are presented in Figure 9 with reference to output phase angle ϕ = 60◦ . In this case,
envelopes ±ΔV 1 /2 and ±ΔV 2 /2 are analytically evaluated by (30) and (31).
Similarly, Figures 10 and 11 present the instantaneous voltage switching ripple across the
capacitors (blue traces) in case of centered PWM together with the theoretical envelopes ±ΔV 1 /2
(upper capacitor) and ±ΔV 2 /2 (lower capacitor) (red traces) for two cases of modulation index m = 0.3
(top) and 0.5 (bottom), considering the output phase angles ϕ = 0 (Figure 10) and ϕ = 60◦ (Figure 11).
257
Energies 2018, 11, 3244
M= 0°
'9
9
'9
9
W V
(a)
'9
9
'9
9
W V
(b)
Figure 8. Capacitor voltage switching ripple (SPWM): simulation results (blue trace) and calculated
peak- to-peak envelope (red traces) over a period for m = 0.3 (a) and m = 0.5 (b) in case of ϕ = 0◦ .
As mentioned in Section 4, the analytical developments could be readily extended to other more
sophisticated modulation strategies, such as optimized centered PWM, but leading to more complex
and less meaningful expressions. For this reason, the envelopes of voltage switching ripple have not
explicitly obtained in case of OCPWM, just numerically derived introducing Equations (2), (7), (11),
(15), and (16) in the basic Equations (28)–(31). Similarly, to previous cases, Figures 12 and 13 present
the instantaneous voltage switching ripple across the capacitors (blue traces) in case of optimized
centered PWM together with the envelopes ±ΔV 1 /2 (upper capacitor) and ±ΔV 2 /2 (lower capacitor)
(red traces) for two cases of modulation index m = 0.3 (top) and 0.5 (bottom), considering the output
phase angles ϕ= 0 (Figure 12) and ϕ = 60◦ (Figure 13).
258
Energies 2018, 11, 3244
Figure 9. Capacitor voltage switching ripple (SPWM): simulation results (blue trace) and calculated
peak- to-peak envelope (red traces) over a period for m = 0.3 (a) and m = 0.5 (b) in case of ϕ = 60◦ .
M = 0°
'9
9
'9
9
W V
(a)
259
Energies 2018, 11, 3244
'9
9
'9
9
W V
(b)
Figure 10. Capacitor voltage switching ripple (CPWM): simulation results (blue trace) and calculated
peak- to-peak envelope (red traces) over a period for m = 0.3 (a) and m = 0.5 (b) in case of ϕ = 0◦ .
Figure 11. Capacitor voltage switching ripple (CPWM): simulation results (blue trace) and calculated
peak- to-peak envelope (red traces) over a period for m = 0.3 (a) and m = 0.5 (b) in case of ϕ = 60◦ .
260
Energies 2018, 11, 3244
Figure 12. Capacitor voltage switching ripple (OCPWM): simulation results (blue trace) and calculated
peak- to-peak envelope (red traces) over a period for m = 0.3 (a) and m = 0.5 (b) in case of ϕ = 0◦ .
Figure 13. Capacitor voltage switching ripple (OCPWM): simulation results (blue trace) and calculated
peak- to-peak envelope (red traces) over a period for m = 0.3 (a) and m = 0.5 (b) in case of ϕ = 60◦ .
261
Energies 2018, 11, 3244
FKDQQHOGLJLWDO
RVFLOORVFRSH 7KUHHSKDVH7W\SH
13&LQYHUWHU
706)
'63ERDUG
Experimental results are shown by Yokogawa DLM 2024 oscilloscope screenshots. Figure 15
presents an example of load voltage and current (blue and red traces, respectively) obtained by the
laboratory setup in case of sinusoidal PWM and unity power factor (m = 0.5).
Figure 15. Example of load voltage (blue) and current (red) for SPWM (m = 0.5, ϕ = 0◦ ).
Figures 16 and 17 present the results with reference to sinusoidal PWM and centered PWM
techniques, respectively. Two values of modulation index: m = 0.3 and 0.5 (from top to bottom)
and two values of the output phase angles ϕ = 0 and ϕ = 60◦ are considered (left and right column,
262
Energies 2018, 11, 3244
respectively). In all screenshots, upper traces present the capacitor voltage and its averaged counterpart
(blue and green traces, respectively) and the bottom traces present the measured capacitor voltage
switching ripple and the calculated peak-to-peak envelopes provided by the DSP board and displayed
using DAC block with a proper voltage scaling (red and green traces, respectively).
Π=0 Π = 60°
Figure 16. Experimental results for ϕ = 0◦ (left) and ϕ = 60◦ (right). Upper half: capacitor voltage and
its averaged value. Lower half: calculated peak-to-peak envelope and measured capacitor voltage
switching ripple with different modulation indexes: m = 0.3 and 0.5 (from top to bottom) in case
of SPWM.
Π=0 Π = 60°
263
Energies 2018, 11, 3244
Figure 17. Experimental results for ϕ = 0◦ (left) and ϕ = 60◦ (right). Upper half: capacitor voltage and
its averaged value. Lower half: calculated peak-to-peak envelope and measured capacitor voltage
switching ripple with different modulation indexes: m = 0.3 and 0.5 (from top to bottom) in case
of CPWM.
The capacitor voltage switching ripple has been obtained experimentally by simply using the
“ac coupling” built-in function of the oscilloscope together with the built-in low-pass filter, on the basis
of the instantaneous capacitor voltage, according to Equation (26).
Simulation and experimental results have a good matching for all the considered cases, as proved
by comparing Figures 8 and 9 with Figure 16 in case of SPWM and by comparing Figures 10 and 11
with Figure 17 in case of CPWM. Note that the same scale is adopted in corresponding simulation and
experimental di agrams to facilitate the comparison.
7. Conclusions
This paper deals with input current analysis and determination of capacitors voltage switching
ripple in three-phase three-level neutral point clamped inverters. Reference is made to the basic
modulation strategies, namely sinusoidal PWM, centered PWM, and optimized centered PWM, but the
proposed method be easily extended to other modulation techniques. The switching frequency current
and voltage ripple components have been analytically determined for the two dc-link capacitors.
In particular, the peak-to-peak voltage ripple amplitudes have been calculated as a function of the
inverter modulation index and the output current amplitude. Simple and effective guidelines for
a preliminary design the dc-link capacitors of the NPC configuration have been also introduced.
Developments have been carried out in case of general output power factor, representing either grid
connections, motor, or passive loads.
The mathematical developments have been verified, both numerically and experimentally,
for different values of modulation indices and specifically for two output phase angles ϕ = 0
(corresponding to most of the grid-connected applications) and ϕ = 60◦ . A very satisfactory matching
between analytical, numerical, and experimental results has been achieved, proving the validity of the
proposed approach.
Author Contributions: M.H. developed the theoretical analysis and the simulation results, also providing for
the manuscript arrangement in cooperation with R.M. G.R. performed the experimental test and revised the
manuscript, supported by M.H. and R.M. G.G. generally supervised and finalized the work.
Funding: This research received no external funding.
Conflicts of Interest: The authors declare no conflict of interest.
264
Energies 2018, 11, 3244
References
1. Nabae, A.; Takahashi, I.; Akagi, H. A New Neutral-Point-Clamped PWM Inverter. IEEE Trans. Ind. Appl.
1981, 17, 518–523. [CrossRef]
2. Giri, S.K.; Mukherjee, S.; Kundu, S.; Banerjee, S.; Chakraborty, C. A Carrier-Based PWM Scheme for Neutral
Point Voltage Balancing in Three-Level Inverter Extending to Full Power Factor Range. IEEE J. Emerg. Sel.
Top. Power Electron. 2017, 64, 1873–1883. [CrossRef]
3. Liu, P.; Duan, S.; Yao, C.; Chen, C. A Double Modulation Wave CBPWM Strategy Providing Neutral-Point
Voltage Oscillation Elimination and CMV Reduction for Three-Level NPC Inverters. IEEE Trans. Ind. Electron.
2018, 65, 16–26. [CrossRef]
4. Dordevic, O.; Jones, M.; Levi, E. A Comparison of Carrier-Based and Space Vector PWM Techniques for
Three-Level Five-Phase Voltage Source Inverters. IEEE Trans. Ind. Inform. 2013, 9, 609–618. [CrossRef]
5. Petrella, R.; Pevere, A. Interleaved Carrier-Based Modulations for Reducing Low-Frequency Neutral Point
Voltage Ripple in the Three-Phase Neutral Point Clamped Inverter. In Proceedings of the 2014 IEEE Applied
Power Electronics Conference and Exposition APEC, Fort Worth, TX, USA, 16–20 March 2014; pp. 2386–2393.
6. Xia, C.L.; Zhang, G.Z.; Yan, Y.; Gu, X.; Shi, T.N.; He, X.N. Discontinuous Space Vector PWM Strategy of
Neutral-Point-Clamped Three-Level Inverters for Output Current Ripple Reduction. IEEE Trans. Power
Electron. 2017, 32, 5109–5121. [CrossRef]
7. López, I.; Ceballos, S.; Pou, J.; Zaragoza, J.; Andreu, J.; Ibarra, E.; Konstantinou, G. Generalized PWM-Based
Method for Multiphase Neutral-Point-Clamped Converters with Capacitor Voltage Balance Capability.
IEEE Trans. Power Electron. 2017, 32, 4878–4890. [CrossRef]
8. Pevere, A.; Petrella, R. Discontinuous Hybrid Modulation Technique for Three-Phase Three-Level Neutral
Point Clamped Inverters. In Proceedings of the 2013 IEEE Energy Conversion Congress and Exposition
ECCE, Denver, CO, USA, 15–19 September 2013; pp. 3992–3999.
9. Bianchi, N.; Di Pre, M. Active Power Filter Control Using Neural Network Technologies. IEE Proc. Electr.
Power Appl. 2003, 150, 139–145.
10. Vujacic, M.; Hammami, M.; Srndovic, M.; Grandi, G. Evaluation of DC Voltage Ripple InSingle-Phase
H-Bridge PWM Inverters. In Proceedings of the IEEE 26th International Symposium on Industrial Electronics,
Scotland, UK, 19–21 June 2017; pp. 711–716.
11. Vujacic, M.; Hammami, M.; Srndovic, M.; Grandi, G. Theoretical and Experimental Investigation of Switching
Ripple in the DC-Link Voltage of Single-Phase H-Bridge PWM Inverters. Energies 2017, 10, 1189. [CrossRef]
12. Hammami, M.; Vujacic, M.; Grandi, G. Dc-Link Current and Voltage Ripple Harmonics in Three-Phase
Three-Level Flying Capacitor Inverters with Sinusoidal Carrier-Based PWM. In Proceedings of the IEEE
International Conference Industrial Technology, Lyon, France, 20–22 February 2018.
13. Liang, Z.; Li, M.; Dong, Z.; Tian, S.; Li, K. Analytical Closed-Form Expressions of DC Current Ripple for
Three-Level Neutral Point Clamped Inverters with Space-Vector Pulse-Width Modulation. IET Power Electron.
2016, 9, 930–937.
14. Gopalakrishnan, K.S.; Das, S. Analytical Expression for RMS DC Link Capacitor Current in a Three-Level
Inverter. In Proceedings of the Centenary Conference Electrical Engineering, Indian Institute of Science,
Bangalore, India, 15–17 December 2011.
15. Orfanoudakis, G.I.; Sharkh, S.M.; Yuratich, M.A. Analysis of Dc-Link Capacitor Current in Three-Level
Neutral Point Clamped and Cascaded H-Bridge Inverters. IET Power Electron. 2013, 6, 1376–1389. [CrossRef]
16. Pou, J.; Pindado, R.; Boroyevich, D.; Rodríguez, P. Evaluation of the Low-Frequency Neutral-Point Voltage
Oscillations in the Three-Level Inverter. IEEE Trans. Ind. Electron. 2005, 52, 1582–1588. [CrossRef]
17. Pou, J.; Zaragoza, J.; Rodríguez, P.; Ceballos, S.; Sala, V.M.; Burgos, R.P.; Boroyevich, D. Fast-Processing
Modulation Strategy for the Neutral-Point-Champed Converter with Total Elimination of Low-Frequency
Voltage Oscillations in the Neutral Point. IEEE Trans. Ind. Electron. 2007, 54, 2288–2294. [CrossRef]
18. Fujii, K.; Kikuchi, T.; Koubayashi, H.; Yoda, K. 1-MW Advanced T-Type NPC Converters for Solar Power
Generation System. In Proceedings of the 2013 15th European Conference on Power Electronics and
Applications (EPE), Lille, France, 2–6 September 2013.
265
Energies 2018, 11, 3244
19. Zhang, Z.; Anthon, A.; Andersen, M.A.E. Comprehensive Loss Evaluation of Neutral-Point-Clamped (NPC)
and T-Type Three-Level Inverters Based on a Circuit Level Decoupling Modulation. In Proceedings of the
2014 International Power Electronics and Application Conference and Exposition PEAC, Shanghai, China,
5–8 November 2014.
20. Grandi, G.; Loncarski, J. Simplified Implementation of Optimised Carrier-Based PWM in Three-Level
Inverters. Electron. Lett. 2014, 50, 631–633. [CrossRef]
© 2018 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access
article distributed under the terms and conditions of the Creative Commons Attribution
(CC BY) license (http://creativecommons.org/licenses/by/4.0/).
266
energies
Article
Design and Controller-In-Loop Simulations of a Low
Cost Two-Stage PV-Simulator
Sridhar Vavilapalli 1 , Umashankar Subramaniam 1 , Sanjeevikumar Padmanaban 2, * and
Frede Blaabjerg 3
1 Department of Energy and Power Electronics, School of Electrical Engineering, VIT University,
Vellore 632014, India; [email protected] (S.V.); [email protected] (U.S.)
2 Department of Energy Technology, Aalborg University, 6700 Esbjerg, Denmark
3 Center of Reliable Power Electronics (CORPE), Department of Energy Technology, Aalborg University,
9100 Aalborg, Denmark; [email protected]
* Correspondence: [email protected]; Tel.: +45-209-751-79
1. Introduction
The operation and efficiency of a solar power conditioning system at different operating points can
be tested using a variable DC source in the laboratory, but to validate the ability to track the maximum
power point (MPP) in the power conditioning system, it is necessary to test the system with an actual
PV array, but with an actual PV array, it is difficult to test the system at predefined operating points
due to varying climatic changes. The space and cost required for the installation of an actual PV array
are also more. With an actual PV array on site, it is necessary to alter the series/parallel combination
of PV modules for testing different rated PV power conditioning systems. Hence a PV simulator
is required to validate the solar power conditioning system at the laboratory level itself before any
actual site trials [1,2]. A PV-simulator system is a DC power source in which the current-voltage (I-V)
characteristics of different PV arrays can be programmed so that the operation of the solar power
conditioning system can be validated. With a PV-simulator, it is possible to test the power conditioning
systems for different voltage current combinations within the rated values of the PV-simulator.
An LLC resonant DC-DC converter-based PV-simulator discussed in [3,4] consists of a current
driven centre tapped transformer which provides galvanic isolation between input and output
circuits. A PV-simulator based on an interleaved buck converter is presented in [5,6]. A buck-boost
chopper-based PV-simulator with double current mode control is proposed in [7] and a buck
chopper-based PV-simulator with a two stage LC filter is discussed in [8]. A PV-simulator based
on a two-quadrant DC-DC converter is proposed in [9]. A buck-chopper-based DC-DC converter
with a single stage L-C filter is presented in [10–12]. The above discussed configurations and the
components required for each configuration are summarized in Table 1 and it is observed that the
buck-chopper-based PV-simulator is the most economical compared to other configurations due to its
lesser number of magnetic components and power switches.
268
Energies 2018, 11, 2774
clamped three level inverter [18]. Due to the above advantages a front-end converter based on a T-type
configuration is selected in this work.
In this work, the design of a low cost PV-simulator with a single phase front end converter and
a buck-chopper-based DC-DC converter is proposed. The block diagram of the proposed simulator
is shown in Figure 1. Parameters such as open-circuit voltage, short-circuit current, MPP voltage,
MPP current, power rating, series resistance, parallel resistance and temperatures coefficients of the
selected PV array which are usually available from the product datasheet and can be programmed
in the PV-simulator. The variable inputs such as irradiance on the PV array and the temperature of
PV array can be varied from the user interface for testing the power conditioning system at various
operating points. The maximum ratings of the PV array that can be programmed are restricted to the
rated output voltage and currents of PV-simulator.
77<3( 62/$5
'&'& ,19(57(5
$& )5217(1'
&219(57(5 81'(5
&219(57(5
7(67
,$&
939
9$& &21752//(5
,55$',$1&( 7(03(5$785(
21 2)
39$55$< 39$55$<
23(1&,5&8,792/7$*(92& #:6TP2&
6+257&,5&8,7&855(17 ,6& #:6TP2&
03392/7$*( 9033 #:6TP2&
033&855(17 ,033 #:6TP2&
0$;,08032:(5 30$; #:6TP2&
7(03(5$785(&2((),&,(172)92/7$*(
7(03(5$785(&2((),&,(172)32:(5
7(03(5$785(&2((),&,(172)&855(17
39$55$<6(5,(65(6,67$1&(
39$55$<3$5$//(/5(6,67$1&(
39$55$<3$5$0(7(56
352*5$00$%/(
Figure 1. Block diagram of the proposed PV-Simulator.
269
Energies 2018, 11, 2774
270
Energies 2018, 11, 2774
response of the system can be studied by applying a step change in reference DC voltage (Vdc_Ref)
and the load current (Idc) [22].
)URQW(QG&RQYHUWHU
,VRODWLRQ
&219(57(5
/
'&'&
&
6D
9V
9GF
&
6E
6D 6E
&
6D 6E
9GF
,GF
&RQWUROOHU *$7(38/6(*(1(5$725
3,&21752//(5
9GFB5HI
,DF
3,
9DF 6LQZW
3// ; .
Figure 2. Control Block diagram of T-Type Front-End Converter.
Operation of FEC and the dynamic response of the system are validated through real-time
simulations using an Opal RT real-time simulator. The electrical scheme for real-time simulation
validation is shown in Figure 3. In this setup, the plant, comprised of an input supply, transformer,
T-Type converter, DC-link capacitors, and the load are modeled in Matlab-Simulink with a sample time
of 10 microseconds. The simulated model is compiled and loaded in the high speed processor of the
real-time simulator. The control software for T-type front end converter is developed through a Matlab
embedded coder and loaded in the controller card based on a Texas Instruments TMS320F2812 digital
single processor. Details of the controller card used and the real-time simulator are shown in Table 3.
Start/Stop commands are given to the controller from external pushbuttons. The DC link voltage
reference VDC_Ref signal is also given from user interface to the analog input channel of the controller
card. Using the analog output channels of the real-time simulator, the voltage and current signals from
the plant are given to the analog input channels of the controller card.
The controller card provides gate signals for the FEC through the digital input channels of the
real-time simulator. A simulated ‘Stack faulty signal’ in the plant is given to the controller card through
the digital output channel of the real-time simulator. On receiving the stack faulty signal from the
plant, the controller blocks the gate pulses to the FEC and also provides an off command to the input
AC breaker Q1. To provide step changes in the load, two contactors Q2, Q3 are simulated and the
control signals for these load switches are provided by the controller through the digital input channels
of the real-time simulator. The dynamic response of the FEC is observed for sudden changes in the DC
link voltage reference (VDC_Ref) and for sudden changes in load.
271
Energies 2018, 11, 2774
6,08/$7('32:(5&,5&8,7,15($/7,0(6,08/$725
)URQW(QG&RQYHUWHU
,VRODWLRQ
7UDQVIRUPHU 6D 6E
&
4
4
4
/
&
9V 6D
&
6E
5/
5/
&
6D 6E
6D 6E
21&RPPDQG±4
2XWSXW9ROWDJH9GF
21&RPPDQG4
2XWSXW&XUUHQW,GF
,QSXWYROWDJH9DF
,QSXW&XUUHQW,DF
6WDFN)DXOW\
&21752//(5&$5'
'LJLWDO,QSXW $QDORJ,QSXW
4B212))
4B212))
6WDUW6WRS
9'&B5HI
86(5,17(5)$&(
Figure 3. Electrical scheme for controller-In-Loop simulation validation of T-Type Front-End Converter.
272
Energies 2018, 11, 2774
'&/,1.92/7$*(
9ROWDJH
)(&3:092/7$*(
7LPH
D
92/7$*(
&855(17
9ROWDJH
&XUUHQW
7LPH
E
Figure 4. (a) Voltage and Current Waveforms of T-Type Front-End Converter (b) Input Voltage and
Current Waveforms of Front-End Converter during Transition time for a step change in DC link voltage.
273
Energies 2018, 11, 2774
'&/,1.92/7$*(
'&/,1.92/7$*(
9ROWDJH
9ROWDJH
)(&3:092/7$*(
)(&3:092/7$*(
7LPH
D
92/7$*(
92/7$*( &855(17
&855(17
9ROWDJH
9ROWDJH
&XUUHQW
&XUUHQW
7LPH
E
Figure 5. (a) Input Voltage and Current Waveforms of T-Type Front-End Converter (b) Input Voltage
and Current Waveforms of T-Type Front-End Converter during Transition time for a step change
in Load.
A step change in DC load is applied and it is observed that the actual DC link voltage drops by
approximately 40 volts at that instant and increases gradually to the reference value, i.e., 600 volts,
as shown in Figure 5a. Since the load is increased on the DC side, there in an increase in the input side
current. It is observed that the input current is increased but the unity power factor is still maintained
as shown in Figure 5b.
From the presented real-time simulation results, it is observed that the FEC controls programmed
in the real controller are satisfactory as the system operation is as desired under different operating
conditions. The dynamic response of the system and the associated controls are also good as the
settling time and overshoots are less. For PV-simulator applications, the reference DC link voltage
274
Energies 2018, 11, 2774
of the FEC is always adjusted to be more than the open circuit voltage of the programmed PV array.
The FEC always operates at unity power factor and the input current depends on the DC-DC converter
operation which is connected as load to the FEC. Detailed discussions on DC-DC converter and
associated controls are presented in the next section.
%XFN&KRSSHU
/
6
)URQW(QG
&RQYHUWHU
/ '
62/$5,19(57(5
81'(57(67
9V
9B39
'
&
*DWH6LJQDO
,B39B5HI
3:0
,B39
,UUDGLDQFHRQ
39&XUUHQW 39$UUD\
5HIHUHQFH
3, 7HPSHUDWXUHRI
*HQHUDWRU
39$UUD\
&21752//(5
In this work, the reference DC current is obtained from the PV current equation given in [11] as
shown in Equation (1):
I_PV _Ref = Iph − (Is *(e (V + I*Rse)/N*Vt−1) )) − ((V + I*Rse )/Rp ) (1)
where I = PV current, V = PV voltage, Isc = short circuit current and Voc = Open circuit Voltage
where Boltzmann’s constant (k) = 1.3806 × 10−23 , operating temperature (T) = 25 ◦ C and the charge of
an electron (q) = 1.602 × 10−19 .
Irradiance and temperature of PV array signals are adjustable by the user in this PV-simulator to
test the solar power conditioning system under different operating conditions. To verify the operation
of the PV-simulator, a PV array with the specifications listed in Table 4 and the proposed PV-simulator
circuit are simulated for the same operating conditions and compared with each other.
275
Energies 2018, 11, 2774
Table 4. Parameters of Programmed PV-Array at Irradiance Inputs of 1000 W/Sq.m and 600 W/Sq.m.
The PV array and the PV-simulator are simulated in two different cases. In case-1, load resistance
is maintained constant and the irradiance value is varied in steps. In case-2, irradiance is kept constant
and the load resistance is varied.
Case-1: A fixed resistive load is connected to the PV array and the PV-array output voltage, current
and power are monitored by varying the irradiance. PV current is proportional to the irradiance and
the PV voltage is the product of PV current and the load resistance. Similarly the PV-simulator is also
connected to the same load and tested for the same conditions to compare the results with the results
obtained by simulating a PV array. It is observed that the outputs of PV array and the PV-simulator
match with each other as shown in Figure 7. Irradiance input to the simulator is reduced in steps
of 200 W/sq.m at each 0.5 s time and it is observed that the reference current to the chopper is also
reduced proportionally to the irradiance. The controller ensures the actual output current remains
equal to the reference output current with the help of a closed-loop current controller.
,UUDGLDQFHLQ:VTP
,UUDGLDQFHRQ39$UUD\
7LPHLQVHFRQG
&XUUHQWLQDPSHUH
396LPXODWRU2XWSXW&XUUHQW
39$UUD\2XWSXW&XUUHQW
7LPHLQVHFRQG
396LPXODWRU2XWSXW9ROWDJH
9ROWDJHLQYROW
39$UUD\2XWSXW9ROWDJH
7LPHLQVHFRQG
3RZHULQN:
396LPXODWRU2XWSXW3RZHU
39$UUD\2XWSXW3RZHU
7LPHLQVHFRQG
Figure 7. Output Voltage, Current and Powers from an Actual PV array and the PV-simulator for
Different Irradiance Values.
276
Energies 2018, 11, 2774
Case-2: An irradiance of 600 W/Sq.m is applied as input to both the PV array and PV-simulator.
Table 3 shows the parameters of the PV array at 600 W/sq.m which are derived based on the parameters
in the datasheet of the PV module (Type number SPR-435NE-WHT-D of M/s Sun Power) selected.
Independent variable loads are connected to PV array and the PV-simulator outputs. Loads on the
PV-Array and the PV-simulator are increased in steps and monitored the output voltages, currents and
powers. From the results shown in Figure 8, it is observed that the output values obtained from the
PV-simulator are identical to the values obtained from the PV array.
39$UUD\&XUUHQW 396LPXODWRU2XWSXW&XUUHQW
&XUUHQWLQDPSHUH
&XUUHQLQDPSHUH
7LPHLQVHFRQG 7LPHLQVHFRQG
39$UUD\9ROWDJH 396LPXODWRU2XWSXW9ROWDJH
9ROWDJHLQYROW
9ROWDJHLQYROW
7LPHLQVHFRQG 7LPHLQVHFRQG
39$UUD\3RZHU 396LPXODWRURXWSXW3RZHU
3RZHULQN:
3RZHLQN:
7LPHLQVHFRQG 7LPHLQVHFRQG
Figure 8. Output Voltage, Current and Powers from an Actual PV array and the PV-Simulator for at an
Irradiance of 600 W/Sq.m.
From the simulation results shown in Figures 7 and 8, it is evident that the proposed PV-simulator
can replicate the actual PV-array by programming the actual PV-array parameters, so that it can be
used for testing solar power conditioning systems.
277
Energies 2018, 11, 2774
required from the plant such as input voltage, input current, output voltage and output currents from
the simulated plant through the analog out (AO) channels of the real-time simulator.
6,08/$7('32:(5&,5&8,7,15($/7,0(6,08/$725
)URQW(QG&RQYHUWHU %XFN&KRSSHU 5/
,VRODWLRQ
7UDQVIRUPHU 6D 6E
& 6
4 /
&
6D / '
9V
&
6E
& ' &
6D 6E
6D 6E
&KRSSHU2XWSXW&XUUHQW
*DWH3XOVHIRU&KRSSHU
&KRSSHU2XWSXW9ROWDJH
,QFUHDVH/RDG5HVLVWDQFH
6WDFN)DXOW\B&KRSSHU
*DWH3XOVHVIRU)(&
'&/LQN9ROWDJH9GF
6WDFN)DXOW\B)(&
'&/LQN&XUUHQW,GF
21&RPPDQG4
,QSXWYROWDJH9DF
,QSXW&XUUHQW,DF
'LJLWDO2XWSXW 'LJLWDO,QSXW $QDORJ,QSXW
&21752//(5&$5'
'LJLWDO,QSXW $QDORJ,QSXW
7HPSHUDWXUH
4B212))
4B212))
6WDUW6WRS
,UUDGLDQFH
9'&B5HI
86(5,17(5)$&(
Figure 9. Controller-In-Loop Simulation setup for validation of proposed PV-Simulator Controls.
As discussed in previous sections, on receiving the actual analog signals from the plant,
the controller generates the gate pulses to maintain the actual values equal to the reference values
for both FEC and DC-DC converters.The controller provides the gGate pulses to the simulated FEC
and DC-DC converter through the digital input channels of the real-time simulator. The real-time
simulator converts the gate pulses received into data to trigger the IGBTs. All this process happens
with real-time speed.
In this work, the PV array with the parameters shown in Table 4 are programmed in the
PV-simulator and the load current is varied from short circuit current to zero current. The voltage and
power of the PV array are monitored for different irradiance Inputs. From the presented results shown
in Figure 10, it is observed that for different irradiance inputs, the MPP voltage is almost constant with
a value of approximately 250 volts. The MPP voltages and powers obtained from the PV-simulator at
different irradiance inputs are compared with the PV module datasheet (SPR-435NE-WHT-D) and it is
found that the proposed PV-simulator can replicate the actual PV array characteristics.
278
Energies 2018, 11, 2774
9ROWDJH
9033
28738792/7$*( 28738792/7$*(
96& 96&
#:VTP #:VTP
28738732:(5 28738732:(5
3RZHU
3RZHU
,6& ,033 ,2&
,6& ,033 ,2&
&XUUHQW &XUUHQW
D F
9RF
9ROWDJH
9ROWDJH
9033 9033 9RF
28738792/7$*(
28738792/7$*(
96& 96&
#:VTP #:VTP
28738732:(5
28738732:(5
3RZHU
3RZHU
Figure 10. Output Voltage and Powers of PV-Simulator for Different Irradiance Inputs.
5. Future Scope
In the present work, operation of a PV-simulator is validated through controller in loop
simulations by interfacing the real controller hardware with the simulated power circuit by using a
real-time simulator. Through controller-in-loop simulations, tuning of control software and the power
circuit parameters is carried out. As a future work, it is envisaged to build a PV-simulator based on the
present work.
A dual-active bridge (DAB)-based DC-DC converter with high frequency transformer presented
in [23] is also investigated along with the chopper-based DC-DC converter for the present application.
As a future work, it is envisaged to study a DAB-based PV-simulator to reduce the size of
the equipment.
6. Conclusions
The proposed PV-simulator configuration provides better input THD as the front-end converter
of a three-level rectifier. Unity power factor operation is achieved with this configuration which results
in an optimized power rating of the simulator. FEC also helps in boosting the DC link voltage without
using a step-up transformer on the AC side which results in lesser cost. From the presented results
it can be concluded that the dynamic response of the system is satisfactory for sudden changes in
load, sudden changes in the irradiance inputs and sudden changes in the DC link voltage reference.
Instead of using an isolation transformer on the input side, it is also feasible to use a high-frequency
transformer in the DC-DC converter which can reduce the size of the simulator. With the proposed
configuration, multiple numbers of PV simulators can be connected in parallel for testing higher
rated power conditioning systems. Operation of two PV-simulators connected in parallel subjected to
unequal irradiance inputs can be studied which should help in analyzing the system operation during
partial shading conditions.
279
Energies 2018, 11, 2774
Author Contributions: S.V., S.P., U.S., had developed the original proposed research work and implemented
with numerical simulation software and real time RTDS system for investigation and performance validation.
F.B. contributed his expertise in the proposed subject of research and verification of the obtained results based
on theoretical concepts and insight background. All authors involved to articulate the research work for its final
depiction as research paper.
Conflicts of Interest: The authors declare no conflict of interest.
References
1. Jin, S.; Zhang, D.; Wang, C. UI-RI Hybrid Lookup Table Method with High Linearity and High-Speed
Convergence Performance for FPGA-Based Space Solar Array Simulator. IEEE Trans. Power Electron. 2018,
33, 7178–7192. [CrossRef]
2. Zhou, Z.; Macaulay, J. An Emulated PV Source Based on an Unilluminated Solar Panel and DC Power
Supply. Energies 2017, 10, 2075. [CrossRef]
3. Chang, C.; Chang, E.; Cheng, H. A High-Efficiency Solar Array Simulator Implemented by an LLC Resonant
DC–DC Converter. IEEE Trans. Power Electron. 2013, 28, 3039–3046. [CrossRef]
4. Chang, C.H.; Cheng, C.A.; Cheng, H.L. Modeling and design of the LLC resonant converter used as a
solar-array simulator. IEEE J. Emerg. Sel. Top. Power Electron. 2014, 2, 833–841. [CrossRef]
5. Mahmud, M.H.; Zhao, Y.; Wang, L. A high-bandwidth PV source simulator using a sliding mode controlled
interleaved buck converter. In Proceedings of the IEEE International Conference IECON, Beijing, China,
29 October–1 November 2017; pp. 2326–2331.
6. Koran, A.; LaBella, T.; Lai, J.S. High efficiency photovoltaic source simulator with fast response time for solar
power conditioning systems evaluation. IEEE Trans. Power Electron 2014, 29, 1285–1297. [CrossRef]
7. Zhang, W.; Kimball, J.W. DC–DC Converter Based Photovoltaic Simulator with a Double Current Mode
controller. IEEE Trans. Power Electron. 2018, 33, 5860–5868. [CrossRef]
8. Koran, A.; Sano, K.; Kim, R.Y.; Lai, J.S. Design of a Photovoltaic Simulator with a Novel Reference Signal
Generator and Two-Stage LC Output Filter. IEEE Trans. Power Electron. 2010, 25, 1331–1338. [CrossRef]
9. Cordeiro, A.; Foito, D.; Pires, V.F. A PV panel simulator based on a two quadrant DC/DC power converter
with a sliding mode controller. In Proceedings of the IEEE International Conference on Renewable Energy
Research and Applications (ICRERA), Padova, Italy, 22–25 November 2015; pp. 928–932.
10. Kawano, M.; Sato, T.; Taguchi, T.; Genzima, Y.; Teramoto, S. Simple and low cost PV simulator using diode
characteristics for development of PV system. In Proceedings of the INTELEC 2015—IEEE International
Conference on Telecommunications Energy, Osaka, Japan, 18–22 October 2015; pp. 1–5.
11. Özden, Ö.; Duru, Y.; Zengin, S.; Boztepe, M. Design and implementation of programmable PV simulator.
In Proceedings of the IEEE International Conference on Fundamentals of Electrical Engineering (ISFEE),
Bucharest, Romania, 30 June–2 July 2016; pp. 1–5.
12. Seo, Y.T.; Park, J.Y.; Choi, S.J. A rapid IV curve generation for PV model-based solar array simulators.
In Proceedings of the IEEE International Conference on Energy Conversion Congress and Exposition (ECCE),
Milwaukee, WI, USA, 18–22 September 2016; pp. 1–5.
13. Shinde, U.K.; Kadwane, S.G.; Keshri, R.K.; Gawande, S.P. Dual Mode Controller-Based Solar Photovoltaic
Simulator for True PV Characteristics. Can. J. Electr. Comput. Eng. 2017, 40, 237–245.
14. Piao, Z.G.; Gong, S.J.; An, Y.H.; Cho, G.B. A study on the PV simulator using equivalent circuit model and
look-up table hybrid method. In Proceedings of the IEEE International Conference on Electrical Machines
and Systems (ICEMS), Busan, Korea, 26–29 October 2013; pp. 2128–2131.
15. Alemi, P.; Lee, D.C. Power loss comparison in two-and three-level PWM converters. In Proceedings of
the IEEE International Conference on Power Electronics and ECCE Asia (ICPE & ECCE), Jeju, Korea,
30 May–3 June 2011; pp. 1452–1457.
16. Schweizer, M.; Friedli, T.; Kolar, J.W. Comparative evaluation of advanced three-phase three-level
inverter/converter topologies against two-level systems. IEEE Trans. Ind. Electron. 2013, 60, 5515–5527.
[CrossRef]
17. Masisi, L.; Choudhury, A.; Pillay, P.; Williamson, S. Performance comparison of a two-level and three-level
inverter permanent magnet synchronous machine drives for HEV application. In Proceedings of the IEEE
International Conference on Industrial Electronics Society (IECON), Vienna, Austria, 10–13 November 2013;
pp. 7262–7266.
280
Energies 2018, 11, 2774
18. Shin, H.; Lee, K.; Choi, J.; Seo, S.; Lee, J. Power loss comparison with different PWM methods for 3L-NPC
inverter and 3L-T type inverter. In Proceeding of the IEEE Power Electronics and Application Conference
and Exposition (PEAC), Shanghai, China, 5–8 November 2014; pp. 1322–1327.
19. Labaki, R.; Kedjar, B.; Al-Haddad, K. Single-Phase Active Front End Converter with series compensation.
In Proceedings of the IEEE International Symposium on Industrial Electronics, Montreal, QC, Canada,
9–13 July 2006; pp. 769–774.
20. Huerta, F.; Stynski, S.; Cobreces, S.; Malinowski, M.; Rodriguez, F.J. Novel Control of Three-Phase Active
Front-End Converter with Compensation of Unknown Grid-Side Inductance. IEEE Trans. Ind. Electron. 2011,
58, 3275–3286. [CrossRef]
21. Sridhar, V.; Umashankar, S. A comprehensive review on CHB MLI based PV inverter and feasibility study of
CHB MLI based PV-STATCOM. Renew. Sustain. Energy Rev. 2017, 78, 138–156. [CrossRef]
22. Hou, C.C.; Cheng, P.T. Experimental Verification of the Active Front-End Converters Dynamic Model and
Control Designs. IEEE Trans. Power Electron. 2011, 26, 1112–1118. [CrossRef]
23. Sridhar, V.; Sanjeevikumar, P.; Umashankar, S.; Mihet-Popa, L. Power Balancing Control for Grid Energy
Storage System in Photovoltaic Applications-Real Time Digital Simulation Implementation. Energies J. 2017,
10, 928.
© 2018 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access
article distributed under the terms and conditions of the Creative Commons Attribution
(CC BY) license (http://creativecommons.org/licenses/by/4.0/).
281
energies
Article
Experimental Evaluation of the Performance of a
Three-Phase Five-Level Cascaded H-Bridge Inverter
by Means FPGA-Based Control Board for Grid
Connected Applications
Fabio Viola
Dipartimento Energia, ingegneria dell’Informazione e modelli Matematici, DEIM, University of Palermo,
90133 Palermo, Italy; [email protected]; Tel.: +39-091-238-60253
Abstract: Over the last decades, plants devoted to the generation of green energy significantly
increased their number, together with the demand of same electrical energy, also stored in
battery systems. This fact produced the growth of energy conversion systems with advanced
performances with respect to the traditional ones. In this circumstance, multilevel converters play a
significant role for their great advantages in performances, flexibility, fault-tolerability, employment of
renewable energy sources and storage systems and finally yet importantly reduced filter requirements.
In this context, this paper faces the performance of a cascaded H-bridge 5 level inverter in terms
of harmonic distortion generated and injected into the grid. Through an accurate analysis that
takes into account the pulse width modulation (PWM) multicarrier modulation techniques (phase
disposition PD, phase opposition disposition POD, alternative phase opposition disposition APOD,
phase shifted PS) and related reference signals (sinusoidal reference; third harmonic injection THI
reference, switching frequency optimal SFO reference), a framework of distorting harmonics is
presented by comparing twelve cases. The results obtained from the simulations are reproduced
and validated in a prototype system of five level cascaded H-bridge multilevel inverter. A deep
discussion of control and filtering system is provided to justify the choice of the best modulation
technique to adopt.
Keywords: Cascaded H-bridge multilevel inverter (CHBMI); field-programmable gate array; total harmonic
distortion (THD); modulation techniques
1. Introduction
The increased demand of green energy has led to the development of even more performing
structures allowing the generation and storage of energy in DC form. The drawbacks are due to the
increased number of harmonics introduced and filtered in the power grids.
The three main multilevel power inverter (MPI) structures proposed in technical literature, with
their related benefits and disadvantages, according to [1–3] are diode clamped converter (DCC),
capacitor-clamped inverter (CCI) and cascaded H-bridge (CHB) multilevel inverter.
The neutral point clamped converter (NPC) was the first multilevel structure proposed.
The common DC-link is composed of four capacitors connected in series that split the voltage into
four level. The middle point of the capacitors n is used as neutral point. The peculiar components,
that differentiate this circuit from the others multilevel inverters, are the clamping diodes that allow
to subdivided the DC voltage on the switches. Thus, the voltage across on the switches is limited to
one capacitor voltage equal to Vdc /(nL − 1), where nL is the number of level. By supposing that for
each blocking diode its voltage value is identical to the voltage rating of active device, the number
of diodes requested for each phase will be (nL − 1)·(nL − 2). This converter presents some operative
limits as: (1) max number of levels is five, due both to the complexity of the circuit and both to the large
number of components demanded; (2) uneven distribution of semiconductor power losses among
the switches, which reduces the switching frequency and the output power; (3) unbalanced capacitor
voltages which generate low frequency harmonics; (4) the system cannot involve a modular structure
(non-modular topology structure).
Flying capacitor inverters (FCIs) or CCIs are an alternative to overcome some of the
DCC disadvantages. The structure of CCIs have similarity to NPC inverter except the CCI uses several
capacitors in the place of the clamping diodes. The main advantage of the CCI are the redundant states
to obtain the voltage levels. In this way, it is possible an even distribution of semiconductor losses
among the switches but it is necessary a dedicated control algorithm to balance the capacitors voltage.
The increase of voltage levels confines the proper charging and discharging mechanism
of capacitors. By considering the economical aspect, the cost of the inverter follows the increase
of the number of levels, but also the device becomes bulkier and its lifetime decreases due to the
growing number of used capacitors. For a nL -level converter, it is necessary (nL − 1)·(nL − 2)/2
clamping capacitors per phase in addition to the (nL − 1)·main dc bus capacitors. Thus, the high
number of capacitors limit the use to three or five levels. Moreover, lack of modularity and high
quantity of capacitors for higher number of voltage levels reduces the reliability of this converter.
Figure 1 shows the topology structure of a single-phase five-level cascaded H-bridge
multilevel inverter.
Sa1,1 Sa1,2
+
V DC, a1 C
Sa1,3 Sa1,4
vout
Sa2,1 Sa2,2
+
V DC, a2 C
Sa2,3 Sa2,4
This topology has a main advantage: the modular configuration, blocks can be added to reach
voltage levels, control is easily performed, and maintenance, in case of fault, requires the disconnection
of a block to keep the system working. Thus, each module can be either half- or full-bridge with
separated DC source and can be controlled as a single-phase converter. This topology reaches in output
medium voltage levels, by enforcing only common low-voltage components so there are not operative
limits about max number of the voltage levels. Matching the number of capacitors and diodes between
the cited topologies yields that CHB converter has the least number of components.
The phase voltage is synthesized by the addition of the voltages generated by the
different modules. Thus, the voltage levels nL depend of the number of modules connected in
series for phase through the equation:
n L = 2n HB + 1 (1)
283
Energies 2018, 11, 3298
Separated DC sources are an advantage in many applications but this feature leads to a more
complex DC-voltage regulation loop.
Others topology structures of multilevel inverters and different classification methods were
reported in literature [4]. In [5], an interesting classification into two comprehensive categories
according to the applied DC source structure were discussed. A high number of topology structures
were developed since separated DC sources are very diffused in renewable energy plants (PV, Wind
farm, Fuel cell, etc.).
• Phase Disposition (PD) (Figure 2a), where all carriers are in phase;
• Phase Opposition Disposition (POD) (Figure 2b), where the carriers above the reference zero point
have a difference of phase respect those below the zero point of π;
• Alternative Phase Opposition Disposition (APOD) (Figure 2c), where each carrier is phase shifted
by π from its adjacent carriers.
The carrier number nc of the level shifted multicarrier PWM in function of the number of the
converter level nL , is equal to:
nc = n L − 1 (2)
These strategies lead to elimination of all carriers and related sideband harmonics up to the
switching frequency.
Phase shifted multicarrier PWM strategy, shown in Figure 2d, is an extension of the unipolar PWM
for traditional single-phase two-level inverter. For this technique, the modulation of the H-bridge
inverters in each phase leg is modular. Thus, the reference waveforms for the two-phase legs inverter
are phase shifted by π. The number of the carrier signals is equal to nHB while the phase shifted
optimum (PSO) to obtain harmonic cancellation, is achieved:
( i − 1) π
PSO = (3)
n HB
where i is the ith H-Bridge series connected per phase. For a five-level inverter two carrier signals
with mutual phase shift equal to π/2, Figure 2b, are necessary. This scheme leads to elimination of all
carriers and associated sideband harmonics up to the 2nHB times of the switching frequency.
284
Energies 2018, 11, 3298
(a) (b)
(c) (d)
Figure 2. Multicarrier strategies for five-level converter: (a) Phase Disposition (PD); (b) Phase
Opposition Disposition (POD); (c) Alternative Phase Opposition Disposition (APOD); (d) Phase
Shifted (PS). For the first three modulation techniques, four carriers are required, for example in
PD technique blue and red lines enable the voltage control of higher bridge, green and cyan the
lower bridge. In PS each only two carriers are required since each phase leg has a modular control.
1. Sinusoidal reference;
2. Third harmonic injection (THI);
3. Switching frequency optimal (SFO).
The THI allows overcoming the limit of√ the three-phase inverters about the reduction of the
maximum peak fundamental line voltage of 3VDC /2 (86.60% of VDC ). Modulation index can be
increased by including a common mode third-harmonic term into the reference signal of each phase
leg, as shown in Figure 3a (green curve).
This third-harmonic component does not effect on the fundamental line-to-line voltage because the
common mode voltages cancel between the phase legs. According to [9], the optimum third-harmonic
injection component must have a magnitude of 25% of the fundamental reference. In this way, it is
possible to obtain an increasing of the modulation index up to 1.12 and a maximum value of the peak
fundamental line-to-line voltage equal to 97% of VDC .
Figure 3b shows the SFO signal (green curve) for a phase of the converter. As demonstrated in [9],
SFO is a space vector equivalent reference voltage that can be used in PWM modulation to produce
output voltages with the same average low-frequency content.
285
Energies 2018, 11, 3298
(a) (b)
Figure 3. Reference signal for a phase of the converter: (a) third harmonic injection (THI); (b) switching
frequency optimal (SFO). Blue waveform represents the fundamental, orange is the adjustment signal
and blue is the modified reference.
where va (t), vb (t) and vc (t) are the sinusoidal reference that can be expressed in function of the
modulation index M as (5):
v a (t) = M sin(ωt)
vb (t) = M sin ωt − 2π 3 (5)
vc (t) = M sin ωt − 4π 3
max(v a , vb , vc ) + min(v a , vb , vc )
vo f f set = (6)
2
The arrangement between carrier signals and modulating references produces twelve modulation
techniques, graphically summarized in Figures 4–6.
286
Energies 2018, 11, 3298
(a) (b)
(c) (d)
Figure 4. Proposed modulation techniques with sinusoidal reference: (a) Phase Disposition (PD);
(b) Phase Opposition Disposition (POD); (c) Alternative Phase Opposition Disposition (APOD);
and (d) Phase Shifted (PS). Blue, red and orange sinusoidal signals represent the reference signals;
interferences with the triangular signals generate the modulation angles for the four switches.
(a) (b)
(c) (d)
Figure 5. Proposed modulation techniques with THI reference: (a) Phase Disposition PD; (b) Phase
Opposition Disposition POD; (c) Alternative Phase Opposition Disposition APOD; and (d) Phase
Shifted PS. Blue, red and orange THI signals represent the reference signals; interferences with the
triangular signals generate the modulation angles for the four switches.
287
Energies 2018, 11, 3298
(a) (b)
(c) (d)
Figure 6. Proposed modulation techniques with SFO reference: (a) Phase Disposition (PD); (b) Phase
Opposition Disposition (POD); (c) Alternative Phase Opposition Disposition (APOD); and (d) Phase
Shifted (PS). Blue, red and orange SFO signals represent the reference signals; interferences with the
triangular signals generate the modulation angles for the four switches.
An interesting deep discussion on the previous proposed techniques can be found in [10],
in which some features of the proposed technique can be found without the control issue and filter
design; preliminary simulations of the multicarrier PWM modulation techniques for a three-phase
five-level cascaded H-bridge multilevel inverter (CHBMI) were also reported in [11,12]. In these works,
the authors addressed that the modulation techniques with sinusoidal reference should present the
lower values of the total harmonic distortion rate. A complementary study on the use of B-Spline
functions as carrier signals replacing triangular waveforms, can be found in [13,14]. This study confirms
that the traditional triangle waveforms as carrier signals are solutions that allow best performances.
Signal Power
generator Converter Grid
and filter
HMI
Control system
288
Energies 2018, 11, 3298
The block named Power Converter and filter requires a control system supervising the behavior
(harmonic reduction, filter efficiency, etc.). Generally, the control system consists of four parts:
1. Acquisition system, which provides signal conditioning and digital acquisition of electrical
measures (usually current, voltage, frequency) and other quantities (usually solar irradiation,
temperature, etc.);
2. Digital controller, required for algorithms employment (filtering, identification, control,
modulation of output signals and others);
3. Human–machine interface (HMI), suitable for setup phase as well as for monitoring functions;
4. Signal generator, allowing conversion of the digital signals to analog signals for the
power components.
Digital controller represents the core of the control system, different are the digital controller
available in the market. A first example of digital controller is the Microcontrollers or DSP
(digital signal processor), allowing the implementation of the control algorithms through a purely
software programming (with C or C++). The constructor defines the DSP hardware and it is composed
by several peripherals, such as the RAM or the ROM. However, an already designed hardware structure
reduces the flexibility in the use of the microcontroller. In fact, a complex issue is related to the time of
computing of the control algorithm, due to the fact that all the operation needed for this computing
are executed in a sequential routine, causing losses in terms of efficiency of the control system [15].
The FPGA (field programmable gate array) is another example of digital controller, composed by
a matrix of configurable logic blocks (CLBs) with completely reprogrammable connections. This fact
leads to a higher flexibility with respect to a DSP, allowing the realization of specific hardware structures
in dependence of the nature of applications. In addition, this feature allows the realization of a system
of logic operations developed in parallel, reducing the time of computing. Thus, by means of an
FPGA, high-performance control systems can be realized, even comparable with equivalent controllers
composed by analogical components, as reported in [16–18].
For instance, the main advantages provided by the adoption of an FPGA-based system for the
current control in AC machine drives is presented in [19]. In particular, the FPGA system significantly
reduces the execution time of the control algorithm, increasing, therefore, the performances of the
related system.
289
Energies 2018, 11, 3298
implement innovative fast switching modulation, with or without considering power losses [30,31].
As reference, the authors of [32] used a single-phase multilevel inverter scheme, employing three series
connected full-bridge stages and a single half-bridge inverter. The result was a reduction of harmonics,
evaluated in terms of total harmonic distortion rate, about 9.85%. Spice models help researchers
to consider coupled issues such as THD and storage elements [33]. Again, simulation allows the
tracking of the performance of a multilevel inverter in partial shaded condition of PV panels [34].
Simulation seems to be the best way to predict how reduce the THD with grid connected systems [35].
The simulation produces a 15-level output voltage, the total harmonic distortion was about 8.12%,
a very low level was reached, but similar multilevel inverters will be overpriced.
On the opposite side, higher frequency modulation presents harmonics with higher frequencies,
which requires an economic filters, but high frequency switching brings also higher losses due
circulating currents. An evaluation of harmonics content, useful to better define the output voltage
waveforms, are reported [10–12], and will be objects of deeper discussions in this paper.
High power electrical drives applications need mainly the reduction of the switching losses and
electromagnetic interferences (EMI). Losses concur to define efficiency of converter, so soft switching
modulation techniques, employing selective harmonic elimination (SHE) technique and selective
harmonic mitigation (SHM) technique, are frequently chosen. SHE method requires the choosing of a
single hth harmonic to be removed, so a set of non-linear sinusoidal formulas is solved by choosing
the switching angles. The SHM techniques, instead, mitigates simultaneously different harmonics by
correctly choosing the switching angles.
Whichever technique is employed, SHE or SHM, to resolve the group of transcendental equations
and to discover the related switching angles, different approaches can be taken into account.
Obviously, the simplest approach develops iterative methods such as Newton–Rhapson. As reference
in [36], the Newton–Rhapson iterative method is employed for the assessment of switching angles for
a seven level inverter. The total harmonic distortion of the staircase voltage output is equal to 11.8%.
The authors of [37] present an evaluation between different modulation techniques, applied
for a five-level cascaded H-bridge multilevel inverter. The employed control scheme enforces
three different pre-defined arrangements for the switching angles. By the uses of these schemes
there is an achievement of a minimum THD around 17.07% for the waveform of voltage. The work
presented in [38], employs a particularly fast optimal solution of harmonic elimination techniques,
used inverter is a five-level multilevel one, and also non-equal DC sources feed the different levels.
The solution of the problem is entrusted to a novel particle swarm optimization (PSO) algorithm,
and THD achieved a minimum value of 5.44%.
Authors of [39] proposed an optimal SHM technique for a seven-level inverter scheme.
The individual harmonic to be mitigated and the THD are subjected to satisfaction of three voltage
harmonic standards, named EN50160 [40], CIGRE JWG C4.07 [41] and IEC61000-3-6 [42].
Paper [43] proposes again the PSO technique in presence of PV sources with different voltage
levels, the non-linear transcendental equations were solved offline. THD was minimized by employing
of pre-calculated switching angles. By the dual employment of the adaptive neuro fuzzy inference
system (ANFIS) and also maximum power point tracker (MPPT) algorithm, PV DC sources were
transformed in identical DC source. The resulting THD was around 3.7%, less than the ones
recommended by IEEE-519 (5%).
Author of [44] again employed an adaptive neuro-fuzzy interference system in order to eliminate
voltage harmonics. The proposed comparison shows a best performance of ANFIS referred to neuro
fuzzy controller (NFC), in the case of studying a seventh level inverter with active filter. Again the
option of an active filter, used in order to improve the performance of the control, can be find in [45].
In [46] the method known as “voltage cancelation” is used for single-phase H-bridge inverters,
and in [47] was applied for a single-phase five-level CHBMI.
In this paper the structures used in [47] with a soft switching modulation is used with high
switching PWM in order to achieve the same or a better THD.
290
Energies 2018, 11, 3298
2. Cascaded H-Bridge Inverter for Grid Connected Applications: Modelling and Control
The purpose of this section is to provide all the useful information to realize a virtual model of
a CHBMI.
V DC,a2 V DC,a1
Sa1,1 Sa1,2
H-Bridge H-Bridge V DC,a1 C va1
module a2 module a1
Sa1,3 Sa1,4
va2 va1
V DC,b2 V DC,b1 vga
ia L Lg iga
H-Bridge H-Bridge
module b2 module b1 vgb
ib L Lg igb
n' vb2 vb1 n
V DC,c2 V DC,c1 vgc
ic L Lg igc Transformer
H-Bridge H-Bridge
module c2 module c1 Cf Cf Cf
vc2 vc1
nf
Each phase of the CHB inverter consists of two cascaded H-bridges in series connected.
Thus, the phase voltages va (t), vb (t) and vc (t), referred on the n’ point, is obtained by summing
output voltage of the series connected H-Bridges (7):
291
Energies 2018, 11, 3298
Taking into account the switching state of the power components, the instantaneous model
of the three-phase five-level CHBMI in both the AC and DC side can be totally described by the
following equations:
The model is complete with the equations to describe the LCL filter behavior and the transformer.
Thus, the equivalent circuit have to be taken in to account where rTR and LTR (rTR = 25 mΩ and
LTR = 108.23 μH) represent the short-circuit impedance reported on the low side of the transformer.
Finally, the following equations can be used for the rating the output currents i{a,b,c} of the
converter (15), grid currents ig{a,b,c} (16) and the capacitor voltages v* {a,b,c} (17), where r and rg are the
resistance of the inductance L and Lg of LCL filter.
L didta = v a − i a r − v∗a − vn f n
L didtb = vb − ib r − v∗b − vn f n (15)
L didtc = vc − ic r − v∗c − vn f n
292
Energies 2018, 11, 3298
di
L g + L TR · dtga = v∗a − i ga · r g + r TR − v ga − vnn f
di
L g + L TR · dtgb = v∗b − i gb · r g + r TR − v gb − vnn f (16)
di gc
L g + L TR · dt = v∗c − i gc · r g + r TR − v gc − vnn f
dv∗a
Cf dt = i a − i ga
dv∗
C f dtb = ib − i gb (17)
dv∗
C f dtc = ic − i gc
where vn f n is the voltage between the point nf and n’ and vnn f is the voltage between the point n and
nf that can be expressed by the Equation (18).
vn f n = 13 (v a + vb + vc ) − r (i a + ib + ic ) − L didta + didtb + didtc
di
(18)
di di
vnn f = 13 v∗a + v∗b + v∗c − r g i ga + i gb + i gc − L g dtga + dtgb + dtgc
In the case of the equilibration system, the voltage vnnf is equal to zero. In order to design the
control system, it is necessary to develop an average model of the system. Generally, the average
model takes into account the average values in a switching period Tsw . In this way, the average phase
voltages and average currents can be expressed as (19) and (20):
Tsw
v a (t) = 1
Tsw VDC · (Sa1 + Sa2 )dt
0
Tsw
vb (t) = 1
Tsw VDC · (Sb1 + Sb2 )dt (19)
0
Tsw
vc (t) = 1
Tsw VDC · (Sc1 + Sc2 )dt
0
Tsw Tsw
i DC,a1 = 1
Tsw i a · Sa1 dt i DC,a2 = 1
Tsw i a · Sa2 dt
0 0
Tsw Tsw
i DC,b1 = 1
Tsw ib · Sb1 dt i DC,b2 = 1
Tsw ib · Sb2 dt (20)
0 0
Tsw Tsw
i DC,c1 = 1
Tsw ic · Sc1 dt i DC,c2 = 1
Tsw ic · Sc2 dt
0 0
As demonstrated in [46], the equations of the average voltages and average currents in a switching
period become (21) and (22):
v a (t) = VDC · (m a1 + m a2 )
vb (t) = VDC · (mb1 + mb2 ) (21)
vc (t) = VDC · (mc1 + mc2 )
i DC,a1 = i a · m a1 i DC,a2 = i a · m a2
i DC,b1 = ib · mb1 i DC,b2 = ib · mb2 (22)
i DC,c1 = ic · mc1 i DC,c2 = ic · mc2
where mji (j = a . . . c; i = 1 or 2) is the modulation index of each H-Bridge module. Equations (21) and
(22) represent the average model of the converter in a switching period.
293
Energies 2018, 11, 3298
by IEEE 1574 and IEC 61727 at the point of common coupling (PCC), are summarized in Table 1.
Therefore, the level fixed of the total harmonic distortion (THD%) is <5%.
On the grid side, a LCL-filter to reduce high-order harmonics that can interfere with other
equipment is typically adopted [50]. A step-by-step design procedure for an LCL filter has been
proposed in [51,52]. The proposed method employs different factors as inputs such the power rating
of the converter, the chosen line frequency and obviously the switching frequency.
According to [52,53], the converter side inductance L is defined in order to bound the current
ripple produced by the converter. Grid side inductance L* g can be determined as a function of L, using
the index r (L* g = r·L). While, Capacitor value Cf can be determined as a percentage x% of the delivered
reactive power under rated conditions.
Aim of this section is to design the LCL filter parameters with the step-by-step method for each
modulation techniques taken into account. The step-by-step procedure was applied by considering a
system with a line voltage of 50 Vrms , frequency 50 Hz and rated power of 600 W (parameters of the
test bench in Laboratory of Electrical Applications-LEAP of the University of Palermo).
In Table 2 are reported the converter side inductance L values for each modulation techniques
taken into account. It should be noted that the lower values of L have been obtained with phase
disposition based modulation techniques. Moreover, also phase shifted modulation techniques based
present interesting results.
PD POD APOD PS
Sine 0.260 mH 0.882 mH 0.530 mH 0.371 mH
THI 0.222 mH 1.938 mH 0.584 mH 0.393 mH
SFO 0.260 mH 0.882 mH 0.530 mH 0.371 mH
Addition, in the design of the grid side inductance L*g has been taken into account the inductance
of the transformer, thus, can be expressed as L*g = Lg + LTR . Table 3 reports the current ripple
attenuation depending of the r and x values.
Thus, fixing different values of x and r, in particular x% less than 5% according to limit reported
in [52], have been evaluated the current ripple for each modulation techniques taken into account.
In this way, have been identified the values of r and x%, summarized in Table 3, that allow to obtain a
294
Energies 2018, 11, 3298
current ripple approximately then 10%. By using the values reported in Table 3, have been calculated
the filter parameters and are summarized in Table 4.
An interesting consideration is about the PD based modulation techniques because the converter
side inductance L and grid side inductance Lg present the lower values. Higher value of the
converter side inductance were obtained with THIPOD modulation technique. This phenomenon
is attributable at the higher number of the side band harmonics generated by POD carrier signals.
In fact, also SPOD and SFOPOD present higher values of the converter side inductance compared
others modulation techniques. Regarding the capacitor filter values Cf , it is interesting to note that
have been obtained similar values among the modulation techniques taken into account.
As stated earlier, it is necessary to evaluate the limits on the parameter values, introduced in
step-by-step method, to verify the filter effectiveness. In Table 5 are reported the limits on the LCL
parameters values for each modulation techniques.
Each LCL configuration designed allows to respect the limits introduced in step-by-step method.
In the next section, is reported the design of the control system for each modulation techniques taken
into account.
295
Energies 2018, 11, 3298
According to [54–56], the control strategy is based on the synchronous reference frame, also called dq
control. Figure 9 shows the schematic block diagram of the dq control.
ia v ga
ș v*a
abc v*b Power ib v gb
PWM LCL filter Grid
dq Converter v gc
v*c ic
V*d V*q
Id , Iq
Current ș ș
controller Vd , Vq abc abc
PLL
dq dq
I*d I*q Id Iq Vd Vq
The system needs the measurement of the current and voltage through the sensors. Figure 9
shows that the current sensors are on the converter side, since in more applications they are also
employed to protect the power converter. Moreover, the LCL filter design and the control design are
influenced by the position of the sensors [51].
Synchronous reference frame control is based on the Park’s transformation to express both grid
currents and voltages into a reference structure rotating synchronously with the grid frequency. In this
way, the dq components of the voltage and current assume continuous trend and it is possible to use
the PI regulator.
The phase-locked loop (PLL) technique [55], allows extracting the instantaneous phase angle of
the grid voltage in order to synchronize the voltage waveforms.
For the control design, the instantaneous model of the system, Equations (15) and (16), can be
simplified neglecting the filter capacitor Cf .
Using the Park’s transformation, the Equations (15) and (16) can be rewritten as (23):
did (t)
vd (t) = r T id (t) + L T dt − ω g L T iq (t) + v gd (t)
diq (t) (23)
vq (t) = r T iq (t) + L T dt + ω g L T id (t) + v gq (t)
where rT is the sum of the internal resistance of the inductors (rT = r + rg + rTR ) and the LT is the sum
of the inductance of the LCL filter and the short-circuit inductance reported on the low side of the
transformer (LT = L + Lg + LTR ).
In synchronous reference frame, it is possible to control the dq components independently thanks
the decoupling of the two-channel control. In this way, through the d component it is possible to
control the active power while through the q component it is possible to control the reactive power.
For the design of the proportional-integral (PI) regulators, the method used to tune the parameters
of the PI is the “technical optimum” criterion where both plant and PI regulator have the same time
constant in order to simplify the closed loop transfer function.
By according the PI integrator time constant TI equal to the plant time constant TI = LT /rT ,
with the aim to delete the slower plant pole and supposing a perfect pole-zero cancellation, the current
closed-loop transfer function W(s) become of the second order Equation (24).
kp
1.5L T T
W (s) = kp
(24)
s2 + 1.5T s + 1.5L T T
1
where kp is the proportional gain, TI is the integral time constant and T is the sampling period.
By the analysis of Equation (24), the proportional gain kp depends on the inductance of the
LCL filter. In this way, it is possible to evaluate the PI regulators parameters for each modulation
techniques choosing a damping coefficient equal to 0.707. In Table 6 are reported the PI regulator
parameters for each modulation techniques taken into account.
296
Energies 2018, 11, 3298
In the next section, simulation results were reported to evaluate the performance of the system
with each modulation techniques taken into account.
LCL filter requirements and parameters of regulators were determined in the precedent
sub-sections (2.2. LCL Filter Design and 2.3. Controller Design). In the follow are reported the
results obtained in simulation analysis for each modulation techniques taken into account and have
been compared the results among the modulation with the same carrier signals.
Figure 10. Phase voltage harmonic spectra centered around the switching frequency (10kHz) in percent
respect to the fundamental amplitude of (a) SPD, (b) THIPD and (c) SFOPD.
297
Energies 2018, 11, 3298
This phenomenon explains the different values of THD% and different LCL filter requirements.
Consequently, the performance in terms of the harmonic content on the current will be different.
Figures 11–13 show the transitory of the converter side currents and grid side currents from zero to the
rated current obtained with SPD, THIPD, and SFOPD, respectively. As mentioned above, are visible
little differences in the currents trend among SPD, THIPD, and SFOPD, as emphasized by red and
green zoom windows. In particular, these differences are present in terms of harmonic content around
the switching frequency and the low order harmonics.
Overall, the three-grid side current have a total harmonic distortion—THD% less then 5%
according to IEEE 1574 and IEC 61727.
(b)
(a)
(c)
Figure 11. Converter side and grid side three-phase current with SPD. (a) Transient behavior in
multiple cycles; (b) Ripple magnification for converter side current; (c) Ripple magnification for grid
side current.
(b)
(a)
(c)
Figure 12. Converter side and grid side three-phase current with THIPD. (a) Transient behavior in
multiple cycles; (b) Ripple magnification for converter side current; (c) Ripple magnification for grid
side current.
298
Energies 2018, 11, 3298
(b)
(a)
(c)
Figure 13. Converter side and grid side three-phase current with SFOPD. (a) Transient behavior in
multiple cycles; (b) Ripple magnification for converter side current; (c) Ripple magnification for grid
side current.
Figure 14 shows the low order harmonics (from third to fortieth harmonic) in grid side current Iga
obtained with SPD, THIPD, and SFOPD, respectively.
In the first all, it is interesting to note that the amplitude of the lower order harmonics are below
of the standard harmonic current limits defined by IEEE 1574 and IEC 61727 at the PCC. However, is
visible only a predominant fifth harmonic in low order spectra obtained with SPD while there are also
the eleventh and thirteenth harmonics in the low order spectra obtained with THIPD and SFOPD.
Figure 15 shows a comparison among harmonic spectra centered around the switching frequency
of 10 kHz among line voltage Vab (blue bars), converter side current Ia (red bars) and grid side current
Iga (yellow bars) obtained with SPD, THIPD, and SFOPD, respectively. The lower values of the grid
side current harmonics, less of 0.3% referred to the fundamental amplitude, demonstrate the LCL
filter effectiveness. It should be noted that in the spectra of the line voltage and currents appear only
side band harmonics thanks to the three-wired connection.
299
Energies 2018, 11, 3298
In particular, harmonic spectra obtained with SPD modulation technique presents three-pair
predominant of the side band harmonics while the harmonic spectra obtained with THIPD and SFOPD
are different. The tool used to compare the harmonic content around the switching frequency among
the SPD, THIPD, and SFOPD is the “Partial Total Harmonic Distortion” (PTHD%) defined as:
f SW +n/2
∑ Vh2
f SW −n/2
PTHD% = · 100 (25)
V1
where fSW is the switching frequency, n is the bandwidth centered around the switching frequency, h is
the harmonic order and V 1 is the fundamental amplitude.
In Table 8 are summarized the PTHD% calculated for line voltage Vab , converter side current Ia
and grid side current Iga .
Table 8. Partial Total Harmonic Distortion” (PTHD%) values obtained with SPD, THIPD, and SFOPD.
Vab Ia Iga
SPD 7.94% 3.92% 0.38%
THIPD 7.86% 4.61% 0.43%
SFOPD 8.29% 4.08% 0.38%
It is interesting to note that the SPD and SFOPD present the lower values of the PTHD% as regard
to the currents. While, the lower values of the PTHD% of the line voltage has been obtained with
THIPD modulation technique. Obviously, both the modulation technique and the LCL filter concur to
define the harmonic content.
300
Energies 2018, 11, 3298
As shown in Figure 16, the harmonic spectra are similar with a pair component predominant
respect to the others while only the SAPOD (Figure 16d) presents little differences. Respect the
modulation techniques PD or PS based, in the sub-section 2.4. LCL Filter Design the higher values of
the filter requirements were obtained with POD and APOD.
Figures 17–22 show the transitory of the converter side currents and grid side currents
from zero to the rated current obtained with SPOD, THIPOD, SFOPOD, SAPOD, THIAPOD,
and SFOAPOD respectively.
(b)
(a) (c)
Figure 17. Converter side and grid side three-phase current with SPOD. (a) Transient behavior in
multiple cycles; (b) Ripple magnification for converter side current; (c) Ripple magnification for grid
side current.
301
Energies 2018, 11, 3298
(b)
(a) (c)
Figure 18. Converter side and grid side three-phase current with THIPOD. (a) Transient behavior in
multiple cycles; (b) Ripple magnification for converter side current; (c) Ripple magnification for grid
side current.
(b)
(a) (c)
Figure 19. Converter side and grid side three-phase current with SFOPOD. (a) Transient behavior in
multiple cycles; (b) Ripple magnification for converter side current; (c) Ripple magnification for grid
side current.
(b)
(a) (c)
Figure 20. Converter side and grid side three-phase current with SAPOD. (a) Transient behavior in
multiple cycles; (b) Ripple magnification for converter side current; (c) Ripple magnification for grid
side current.
302
Energies 2018, 11, 3298
(b)
(a) (c)
Figure 21. Converter side and grid side three-phase current with THIAPOD. (a) Transient behavior in
multiple cycles; (b) Ripple magnification for converter side current; (c) Ripple magnification for grid
side current.
(b)
(a) (c)
Figure 22. Converter side and grid side three-phase current with SFOAPOD. (a) Transient behavior in
multiple cycles; (b) Ripple magnification for converter side current; (c) Ripple magnification for grid
side current.
As before, the grid currents trend presents a THD% less then 5% according to IEEE 1574 and
IEC 61727, but it is necessary to study the lower order harmonics and the ones around the switching
frequency, in order to investigate in depth the performances. Figure 23 shows the low order harmonics
(from third to fortieth harmonic) in grid side current Iga obtained with SPOD, THIPOD, SFOPOD,
SAPOD, THIAPOD, and SFOAPOD, respectively.
303
Energies 2018, 11, 3298
It should be noted that the amplitude of the lower order harmonics are below of the standard
harmonic current limits defined by IEEE 1574 and IEC 61727 at the PCC. Interesting results
were obtained with THIPOD (Figure 23b) considering that are visible only fifth and seventh
components with the lower amplitude compared to others modulation techniques POD and
APOD based. Moreover, this is the best results also compared with modulation techniques PD based.
This phenomenon is also explained by the higher values of the LCL filter parameters.
Figure 24 shows a comparison among harmonic spectra centered around the switching
frequency of 10 kHz among line voltage Vab (blue bars), converter side current Ia (red bars) and
grid side current Iga (yellow bars) obtained with SPOD, THIPOD, SFOPOD, SAPOD, THIAPOD,
and SFOAPOD, respectively.
The lower values of the grid side current harmonics, less of 0.3% referred to the fundamental
amplitude, demonstrate the LCL filter effectiveness. While, the predominant pair of the side band
harmonic that appear in all harmonics spectra explains the higher values of the LCL filter parameters
compared with modulation techniques PD or PS based. An interesting consideration is about the grid
side current, the values are very lower respect to the modulation techniques PD based.
304
Energies 2018, 11, 3298
Figure 24. Comparison of line voltage harmonic spectra Vab , converter side current Ia and grid side
current Iga centered around the switching frequency (10 kHz) in percent respect to the fundamental
amplitude for (a) SPOD, (b) THIPOD, (c) SFOPOD, (d) SAPOD, (e) THIAPOD, and (f) SFOAPOD.
In Table 9 are reported the values of the PTHD% for line voltage Vab , converter side current Ia and
grid side current Iga .
Table 9. PTHD% values obtained with SPOD, THIPOD, SFOPD, SAPOD, THIAPOD, and SFOAPOD.
Vab Ia Iga
SPOD 25.62% 3.37% 0.33%
THIPOD 29.12% 1.72% 0.18%
SFOPOD 30.60% 4.12% 0.40%
SAPOD 24.17% 5.68% 0.53%
THIAPOD 29.78% 6.16% 0.61%
SFOAPOD 30.65% 7.21% 0.77%
As expected, the PTHD% relatively of the line voltages present higher values compared with
modulation techniques PD based. While, the low values of PTHD% relatively of the currents are
similar respect to the values calculated with modulation techniques PD based.
Figure 25. Phase voltage harmonic spectra centered around four times of the switching frequency
(10 kHz) in percent respect to the fundamental amplitude of (a) SPS, (b) THIPS, and (c) SFOPS.
305
Energies 2018, 11, 3298
The harmonic spectra are similar respect to the harmonic spectra obtained with POD and APOD
but the amplitude of the predominant harmonics are lower.
Figures 26–28 show the transitory of the converter side currents and grid side currents from zero
to the rated current obtained with SPS, THIPS, and SFOPS, respectively.
(b)
(a) (c)
Figure 26. Converter side and grid side three-phase current with SPS. (a) Transient behavior in
multiple cycles; (b) Ripple magnification for converter side current; (c) Ripple magnification for grid
side current.
(b)
(a) (c)
Figure 27. Converter side and grid side three-phase current with THIPS. (a) Transient behavior in
multiple cycles; (b) Ripple magnification for converter side current; (c) Ripple magnification for grid
side current.
306
Energies 2018, 11, 3298
(b)
(a) (c)
Figure 28. Converter side and grid side three-phase current with SFOPS. (a) Transient behavior in
multiple cycles; (b) Ripple magnification for converter side current; (c) Ripple magnification for grid
side current.
As previously noted, the grid currents trend presents a THD% less then 5% according to IEEE 1574
and IEC 61727 but observing the grid currents trend is evident the presence of low order harmonics.
Figure 29 shows the low order harmonics (from third to fortieth harmonic) in grid side current Iga
obtained with SPS, THIPS, and SFOPS, respectively.
As presumed, by analyzing Figure 29, low order harmonics contents are present, in particular
the fifth, seventh are predominant respect to the others, which anyway are under the harmonics
current limits. Modulation techniques PS based have the higher values of the lower order harmonics
compared with all modulation techniques previously described. Figure 30 shows a comparison
among harmonic spectra centered around the switching frequency of 10 kHz among line voltage Vab
(blue bars), converter side current Ia (red bars) and grid side current Iga (yellow bars) obtained with
SPS, THIPS, and SFOPs, respectively.
307
Energies 2018, 11, 3298
Also for modulation techniques PS based, the grid side current harmonics are less than 0.3%
referred to the fundamental amplitude demonstrating the LCL filter effectiveness. In terms of harmonic
spectra of the line voltage, there are a pair of the predominant side band harmonics that are present
also in the current spectra. In order to compare the performance were evaluated the PTHD% where
the values are summarized in Table 10.
Table 10. PTHD% values obtained with SPS, THIPS, and SFOPS.
Vab Ia Iga
SPS 23.51% 1.80% 0.0095%
THIPS 29.84% 2.16% 0.0117%
SFOPS 30.51% 2.35% 0.0124%
As shown in Table 10, the values of the PTHD% are lower compared with other values
previously calculated. These are interesting results because on the grid side current are present
only low order harmonics that are under the current limits (IEEE 1574 and IEC 61727).
In conclusion, modulation techniques PD based allow obtaining good results in terms of the
harmonic content on the grid current with the lower values of the LCL filter parameters. In particular,
SPD represent the best solution. Interesting results have been obtained also with modulation
techniques PS based thanks to the feature that allows to shift the harmonic content respect to the
switching frequency. In fact, have been obtained the lower values of the PTHD% about the grid side
currents among all the modulation techniques taken into account. Moreover, modulation techniques
PS based allow to control the power flow from the DC sources because each level can be controlled as
a single-phase converter. This feature is important in very applications like PV systems for example.
In the next section the experimental validation to confirm the simulation results were reported.
3. Experimental Validation
The purpose of this section is to provide all the useful information to describe the employed of a
prototype CHBMI.
The first aim of the experimental validation is to validate the model of the system previously
described and to confirm the effectiveness of the LCL filter design and the control strategy. In particular,
the experimental tests have been executed with a prototype of a three-phase five-level multilevel
converter with topology structure cascaded H-bridge inverter. Moreover, also the control board FPGA
based is a prototype designed for power electronics applications. In this section were reported detailed
descriptions of the test bench, control algorithm design and the experimental results. By the simulation
308
Energies 2018, 11, 3298
analysis, reported in section “2.4 Performances Evaluation”, the experimental validation was focused
on SPD and SPS modulation techniques.
Figure 32a shows the prototype of the H-Bridge that is based on power Mosfet
(International Rectifier—model IRFB4115PbF [57]) whose technical features are reported in Table 11.
While, Figure 32b shows the FPGA-based control board where the FPGA is produced by Altera—model
Cyclone III and the features reported in [58,59].
(a) (b)
Figure 32. A photograph of the prototype (a) H-Brides and (b) field programmable gate array (FPGA)
control board.
309
Energies 2018, 11, 3298
Figure 33 shows the three-phase LCL filter especially designed and assembled with commercial
components at SDESLAB and LEAP laboratories of the University of Palermo. For the converter and
grid side inductance have been used commercial inductance of 560 μH with rated current of 4A in
parallel connected to obtain an inductance then 280 μH with rated current of 8A.
While, for the capacitor filter have been used the ceramic capacitors of 4.7 μF with rated voltage
of 100 V in parallel connected to obtain a capacitor of 9.4 μF.
310
Energies 2018, 11, 3298
v{a, b, c}
ADC Current PWM Gate
i{a, b, c} converter Control modulator signals
PLL
The block named “ADC converter” represent the algorithm to manage the acquisition of the
electrical quantities. In the prototype FPGA-Based control board is available an ADC converter with
16 channel (no simultaneously), 1 MSPS, 12 bit successive approximation ADC produced by Analog
Devices model AD7490 16. The conversion process is managed by a clock signal reference with a
frequency at 10MHz and conversion time (analog to digital signal) is equal to 2 μs. For the system
under test, three voltage (va , vb and vc ) and three current (ia , ib and ic ) are acquired; the conversion
process is subdivided in two sub-conversion process relatively for the voltages and currents with a
conversion time equal to 6 μs, respectively. In this way, the operation are executed in parallel, so when
finished the first sub-conversion process relatively to the voltages, the mathematic elaborations for PLL
with voltages samples start jointly with the second sub-conversion process relatively to the currents.
After the conversion process, the mathematic elaboration with a resolution of 32 bit Floating Point
(FP) single precision and a clock reference equal to 100 MHz starts. In Table 12 are summarized the
execution time of the main mathematic operation.
It should be noted that between two operations there is a delay time equal to 10 ns in order to
stabilize and address the digital signals.
The equivalent schematic block diagram of the PLL to describe the implementation in VHDL is
shown in Figure 35.
V*q=0 Ȧg ș
PI I
Ȧ*
Vq
sin ș
dq look up ș Overflow
cos ș table control
abc
v{a,b,c}
Figure 35. Equivalent schematic block diagram of the PLL. PI: proportional-integral; I: integral.
kpT
u(k) = k p e(k) + e ( k ) + u i ( k − 1) (26)
Ti
where k indicate the k-sample, u(k) is the output term of the PI regulator, e(k) is the error, T is the
sampling time, Ti is the time-integral and ui (k − 1) is the k − 1 integral output. In order to optimize
the execution time to evaluate the sinθ and cosθ, where θ is the instantaneous phase of the space
311
Energies 2018, 11, 3298
vector voltage, a look-up table was used. Each value of the instantaneous phase was used as an
address (from 0 to 6280) to determinate the values of the sinθ and cosθ. In the look-up table there are
only a quarter of the sine waveform with a number of the sample equal to 1570 and it is possible to
determinate the sinθ and cosθ values through a logic circuit. The block “Overflow Control” is necessary
to limit the instantaneous phase value to 2π. In this way, the instantaneous phase of the space vector
voltage θ assumes the sawtooth trend. In Table 13 are summarized the execution time of the main
block of the PLL algorithm.
Operation Time
ABC to DQ transformation (FP 32bit) 880 ns
PI regulator (FP 32 bit) 540 ns
Integral (FP 32 bit) 270 ns
Overflow control and look-up table (FP 32 bit) 450 ns
The total execution time algorithm from the end of the acquisition voltage to the instantaneous
phase θ is equal to 3 μs. Figure 36 shows the experimental PLL effectiveness through a comparison of
the grid voltage (red trend) and phase voltage of the converter (yellow trend) before carrying out the
parallel with the grid.
Figure 37 shows the execution time of the current control scheme where the total execution time
is 3.13 μs.
vgd
i*d v*d
PI
id
i{a,b,c} abc wgLT *
abc v{a,b,c}
number
conversion
dq iq dq
wgLT
i*q
PI
v*q
vgq
execution time 360 ns execution time 880 ns execution time 1070 ns execution time 830 ns
312
Energies 2018, 11, 3298
The block “PWM generator” generates the gate signals for the converter. Generally, a carrier
generator, comparator circuit and a logic circuit to generate the “dead time” compose the
“PWM generator”. Figure 38 shows the screenshot of the schematic block diagram of the PWM
modulator implemented in Quartus II environment for SPD modulation technique.
Comparator
Carriers
D Flip-flop
Figure 38. Screenshot of the schematic block diagram of the pulse width modulation (PWM) modulator
implemented in Quartus II environment for SPD modulation technique.
S
S1
D Q
clk clk S1
D Flip-flop
Figure 39. Logic circuit to generate the gate signals with dead time.
The delayed signal is obtained by using several cascaded-connected D flip-flops, whose number
is dependent on the adopted clock signal. In order to obtain 400 ns of delay, four D flip-flops have
been connected and managed with the 10 MHz clock signal. Figure 40 shows the simulation of the
“PWM Generator” carried out in ModelSim environment relatively a phase of the converter.
313
Energies 2018, 11, 3298
From the technical features of the IRFB4115PBF reported in Table 12, the minimum dead time is
equal to 100 ns, approximately. Thus, has been chosen for safe reason a dead time equal to 400 ns.
Figure 41 shows a screenshot of the experimental validation between gate signals of the same leg
in order to establish the proper operation of the digital system.
Figure 41. Experimental validation between gate signals of the same leg.
It should be noted that the dead time obtained is equal to 400 ns.
! 2
! Vrms − Vrms,1
2
THD% = " 2
· 100 (27)
Vrms,1
where Vrms is the root mean square (rms) value of the phase voltage and Vrms,1 defines the rms value
of the fundamental harmonic.
314
Energies 2018, 11, 3298
Figures 42–44 show the comparison between the simulated (blue bars) and the experimental
(yellow bars) THD% values obtained with Sinusoidal (Figure 42), THI (Figure 43) and SFO (Figure 44) as
reference signals for each modulation techniques taken into account with the designed filter discussed
in Section 2.2.
(a) (b)
100
SPOD simulation
SPOD experimental
80
60
40
20
0
0.4 0.6 0.8 1 1.2
modulation index
(c) (d)
100
SAPOD simulation
SAPOD experimental
80
60
40
20
0
0.4 0.6 0.8 1 1.2
modulation index
(e) (f)
(g) (h)
Figure 42. Comparison between the simulated (blue) and the experimental (yellow) THD% values:
(a) SPD line voltage, (b) SPD phase voltage, (c) SPOD line voltage, (d) SPOD phase voltage, (e) SAPOD
line voltage, (f) SAPOD phase voltage, (g) SPS line voltage, and (h) SPS phase voltage.
315
Energies 2018, 11, 3298
(a) (b)
(c) (d)
(e) (f)
(g) (h)
Figure 43. Comparison between the simulated (blue) and the experimental (yellow) THD% values:
(a) THIPD line voltage, (b) THIPD phase voltage, (c) THIPOD line voltage, (d) THIPOD phase voltage,
(e) THIAPOD line voltage, (f) THIAPOD phase voltage, (g) THIPS line voltage, and (h) THIPS
phase voltage.
316
Energies 2018, 11, 3298
100
SFOPD simulation
SFOPD experimental
80
60
40
20
0
0.4 0.6 0.8 1 1.2
modulation index
(a) (b)
100
SFOPOD simulation
SFOPOD experimental
80
60
40
20
0
0.4 0.6 0.8 1 1.2
modulation index
(c) (d)
(e) (f)
(g) (h)
Figure 44. Comparison between the simulated (blue) and the experimental (yellow) THD% values:
(a) SFOPD line voltage, (b) SFOPD phase voltage, (c) SFOPOD line voltage, (d) SFOPOD phase voltage,
(e) SFOAPOD line voltage, (f) SFOAPOD phase voltage, (g) SFOPS line voltage, and (h) SFOPS
phase voltage.
It should be noted that the simulated and experimental THD% presents similar values. For this
reason, it is possible to establish the effectiveness of the model implemented.
Interesting comparison among the experimental THD% values for each reference signals taken
into account, is shown in Figure 45. Modulation technique with PD as carrier signals and sinusoidal
reference SPD seems to be the best solution in terms of the harmonic content. Moreover, also the SPS is
a good solution for grid-connected applications.
317
Energies 2018, 11, 3298
(a) (b)
(c) (d)
(e) (f)
Figure 45. Comparison between the experimental THD% results: (a) Sinusoidal line voltage,
(b) Sinusoidal phase voltage, (c) THI line voltage, (d) THI phase voltage, (e) SFO line voltage,
and (f) SFO phase voltage.
In conclusion, modulation technique with PD as carrier signals and sinusoidal reference SPD
present interesting results. Moreover, also the PS carrier signal is a good solution due to high order
harmonic components respect other carrier signals.
In the next section, experimental validation of the grid-connected application is reported.
The experimental validation considers only the SPD and SPS modulation techniques.
318
Energies 2018, 11, 3298
it is possible to control the active power while through the q component it is possible to control the
reactive power. Thus, fixing q component of the current equal to zero and d component of the current
equal to rated value (6A) it is possible to inject only active power on the grid as shown in Figure 46.
Figure 46. Measured grid voltages (20 V/div) and grid currents (5 A/div) of the phase a and b obtained
with SPD at the rated power.
Figure 47 shows measured converter side current obtained with SPD at rated power while
Figure 48 shows the measured grid side current in the same conditions.
First all, the differences in terms of the harmonic content between the trend of the converter side
and grid side currents are evident. Moreover, a not perfect half-wave symmetry in the currents trend
was observed. This phenomenon determined the present of the even-harmonics in the current.
(a) (b)
Figure 47. Measured converter side currents (2 A/div) obtained with SPD at the rated power. (a) Ripple
in different cycles; (b) Magnification of ripple.
319
Energies 2018, 11, 3298
(a) (b)
Figure 48. Measured grid side currents (2 A/div) obtained with SPD at the rated power. (a) Ripple in
different cycles; (b) Magnification of ripple.
Figure 49a shows the low order harmonics spectra of the grid side current at rated power. In the
first all, it interesting to note that the amplitude of the lower order harmonics are below of the standard
harmonic current limits defined by IEEE 1574 and IEC 61727 at the PCC. Nevertheless, as stated
above are present the even-harmonics on the harmonic spectra. Interesting comparison between the
harmonic spectra centered on switching frequency of the converter side current Ia (blue bars) and grid
side current Iga (yellow bars) is shown in Figure 49b. The lower values of the harmonics of the grid
side current demonstrate the effectiveness of the LCL filter.
(a) (b)
Figure 49. Calculated (a) low order harmonics of the grid side current and (b) switching frequency
harmonics spectra of the converter side and grid side currents.
In Table 14 are summarized the calculated THD% for different values of the grid side
current injected. It should be noted that the THD% values increase when the current injected in
the grid is reduced and it is less then 5% up to In /2.
Table 14. Experimental THD% of the converter and grid side currents, obtained with SPD, for different
values of the injected current into the grid.
In /3 In /2 2In /3 In
Converter side current 12.17% 7.82% 6.46% 5.88%
Grid side current 7.97% 4.78% 4.26% 3.72%
Figure 50 shows the measured line voltage of the converter at rated power. It interesting to note
that the line voltage presents nine-level.
320
Energies 2018, 11, 3298
Figure 51 shows the measured capacitor voltage of the LCL filter at rated power. The evident low
harmonic content in the trend of the capacitor voltage demonstrate the efficacy of the LCL filter.
Figure 51. Measured capacitor voltage of the LCL filter at rated power.
As stated earlier, the second experimental tests have been carried out with SPS modulation
techniques with the same filter used for SPD modulation techniques thank to the similar values
obtained in the subsection “LCL filter Designs”.
Figure 52. Measured grid voltages (20 V/div) and grid currents (5 A/div) of the phase a and b obtained
with SPS at the rated power.
321
Energies 2018, 11, 3298
Also for this case, the phase angle between voltage and current of the same phase is equal to zero,
thus this result demonstrates the efficacy of the control strategy.
Figures 53 and 54 show the measured converter side and grid side currents, respectively.
As mentioned above, the currents trends present a not perfect half-wave symmetry and this
phenomenon determined the even harmonics.
(a) (b)
Figure 53. Measured converter side currents (2 A/div) obtained with SPS at the rated power. (a) Ripple
in different cycles; (b) Magnification of ripple.
(a) (b)
Figure 54. Measured grid side currents (2 A/div) obtained with SPS at the rated power. (a) Ripple in
different cycles; (b) Magnification of ripple.
Figure 55a shows the low order harmonics of the grid current at rated power. The amplitude of
the all low order harmonics are less of the current limits reported in Table 1. However, by comparing
the low order harmonic spectra of SPD and SPS, it can be noted that the second order harmonic is
higher in SPS modulation technique. The presence of the even harmonics also is due to absence of the
DC voltage control. Moreover, in both low order harmonic spectra of the SPD and SPS is predominant
a seventh harmonic with similar value.
In Figure 55b is shown the comparison between the harmonic spectra centered on switching
frequency of the converter side current Ia (blue bars) and grid side current Iga (yellow bars). The lower
values of the harmonics of the grid side current demonstrate the effectiveness of the LCL filter.
322
Energies 2018, 11, 3298
(a) (b)
Figure 55. Calculated (a) low order harmonics of the grid side current and (b) switching frequency
harmonics spectra of the converter side and grid side currents.
In Table 15 are summarized the calculated THD% for different values of side current injected in
the grid. The THD% values obtained with SPS are similar respect to the previously calculated with SPD.
This is an interesting result, because the modulation techniques PS based are more versatile respect
to the others multicarrier modulation techniques for grid connected applications like PV systems,
for example. The modulation techniques PS based allow to control each H-Bridge like a single-phase
inverter and it is possible to use innovative control algorithms especially designed in dependence of
the application.
Table 15. Experimental THD% of the converter and grid side currents, obtained with SPS, for different
values of the injected current into the grid.
In /3 In /2 2In /3 In
Converter side current 12.28% 8.41% 6.80% 5.64%
Grid side current 7.42% 4.45% 3.91% 3.33%
In addition, the line voltage build with the SPS modulation technique has nine level, as shown in
Figure 56.
Figure 57 shows the measured capacitor voltage of the LCL filter with an evident low harmonic
content that also in this case demonstrate the efficacy of the LCL filter.
323
Energies 2018, 11, 3298
Figure 57. Measured capacitor voltage of the LCL filter at rated power.
4. Discussion
In order to face the harmonic distortion problem, two issue can be distinctly taken into account:
the generation of harmonics and their suppression. Although the approach is not purely dichotomous,
since a lower generation corresponds to an easier suppression, here the main results of this work can
be approached with an etiological methodology.
The modulation techniques with PD as carrier signals shows a harmonic spectrum of the
phase voltage with a predominant harmonic centered on the switching frequency and side band
harmonics (Figure 10). By considering the modulation with POD and APOD as carriers, in the
spectra, the harmonic component at switching frequency does not appear but there are only side
bands (Figure 16). By considering the modulation with PS disposition, the harmonics are centered
around four times the switching frequency, are present only side bands harmonics like in modulation
techniques POD and APOD based (Figure 25).
In order to reduce the harmonics in the grid side, a filtering system is correctly designed. For the
PD based modulation techniques, the converter side inductance L and grid side inductance Lg
present the lower values (Table 4). Higher value of the converter side inductance were obtained
with THIPOD modulation technique, phenomenon attributable to the higher number of the side band
harmonics generated by POD carrier signals. Figure 14 (PD), 23 (POD and APOD) and 29 (PS) show the
performances of the filtering by considering the different modulation techniques. For each techniques,
the third harmonic of injected current is much reduced, so the comparison moves on the fifth harmonic:
PD is around 1%, POD and APOD less than 0.5%, PS around 2%. Excellent performance of THIPOD
for its very low values of fifth and also seventh harmonic, are remarkable, but the side inductance L is
eight times the value for PD ones. By analyzing Figure 29, low order harmonics contents are present,
in particular besides the fifth, seventh is predominant. Modulation techniques PS based have the higher
values of the lower order harmonics compared with all modulation techniques previously described.
In conclusion, modulation techniques PD based allow obtaining good results in terms of the
harmonic content on the grid current with the lower values of the LCL filter parameters. In particular,
SPD represent the best solution.
The previous described good results are validated in Figure 45 with the experimental test phase;
moreover, it is possible to find an experimental behavior better than the simulated one for SPD for
different modulation indexes.
Finally, the approach was validated for a grid-connected system by exploiting the three-phase
Variac to grid interface. Different current values were injected in the power grid, Tables 14 and 15
report that the THD% remained below the 4%, 3.72% for SPD and 3.33% for SPS techniques.
By considering the work of Colak et al. [64], as the number of levels in multilevel inverter increases,
the THD in the output voltage reduces, but the drawback of increasing the levels is that that the control
circuit becomes hard challenges. A comparison can be done with recent results found in literature.
Kavali and Mittal obtained by MATLAB based simulation with SIMULINK environment interesting
results for their single-phase five level CHBMI topology with sinusoidal pulse width modulation
schemes [37]. For PD the THD was reduced to 5.69%; in case of POD it was 5.75%; for APOD it was
324
Energies 2018, 11, 3298
5.73%; the THD was 7.42% in case of PS. Results obtained in the present work follow those obtained
in [37], the obtained THDs are below, and add an experimental validation to them.
5. Conclusions
As previously described, the PWM modulation techniques found large use in many industrial
applications thanks their main features as easy implementation in electronic control systems, low
computational cost and high flexibility. Moreover, for grid-connected applications the PWM
modulation techniques are the best solution due to the lower amplitude of the low-order harmonics,
reducing the filter requirements. Thus, in this work a detailed analysis taking into account
all PWM modulation techniques, the LCL filter requirements and the real time implementation
issues in FPGA-based prototype control board for a grid-connected three-phase five-level CHBMI,
was presented.
Firstly, through a simple step-by-step procedure to design LCL filter for each modulation
techniques taken into account, it was demonstrated that the lower values of the filter parameters
are obtained for modulation techniques employing sinusoidal as reference signals. These interesting
results were confirmed by the experimental validation of the THD% values. In particular, the SPD and
SPS showed the best results in terms of the THD% values. Then, the experimental tests was focused
by using the SPD and SPS modulation techniques in order to inject in the power grid different values
of current through the specially designed LCL filter. Notably, the experimental tests confirmed the
effectiveness of the LCL filter. The amplitude of the lower order harmonics are below of the standard
harmonic current limits at the point of common coupling. Nevertheless, appeared even-harmonics
on the amplitude spectra. Finally, it is possible to claim that the modulation technique SPS is the best
solution for all grid-connected applications where it is necessary to control the power flow of the DC
sources separately.
References
1. Rashid, M.H. Power Electronics Handbook, Devices, Circuits and Applications, 3rd ed.; Butherworth-Heirmann is
an imprint of Elsevier; Pearson Education Limited: New York, NY, USA, 2011.
2. Rodriguez, J.; Lai, J.-S.; Peng, F.Z. Multilevel inverters: A survey of topologies, controls, and applications.
IEEE Trans. Ind. Electron. 2002, 49, 724–738. [CrossRef]
3. Malinowski, M.; Gopakumar, K.; Rodriguez, J.; Perez, M.A. A Survey on Cascaded Multilevel Inverters.
IEEE Trans. Ind. Electron. 2010, 57, 2197–2206. [CrossRef]
4. Kouro, S.; Malinowski, M.; Gopakumar, K.; Pou, J.; Franquelo, L.G.; Wu, B.; Rodriguez, J.; Perez, M.A.;
Leon, J.I. Recent Advances and Industrial Applications of Multilevel Converters. IEEE Trans. Ind. Electron.
2010, 57, 2553–2580. [CrossRef]
5. El-Hosainy, A.; Hamed, H.A.; Azazi, H.Z.; El-Kholy, E.E. A review of multilevel inverter topologies, control
techniques and applications. In Proceedings of the 2017 Nineteenth International Middle East Power Systems
Conference (MEPCON), Cairo, Egypt, 19–21 December 2017; pp. 1265–1275.
6. McGrath, B.P.; Holmes, D.G. Multicarrier PWM strategies for multilevel inverters. IEEE Trans. Ind. Electron.
2002, 49, 858–867. [CrossRef]
7. McGrath, B.P.; Holmes, D.G. A comparison of multicarrier PWM strategies for cascaded and neutral point
clamped multilevel inverters. In Proceedings of the 2000 IEEE 31st Annual Power Electronics Specialists
Conference, Conference Proceedings (Cat. No.00CH37018), Galway, Ireland, 23–23 June 2000; Volume 2,
pp. 674–679.
325
Energies 2018, 11, 3298
326
Energies 2018, 11, 3298
28. Talon Louokdom, E.; Gavin, S.; Siemaszko, D.; Biya-Motto, F.; Essimbi Zobo, B.; Marchesoni, M.;
Carpita, M. Small-Scale Modular Multilevel Converter for Multi-Terminal DC Networks Applications:
System Control Validation. Energies 2018, 11, 1690. [CrossRef]
29. Kumar, N.; Saha, T.K.; Dey, J. Modeling, control and analysis of cascaded inverter based grid-connected
photovoltaic system. Int. J. Electr. Power Energy Syst. 2016, 78, 165–173. [CrossRef]
30. Ravi, A.; Manoharan, P.S.; Anand, J.V. Modeling and simulation of three phase multilevel inverter for grid
connected photovoltaic systems. Sol. Energy 2011, 85, 2811–2818. [CrossRef]
31. Rajkumar, M.V.; Manoharan, P.S. FPGA based multilevel cascaded inverters with SVPWM algorithm for
photovoltaic system. Sol. Energy 2013, 87, 229–245. [CrossRef]
32. Prabaharan, N.; Palanisamy, K. Analysis and integration of multilevel inverter configuration with boost
converters in a photovoltaic system. Energy Convers. Manag. 2016, 128, 327–342. [CrossRef]
33. Iero, D.; Carbone, R.; Carotenuto, R.; Felini, C.; Merenda, M.; Pangallo, G.; Della Corte, F.G. SPICE modelling
of a complete photovoltaic system including modules, Energy storage elements and a multilevel inverter.
Sol. Energy 2014, 107, 338–350. [CrossRef]
34. Javad, O.; Shayan, E.; Ali, M. Compensation of voltage sag caused by partial shading in grid-connected PV
system through the three-level SVM inverter. Sustain. Energy Technol. Assess. 2016, 18, 107–118.
35. Prabaharan, N.; Palanisamy, K. A Single Phase Grid Connected Hybrid Multilevel Inverter for Interfacing
Photo-voltaic System. Energy Procedia 2016, 103, 250–255. [CrossRef]
36. Rahim, N.A.; Ping, H.W.; Selvaraj, J. Elimination of harmonics in photovoltaic seven-level inverter with
Newton-Raphson optimization. Procedia Environ. Sci. 2013, 17, 519–528.
37. Kavali, J.; Mittal, A. Analysis of various control schemes for minimal Total Harmonic Distortion in cascaded
H-bridge multilevel inverter. J. Electr. Syst. Inf. Technol. 2016, 3, 428–441. [CrossRef]
38. Al-Othman, A.K.; Abdelhamid, T.H. Elimination of harmonics in multilevel inverters with non-equal dc
sources using PSO. In Proceedings of the 2008 13th International Power Electronics and Motion Control
Conference (EPE-PEMC 2008), Poznan, Poland, 1–3 September 2008; pp. 756–764.
39. Marzoughi, A.; Imaneini, H.; Moeini, A. An optimal selective harmonic mitigation technique for high
power converters. Int. J. Electr. Power Energy Syst. 2013, 49, 34–39. [CrossRef]
40. Voltage Characteristics of Electricity Supplied by Public Electricity Networks. Available online: http://fs.
gongkong.com/files/technicalData/201110/2011100922385600001.pdf (accessed on 15 January 2018).
41. Personen, M.A. Harmonics characteristic parameters methods of study estimates of existing values in
the network. Electra 1981, 77, 35–54.
42. Electromagnetic Compatibility (EMC)–Part 3-7: LIMITS–Assessment of Emission Limits for the Connection
of Fluctuating Installations to MV, HV and EHV Power Systems. Available online: https://ieeexplore.ieee.
org/document/6232421/ (accessed on 15 January 2018).
43. Letha, S.S.; Thakur, T.; Kumar, J. Harmonic elimination of a photo-voltaic based cascaded H-bridge multilevel
inverter using PSO (particle swarm optimization) for induction motor drive. Energy 2016, 107, 335–346.
[CrossRef]
44. Rao, G.N.; Raju, P.S.; Sekhar, K.C. Harmonic elimination of cascaded H-bridge multilevel inverter based
active power filter controlled by intelligent techniques. Int. J. Electr. Power Energy Syst. 2014, 61, 56–63.
45. Panda, A.K.; Patnaik, S.S. Analysis of cascaded multilevel inverters for active harmonic filtering in
distribution networks. Int. J. Electr. Power Energy Syst. 2015, 66, 216–226. [CrossRef]
46. Mohan, N.; Undeland, T.M.; Robbins, W.P. Power Electronics–Converter, Applications and Design, 3rd ed.;
John Wiley & Sons, Inc.: New York, NY, USA, 1989.
47. Miceli, R.; Schettino, G.; Viola, F. A Novel Computational Approach for Harmonic Mitigation in PV Systems
with Single-Phase Five-Level CHBMI. Energies 2018, 11, 2100. [CrossRef]
48. IEEE. IEEE Application Guide for IEEE Std 1547, IEEE Standard for Interconnecting Distributed Resources with
Electric Power Systems IEEE Standard 1547.2-2008; IEEE: Biloxi, MI, USA, 2009.
49. Crăciun, B.I.; Kerekes, T.; Séra, D.; Teodorescu, R. Overview of recent Grid Codes for PV power integration.
In Proceedings of the 2012 13th International Conference on Optimization of Electrical and Electronic
Equipment (OPTIM), Brasov, Romania, 24–26 May 2012; pp. 959–965.
50. Beres, R.N.; Wang, X.; Liserre, M.; Blaabjerg, F.; Bak, C.L. A Review of Passive Power Filters for Three-Phase
Grid-Connected Voltage-Source Converters. IEEE J. Emerg. Sel. Top. Power Electron. 2016, 4, 54–69. [CrossRef]
327
Energies 2018, 11, 3298
51. Liserre, M.; Blaabjerg, F.; Dell’Aquila, A. Step-by-step design procedure for a grid-connected three-phase
PWM Voltage Source Converter. Int. J. Electron. 2004, 91, 445–460. [CrossRef]
52. Liserre, M.; Blaabjerg, F.; Hansen, S. Design and control of an LCL-filter-based three-phase active rectifier.
IEEE Trans. Ind. Appl. 2005, 41, 1281–1291. [CrossRef]
53. Bojrup, M. Advanced Control of Active Filters in a Battery Charger Application. Ph.D. Thesis, Lund University
of Technology, Lund, Sweden, 1999.
54. Teodorescu, R.; Liserre, M.; Rodriguez, P. Grid Converters for Photovoltaic and Wind Power System; John Wiley
& Sons, Ltd.: New York, NY, USA, 2011; ISBN 978-0-470-05751-3.
55. Blaabjerg, F.; Teodorescu, R.; Liserre, M.; Timbus, A.V. Overview of Control and Grid Synchronization for
Distributed Power Generation Systems. IEEE Trans. Ind. Electron. 2006, 53, 1398–1409. [CrossRef]
56. Timbus, A.; Liserre, M.; Teodorescu, R.; Blaabjerg, F. Synchronization methods for three phase distributed
power generation systems—An overview and evaluation. In Proceedings of the 2005 IEEE 36th Power
Electronics Specialists Conference, Recife, Brazil, 16 June 2005; pp. 2474–2481.
57. International Rectifier, “Data Sheet IRFB4115PbF”. Available online: www.irf.com (accessed on 15 January 2018).
58. ALTERA. Cyclone III Device Handbook—Volume 1; ALTERA: San Jose, CA, USA, December 2011;
Available online: http://www.altera.com (accessed on 15 January 2018).
59. ALTERA. Cyclone III Device Handbook—Volume 2; ALTERA: San Jose, CA, USA, July 2012; Available online:
http://www.altera.com (accessed on 15 January 2018).
60. ALTERA. Quartus II Handbook Version 13.1—Volume 1: Design and Synthesis; ALTERA: San Jose, CA, USA,
November 2013; Available online: http://www.altera.com (accessed on 15 January 2018).
61. ALTERA. Quartus II Handbook Version 13.1—Volume 2: Design Implementation and Optimization; ALTERA:
San Jose, CA, USA, November 2013; Available online: http://www.altera.com (accessed on 15 January 2018).
62. Zwoliński, M. Digital System Design with VHDL, 2nd ed.; Pearson-Prentice Hall: Upper Saddle River, NJ, USA, 2004.
63. Dordevic, O.; Jones, M.; Levi, E. Analytical Formulas for Phase Voltage RMS Squared and THD in PWM
Multiphase Systems. IEEE Trans. Power Electron. 2015, 30, 1645–1656. [CrossRef]
64. Colak, I.; Kabalci, E.; Bayindir, R. Review of multilevel voltage source inverter topologies and control schemes.
Energy Convers. Manag. 2011, 52, 1114–1128. [CrossRef]
© 2018 by the author. Licensee MDPI, Basel, Switzerland. This article is an open access
article distributed under the terms and conditions of the Creative Commons Attribution
(CC BY) license (http://creativecommons.org/licenses/by/4.0/).
328
energies
Article
Fault Detection and Location of IGBT Short-Circuit
Failure in Modular Multilevel Converters
Bin Jiang *, Yanfeng Gong and Yan Li
Department of Electrical and Electronic Engineering, North China Electric Power University,
Beijing 102206, China; [email protected] (Y.G.); [email protected] (Y.L.)
* Correspondence: [email protected]; Tel.: +86-10-6177-1571
Abstract: A single fault detection and location for Modular Multilevel Converter (MMC) is of great
significance, as numbers of sub-modules (SMs) in MMC are connected in series. In this paper, a novel
fault detection and location method is proposed for MMC in terms of the Insulated Gate Bipolar
Translator (IGBT) short-circuit failure in SM. The characteristics of IGBT short-circuit failures are
analyzed, based on which a Differential Comparison Low-Voltage Detection Method (DCLVDM) is
proposed to detect the short-circuit fault. Lastly, the faulty IGBT is located based on the capacitor
voltage of the faulty SM by Continuous Wavelet Transform (CWT). Simulations have been done in
the simulation software PSCAD/EMTDC and the results confirm the validity and reliability of the
proposed method.
Keywords: modular multilevel converter; IGBT short-circuit; fault detection; fault location;
Differential Comparison Low-Voltage Detection Method (DCLVDM); Continuous Wavelet Transform
1. Introduction
Modular multilevel converters (MMCs) have attracted extensive attention and research in
high-voltage and high-power applications. MMCs are composed of numbers of SMs connected
in series and each SM is built up with two Insulated Gate Bipolar Translators (IGBTs), anti-paralleled
diodes and a capacitor. The modular structure provides excellent features such as high output voltage
quality, low harmonic distortion, low power loss, ease of construction and assembly, etc. MMC has
been proved to be a valid and reliable topology for power transmission and it can be applied in
many situations, i.e., interconnection with AC gird, the accessing of clean energy, the construction
of DC distribution network and power supply to isolated passive loads. So far, there have been
several MMC-based multi-terminal High Voltage Direct Current (MMC-MTDC) projects in operation
or under construction, i.e., Tres Amigas superconductor transmission project in North American,
Nan’ao MMC-MTDC and Zhoushan MMC-MTDC project in China, South-West Scheme MMC-MTDC
project in Norway- Sweden, etc. [1–8].
A complete fault-tolerant strategy mainly includes fault detection, location, isolation and
reconfiguration. Fault detection, as the first step in fault tolerance, should be conducted as fast
as possible. A quick, reliable and precise fault detection method can gain time for the following steps
which can prevent further failure and maintain steady operation [9–11]. The power semiconductor
switch is one of most failure-prone components in a converter [12,13]. Considering that there are
usually a large number of IGBTs in MMC, IGBT failures are more likely to take place. IGBT failures
may result the converter operating abnormally, thus causing damage to other devices and might even
threaten the security and reliability of power systems. Therefore, quick fault detection and isolation is
vital and significant to MMCs.
For IGBT open-circuit fault detection methods, there has been extensive research. Reference [14]
proposed a fault detection method by comparing the measured arm current and the expected current
calculated by gate signals, capacitor voltage and phase voltage. The fault was identified if the measured
current did not change as it was calculated. Reference [15] changed the voltage measurement point to
the cell output terminal for control purposes to avoid extra sensors, and detected the fault based on the
unconformity between the output voltage and the switching signals. However, this method required
a delay unit and a memory unit in every SM, which led to high cost and complexity. The authors
of [9,16] proposed a fault detection method based on a Sliding Mode Observer (SMO) for MMC.
Fault occurrence is verified by comparing the observed and the measured states based on a switching
model of every SM, then the SMO equations are modified to detect the faulty SM. Reference [17]
proposed a fault diagnosis and tolerant control method and the fault diagnosis method detected the
fault by a state observer and the knowledge of fault behaviors. In [18], a Kalman Filter (KF) was
employed to detect the fault through comparing the measured state value and the estimated state
value by KF and the faulty SM was located based on the voltage comparison between the faulty SM
and the normal SMs. Reference [16–18] detected the fault by the changes of the circulating current,
but the circulating current could also be influenced by other fault types, which may cause misjudgment.
Moreover, SMO and KF require complex algorithm, huge computation and complex parameter setting.
IGBT short-circuit fault should be detected as fast as possible to protect the IGBT from destruction
and to avoid another potential shoot-through fault [19,20]. Reference [21] proposed a fault detection
method in multilevel converter STATCOMs based on the output DC link voltage of each phase but
the method did not respond rapidly. Reference [22] proposed a quick fault identification method in
cascaded H-bridge multilevel converters through the comparison between the output voltage and
the reference voltage of each phase. However, this method heavily relies on the switching model
of each phase. Reference [23] proposed a short-circuit fault detection method in one sub-module of
cascaded H-bridge with dc link voltage but it neglected that voltage error could be generated not
merely by short-circuit fault. Reference [24] proposed a short-circuit detection method through pattern
recognition of IGBT gate voltage. Reference [25] proposed a self-diagnosis function for power MOSFETs
and IGBTs based on monitoring of the gate charge and discharge current. However, a short-circuit
fault in IGBT is usually detected by additional sensors or detection circuit such as those in [24,25].
The additional sensors and circuits add not only extra cost but also extra complexity to the systems.
Comparisons are made in Table 1 to make the methods more straightforward.
The contributions of the paper are: (1) Differential Comparison Low-Voltage Detection Method
(DCLVDM) is proposed for fault detection in terms of IGBT short-circuit. The DCLVDM is composed
of two parts—the low-voltage part and the differential comparison part. (2) Continuous Wavelet
Transform (CWT) is applied to locate the faulty IGBT based on the singularity of the capacitor voltage.
The fault detection and location method proposed in this paper requires no additional measuring
device and the algorithm is easy to realize. The simulation results also confirm the effectiveness and
reliability of the proposed method.
330
Energies 2018, 11, 1492
where g1 and g2 are the gate signals for switches. When S is 1, the SM is “ON” and T1 is conducted
and T2 is blocked. When S is 0, the SM is “OFF” and T1 is blocked and T2 is conducted. In normal
operation, to maintain the required DC voltage, a Capacitor Voltage Balancing Method (CVBM) is
applied in MMC-HVDC system [26,27]. The CVBM, SMs with higher voltages discharging (iarm < 0)
in priority and SMs with lower voltages charging (iarm > 0) in priority, determines which SMs are
ON/OFF, that is the value of S.
2.2.1. T1 Short-Circuit
With iarm > 0 and S = 1, T1 short-circuit will have no impact on capacitor charging process. When S
is 0 and T2 is conducted, T1 short-circuit will result in the capacitor’s short-circuit via T1 and T2 and
the capacitor discharges rapidly. The current path is shown in Figure 2. Similarly, with iarm < 0 and
S = 1, T1 short-circuit will have no influence on capacitor discharging process. Only when S is 0, T1
short-circuit will result in the capacitor short-circuit. The current path is shown in Figure 3.
331
Energies 2018, 11, 1492
(a) (b)
Figure 2. Current path when T1 is short-circuit with iarm > 0. (a) S = 1. (b) S = 0.
(a) (b)
Figure 3. Current path when T1 is short-circuit with iarm < 0: (a) S = 1; (b) S = 0.
2.2.2. T2 Short-Circuit
With iarm > 0 and S = 0, T2 short-circuit will have no impact on capacitor charging process. When S
is 1, T2 short-circuit will cause the capacitor’s short-circuit via T1 and T2 . As a result, the capacitor
switches from normal charging state to fault discharging state. Similarly, with iarm < 0 and S = 1, T2
short-circuit will result in the capacitor switching from normal discharging state to fault discharging
state. The current path is shown in Figures 4 and 5.
332
Energies 2018, 11, 1492
Based on the analysis above, state of the capacitor under different IGBTs short-circuit faults can
be obtained as shown in Table 2. It can be concluded that an IGBT short-circuit will result in the
capacitor’s short-circuit once the other IGBT is “ON” in the same SM. Because of the small value of
the time constant, the capacitor discharges rapidly. The capacitor voltage decreases and the capacitor
current increases rapidly at the same time. The capacitor voltage and current saltation are the most
apparent characteristics when short-circuit occurs, which can be applied to short-circuit detection
method directly.
333
Energies 2018, 11, 1492
The equivalent discharge circuit is a first-order RC circuit. Therefore, the circuit equations can be
deduced as Equations (2) and (3)
duc
ic = −C0 (2)
dt
duc
uc +RC0 =0 (3)
dt
With The initial state uc (0) = U0 , so uc and its derivation can be deduced as Equations (4) and (5)
− RCt
uc (t) = U0 e 0 (t ≥ 0) (4)
duc (t) U − t uc ( t )
= − 0 e RC0 = − (t ≥ 0) (5)
dt RC0 RC0
|uc (t)| ≤ α is the low-voltage part. α is the threshold value accordingly and is defined as
Equation (7) where Kα is reliability coefficient and uce is the rated value of uc under steady state.
|duact (t) − ducal (t)| ≤ ε is the differential comparison part. ε is the threshold value accordingly.
duact and ducal are the actual value and calculation value of change rate of uc , respectively, and they
are formulated as Equations (8) and (9). Ts is the sample period.
α = Kα uce (7)
uc ( t )
duact (t) = − (8)
RC0
u c ( t ) − u c ( t − Ts )
ducal (t) = (9)
Ts
The criteria of DCLVDM consists of two parts: the low-voltage part and the differential comparison
part. In the low-voltage part, a tentative conclusion that a short-circuit fault occurs can be reached
if the capacitor voltage declines to the threshold value. However, IGBT short-circuit is not the only
fault type which can cause capacitor voltage to decline, so differential comparison is introduced to
confirm the fault. In differential comparison part, the calculation of duact is based on the short-circuit
characteristics as Equation (5), hence, the error between duact and ducal under fault condition can be
much smaller than that under steady state, which can be used to distinguish the fault. Only if Equation
(6) is proved to be true and it lasts for a certain period T0 , the IGBT short-circuit fault can be confirmed
in a SM. The proposed DCLVDM requires no extra voltage measurement as the capacitor voltage is
continuously measured for MMC control purpose.
Stage 2: Faulty IGBT Location Stage
As is indicated in Table 2, to locate the specific faulty IGBT, the value of Function S should be
confirmed when the capacitor discharges. If there is S = 1(S = 0) at the time when the capacitor voltage
334
Energies 2018, 11, 1492
decreases, then T2 (T1 ) is proved to be faulty. Hence the key to locate the faulty IGBT is to locate the
time spot when the capacitor voltage begins to decrease, that is, the singularity of uc .
Continuous Wavelet Transform(CWT) is an effective time-frequency signal processing tool
as it decomposes a signal in multiple scales or resolutions and retains both time and frequency
domain information in the transform coefficients, which turns out to be useful in fault detection and
location [28]. The CWT of a function f(t) with respect to a mother wavelet ψ(t) is defined as Equations
(10) and (11) +∞
∗
W(a, b) = f(t)ψa,b (t)dt (10)
−∞
1 t−b
ψa,b (t) = √ ψ( ) (11)
a a
Here, a and b are the scale and translation factors, respectively. ‘*’ indicates a complex conjugate.
W(a,b) is the Wavelet Transform Coefficient (WTC) of f(t).
In time domain, the modulus maxima of the WTC represent the singularity of a signal and
the degree of signal saltation can be characterized by the amplitude of the modulus maxima.
For time-frequency analysis, a smoother continuous wavelet in time-domain is preferred as it brings
better localization characteristics. In this paper, the second-order Gauss wavelet is chosen as the
mother wavelet, which has excellent performance in the singularity detection [29].
To make the short-circuit fault detection and location method easier to understand, the flowchart
of the method is displayed in Figure 7.
335
Energies 2018, 11, 1492
4. Case Studies
In this section, to evaluate the effectiveness of the proposed fault detection and location method,
a two-terminal MMC-HVDC system is constructed in the professional software PSCAD/EMTDC.
The MMC circuit parameters are given in the Appendix A. Two cases are conducted:
Case 1: short-circuit fault of T2 occurs in a SM at t = 0.02100 s.
Case 2: short-circuit fault of T1 occurs in a SM at t = 0.03500 s.
(a) (b)
Figure 8. Performance of MMC under faulty operation: (a) Case 1; (b) Case 2.
(a) (b)
Figure 9. Performance of the proposed DCLVDM under faulty condition: (a) Case 1; (b) Case 2.
336
Energies 2018, 11, 1492
For Case 1, the short-circuit fault is detected 1.36 ms later after the fault occurs. The detection
time is 1.26 ms for Case 2. The error between duact and ducal in steady state is much larger than that of
faulty state, which is very useful in fault detection.
To prove the validity of the proposed DCLVDM, numerous simulations are carried out. The values
of Kα , ε, T0 remain the same as mentioned above. The simulation performance is similar to Figure 9.
Because of space constraints, the simulation performance is not displayed. The proposed DCLVDM
combined with the proper value of related parameters can detect the short-circuit fault accurately.
For reliability coefficient Kα , a larger value will improve the sensitivity of the low-voltage part to
voltage decline, which can shorten the detection time. However, too large a value will reduce the
reliability because potential disturbance or noise, etc. which may cause minor voltage decline, can be
mistaken for short-circuit fault. For the threshold, ε, the value of ε should be set between the minimum
of the differential comparison under steady state and the maximum under faulty state combined with
a margin. In this paper, the range of ε is about 0.35–1.48 according to the simulations. Therefore,
setting ε as 0.7 is sufficient and reasonable to detect the fault. As for T0 , a larger value will improve
the reliability of the fault detection process but lengthen the detection time. Because the IGBTs are
of the same model in the same MMC converter and each SM has the same operation characteristics,
the proposed DCLVDM and the parameter value setting are universally effective, which has been
validated by numerous simulations. Actually, there is no a specification standard for the parameters
setting with SM short-circuit, the parameters setting should take into consideration the sensitivity,
speed, and reliability of the detection process comprehensively.
2
ψ(t) = √ π−1/4 (t 2 − 1)e−t /2
2
(12)
3
Figure 10 shows the performance of the Gauss wavelet under various scales on the capacitor
voltage. It is noticed that the Gauss wavelet under scale 1 to 8 produces the WTC modulus maxima
exactly at the voltage singularity. However, a location deviation is produced under scale 12, 16, and 20.
So scale 1 to 8 is sufficient to detect the singularity under this simulation condition.
(a) (b)
Figure 10. Wavelet Transform Coefficient under various scales: (a) Case 1; (b) Case 2.
However, noise may occur in practical operation. To investigate the influence of noise on the
accuracy of the estimated singularity point, 40-db white Gaussian noise is added to the voltage
signal [30,31]. As the two cases have similar characteristics, only Case 2 is conducted as an example.
The simulation result is shown in Figure 11.
337
Energies 2018, 11, 1492
(a) (b)
Figure 11. Fault location result with 40-db white Gaussian noise for Case 2: (a) Contaminated capacitor
voltage; (b) Wavelet Transform Coefficients under various scales.
In Figure 11, firstly, a location deviation is still produced under scale 12, 16, and 20. Secondly,
the fault singularity is hard to locate under scale 1 and 2 as the noise produces many more singularities
in the process. Lastly, scale 3 to 8 may be chosen to locate the voltage singularity because the amplitude
of the modulus maxima produced by the fault is much higher than that produced by the noise.
Therefore, to locate the voltage singularity, the value of the scale cannot be too high or too low. In this
paper, scale 4 is chosen to conduct the fault location as is shown in Figure 12.
(a) (b)
Figure 12. Faulty IGBT location under scale 4: (a) Case 1; (b) Case 2.
Figure 12 shows the detailed Wavelet Transform Coefficient (WTC) of SM voltages under scale 4
with or without noise, as well as their Function S. The singularity of the capacitor voltage caused by
the fault is accurately located by the WTC modulus maxima. In Figure 12a, the singularity is located at
t = 0.02100 s, meanwhile, the value of S is 1, So T2 is proved to be faulty. Similarly, T1 can be proved to
be faulty according to Figure 12b at t = 0.03500 s. The proposed faulty IGBT location method based on
CWT can accurately locate the singularity of the voltage capacitor caused by the fault, thus locating
the faulty IGBT efficiently and precisely.
338
Energies 2018, 11, 1492
composed of a series of SMs and each SM contains two IGBTs, thus, For an N+1 level half-bridge MMC
system shown in Figure 1, at least 12N IGBTs are configured. Therefore, if the hardware detection
method is adopted, for a 501-level MMC, 6000 detection circuits have to be configured besides more
sensors. It absolutely adds complexity and huge cost to the MMC system. The proposed fault detection
and location method in this paper is algorithm-based. The method detects the fault only by the
capacitor voltage and the switch function, requiring no detection circuit or additional sensors as the
capacitor voltage and switch function are originally measured for MMC control purpose. Therefore,
hardware-based detection method and the algorithm-based method proposed in this paper have merits
and demerits respectively, especially for IGBT of MMC, but they both provide valuable reference for
MMC protection system construction in the future work.
5. Conclusions
In this paper, a novel fault detection and location method is proposed for IGBT short-circuit
fault in MMC based on the SM capacitor voltage. The fault detection is carried out based on the
proposed Differential Comparison Low-Voltage Detection Method (DCLVDM). No additional sensors
are required, and a simple arithmetic operation is sufficient to detect the faulty SM. The fault location
is fulfilled by the Continuous Wavelet Transform (CWT) based on the capacitor voltage of the faulty
SM. The proposed method not only detects the faulty SM rapidly, but it can also locate the specific
faulty IGBT precisely. Simulation studies conducted in PSCAD/EMTDC prove that the proposed
fault detection and location method in this paper is effective. In respect of practical application,
this method requires accurate voltage measurement and fast sampling frequency, both of which bring
more challenges to the sensors and the calculation equipment. Both reliability and rapidity must be
taken into consideration when setting the corresponding threshold values of DCLVDM. In the future,
the authors will conduct deep research on the influence exerted by different disturbances and other
fault location methods besides wavelet and aim to make the fault detection and location of IGBT
short-circuit failure in MMC more universal, reliable and feasible.
Author Contributions: B.J. defined the problem, proposed the fault detection method and conducted the
simulation. Y.G. developed the fault location method. Y.L. gathered the necessary data. B.J. and Y.G. contributed
in the paper writing. B.J. and Y.L. handled the paper revisions.
Acknowledgments: This research was funded by “the Fundamental Research Funds for the Central Universities
2017XS015”.
Conflicts of Interest: The authors declare no conflict of interest.
Appendix A
Quantity Value
DC nominal voltage (Udc ) ±20 kV
Number of SMs per arm (N) 20
Power transmission (P) 20 MW
Arm inductor (L0 ) 15 mH
SM capacitance (C0 ) 6 mF
AC line voltage (Vac) 10 kV
Loss resistance (R0 ) 0.1 Ω
SM capacitor voltage 2 kV
equivalent on-resistance (R1 , R2 ) 0.01 Ω
References
1. Debnath, S.; Qin, J.; Bahrani, B.; Saeedifard, M.; Barbosa, P. Operation, Control, and Applications of the
Modular Multilevel Converter: A Review. IEEE Trans. Power Electron. 2015, 30, 37–53. [CrossRef]
339
Energies 2018, 11, 1492
2. Perez, M.A.; Bernet, S.; Rodriguez, J.; Kouro, S.; Lizana, R. Circuit Topologies, Modeling, Control Schemes,
and Applications of Modular Multilevel Converters. IEEE Trans. Power Electron. 2015, 30, 4–17. [CrossRef]
3. Nami, A.; Liang, J.; Dijkhuizen, F.; Demetriades, G.D. Modular Multilevel Converters for HVDC Applications:
Review on Converter Cells and Functionalities. IEEE Trans. Power Electron. 2015, 30, 18–36. [CrossRef]
4. Harnefors, L.; Antonopoulos, A.; Norrga, S.; Angquist, L.; Nee, H.P. Dynamic Analysis of Modular Multilevel
Converters. IEEE Trans. Ind. Electron. 2013, 60, 2526–2537. [CrossRef]
5. Gebreel, A.A.; Xu, L. Power quality and total harmonic distortion response for MMC with increasing arm
inductance based on closed loop–needless PID controller. Electr. Power Syst. Res. 2016, 133, 281–291.
[CrossRef]
6. Rohner, S.; Bernet, S.; Hiller, M.; Sommer, R. Modulation, Losses, and Semiconductor Requirements of
Modular Multilevel Converters. IEEE Trans. Ind. Electron. 2010, 57, 2633–2642. [CrossRef]
7. Wu, J.; Wang, Z.X.; Xu, L.; Wang, G.Q. Key technologies of VSC–HVDC and its application on offshore wind
farm in China. Renew. Sustain. Energy Rev. 2014, 36, 247–255. [CrossRef]
8. Jiang, B.; Wang, Z. The key technologies of VSC–MTDC and its application in China. Renew. Sustain.
Energy Rev. 2016, 62, 297–304.
9. Shao, S.; Watson, A.J.; Clare, J.C.; Wheeler, P.W. Robustness Analysis and Experimental Validation of a Fault
Detection and Isolation Method for the Modular Multilevel Converter. IEEE Trans. Power Electron. 2016,
31, 3794–3805. [CrossRef]
10. Sujil, A.; Choudhary, S.; Verma, J.; Kumar, R. Agent based intelligent fault detection, isolation and restoration
in smart power system. In Proceedings of the 2016 IEEE Students’ Conference on Electrical, Electronics and
Computer Science (SCEECS), Bhopal, India, 5–6 March 2016; pp. 1–6.
11. Hwang, I.; Kim, S.; Kim, Y.; Seah, C.E. A Survey of Fault Detection, Isolation, and Reconfiguration Methods.
IEEE Trans. Control Syst. Technol. 2010, 18, 636–653. [CrossRef]
12. Lu, B.; Sharma, S.K. A Literature Review of IGBT Fault Diagnostic and Protection Methods for Power
Inverters. IEEE Trans. Ind. Appl. 2009, 45, 1770–1777.
13. Yang, S.; Bryant, A.; Mawby, P.; Xiang, D.; Ran, L.; Tavner, P. An Industry–Based Survey of Reliability in
Power Electronic Converters. IEEE Trans. Ind. Appl. 2011, 47, 1441–1451. [CrossRef]
14. Salimian, H.; Iman–Eini, H.; Farhangi, S. Open–circuit fault detection and location in Modular Multilevel
Converter. In Proceedings of the 6th Power Electronics, Drive Systems & Technologies Conference
(PEDSTC2015), Tehran, Iran, 3–4 February 2015; pp. 383–388.
15. Haghnazari, S.; Khodabandeh, M.; Zolghadri, M.R. Fast fault detection method for modular multilevel
converter semiconductor power switches. IET Power Electron. 2016, 9, 165–174. [CrossRef]
16. Shao, S.; Wheeler, P.W.; Clare, J.C.; Watson, A.J. Fault Detection for Modular Multilevel Converters Based on
Sliding Mode Observer. IEEE Trans. Power Electron. 2013, 28, 4867–4872. [CrossRef]
17. Li, B.; Shi, S.; Wang, B.; Wang, G.; Wang, W.; Xu, D. Fault Diagnosis and Tolerant Control of Single IGBT
Open–Circuit Failure in Modular Multilevel Converters. IEEE Trans. Power Electron. 2016, 31, 3165–3176.
[CrossRef]
18. Deng, F.; Chen, Z.; Khan, M.R.; Zhu, R. Fault Detection and Location Method for Modular Multilevel
Converters. IEEE Trans. Power Electron. 2015, 30, 2721–2732. [CrossRef]
19. Chokhawala, R.S.; Catt, J.; Kiraly, L. A discussion on IGBT short-circuit behavior and fault protection
schemes. IEEE Trans. Ind. Appl. 1995, 31, 256–263. [CrossRef]
20. Barnes, M.J.; Blackmore, E.; Wait, G.D.; Lemire-Elmore, J.; Rablah, B.; Leyh, G.; Nguyen, M.N.; Pappas, C.
Analysis of High–Power IGBT Short Circuit Failures. IEEE Trans. Plasma Sci. 2005, 33, 1252–1261. [CrossRef]
21. Yazdani, A.; Sepahvand, H.; Crow, M.L.; Ferdowsi, M. Fault Detection and Mitigation in Multilevel Converter
STATCOMs. IEEE Trans. Ind. Electron. 2011, 58, 1307–1315. [CrossRef]
22. Brando, G.; Dannier, A.; del Pizzo, A.; Rizzo, R. Quick identification technique of fault conditions in cascaded
H–Bridge multilevel converters. In Proceedings of the 2007 International Aegean Conference on Electrical
Machines and Power Electronics, Bodrum, Turkey, 10–12 September 2007; pp. 491–497.
23. Shahbazi, M.; Zolghadri, M.R.; Poure, P.; Saadate, S. Fast short circuit power switch fault detection in
cascaded H–bridge multilevel converter. In Proceedings of the 2013 IEEE Power & Energy Society General
Meeting, Vancouver, BC, Canada, 21–25 July 2013; pp. 1–5.
340
Energies 2018, 11, 1492
24. Lee, J.B.; Hyun, D.S. Gate Voltage Pattern Analyze for Short-circuit Protection in IGBT Inverters.
In Proceedings of the 2007 IEEE Power Electronics Specialists Conference, Orlando, FL, USA, 17–21 June 2007;
pp. 1913–1917.
25. Lihua, C.; Peng, F.Z.; Cao, D. A smart gate drive with self–diagnosis for power MOSFETs and IGBTs.
In Proceedings of the 2008 Twenty–Third Annual IEEE Applied Power Electronics Conference and Exposition,
Austin, TX, USA, 24–28 February 2008; pp. 1602–1607.
26. Yinglin, X.; Zheng, X. On the Bipolar MMC–HVDC Topology Suitable for Bulk Power Overhead Line
Transmission: Configuration, Control, and DC Fault Analysis. IEEE Trans. Power Deliv. 2014, 29, 2420–2429.
27. Wang, S.S.; Zhou, X.X.; Tang, G.F.; He, Z.; Teng, L.; Bao, H.L. Analysis of submodule overcurrent caused by
dc pole–to–pole fault in modular multilevel converter HVDC system. Proc. CSEE 2011, 31, 1–7. (In Chinese)
28. Silva, M.D.; Coury, D.V.; Oleskovicz, M.; Segatto, E.C. Combined solution for fault location in three–terminal
lines based on wavelet transforms. IET Gener. Trans. Dis. 2010, 4, 94–103. [CrossRef]
29. Lin, S.; He, Z.Y.; Li, X.P.; Qian, Q.Q. Travelling wave time–frequency characteristic–based fault location
method for transmission lines. IET Gener. Trans. Dis. 2012, 6, 764–772. [CrossRef]
30. Azizi, S.; Sanaye–Pasand, M.; Abedini, M.; Hasani, A. A Traveling–Wave–Based Methodology for Wide–Area
Fault Location in Multi–terminal DC Systems. IEEE Trans. Power Deliv. 2014, 29, 2552–2560. [CrossRef]
31. Liu, X.; Osman, A.H.; Malik, O.P. Hybrid Traveling Wave/Boundary Protection for Monopolar HVDC Line.
IEEE Trans. Power Deliv. 2009, 24, 569–578. [CrossRef]
© 2018 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access
article distributed under the terms and conditions of the Creative Commons Attribution
(CC BY) license (http://creativecommons.org/licenses/by/4.0/).
341
energies
Article
FPGA-Based Controller for a Permanent-Magnet
Synchronous Motor Drive Based on a Four-Level
Active-Clamped DC-AC Converter
Joan Nicolas-Apruzzese *, Emili Lupon, Sergio Busquets-Monge, Alfonso Conesa,
Josep Bordonau and Gabriel García-Rojas
Electronic Engineering Department, Universitat Politècnica de Catalunya, 08028 Barcelona, Spain;
[email protected] (E.L.); [email protected] (S.B.-M.); [email protected] (A.C.);
[email protected] (J.B.); [email protected] (G.G.-R.)
* Correspondence: [email protected]; Tel.: +34-93-401-7152
Abstract: This paper proposes a closed-loop control implementation fully-embedded into an FPGA
for a permanent-magnet synchronous motor (PMSM) drive based on a four-level active-clamped
converter. The proposed FPGA controller comprises a field-oriented control to drive the PMSM,
a DC-link voltage balancing closed-loop control (VBC), and a virtual-vector-based modulator for a
four-level active-clamped converter. The VBC and the modulator operate in consonance to preserve
the DC-link capacitor voltages balanced. The FPGA design methodology is carefully described and
the main aspects to achieve an optimal FPGA implementation using low resources are discussed.
Experimental results under different operating conditions are presented to demonstrate the good
performance and the feasibility of the proposed controller for motor-drive applications.
1. Introduction
The use of multilevel power converters for industrial applications has increased significantly in the
last years thanks to their advantages compared to conventional two-level converters [1]. Some of these
advantages are higher efficiency, higher power density, reduced harmonic distortion, etc. However,
multilevel converters present some drawbacks, such as a higher number of switches and an increased
control complexity. The higher control complexity is not just because they contain more devices.
In some multilevel topologies, the DC-link bus is split into several partial voltages with the inclusion
of capacitors. This implies necessary control actions to keep these capacitor voltages balanced.
This is the case, for instance, of the multilevel active-clamped (MAC) topology [2]. Figure 1
depicts the four switching states of a four-level MAC converter leg to illustrate the converter operation.
The circled switches are on-state devices and the non-circled ones are off-state devices. The solid-line
circled switches conduct the main current (io ) and the dotted-line circled switches simply clamp
the blocking voltage of the off-state devices to the voltage across adjacent levels. Compared to the
commonly-used diode-clamped topology, which presents a lower number of switches, the MAC
converter advantages are: lower conduction losses, improved switching-losses distribution, blocking
voltage of a device always equal to the voltage across adjacent levels, and improved fault-tolerance
capacity [3]. Motor drives, and in particular the traction inverter of electric vehicles, is one of the
applications where the MAC converter appears to be of interest. Therefore, the authors propose to use
a MAC converter to drive a permanent-magnet synchronous motor (PMSM).
(a) (b)
(c) (d)
Figure 1. Four-level MAC leg switching states. (a) Connection to node i1 . (b) Connection to node i2 .
(c) Connection to node i3 . (d) Connection to node i4 .
The MAC topology belongs to the family of neutral-point clamped (NPC) topologies [4]. In this
family of topologies, one typical configuration consists of connecting a set of capacitors in series to
passively generate the multiple voltage levels, see Figure 2. Other configurations are possible, as for
instance connecting DC-voltage sources or batteries instead of capacitors across the adjacent input
nodes. When DC-link capacitors are used, as in the present proposal, these topologies intrinsically
present the challenge of balancing the capacitor voltages, since the classical modulation schemes
lead to a voltage unbalancing. The voltage balancing problem arises from the existence of non-zero
currents in the inner DC-link points (nodes i2 and i3 in Figure 1). This issue has been widely reported
and investigated in the literature [5]. The diverse solutions proposed to solve this problem can be
generally classified as hardware and software solutions. Hardware solutions introduce auxiliary
circuitry to inject/draw additional current into/from the inner DC-link points to compensate the
inherent converter current. Software solutions consist in defining a suitable modulation that is defined
so as to maintain the average current of each inner node equal to zero over a specific period of time.
Among the software and hardware solutions, the authors propose to use a software solution
since they are cheaper, present better performance, and they are simpler to implement. Among the
different software solutions, the authors have selected the virtual-vector-based modulation originally
introduced for three levels in [6] and extended to an arbitrary number of levels in [7], in which the
average current of each inner DC-link point is maintained equal to zero over a single switching cycle.
This modulation strategy enables to minimize the size of the capacitors, which leads to a higher
power density. Although the applied modulation scheme is intended to preserve the balance of the
DC-link capacitor voltages in every switching cycle, it is necessary to apply an additional control
loop to guarantee a tight voltage balancing, since non-idealities lead to DC-link voltage unbalancing.
The voltage balancing control (VBC) scheme proposed in [5] is implemented here to perform this action.
343
Energies 2018, 11, 2639
It is noteworthy that [8,9] state that the modulation scheme used here cannot work properly with
dynamic loads such as motors, because the converter would not be able to keep the capacitor-voltage
fluctuations low, leading to a system instability. This modulation is implemented here together with
the VBC to drive a PMSM, demonstrating the feasibility of the proposed controller for motor-drive
applications. Additionally, a four-level converter is used, in which the capacitor voltage balancing
is much more challenging than in a three-level converter since some of the capacitor voltages may
collapse [4].
FPGA
Signal Acquisition Field-oriented control
ω* Speed PI iq* Cur rent PI dq,raw* dq* m*
ࢥ compensator (kpω, kiω) compensator (kpi, kii) Coor dinate
Encoder
inter face ω ω iq id transform.
2·ωe·L/Vdc dq to
processing
id (magnitude,
Analog iA Coor dinate
id* = 0 Cur rent PI dd,raw* dd* phase) θ*
Filt ering iB transform. iq
iA compensator (kpi, kii ) Modulation
ab to dq
iB id iq ࢥ (virtual-vector
ࢥ 2·ωe·L/Vdc PWM including Control
ADC overmodulation signals
ω*, kpω, kiω, kpi, kii region)
ADC interface
processing v21 DC-link voltage balancing control
v32 k2 Limiter
imb 2=(v32+v43)/2−v21 Voltage PI & sign mod 2
v43 pow_sign (pow=dd*·id+dq*·iq)
compensator (kpv, kiv)
k3 Limiter
imb 3=v43−(v21+v32)/2 Voltage PI & sign mod 3
compensator (kpv, kiv)
kpv, kiv
User-interface processing
In order to take full advantage of the traction inverter, a proper and proficient controller has to
be developed. Typical power-converter digital controllers are implemented on microprocessors (μP),
digital signal processors (DSP) and/or field-programmable gate arrays (FPGA). FPGA architecture
permits both the parallel and sequential processing of data at high clock frequencies, which
dramatically reduces the needed processing time, compared to μPs and DSPs. In addition, in cases
in which the desired controller benefits from the utilization of a general-purpose processor, it can be
embedded within the FPGA as many microprocessor cores are available as IPs.
The controller has to generate the 36 signals for the four-level MAC legs (12 devices per leg) at
each switching cycle. Then, different automata with some duty ratios as inputs and running at high
frequency (i.e., 50 MHz, which allows a time accuracy of 20 ns) have to be implemented. An FPGA
implementation of such automata appears as a better solution than using a general-purpose processor
with lots of timers. Additionally, for each new switching cycle, the new duty ratios have to be computed
from the system input variables (currents, voltages, and rotor angle). For performing these calculations,
it is desired to use measured values of the input variables as close as possible to the start of the next
switching cycle, in order to maximize the control bandwidth. To this end, an ad hoc processing unit
(specific purpose processing unit), implemented in the same FPGA as the above indicated automata,
appears as a better solution than using an additional device, as a general-purpose processor or a DSP
344
Energies 2018, 11, 2639
platform. Delay between measurement and the application of the resulting duty ratios is reduced, cost
is also reduced, and synchronization between different devices is not required.
Due to the general FPGA advantages and to the specific reasons presented above in the last two
paragraphs, respectively, the authors propose a full FPGA-based control implementation of a four-level
three-phase MAC inverter to drive a three-phase four-pole pairs PMSM. Figure 2 presents the general
overview of the electrical circuit and the proposed FPGA control structure. As it can be seen in the
Figure 2, as well as the VBC closed-loop control already introduced above, a closed-loop field-oriented
control (FOC) is used for driving the PMSM.
A preliminary open-loop FPGA controller implementation with the same virtual-vector
modulation was presented in [10]. However, the controller in [10] did not include the closed-loop
controls to operate the converter as a motor drive and to preserve the capacitor voltages balanced.
FPGAs have been employed for implementing diverse control schemes of multilevel converters
([11–21]), and also for implementing motor-drive controllers ([17–26]). References [17–21] propose
FPGA-based controllers for multilevel converters operating as motor drives, as it is proposed here.
However, [17–21] do not explain the FPGA controller structure, do not discuss the design methodology
to obtain an efficient implementation, and generally do not deal with the voltage balancing problem.
To the best of the authors’ knowledge, for the first time, a complete controller for a four-level
converter of the NPC converter family [4], operating as a motor drive and including DC-link voltage
balancing control, is fully-embedded into an FPGA. In addition, the controller implementation has
been optimized to save FPGA resources and also to take full advantage of the FPGA potential
performance capabilities.
The paper is organized as follows: Section 2 presents a summary of the used VBC, field-oriented
control (FOC), and modulation scheme, presenting the equations to be implemented in the FPGA.
Section 3 details the FPGA structure, and describes relevant aspects to achieve an efficient controller.
In Section 4, experimental results are shown to verify the good operation of the controller under
different conditions. Finally, Section 5 outlines the conclusion.
345
Energies 2018, 11, 2639
Finally, the preliminary leg duty-ratios are modified using variables k2 and k3 , so that the balancing
of the capacitor voltages can be recovered. This part is explained below at the end of the modulation
strategy subsection.
346
Energies 2018, 11, 2639
modulation index (mc ) and reference vector angle (θ c ). Tables 2 and 3 summarize these calculations.
The index hbc is fixed to 0.98. Then, the range limits are:
∗
hbc · mmaxI = 0.98 · 3 ln√(3)/π = 1.0281
∗ (3)
hbc · mmaxII = 0.98 · 2 3/π = 1.0806
Table 3. Corrected values of modulation index (mc ) and reference vector angle (θc ).
The preliminary leg duty ratios dx1 and dx4 (indicating the duty ratio of connection of phase x to
levels 1 and 4, respectively) are determined according to Table 4 from the value of the sextant of each
phase sextant_x, and from the auxiliary variables d1 , d4 and d5 .
sextant_x 0 1 2 3 4 5
dx1 0 d5 d4 d4 d1 0
dx1 d4 d1 0 0 d5 d4
The leg duty ratios of the inner levels 2 and 3 are then calculated as follows:
d x2 = d x3 = (1 − d x1 − d x4 )/2 (5)
In order to finally implement the VBC, preliminary leg duty ratios are modified according to the
following equations:
347
Energies 2018, 11, 2639
348
Energies 2018, 11, 2639
The FPGA has been mounted on a printed circuit board together with the sensors, the filtering
circuitry, the ADC chip, and the user-interface (see Figure 3). The user-interface comprises a 4 × 3
matrix keyboard to introduce the values of some control variables, a three-line sixteen-character LCD
screen, two pushbuttons, and eleven LEDs to easily visualize some errors and the ON-state.
Three operating modes have been defined in order to enable the use of the inverter under different
system configurations, and also to bring the possibility of evaluating and tuning the different control
structures individually:
- Voltage-balancing controller mode (mode 0): in this mode, FOC is disabled, but the dc-link
voltage control is enabled. With this mode, it is necessary to introduce the command values of m*
and f * to make it operate at desired conditions.
- Torque controller mode (mode 1): this mode enables the inner current control loop of the FOC,
but the outer speed control loop is disabled. DC-link voltage control is also enabled. With this
mode, it is necessary to introduce the value of iq *, which is proportional to the torque, to make it
operate at desired conditions.
- Speed controller mode (mode 2): this mode enables the whole closed-loop control. With this
mode, it is necessary to externally introduce the command value of rotational speed ω* to make
it operate at desired conditions.
Since the control scheme requires five analog inputs (sensed iA , iB , v21 , v32 , and v43 ), and the
position of the rotor, an analog-to-digital converter chip and an encoder are necessary.
The AD7658 from Analog Devices has been selected as ADC chip, as it allows converting up to
six analog signals synchronously. This chip is configured in parallel interface to minimize the time
needed for data transmission.
Encoder RP1410 (IFM, El Prat de Llobregat, Spain) is used for obtaining the rotor position. This
encoder generates three digital signals: enc_A, enc_B, and index_zc. Signals enc_A and enc_B present
each 1024 pulses for a rotor revolution (with a phase delay of 90◦ ). To determine the rotor angle,
any single rising or falling edge of enc_A and enc_B can be counted, giving a resolution of 4096
edges per revolution, so 1024 edges per electrical cycle (the motor is a four-pole PMSM). Then, the
mechanical rotor angle ϕm presents a resolution of 0.08789◦ (360◦ /4096 edges), and the electrical
angle ϕ resolution is 0.35156◦ . Signal index_zc presents a small pulse each time a rotor revolution is
accomplished (zero-crossing detection).
349
Energies 2018, 11, 2639
in Figure 3 the time constants k_tb , k_td , and k_ts , that are defined as k_tb = tb /tck = 2, k_td = td /tck = 40,
and k_ts = ts /tck = 10,000.
As in [10], most of the FPGA processing is synchronized with the switching cycle. A divider-
by-10,000 counter cnt_ts is used to this purpose. Figure 4 illustrates the timing overview of a cnt_ts cycle
and its synchronization with a switching period. A cnt_ts cycle starts performing all the samplings and
calculations required to stablish the behavior of the next switching cycle, which starts at cnt_ts = 234,
as soon as possible after these calculations are completed at cnt_ts = 214. The delay between these
two events, half a blanking time, is required to properly transit from a switching cycle to the next one
(dx4 can change from a null/non-null value to a new null/non-null value, as explained in [10]).
FON0
7LP LQJFRQWURO
FQWBWV
FQWWVB
FQWWVB
FQWWVB
FQWWVB
DGFBVWDUW
DGFBQFV
$'&
DGFBQUG
DGFBGDWD v21 v32 v43 iB iA
*HQHU DOPRGXOHV
*HQHUDOWLPLQJRYHUYLH Z
8VHULQWHUIDFH SURFHVVLQJ
(QFRGHUSU RF HVVLQJ ,QVWDQWLQZKLFKȦDQGࢥDUHFRSLHG
$' &SURFHVVLQJ $OOVHQVHGYDULDEOHVVHQW (QGRIQH[W
VZLWFKLQJF\FOH
)2&SU RF HVVLQJ GXWLHVSURFHVVLQJ
6WDUWRIQH[W
9%&SURFH VVLQJ
VZLWFKLQJF\FOH
GXWLHVSURFHVVLQJ 3: 0SURFHVVLQJ
6ZLWFKLQJF\FOHGLVWULEXWLRQ (QGRIQH[WVZLWFKLQJF\FOHGXWLHVSURFHVVLQJ 7UDQVLHQW 6WDUWRIVZLWF\FOH
A versatile implementation has been conceived, allowing the user to modify important operational
parameters through the user interface, such as the operating mode (mode), the PI compensators
constants kpω , kiω , kpi , kii , kpv and kiv , or the command values ω*, iq *, m* and f *.
350
Energies 2018, 11, 2639
(this part of the process is carried out by module MB1 ), the motor is stopped, and signal detecting_ϕ_zc
is deactivated.
error’ &
edge_onoff WUDQVLWLRQWR error’ & 3ROH21 3ROH21
nreset' 2))VWDWH 21VWDWH cnt_ts = 214 ZDLW Δt =tb ZDLW
HUURU ZDLW
Δt =tb Δt =tb
detected_ϕ_zc · detecting_ϕ_zc
3ROH2)) 3ROH2)) or error’ or edge_onoff
ZDLW Δt =tb ZDLW 21VWDWH
Module MA4 generates the global reset signal nreset from the signal rst provided by the “reset”
pushbutton. Signal nreset is active low, lasting 120 μs to guarantee minimum duration required by
LCD (lcd_nreset and nreset are the same signal). Signal adc_reset, which lasts 10 tck and is active high,
is used to initialize the ADC chip.
Module MA5 is the main synchronization module. It implements the divider-by-10,000 counter
cnt_ts and generates a set of enable signals (cntts_X) to manage the timing of most actions performed
by other modules, as indicated in Figure 4. This module also updates the value of line angle in mode 0
(θ*_0), from the frequency command value in mode 0 (f*_0).
351
Energies 2018, 11, 2639
configurable parameters). The module also includes a ROM containing the visualization format for the
24 variables that can be visualized in the LCD screen (see Figure 3).
The user-interface modules consume substantial resources of the FPGA (21.5% of the used
logic elements and 27% of the used multipliers). Its explanation is simplified here because they are
considered to be of less technical importance, compared to other parts of the design.
Module MD6 implements Equation (1) to calculate the values of id and iq . Module MD7 contains
the id and iq error PI compensators with limited proportional, integral and total outputs. Output
variables of PI compensators are direct and quadrature raw duties dd,raw * and dq,raw *, which are
updated when cnt_ts = 194. √
Module MD8 implements the calculation of the decoupling factor, which is equal to 2 · ωe · L/Vdc
(where L and V dc are usually constant values), its products by currents id and iq , the addition of the
first product to dq,raw * and the subtraction of the second product from dd,raw *, to obtain duties dd * and
dq *, respectively (see Figure 2). In general, products are done followed by a truncation (change of
units), thus allowing optimizing FPGA resources.
Modules MD9 and MD10 implement the dq-to-(magnitude,phase) transformation indicated in
Equation (2) to calculate the modulation index and reference vector angle in modes 1 and 2 (m*_12 and
θ*_12). Both variables are obtained through a successive approximation algorithm. A ROM is used
to calculate the tangent of the provisional reference vector angle used in the algorithm. Octagonal
symmetry is taken into account to reduce the size of the ROM.
Module MD11 is just a selector for the modulation index and the reference vector angle, depending
on the operating mode.
f 5 = min {1 ; (1 − d4 ) / (2 · d4 )}
f 6 = min {0.5 ; 3 · (1 − d4 ) / (1 + 6 · d4 )} (8)
f 7 = min {1 ; 1.5 · (1 − d4 ) / (1 + 3 · d4 )}
Module ME3 is in charge of calculating the sign of power flow, according to the expression shown
in the green inset of Figure 2. Output value of pow_sign is updated at cnt_ts = 196.
352
Energies 2018, 11, 2639
Module ME4 applies simple logic to obtain values of variables k2 and k3 , according to Table 1.
353
Energies 2018, 11, 2639
4. Experimental Tests
The proper operation of the FPGA controller has been tested experimentally within the system
shown in Figure 6a. Main parts of the system are labelled in the figure. The shaft of the PMSM driven
by the FPGA controller is coupled to an induction machine, which is not used, and also to another
PMSM, which is used to set the load torque. A further detailed overview of the experimental test bed
can be observed in a supplementary video attached with this paper. Figure 6b depicts FPGA control
board, presenting its main parts/subcircuits.
0$&
LQYHUWHU
'&SRZHUVXSSO\
)3*$
FRQWUROERDUG
3060XVHGWRVHW
WKHORDGWRUTXH 1RWXVHG
3060GULYHQE\WKH
)3*$FRQWUROOHU
(a)
)LOWHULQJ 9DQG,
FLUFXLWU\ VHQVRUV
$'&
FRQYHUWHU
)3*$
(b)
Figure 6. Experimental testbed. (a) Overview of the system; (b) FPGA control board.
The four-level three-phase MAC inverter employs 200 V STP20NF20 MOSFET devices
(ST microelectronics, Amsterdam, Netherlands). The reference of the PMSM driven by the FPGA
controller is 1FT6105-8SB71-2AA0 (Siemens, Berlin, Germany). This motor is a surface-magnet type
PMSM, with a nominal speed of 1500 rpm and a nominal torque of 59 Nm, thus, a nominal power of
9.27 kW.
354
Energies 2018, 11, 2639
The proper system operation can be observed in Figures 7–9. In Figure 7, the good performance
of the VBC under a start-up transition is depicted. Initially, in OFF state, capacitor voltages are
unbalanced, but after 200 ms of operation, they become balanced. It is also remarkable the behavior of
the phase current iA . After the start-up, while the motor is accelerating, the current magnitude keeps
constant at a certain level, set by the speed ramp. As soon as the motor reaches the command speed of
500 rpm, the current magnitude decreases to a lower level.
Figure 7. Experimental results of DC-link voltages and phase current iA under a start-up transition.
Conditions: V dc = 180 V, C = 155 μF, ω* = 500 rpm, kpω = 0.1 A/rpm, kiω = 0.1 A/(rpm·s), kpi = 0.01 A−1 ,
kii = 1 (A·s)−1 , kpv = 0.02 V−1 , kiv = 0 (V·s)−1 , ts = 100 μs, load torque = 0 Nm.
Z*pre Z*post
iC iB iA
Figure 8. Experimental results of phase currents iA , iB , and iC , under a change of the rotation direction.
Conditions: ω*pre = 350 rpm, ω*post = −350 rpm (remaining conditions are the same as in Figure 7).
Figure 8 shows the phase currents under a change of rotation direction, from 350 rpm to −350 rpm.
In the upper part of the figure, the whole transition is depicted. As it can be seen, the current sequence
changes once the motor starts rotating in opposite direction. As in Figure 7, once the motor reaches the
command speed value, the current magnitude decreases to a lower level.
Figure 9 presents the three phase currents and the phase voltage vA1 operating in UM and
OM regions. Figure 9a shows the waveforms for the UM region, with m* = 0.76. Figure 9b shows
the waveforms for region OMI (0.98 < m* < 1.028), operating with m* = 1.01. Figure 9c shows the
waveforms for region OMII (1.028 < m* < 1.081), operating with m* = 1.03. In UM, current waveforms
are sinusoidal with almost no distortion. However, in OMI and OMII, the current waveforms present
a noteworthy distortion, with a higher distortion under OMII. This is the expected behavior, since
the overmodulation intrinsically introduces low-order harmonics in the phase currents [27]. It is also
interesting to note that in waveforms of the phase voltage vA1 , the duty ratio of connection to inner
levels 2 and 3 is lower when operating in OM region.
355
Energies 2018, 11, 2639
vA1
iA iB iC
(a)
vA1
iA iB iC
(b)
vA1
iA iB iC
(c)
Figure 9. Experimental results of phase currents iA , iB , and iC , and phase voltage v1A , operating in UM
and OM regions. (a) Operation in UM: ω* = 450 rpm, load torque = 10 Nm, m* = 0.76; (b) Operation in
OMI: ω* = 610 rpm, load torque = 10 Nm, m* = 1.01; (c) Operation in OMII: ω* = 620 rpm, load torque
= 10 Nm, m* = 1.03 (remaining conditions are the same as in Figure 7 for (a), (b) and (c)).
As stated previously, a complementary video is included with this study. The video shows the
whole system operating under conditions of Figures 7 and 8, and also under other different conditions.
5. Conclusions
A low-cost closed-loop controller fully embedded into an FPGA has been successfully
implemented for a PMSM motor drive based on a four-level three-phase MAC inverter, taking full
advantage of the drive potential performance capabilities. An efficient and robust implementation into
a mid-range FPGA of the closed-loop VBC and FOC, together with a modulation scheme including
the overmodulation region, has been achieved, consuming less than 50% of its total resources and
356
Energies 2018, 11, 2639
obtaining a very low processing time. The remaining FPGA resources can be employed to increase
the switching frequency, or to further improve the controller performance, including, for example,
fault-tolerant controls [3], or an intelligent distribution of switching losses to better distribute the total
semiconductor losses [2]. The proper operation of the whole system demonstrates the feasibility of
using virtual-vector-based PWMs for neutral-point-clamped converters in motor drive applications,
which had been questioned in the previous literature. In the future, the authors envision a motor
drive design approach where an inexpensive switch with good performance is selected, and MAC leg
structures are used to match the motor voltage rating by simply adjusting the number of levels.
References
1. Leon, J.I.; Vazquez, S.; Franquelo, L.G. Multilevel Converters: Control and Modulation Techniques for Their
Operation and Industrial Applications. Proc. IEEE 2017, 105, 2066–2081. [CrossRef]
2. Busquets-Monge, S.; Nicolas-Apruzzese, J. A Multilevel Active-Clamped Converter Topology—Operating
Principle. IEEE Trans. Ind. Electron. 2011, 58, 3868–3878. [CrossRef]
3. Nicolas-Apruzzese, J.; Busquets-Monge, S.; Bordonau, J.; Alepuz, S.; Calle-Prado, A. Analysis of the
Fault-Tolerance Capacity of the Multilevel Active-Clamped Converter. IEEE Trans. Ind. Electron. 2013,
60, 4773–4783. [CrossRef]
4. Busquets-Monge, S. Neutral-Point-Clamped DC-AC Power Converters. In Wiley Encyclopedia of Electrical
and Electronics Engineering; Webster, J.G., Ed.; John Wiley & Sons, Inc.: Hoboken, NJ, USA, 2018; pp. 1–20.
ISBN 9780471346081.
5. Busquets-Monge, S.; Maheshwari, R.; Nicolas-Apruzzese, J.; Lupon, E.; Munk-Nielsen, S.; Bordonau, J.
Enhanced DC-Link Capacitor Voltage Balancing Control of DC-AC Multilevel Multileg Converters.
IEEE Trans. Ind. Electron. 2015, 62, 2663–2672. [CrossRef]
6. Busquets-Monge, S.; Bordonau, J.; Boroyevich, D.; Somavilla, S. The nearest three virtual space vector
PWM—A modulation for the comprehensive neutral-point balancing in the three-level NPC inverter.
IEEE Power Electron. Lett. 2004, 2, 11–15. [CrossRef]
7. Busquets-Monge, S.; Alepuz, S.; Rocabert, J.; Bordonau, J. Pulsewidth Modulations for the Comprehensive
Capacitor Voltage Balance of n-Level Three-Leg Diode-Clamped Converters. IEEE Trans. Power Electr. 2009,
24, 1364–1375. [CrossRef]
8. Choudhury, A.; Pillay, P.; Williamson, S.S. A Hybrid PWM-Based DC-Link Voltage Balancing Algorithm for
a Three-Level NPC DC/AC Traction Inverter Drive. IEEE J. Emerg. Sel. Top. Power Electron. 2015, 3, 805–816.
[CrossRef]
9. Choudhury, A.; Pillay, P.; Williamson, S.S. DC-Bus Voltage Balancing Algorithm for Three-Level
Neutral-Point-Clamped (NPC) Traction Inverter Drive with Modified Virtual Space Vector. IEEE Trans. Ind.
Appl. 2016, 52, 3958–3967. [CrossRef]
10. Lupon, E.; Busquets-Monge, S.; Nicolas-Apruzzese, J. FPGA Implementation of a PWM for a Three-Phase
DC-AC Multilevel Active-Clamped Converter. IEEE Trans. Ind. Inform. 2014, 10, 1296–1306. [CrossRef]
11. Cossutta, P.; Aguirre, M.P.; Engelhardt, M.A.; Valla, M.I. Control System to Balance Internal Currents of a
Multilevel Current-Source Inverter. IEEE Trans. Ind. Electron. 2018, 65, 2280–2288. [CrossRef]
357
Energies 2018, 11, 2639
12. Zhang, Z.; Wang, F.; Wang, J.; Rodríguez, J.; Kennel, R. Nonlinear Direct Control for Three-Level NPC
Back-to-Back Converter PMSG Wind Turbine Systems: Experimental Assessment With FPGA. IEEE Trans.
Ind. Inform. 2017, 13, 1172–1183. [CrossRef]
13. Zhang, Z.; Hackl, C.; Kennel, R. Computationally Efficient DMPC for Three-Level NPC Back-to-Back
Converters in Wind Turbine Systems With PMSG. IEEE Trans. Power Electron. 2017, 32, 8018–8034. [CrossRef]
14. Bennani-Ben Abdelghani, A.; Ben Abdelghani, H.; Richardeau, F.; Blaquière, J.M.; Mosser, F.; Slama-Belkhodja, I.
Versatile Three-Level FC-NPC Converter with High Fault-Tolerance Capabilities: Switch Fault Detection and
Isolation and Safe Postfault Operation. IEEE Trans. Ind. Electron. 2017, 64, 6453–6464. [CrossRef]
15. Moranchel, M.; Huerta, F.; Sanz, I.; Bueno, E.; Rodríguez, F. A Comparison of Modulation Techniques for
Modular Multilevel Converters. Energies 2016, 9, 1091. [CrossRef]
16. Rodríguez-Rodríguez, J.; Venegas-Rebollar, V.; Moreno-Goytia, E. Single DC-Sourced 9-level DC/AC
Topology as Transformerless Power Interface for Renewable Sources. Energies 2015, 8, 1273–1290. [CrossRef]
17. Zhang, Z.; Hackl, C.; Kennel, R. FPGA Based Direct Model Predictive Current Control of PMSM Drives
with 3L-NPC Power Converters. In Proceedings of the International Exhibition and Conference for
Power Electronics, Intelligent Motion, Renewable Energy and Energy Management, Nuremberg, Germany,
10–12 May 2016; pp. 1–8.
18. Umesh, B.S.; Sivakumar, K. Multilevel Inverter Scheme for Performance Improvement of Pole-Phase-
Modulated Multiphase Induction Motor Drive. IEEE Trans. Ind. Electron. 2016, 63, 2036–2043. [CrossRef]
19. Kumar, P.S.; Satyanarayana, M. Comparative analysis of modulation strategies applied to seven-level diode
clamped multi-level inverter fed induction motor drive. In Proceedings of the 2015 Conference on Power,
Control, Communication and Computational Technologies for Sustainable Growth (PCCCTSG), Kurnool,
India, 11–12 December 2015; pp. 231–237.
20. Janik, D.; Kosan, T.; Blahnik, V.; Kamenicky, P.; Peroutka, Z.; Danek, M. Complete solution of 4-level flying
capacitor converter for medium-voltage drives with active voltage balancing control with phase-disposition
PWM. In Proceedings of the 2014 16th European Conference on Power Electronics and Applications,
Lappeenranta, Finland, 26–28 August 2014; pp. 1–8.
21. Hirani, M.; Gupta, S.; Deshpande, D.M. Comparison of performance of induction motor fed by sine
pulse width modulated inverter and multi level inverter using XILINX. In Proceedings of the 2014
IEEE International Conference on Advanced Communications, Control and Computing Technologies,
Ramanathapuram, India, 8–10 May 2014; pp. 264–269.
22. Chun, T.W.; Tran, Q.V.; Lee, H.H.; Kim, H.G.; Nho, E.C. A simple capacitor votage balancing scheme for the
cascaded five-level inverter fed AC machine drive. In Proceedings of the 6th IET International Conference
on Power Electronics, Machines and Drives (PEMD 2012), Bristol, UK, 27–29 March 2012; pp. 1–5.
23. Ponce, R.R.; Talavera, D.V. FPGA Implementation of Decimal Division for Motor Control Drives. IEEE Lat.
Am. Trans. 2016, 14, 3980–3985. [CrossRef]
24. Jabeen, S.; Srinivasan, S.K.; Shuja, S.; Dubasi, M.A.L. A Formal Verification Methodology for FPGA-Based
Stepper Motor Control. IEEE Embed. Syst. Lett. 2015, 7, 85–88. [CrossRef]
25. Gdaim, S.; Mtibaa, A.; Mimouni, M.F. Design and Experimental Implementation of DTC of an Induction
Machine Based on Fuzzy Logic Control on FPGA. IEEE Trans. Fuzzy Syst. 2015, 23, 644–655. [CrossRef]
26. Quang, N.K.; Hieu, N.T.; Ha, Q.P. FPGA-Based Sensorless PMSM Speed Control Using Reduced-Order
Extended Kalman Filters. IEEE Trans. Ind. Electron. 2014, 61, 6574–6582. [CrossRef]
27. Busquets-Monge, S.; Maheshwari, R.; Munk-Nielsen, S. Overmodulation of n-Level Three-Leg DC-AC
Diode-Clamped Converters with Comprehensive Capacitor Voltage Balance. IEEE Trans. Ind. Electron. 2013,
60, 1872–1883. [CrossRef]
© 2018 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access
article distributed under the terms and conditions of the Creative Commons Attribution
(CC BY) license (http://creativecommons.org/licenses/by/4.0/).
358
energies
Article
FPGA-Based Implementation of MMC Control Based
on Sorting Networks
Mattia Ricco 1, *, Laszlo Mathe 1 , Eric Monmasson 2 and Remus Teodorescu 1
1 Department of Energy Technology, Aalborg University, 9100 Aalborg, Denmark;
[email protected] (L.M.); [email protected] (R.T.)
2 SATIE lab, Cergy-Pontoise University, 95031 Cergy Pontoise, France; [email protected]
* Correspondence: [email protected]
Abstract: In Modular Multilevel Converter (MMC) applications, the balancing of the capacitor
voltages is one of the most important issues for achieving the proper behavior of the MMC.
The Capacitor Voltage Balancing (CVB) control is usually based on classical sorting algorithms
which consist of repetitive/recursive loops. This leads to an increase of the execution time when
many Sub-Modules (SMs) are employed. When the execution time of the balancing is longer than
the sampling period, the proper operation of the MMC cannot be ensured. Moreover, due to
their inherent sequential operation, sorting algorithms are suitable for software implementation
(microcontrollers or DSPs), but they are not appropriate for a hardware implementation. Instead,
in this paper, Sorting Networks (SNs) are proposed due to their convenience for implementation
in FPGA devices. The advantages and the main challenges of the Bitonic SN in MMC applications
are discussed and different FPGA implementations are presented. Simulation results are provided
in normal and faulty conditions. Moreover, a comparison with the widely used bubble sorting
algorithm and max/min approach is made in terms of execution time and performance. Finally,
hardware-in-the-loop results are shown to prove the effectiveness of the implemented SN.
1. Introduction
Nowadays, the Modular Multilevel Converter (MMC) has become a promising solution in
different applications, such as in High Voltage Direct Current (HVDC) [1,2], high-power motor
drivers [3,4] and STATic COMpensators (STATCOM) [5,6]. Thanks to several advantages, such as
high modularity, scalability, low Total Harmonic Distortion (THD), high efficiency and high reliability,
the interest in this topology has increased in both industry and academy [7]. However, this topology
presents several challenges, such as the necessity to control the circulating current, ensure the
balance of the losses among the Sub-Modules (SMs) and maintain the capacitor voltage balanced [8].
In the literature, two Capacitor Voltage Balancing (CVB) control algorithms are mainly proposed:
the individual control approach [9] and the global arm control approach. The latter is commonly used
in the Nearest Level Control (NLC) which requires a Sorting Algorithm (SA) [10]. Indeed, to balance
the capacitor voltages (CVs), the SMs with the highest or lowest CV must be selected based on the arm
current direction. Then, the SA provides a sorted list of the SMs according to their capacitor voltages.
In MMC applications, the implementation of SAs is a key challenge mainly due to the timing
performances and the high computation efforts of this kind of algorithms. Low timing performances
can slow down the CVB algorithm by limiting either the maximum sampling frequency or the
maximum allowable number of SMs in the converter. The SAs are usually implemented in
microcontrollers or in digital signal processors due to their easy implementation. However, they are
based on loop/recursive operation leading to a significant increase of the execution time when the
number of SMs grows. Some authors propose max/min approaches to overcome this issue [11–13].
Such methods suppose that only one SM has to be inserted/bypassed in the next sampling instant.
Then, they only find the SM with the maximum (or minimum) CV by achieving a strong reduction
of the execution time. However, in the case of faults or when the capacitors are approaching the
maximum allowable voltage, more SMs need to be inserted or bypassed at the same time. The max/min
algorithms then require more sampling periods to insert or bypass the required SMs, which leads to
slow converter dynamic performance. A solution could be to run multiple times the max/min method
within the same sampling instant; however, this choice increases the whole execution time by leading
to the same problem highlighted for the bubble SA.
For the above-mentioned reasons, a hardware implementation of a sorting method has been
proposed in this paper. Several studies have confirmed that the Field-Programmable Gate Array
(FPGA) technology is really promising in industrial control applications [14]. Such platforms are more
and more used in industry and in academia for achieving high timing performance, which is difficult
to reach with the software counterpart. Since the FPGAs are able to exploit the inherent parallelism of
the algorithm, they lead to a significant reduction of the execution time. Moreover, they are often used
in MMC applications due to the possibility: to drive a huge amount of SMs [15], to implement fast
protections, to interface more ADC modules [16], to implement real-time emulator [17] and for fast
communication [18].
Among the different hardware implementations of sorting approaches, the Sorting Networks
(SNs) have been chosen to be implemented in FPGA due to their inherent parallelism and enhanced
timing performance [19]. The Bitonic SN has been considered due to its low resource requirement
and its modular structure [20]. The authors in [20] compared this SN with the Odd-Even SN.
However, the main aim was to provide a method for pre-evaluating the hardware resources and the
execution time of the network. No simulations or hardware-in-the-loop results were provided, and no
justifications were given for the use of these networks in MMC. In this work, instead, some simulation
results are shown in normal and faulty conditions to highlight the benefits of adopting an algorithm
that provides a complete sorted list with respect to one that only gives the SM with the highest (lowest)
capacitor voltage. Another contribution of this work is the study of the achievable trade-offs between
the execution time and the required resources when this kind of sorting methods are implemented
for MMC applications. For this aim, three kinds of FPGA implementations are presented: a fully
pipelined architecture, a hybrid structure and a fully factorized SN. In this way, designers can choose
the proper solution for their requirements to achieve the best compromise between the required
timing performance and the available resources. After having chosen the right solution that fits
the requirements of the MMC application considered in this work, the SN architecture is compared
with the classical bubble sorting algorithm and the max/min approach in terms of execution time.
To demonstrate the feasibility of the proposed architecture, a Hardware-In-the-Loop (HIL) validation
is also made.
The paper is divided as follows: firstly, an MMC overview is given along with its control
hierarchy. Then, the Bitonic SN is presented and its peculiar aspects in MMC applications are treated.
Section 4 presents the simulation results in normal and faulty conditions. After that, different FPGA
implementations are proposed and compared in terms of required resources and execution time in
Section 5. Then, the chosen hardware implementation is compared with the software implementation
of both the classical bubble SA and the max/min approach. HIL results for a single-phase 32-SM
MMC are given to demonstrate the effectiveness of the proposed SN implementation. Finally,
conclusions are drawn.
360
Energies 2018, 11, 2394
HVDC grid connected MMC application with half-bridge SM is considered (Figure 1). Its topology
and control structure are described in the next sections.
Phase C
S1
Idc Phase B
D1
iSM C
ia,u Phase #1
A vC
#1 S2
vSM D2
SM1,u #2
Vdc /2 #2 ic
vau SM2,u n Lg
Larm
n
Larm
ib
SMN,u Rarm Larm Larm Lg
ic #1 ia
Larm
#1 Lg
Rarm Larm
SM1,l #2 grid
#2
Vdc /2 val SM2,l n
n
SMN,l
ia,l
Vre f ,pm
n pm = (1)
Vdc
where p and m represent the phase (p = a, b, c) and the arm (m = u, l), respectively. It is worth
mentioning that the NLC only results the number of SMs to be inserted and it is indifferent to which
SMs are selected. This task is taken in charge by the CVB control algorithm to ensure the balance
between the capacitor voltages in the arm. The main elements of the CVB control algorithm are the
sorting method and the selection technique. The aim of the sorting method is to put in ascendant order
the SMs of an arm according to the measured capacitor voltages VCi ,pm .
361
Energies 2018, 11, 2394
ic icu icl
ib ibu ibl
Vdc ia iau ial
- VC,al VC,au
+
-
+ + -
Vref,l Vref,u N N
*
*
/ / lower
upper
Sorting
NLC Method
NLC
nal nau
SM
iau Selection
ial c
CVB
b
N N a
PWMal PWMau
PWMbl PWMbu
PWMcl PWMcu
The selection technique intends to select the SMs to be inserted based on the sorted list evaluated
by the sorting method and the direction of the arm current ipm . The best balancing performance is
achieved when the sorting is executed in each sampling period and always the best SMs are selected.
However, in this case, a high switching frequency fsw is resulted. Different improved methods have
been developed to decrease fsw [23–25]. In this work, a reduction of the fsw is achieved by inserting or
bypassing only the difference between the required SMs and the actual ones, as shown in Figure 3.
Moreover, the sorting is also performed if the capacitor voltages reach an upper or lower threshold
value [23]. In this case, the SM with the highest (lowest) capacitor voltage is bypassed if the current is
positive (negative) and another one is inserted in its place.
Another possible solution to reduce the fsw and decrease the execution time is to adopt max/min
approaches. They are based on the fact that only one SM has to be usually inserted/bypassed in one
sampling period. However, this assumption is valid only during steady state operation. During faults,
more SMs have to be manipulated in order to ensure fast reaction from the converter side. The max/min
methods require more sampling periods to insert/bypass the required number of SMs. This leads a
slower control dynamic as shown in Section 4.
1
Ts ≤ (2)
π · N · f grid
362
Energies 2018, 11, 2394
START
Np,m[k] = round(N·np,m[k])
NO Np,m[k] Np,m[k-1]
Vc exceed the limits
YES
Sorting Algorithm
YES NO
ȴNp,m[k] > 0
YES NO YES NO
ip,m > 0 ip,m > 0
STOP
In Equation (2), N is the number of SMs in the arm. Consequently, the controller execution time
Tcontrol has to fulfill:
Tcontrol ≤ Ts (3)
The common solution based on SAs has limited timing performances. They limit either the
maximum allowable sampling frequency or the number of SMs in the arm. A significant reduction of
Tcontrol can be achieved by adopting the proposed SNs. They are convenient for FPGA implementation
due to their parallel structure. Moreover, they avoid the use of iterative and branch instructions.
Different factorization levels are introduced to give the possibility to choose the best tradeoff
between required hardware resources and execution time. For these reasons, they are attractive for
MMC applications and their detailed description is given in the next section.
363
Energies 2018, 11, 2394
Figure 4. Eight-input Bitonic Sorting Network. It consists of six stages that in turn are composed of
four CS operators. It can be seen as two four-input Bitonic SN plus Stages 4, 5 and 6. In this example,
the length of the sorting list is equal to 3 to show its modularity property.
Firstly, each SM is enumerated starting from the top of each arm, as shown in Figure 1, and its
position is named here Pi,pm . Each element xi must consist of the acquired capacitor voltage VCi ,pm and
the corresponding position Pi,pm , as depicted in Figure 4, where the subscript pm has been omitted for
simplicity. A comparison of the capacitor voltages is performed and the swap operation is executed for
both VCi ,pm and Pi,pm if the voltages are not in the right order. The output y results in a sorted list with
the voltages in ascending order along with the corresponding physical SM position. Then, if the SM
with the highest voltage is needed for insertion, the first element y1 is considered; otherwise, the last
one is selected.
Another aspect that should be considered is the length of the list. Indeed, in MMC applications,
the modularity is one of the main advantages [7]. It consists in the possibility to raise the power rating
by adding more SMs in the arm. This means that the number of SMs, and then the length of the
list, is not known a priori. However, a maximum number of SMs in an arm (named here with M)
can always be presumed and then the SN is built for this worst-case scenario. In these conditions,
some elements of the list can be left empty since the actual length of the list N can be different from M.
To guarantee the proper behavior of the SN, these dummy elements have to be filled by setting the
voltage equal to 0 and the position to −1 [20]. Therefore, these elements are kept in the last positions
and the elements with positions different from −1 are selected when the SMs with lowest voltages
are required.
An example of an eight-input Bitonic SN for a MMC with three SMs per arm (M = 8 and N = 3)
is depicted in Figure 4. The dummy element is in Position 4 and it is kept in that position along the net.
The result can be achieved before the last stage by considering only a sub-structure of the network
as shown in the example. After having presented the SNs and having discussed their main peculiar
aspects in MMC applications, some simulation results are shown in the next section.
4. Simulation Results
In this section, the Bitonic SN is compared with the max/min approach to show the differences
between an algorithm that completely sorts the list and one that searches only the SM with the
highest/lowest CV. The simulations have been performed in PLECS® power electronic simulation
environment in both normal and faulty conditions. The MMC and grid parameters are given in
Tables 1 and 2, respectively.
The Bitonic SN and the max/min approach have been implemented in PLECS. It is worth to note
that the SN is intrinsically parallel; to simulate it its treatment has been serialized. Thus, its behavior is
equal to the one achieved with a classical sorting algorithm such as the BSA. A tolerance band has also
364
Energies 2018, 11, 2394
been introduced as shown in [23]. The max/min method proposed in [13] has been adopted in this
work. The tolerance bands are set to 2 kV.
Quantity Value
DC-link Voltage (VDC ) 200 kV
SM Capacitor (C) 600 μF
Arm Inductance (L arm ) 50 mH
Arm Resistance (R arm ) 1.6 Ω
Number of SM (N) 16
Sampling frequency ( f s ) 10 kHz
Quantity Value
Grid frequency ( f grid ) 50 Hz
Grid Voltage (Vgrid ) line to line 121.2 kV
Grid Inductance (L grid ) 3 mH
Grid Resistance (R grid ) 0.1 Ω
Figure 5. Output Current, Circulating Current and Active Power when the fully sorted list is adopted
in the NLC.
When the best SMs are always selected, the algorithm that provides the complete sorted list
achieves a better balance in comparison with the max/min approach. However, it leads to a high
switching frequency, equal to 409 Hz in the studied case (Figure 6a). The max/min approach instead
only selects one SM to be inserted or bypassed when a change in Np,m is resulted from the NLC
(Figure 6b). Then, the switching frequency is intrinsically optimized and almost equal to 60 Hz.
365
Energies 2018, 11, 2394
By adopting the improved fsw for the Bitonic SN, as described in Figure 3, the fsw can be reduced.
In this case, it is comparable to the one achieved with the max/min method, but the achieved balance
is worse than the one achieved without the fsw optimization, as shown in Figure 6c.
(a)
(b)
(c)
Figure 6. Capacitor Voltages of the upper arm in the phase a: (a) Sorting Method without fsw
optimization; (b) Max/Min Approach; and (c) Sorting Method with fsw optimization as shown in
Figure 3.
Finally, it can be concluded that in normal condition and when the fsw optimization is active,
the max/min method and the sorting algorithm give almost the same balancing results and switching
frequency. From now on, the fsw optimization is considered active, if not differently mentioned.
366
Energies 2018, 11, 2394
(a)
(b)
Figure 7. Output Currents, Capacitor Voltages and Number of Switches during Phase to Ground Fault
at 0.5 s: (a) Max/Min Approach; and (b) Sorting Method.
On the other hand, the max/min method keeps only one switch per each Ts , requiring more
sampling periods to insert/bypass the needed SMs. This leads to a lower controller dynamic that
provokes a spike on the output current, as depicted in Figure 8. It is also possible to run the max/min
method several times in the same sampling period to get the required SMs, but this leads to a longer
execution time that can easily exceed the chosen Ts , not guaranteeing the proper controller behavior.
367
Energies 2018, 11, 2394
Figure 8. Zoom of the output currents on phase a during phase to ground fault. Blue line:
Sorting Method without fsw optimization; Green line: max/min approach; Red line: Sorting Method
with fsw optimization.
The advantages of the proposed SN over the min/max approach have been demonstrated and
the FPGA implementation of the Bitonic SN is now dealt with.
368
Energies 2018, 11, 2394
5.2. M-Factorized SN
To reduce the required number of CS operators, the previous SN structure can be factorized.
The objective is to reuse a single CS operator to perform more CS operations. However,
this optimization leads to an increase of the latency in the architecture. Then, a compromise between the
factorization level, i.e., which sub-structure of the Bitonic SN is factorized, and the latency is necessary.
Figure 10 shows an example using M = 8 and the factorization level L equal to 4. This means that the
four-input Bitonic SN sub-structure, highlighted in Figure 4, is factorized.
Figure 10. Hybrid factorized and pipelined synchronous eight-input SN with factorization level
equal to 4.
369
Energies 2018, 11, 2394
This solution allows a reduction of the required CS operators and, therefore, the used resources.
Indeed, the factorized four-input Bitonic SN only requires two CS operators instead of six. However,
the latency will be 6 instead of 3 and no other list can be inserted at the input during this calculation,
reducing the throughput of the architecture. It is worth noting that this solution also requires
eight Multiplexers.
5.4. Comparison
In this section, the previous SN structures are compared in terms of five-input Look-Up-Tables
(LUTs), Flip-Flops (FFs) and latency. The LUTs, FFs and latency for these structures can be easily
pre-evaluated, as shown in [20]. Figure 12a depicts the required LUTs with different factorization level.
It is shown that, by increasing the number of SMs, N, the required LUTs increase. The fully pipelined
is the structure that requires the highest amount of LUTs, as expected. By increasing the factorization
level, the needed LUTs can be reduced. The right y axis shows the percentage of the required LUT
when the selected low-cost System-on-Chip (SoC) device is considered. Then, it is obvious that a fully
pipelined structure for high numbers of N is impracticable with this kind of device. The same happen
for the FFs, as depicted in Figure 12b. On the other side, a higher factorization level leads a higher
latency number, as shown in Figure 12c. Thus, a compromise is required between the LUTs, FFs and
latency. The designer can then pre-evaluate the required resources and the latency to choose the best
solution for its requirements.
370
Energies 2018, 11, 2394
(a)
(b)
(c)
Figure 12. Evaluation of resources and timing performance of the fully pipelined Bitonic SN, the hybrid
structure with different factorization level and the fully factorized SN with different input lengths
(equal to the number of SMs N): (a) LUTs; (b) FFs; and (c) latency number.
371
Energies 2018, 11, 2394
time between the current control time Tcc and the time needed to the Bitonic SN Tbn ; and (b) the time
Tselection needed for selecting the SM to be inserted. From Equation (3) and Figure 13, it is possible to
derive the maximum sorting time Tmax,sort that has to be guaranteed:
6. Hardware-In-the-Loop Results
A MMC system is usually composed by tens or hundreds of modules per arm. The realization
of this kind of systems is very expensive, and then an usual approach is to test the control behavior
using HIL approach. In this section, HIL results are provided to validate the proposed sorting method
and compare it with the bubble SA and with the max/min approach in terms of the achieved sorting
execution time. The Zedboard platform, equipped with a Xilinx SoC Zynq-7020 device (named here as
Zynq), has been employed. This device consists of almost 85,000 logic element cells, 4.9 Mb block RAM,
220 DSP and two embedded ARM cortex A9 processors with a clock frequency equal to 667 MHz.
The MMC control, composed by the output current control and the circulating current control,
has been implemented in the first ARM core of the Processor System (PS). Along with the MMC
control, the bubble sorting algorithm and the max/min approach have been also carried out in the
same core. On the other hand, the proposed Bitonic SN has been implemented in the Programmable
Logic (PL) side by allowing the implementation of the hardware structures presented in Section 3
and the adoption of the timing diagram shown in Figure 13. The fully factorized Bitonic SN structure
has been chosen to save hardware resources. In the remaining ARM core, a single-phase MMC
model has been emulated based on [26]. The case of N = 32 has been considered, which is realistic
in view of the industrial implementation of MMC-HVDC by ABB [27]. A single-phase system has
been chosen considering that the performances of the Bitonic SN are identical for the single-phase and
the three-phase system. Indeed, in the three-phase case, it can be easily implemented in parallel for
achieving the same execution time shown in the following. The adopted capacitor value is 2.4 mF
and the output energy is equal to 33 MW. The remaining MMC parameters are shown in Table 1.
The whole implementation structure is depicted in Figure 14. The internal signals of the board are
read and displayed on the PC through a serial communication. A sag voltage of 50% is emulated after
105 ms. The corresponding capacitor voltages, output currents, and output voltages for the max/min
approach and the Bitonic SN are shown in Figure 15.
372
Energies 2018, 11, 2394
Interface
VCu,i VCl,i VCu,i VCl,i
Master
-
+
AXI
-
-
max/min
BSA
Approach
NLC
NLC pos u,PL pos u,PL Bitonic SN
nl nu
SM
selection
Interface
Slave
AXI
PWM
μC2 Emulated
RAM Plant
Idc iu
SM1,u x1 y1
x2 y2
vu SM2,u
x3 y3
SMN,u x4 y4
Rarm Larm
x5 y5
Lg x6 y6
Rarm Larm
SM1,l
x7 y7
x8 y8
vl SM2,l
Figure 14. Hardware architecture of the developed system. The processor system and the
programmable logic communicate through the AXI bus.
It is worth noting that the limited dynamic performance of the max/min approach cause an
undesired overshoot in is of about 28%. The achieved execution times for the three techniques in both
normal and fault conditions are summarized in Table 3. The sorting network has been implemented
in FPGA and then some operations can be executed in parallel: the current control and the sorting
algorithm in this case. Then, the control time is evaluated by summing up the longer execution time
between the current control and the sorting algorithm with the selection time.
On the other hand, the bubble SA and the max/min approach have been implemented in the
ARM core and then the current control, the sorting algorithm and the selection method are executed
in a sequential manner. The whole execution time is then evaluated by summing up all the terms.
The bubble SA achieves the worst timing performance by requiring maximum 4.56 μs in normal
conditions and 6.46 μs during the emulated fault. It is worth noting that its execution time is not fixed.
Thus, it is not deterministic and can be much higher than the ones obtained in this example.
373
Energies 2018, 11, 2394
Figure 15. Capacitor Voltages, Output Current, and output voltage during HIL results with max/min
approach (blue line) and Bitonic SN (red line).
Table 3. Maximum execution time of current control Tcc , sorting Tsorting , selection Tselection and total
control Tcontrol for the BSA, the max/min approach and the Bitonic SN during either normal (NC) and
fault conditions (FC).
The max/min method needs 2.56 μs and 2.75 μs to be performed in normal and fault conditions,
respectively. However, it does not provide a fully sorted list by causing current overshoot during faults.
It is important to mention that its execution time is also not fixed. On the other hand, the proposed SN
only requires a fixed execution time equal to 0.5 μs. It is also able to provide a fully sorted list useful
during fault cases or when more SMs are required (like at the start-up). Its short execution time allows
the proper behavior of the controller. However, if the number of SMs increases, the execution time
raises and Ts decreases at the same time. In the case the execution time of the fully factorized structure
is higher than the maximum allowable Ts , it is still possible to adopt either a hybrid structure or the
fully pipelined SN that allow a reduction of the execution time. This choice can be done before starting
the implementation thanks to the pre-evaluated resources and latency shown in Section 5 by reducing
the time-to-market. Then, the right compromise between the sorting time and the required resources
can be ensured. Table 4 shows the hardware resources required for the implementation of one fully
factorized 64-Bitonic SN in the adopted device.
Table 4. Required resources for the implementation of one fully factorized Bitonic SN with M = 64 in
the PL side of the Zynq device.
If a three-phase 64-SM MMC is of interest, six Bitonic SN have to be considered and then almost
60% of the available resources are consumed. It is also possible to use only one fully factorized Bitonic
SN for accomplishing the sorting of all the arms. Obviously, this solution leads to an increment in the
374
Energies 2018, 11, 2394
execution time. Another solution can be to implement a fully pipelined Bitonic SN that allows a higher
throughput (a new list can be sent after the first stage has been performed) and then a lower execution
time at the expense of an increment of the required resources. As already said, the right compromise
has to be achieved depending on the case and the discussion in Section 5 is for this aim.
7. Conclusions
In this paper an FPGA-implementation of the Bitonic Sorting Network for MMC applications
has been proposed. The main advantages of the proposed sorting method are: the fixed parallel
structure and the possibility to be efficiently implemented in FPGA devices. This leads to a
shorter and deterministic execution time, which results in a better performance of the CVB control.
Three different architectures have been proposed to meet the different possible requirements of the
application of interest: the fully pipelined architecture, the hybrid structure and the fully factorized SN.
Their hardware resources and latency have been pre-evaluated and compared. This allows choosing
the structure that best fits the application requirements before starting the implementation. Simulation
results have been given in both normal and faulty conditions to compare the proposed sorting method
with the max/min approach. The latter is considered to request the shortest execution time but it does
not provide the fully sorted list by deteriorating the dynamic performance of the controller.
The fully factorized Bitonic SN has been implemented in a low-cost Xilinx Zedboard along with
the MMC plant model and the corresponding control. Based on the HIL results, the proposed sorting
method shows superior performance. Moreover, the execution time and the output current of the
implemented SN have been compared with the ones achieved with the bubble sorting algorithm and
the max/min technique in the case of N = 32 and a sag voltage of 50%. The output current obtained
with the max/min technique presents an overshoot of about 28% in comparison with the one achieved
by adopting an algorithm that provides a fully sorted list. Then, the main gain of the proposed SN
compared to the max/min approach is the ability to handle fault occurrences. Moreover, the sorting
and selection for the SN require 2.96 μs to be executed against the 9.22 μs and 3.05 μs needed by the
bubble SA and the max/min approach, respectively. Considering the hardware resources, it requires
about 10% of the available resources of the adopted board.
Author Contributions: Conceptualization, M.R. and L.M.; Software, M.R.; Validation, M.R.; Writing—original
draft, M.R. and L.M.; Writing—review and editing, E.M. and R.T.
Conflicts of Interest: The authors declare no conflict of interest.
References
1. Lyu, J.; Cai, X.; Molinas, M. Frequency domain stability analysis of MMC-based HVDC for wind farm
integration. IEEE J. Emerg. Sel. Top. Power Electron. 2016, 4, 141–151. [CrossRef]
2. Bergna, G.; Berne, E.; Egrot, P.; Lefranc, P.; Arzande, A.; Vannier, J.C.; Molinas, M. An energy-based controller
for HVDC modular multilevel converter in decoupled double synchronous reference frame for voltage
oscillation reduction. IEEE Trans. Ind. Electron. 2013, 60, 2360–2371. [CrossRef]
3. Jung, J.J.; Lee, H.J.; Sul, S.K. Control strategy for improved dynamic performance of variable-speed drives
with modular multilevel converter. IEEE J. Emerg. Sel. Top. Power Electron. 2015, 3, 371–380. [CrossRef]
4. Antonopoulos, A.; Ilves, K.; Ängquist, L.; Nee, H.P. On interaction between internal converter dynamics and
current control of high-performance high-power AC motor drives with modular multilevel converters.
In Proceedings of the 2010 IEEE Energy Conversion Congress and Exposition, Atlanta, GA, USA,
12–16 September 2010.
5. Jafri, K.; Chen, B.C.; You, S.Z.; Chen, Y. Static and dynamic characteristics of a novel statcom based on
modular multilevel converter. In Proceedings of the IET International Conference on Information Science
and Control Engineering 2012 (ICISCE 2012), Shenzhen, China, 7–9 December 2012.
6. Bhesaniya, M.M.; Shukla, A. current source modular multilevel converter: Detailed analysis and statcom
application. IEEE Trans. Power Deliv. 2016, 31, 323–333. [CrossRef]
375
Energies 2018, 11, 2394
7. Debnath, S.; Qin, J.; Bahrani, B.; Saeedifard, M.; Barbosa, P. Operation, control, and applications of the
modular multilevel converter: A review. IEEE Trans. Power Electron. 2015, 30, 37–53. [CrossRef]
8. Nami, A.; Liang, J.; Dijkhuizen, F.; Demetriades, G. Modular multilevel converters for HVDC applications:
Review on converter cells and functionalities. IEEE Trans. Power Electron. 2015, 30, 18–36. [CrossRef]
9. Hagiwara, M.; Akagi, H. Control and experiment of pulsewidth-modulated modular multilevel converters.
IEEE Trans. Power Electron. 2009, 24, 1737–1746. [CrossRef]
10. Lesnicar, A.; Marquardt, R. An innovative modular multilevel converter topology suitable for a wide
power range. In Proceedings of the 2003 IEEE Bologna Power Tech Conference Proceedings, Bologna, Italy,
23–26 June 2003.
11. Siemaszko, D. Fast sorting method for balancing capacitor voltages in modular multilevel converters.
IEEE Trans. Power Electron. 2015, 30, 463–470. [CrossRef]
12. Li, W.; Gregoire, L.; Belanger, J. A modular multilevel converter pulse generation and capacitor voltage
balance method optimized for FPGA implementation. IEEE Trans. Ind. Electron. 2015, 62, 2859–2867.
[CrossRef]
13. Saad, H.; Guillaud, X.; Mahseredjian, J.; Dennetière, S.; Nguefeu, S. MMC capacitor voltage decoupling and
balancing controls. IEEE Trans. Power Deliv. 2015, 30, 704–712. [CrossRef]
14. Monmasson, E.; Idkhajine, L.; Cirstea, M.N.; Bahri, I.; Tisan, A.; Naouar, M.W. FPGAs in industrial control
applications. IEEE Trans. Ind. Inform. 2011, 7, 224–243. [CrossRef]
15. Fan, B.; Li, Y.; Wang, K.; Zheng, Z.; Xu, L. Hierarchical system design and control of an MMC-based
power-electronic transformer. IEEE Trans. Ind. Inform. 2017, 13, 238–247. [CrossRef]
16. Vasiladiotis, M.; Rufer, A. Analysis and control of modular multilevel converters with integrated battery
energy storage. IEEE Trans. Power Electron. 2015, 30, 163–175. [CrossRef]
17. Shen, Z.; Dinavahi, V. Real-time device-level transient electrothermal model for modular multilevel converter
on FPGA. IEEE Trans. Power Electron. 2016, 31, 6155–6168. [CrossRef]
18. Mathe, L.; Dan Burlacu, P.; Teodorescu, R. Control of a modular multilevel converter with reduced internal
data exchange. IEEE Trans. Ind. Inform. 2017, 13, 248–257. [CrossRef]
19. Mueller, R.; Teubner, J.; Alonso, G. Sorting Networks on FPGAs. VLDB J. 2012, 21, 1–23. [CrossRef]
20. Ricco, M.; Mathe, L.; Teodorescu, R. FPGA-based implementation of sorting networks in MMC applications.
In Proceedings of the 2016 18th European Conference on Power Electronics and Applications (EPE’16 ECCE
Europe), Karlsruhe, Germany, 5–9 September 2016.
21. Perez, M.; Bernet, S.; Rodriguez, J.; Kouro, S.; Lizana, R. Circuit topologies, modeling, control schemes,
and applications of modular multilevel converters. IEEE Trans. Power Electron. 2015, 30, 4–17. [CrossRef]
22. Sharifabadi, K.; Harnefors, L.; Nee, H.P.; Norrga, S.; Teodorescu, R. Design, Control, and Application of Modular
Multilevel Converters for HVDC Transmission Systems; Wiley: Hoboken, NJ, USA, 2016.
23. Hassanpoor, A.; Angquist, L.; Norrga, S.; Ilves, K.; Nee, H. Tolerance band modulation methods for modular
multilevel converters. IEEE Trans. Power Electron. 2015, 30, 311–326. [CrossRef]
24. Ilves, K.; Harnefors, L.; Norrga, S.; Nee, H.P. predictive sorting algorithm for modular multilevel converters
minimizing the spread in the submodule capacitor voltages. IEEE Trans. Power Electron. 2015, 30, 440–449.
[CrossRef]
25. Li, Z.; Gao, F.; Xu, F.; Ma, X.; Chu, Z.; Wang, P.; Gou, R.; Li, Y. Power module capacitor voltage balancing
method for a 350-kv/1000-MW modular multilevel converter. IEEE Trans. Power Electron. 2016, 31, 3977–3984.
[CrossRef]
26. Ricco, M.; Gheorghe, M.; Mathe, L.; Teodorescu, R. System-on-chip implementation of embedded real-time
simulator for modular multilevel converters. In Proceedings of the 2017 IEEE Energy Conversion Congress
and Exposition (ECCE), Cincinnati, OH, USA, 1–5 October 2017.
27. Jacobson, B.; Karlsson, P.; Asplund, G.; Harnefors, L.; Jonsson, T. VSC-HVDC transmission with cascaded
two-level converters. In Proceedings of the CIGRE Conference, Paris, France, 22–27 August 2010.
© 2018 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access
article distributed under the terms and conditions of the Creative Commons Attribution
(CC BY) license (http://creativecommons.org/licenses/by/4.0/).
376
energies
Article
Hybrid Modulated Model Predictive Control in a
Modular Multilevel Converter for Multi-Terminal
Direct Current Systems
Zhi Wu 1 , Jiawei Chu 1 , Wei Gu 1, *, Qiang Huang 2 , Liang Chen 2 and Xiaodong Yuan 2
1 School of Electrical Engineering, Southeast University, Nanjing 210096, China; [email protected] (Z.W.);
[email protected] (J.C.)
2 Jiangsu Electrical Power Company Research Institute, State Grid, Nanjing 211100, China;
[email protected] (Q.H.); [email protected] (L.C.); [email protected] (X.Y.)
* Correspondence: [email protected]; Tel.: +86-25-8779-6169
Abstract: In this paper a hybrid modulated model predictive control (HM2 PC) strategy for
modular-multilevel-converter (MMC) multi-terminal direct current (MTDC) systems is proposed for
supplying power to passive networks or weak AC systems, with the control objectives of maintaining
the DC voltage, voltage stability and power balance of the proposed system. The proposed strategy
preserves the desired characteristics of conventional model predictive control method based on finite
control set (FCS-MPC) methods, but deals with high switching frequency, circulating current and
steady-state error in a superior way by introducing the calculation of the optimal output voltage level
in each bridge arm and the specific duty cycle in each Sub-Module (SM), both of which are well-suited
for the control of the MMC system. In addition, an improved multi-point DC voltage control strategy
based on active power balanced control is proposed for an MMC-MTDC system supplying power
to passive networks or weak AC systems, with the control objective of coordinating the power
balance between different stations. An MMC-HVDC simulation model including four stations has
been established on MATLAB/Simulink (r2014b MathWorks, Natick, MA, USA). Simulations were
performed to validate the feasibility of the proposed control strategy under both steady and transient
states. The simulation results prove that the strategy can suppress oscillations in the MMC-MTDC
system caused by AC side faults, and that the system can continue functioning if any one of the
converters are tripped from the MMC-MTDC network.
Keywords: MMC-MTDC; hybrid modulated model predictive control; optimal output voltage level;
multi-point DC control
1. Introduction
In recent years, MMCs are gaining a lot of attention in high power/high voltage applications
that involve interfacing high-voltage direct current (HVDC) systems to high voltage three-phase
AC grids due to their high modularity and scalability [1,2]. Investment and research in high-voltage
direct-current (HVDC) systems has been actively pursued and expanded with the aim of improving the
efficiency and reliability of electric power generation, large-capacity power transmission, and linkage
among different networks [1–6].
At present, research on control strategies for MMC-HVDC systems has yielded fruitful results in
industry and academia. When an MMC-HVDC transmission system supplying passive networks is
operating normally, its rectifier station generally uses constant current control and constant reactive
control, which contains an outer power loop and an inner current loop. This control method is relatively
mature and fixed, and details on the method are available in the literature [6–10]. Therefore, in this
paper we focus on the control strategy used in the inverter station.
Traditional inverter station control usually involves a double closed-loop control (DCLC) strategy
based on an outer voltage loop and an inner current loop. Since the response speed of the outer
voltage loop is significantly slower than that of the inner current loop, the voltage quality is poor
when supplying power to nonlinear loads. Furthermore, the response time of the voltage recovery
increases when there are load fluctuations. Meanwhile, the overall control structure, embodying
multiple proportional-integral (PI) controllers with hard-to-tune parameters, is relatively complex,
and is therefore susceptible to structural parameters of the model [11,12].
Model predictive control (MPC) is gradually becoming more adopted as a control method of
power converters because it is a non-linear optimization control method that can deal with nonlinear
systems with complex constraints. The advantages demonstrated by this method are diverse, such
as a fast response, flexibility of various goals, easy inclusion of nonlinearities, and the availability of
simple modulation techniques. The MPC method based on a finite control set (FCS-MPC) constructs
a multi-objective optimization function, evaluates the system’s future state corresponding to the
finite-switching combination of the converter, and selects the switch combination that minimizes the
value of the objective function as the switching state for the next switching cycle. MPC has been
applied to motor drives, high power factor rectification, and DC transmission, among others [13–21].
Reference [13] shows that the cost function may include a control target such as reduced switching
frequency, reduced common-mode voltage, reduced reactive power, and reduced current ripple when
controlling a power converter. Compared to proportional integral (PI) or proportional-resonant
(PR) controllers, the MPC method can improve total harmonic distortion (THD) and transient
characteristics [21]. References [16–18] uses FCS-MPC for the control of the MMC, which predicts
the AC current, the circulating current, the sub-module capacitance voltage, and the resulting
switching action of all possible switch combinations of the upper and lower arms in each control cycle.
This method selects the switch combination that minimizes the objective function as the output of the
next cycle and implements multi-objective optimal control.
For an MMC system with a large number of sub-modules, the existing FCS-MPC control methods
involve a large amount of calculation. The Modulated Model Predictive Control (M2 PC) method
preserves all the advantages of the FCS-MPC method and solves some problems associated with the
FCS-MPC method, such as enabling variable switching frequency, delay compensation, and short
sampling times [22–24]. However, little to no effort has been made to develop a M2 PC method for the
control of MMC-HVDC systems supplying power to passive networks or weak AC systems. This paper
aims to propose a new Hybrid M2 PC method for control of the MMC-MTDC system that addresses
the key limitations faced by the FCS-MPC methods.
The contributions of this paper to the research field are:
(1) A novel voltage control strategy based on M2 PC is proposed for MMC-MTDC systems
supplying power to passive networks or weak AC systems, which effectively regulates AC line
currents and allows converters to comply with current references under severe conditions, such as
severe power fluctuations or grid faults.
(2) The proposed strategy reduces the amount of calculation required compared with FCS-MPC
methods when calculating optimal output voltage levels.
(3) An improved multi-point DC voltage control strategy based on active power balanced control
is proposed and proved to be more applicable to MMC-MTDC systems.
378
Energies 2018, 11, 1861
independent AC power supplies. us and up represent the AC voltage of the sending end of the rectifier
station and the receiving end of the inverter station, respectively. idc represents the current of the DC
line. Further, Cdc denotes the DC capacitor, and C1 and L1 (C3 and L3 ) constitute the LC low-pass
filter, which filters out the high-order harmonics on the inverter side, while C2 can also provide some
of the AC network reactive power support to compensate for the impact of load fluctuations on
voltage stability.
X6 X S X
8 6 5 S / S L/
]6 56 /6 /
LGF
X = /
L &
X6 X S
86 ]6 56 /6 5S /S / L/
X = /
L &
Figure 1. System configuration of a modular multilevel converter based multi-terminal direct current
(MMC-MTDC) system for supplying passive networks.
Figure 2a presents the Circuit diagram of the inverter side of a three-phase MMC with six arms.
Generally speaking, each arm is composed of a half-bridge submodule (SM). The MMC legs consist
of three phases, a, b, and c, which are represented by the subscript j. Subscripts u and l represent the
upper and lower arms of each leg. N series-connected SM, as well as the equivalent internal resistance
(R) and an inductor (L), make up each leg. Rp1 and Lp1 denote the AC filter inductance and the line
equivalent resistance of inverter station 1. Figure 2b shows the circuit diagram of SM. The switches T1
and T2 always operate in a complementary fashion.
5 S /S X S
5 5 5
/ / / LRD
LRE
5 S /S
LRF
XGF
/ / / 5 S /S
5 5 5
ȱ
(a)ȱ (b)ȱ
Figure 2. Circuit diagram of MMC: (a) Circuit diagram of the inverter side of a three-phase MMC;
(b) Circuit diagram of Sub-Module (SM).
379
Energies 2018, 11, 1861
Using Kirchhoff’s Voltage Law (KVL), the transient mathematical model of the AC side of an
MMC can be obtained,
disj 1
= (2udj − 2u p1 j − Rse isj ) (1)
dt Lse
dicj 1
= (u − ucj − Ricj ) (2)
dt L dc
where ⎧
⎪ ucj = 12 (uuj + ulj )
⎨ Lse = L + 2L p1
udj = − 2 (uuj − ulj ) = 12 (ulj
1
− uuj ) and
⎪
⎩ Rse = R + 2R p1
icj = 12 (iuj + ilj )
where ucj and udj denote common voltage and differential voltage, respectively, and icj represents
circulation current.
Under balanced control the capacitor voltages of each sub module are equal, and the output
voltage of the upper and lower bridge arm varies from 0 and N levels:
⎧
⎨ u = nuj u , n ∈ [0, 1, · · · , N ]
uj N dc uj
n (3)
⎩ u = lj u dc , n ∈ [0, 1, · · · , N ]
lj N uj
where nuj and nlj represent the number of SMs for upper and lower arm inputs, respectively, and uuj
and ulj represent the voltages of the upper and lower arms, respectively.
1
Ψsj (t) = (2udj − 2u p1 j − Rse isj ) (4)
Lse
1
Ψcj (t) = (u − ucj − Ricj ) (5)
L dc
Let Ts represent the sampling time, kTs represent the present moment and (k + 1)Ts represent the
moment at the next control period. Utilizing the trapezoidal integration formula in Equation (4),
Ts
isj (k + 1) − isj (k ) = (Ψsj (k + 1) + Ψsj (k)) (6)
2
Considering that the fluctuation of usj is negligible over one sampling period from kTs to (k + 1)Ts ,
it can be approximated as invariant. Thus, the discretization of Equation (4) can be obtained,
Similarly, considering that udc is constant during the sampling time, Equation (4) can be
rewritten as,
T
icj (k + 1) = icj (k ) + Ls (udc (k ) − ucj (k )) (8)
Equations (6) and (8) can be used to predict the AC line and circulating current values for all
combinations of SM operations.
M2 PC requires a suitable modulation scheme as part of the minimization of the cost function in
the MPC algorithm. In this paper we use a modulation scheme that is particularly suitable for high
power converter control. In each sampling period, only one branch of one SM is allowed to switch, so
as to obtain the total switching frequency of the SM, which is half of the sampling frequency [22–24].
380
Energies 2018, 11, 1861
This function becomes quite important when considering high power applications. Moreover, this
switching mode helps to reduce the computational needs of the controller.
The proposed M2 PC method evaluates a cost function J(k) for all possible voltage levels in each
leg at the start of each sampling period. This cost function with multiple prediction horizons can be
defined as,
J p1 j (k + 1) = u p1 j (k + 1) − u∗p1 (9)
where
∗ ( k +1) T
u∗p1 j = Us∗ e j2π f s (10)
where nuj * and nlj * represent the reference voltage levels of nuj and nlj , respectively.
In general, the number of sub-modules applied to the MMC is large. If the traditional FCS-MPC
control strategy is used, the computational load is undoubtedly enormous [26]. This paper uses
Equation (11) to calculate the optimal output level of the bridge arm at the next sampling time, and then
considers its neighboring 2M (M ≥ 1) levels as a finite control set by selecting the appropriate M value,
which can significantly reduce the amount of calculations in one control cycle. It is worth noting that
in most cases nuj * and nlj *, calculated according to Equation (11), are not integers. This paper uses the
method of rounding down, then selects the level combination and the upper or lower bridges. The 2M
level combinations adjacent to the arm together constitute a new set of modulable finite controls.
A key point of voltage control in the M2 PC strategy proposed in this paper is to calculate nuj and
nlj based on the two specific voltage values of the passive network output voltage and the circulating
current suppression voltage, based on Equation (11) [27–29]. The reference value thus minimizes
the state performance function in Equation (7) based on the non-monotonic change characteristic of
Jzj (k + 1). From the structural characteristics of the MMC it can be seen that, whether it is the upper or
lower arms, increasing the number of levels in the bridge arm can increase the output value of the
control target to the passive network at a future point, while reducing the number of arm levels will
reduce the output voltage value to the passive network.
Therefore, the corresponding upper and lower arm level configuration parameters can be
calculated according to the voltage prediction reference value at the beginning of the next period. Let
the increase and decrease in the number of levels of the j phase affect the output voltage values of the
next period by Vj 1 and Vj 2 , respectively. In one control period described by setting a specific time node
t p1 j executing the control commands one after another leads u p1 j (k + 1) to finally equal u∗p1 j .
The ratio of time changing between Vj 1 and Vj 2 is called the duty cycle. The details of calculating
this duty cycle for the proposed M2 PC method are explained in detail in Reference [30]. Employing
the formulation from Reference [30], the duty cycle can be obtained as,
u∗p1 j − u2p1 j
d p1 j = (12)
u1p j − u2p
1 1j
where u1p1 j and u2p1 j can be obtained from Equation (10) by substituting usj (k) with Vj 1 and Vj 2
respectively. In Equation (12), d p1 j represents the time ratio of usj (k) needs to be set to Vj 1 .
Similarly, the cost function and the duty cycle corresponding to the circulating current are,
∗
Jcj (k + 1) = icj (k + 1) − icj (13)
381
Energies 2018, 11, 1861
∗ − i2
icj cj
dcj = (14)
i1cj − i2cj
X S M
XS M ǂ
QXM
X S M N
ǂ ǂ
X S M N QXM QXM
ǂ
QXM
X S M N
ǂ
QXM X S M
W
N7V N 7V N 7V
Figure 3. Principle of one step Modulated Model Predictive Control (M2 PC).
X S M
XS M ǂ
QXM
X S M N ǂ
QXM
X S M N ǂ
QXM
ǂ
X S M N QXM
ǂ
QXM X S M
W
N7V N 7V N 7V
Therefore, the key principle of the proposed strategy is to solve for the optimal solution of the
predictive model in multiple periods. In this situation, the value of the state variable in the multi-step
predictive model (X(k + p)) needs to be calculated, and the cost function needs to make corresponding
adjustments. Taking the two-step situation as an example, this paper utilizes Simpson’s formula
382
Energies 2018, 11, 1861
to calculate X(k + 2), which can minimize the calculation error. For multi-step cases, Runge-Kutta
formulae can be used.
Taking two-step in Figure 4 as an example, utilizing the Simpson integration formula in
Equations (4) and (5),
Ts
isj (k + 2) − isj (k ) = (Ψsj (k + 2) + 4Ψsj (k + 1) + Ψsj (k)) (15)
6
Ts
icj (k + 2) − icj (k ) = (Ψcj (k + 2) + 4Ψcj (k + 1) + Ψcj (k)) (16)
6
Similarly, considering that usj and udc are constant during the sampling time,
∗
J (k + 1) = λ1 u p1 j (k + 2) − u∗p1 + λ2 icj (k + 2) − icj (17)
J (k + 1) = λ1 J pj (k + 2) + λ2 Jcj (k + 2) (18)
The two weighting factors, λ1 and λ2 can be adjusted to achieve the desired the control
performance. Since the current cost function Jcj (k + 2) already includes the amount of current necessary
to charge the DC-link capacitor to the desired voltage, the importance of Jpj (k + 2) lies in its ability
to reduce the steady-state error in the DC-link voltage, related to the converter losses, which is not
considered in Jcj (k + 2). Therefore, the ratio λ1 /λ2 is typically set to the minimum value that ensures
zero steady-state error in the DC-link voltage [31,32].
The switching times for the two selected vectors are calculated by solving the linear system of
equations in Equation (18). Once the value of K is obtained from Equation (18), the expressions for the
switching times are obtained
⎧ (1) ⎧
⎪
⎪ Jcj = K(1) ⎪ (2)
⎪
⎪ ⎪
⎪ (1) Jcj
⎨ dcj =
Jcj
⎪
⎨ ⎪ (1) (2)
Jcj + Jcj
(2) K
dcj = (2) ⇒ (19)
⎪
⎪ Jcj ⎪ (2)
⎪
(1)
Jcj
⎪
⎪ ⎪
⎪
⎪
⎩ d (1) + d (2) = 1 ⎩ dcj = (1)
Jcj + Jcj
(2)
cj cj
383
Energies 2018, 11, 1861
Once the switching times are calculated, the M2 PC algorithm chooses the two inverter states for
times dcj (1) and dcj (2) if they minimize the following global cost function:
This solution is proposed as an alternative to an analytical duty cycle calculation. The overall
M2 PC scheme is shown in Figure 5.
8 VS N
3GF N
] T VS 8 VS UPV 8 VS N LVS N
LVS N
*LS
*VS
3GF N LVS N
LVS N *LS
LDF N
8 GF N 6 VS N G VS N
] ]
6VS N G VS N
6VS00&V
N
(3) The system level control system only updates the active power reference value to each
converter station when changing the scheduling trend. At the other times, the converter stations are
independently controlled according to the reference value calculated from the active power after the
latest update, without much communication needs.
384
Energies 2018, 11, 1861
Quantity Value
AC sources system nominal Voltage 35 kV
Nominal DC voltage ±10 kV
Rs 0.1 Ω
Ls 5 mH
Rp 0.02 Ω
L2 1.3 mH
C2 200 μF
DC capacitance Cdc 4700 μF
DC line length 10 km
AC load system nominal voltage 20 kV
The number of stations 4
Arm inductance L 1 mH
Arm resistance R 0.2 Ω
SM capacitor C 1.2 mF
The number of SMs 10
385
Energies 2018, 11, 1861
1000
500
I/A
-500
-1000
0.02 0.025 0.03 0.035 0.04 0.045 0.05 0.055 0.06
t/s
(a)ȱ
1000
500
0
I/A
-500
-1000
0.02 0.025 0.03 0.035 0.04 0.045 0.05 0.055 0.06
t/s
(b)ȱ
Figure 6. The simulation results of AC current: (a) Traditional control strategy; (b) The strategy
proposed in this paper.
By comparing and calculating the current error of the traditional control strategy and the strategy
proposed in this paper, the current signal Total Harmonic Distortion (THD) values are 9.88% and
1.83%, respectively. It can be seen that when large-capacity nonlinear loads are connected to the grid
system the quality of the power supply using the traditional control strategy is significantly reduced,
while the proposed method can still maintain acceptable static performance. Therefore, in the face of
large-scale renewable energy integration into the distribution network, the proposed control strategy
has great advantages in ensuring the quality of the power supply.
The simulation results in Figure 7a,b compare the inhibition of circulation current in a MMC
converter using M2 PC with the improved multi-step M2 PC. At 0.25 s, the circulation suppression
function is enabled separately. As can be seen, the circulation current contains some DC and low
harmonic components. After the function is enabled, the circulation current under both control
methods is rapidly reduced. The difference is that the improved multi-step M2 PC is able to further
reduce the size of the circulation current and lower the amplitude of the pulse in the circulation current.
400
300
200
I/A
100
0
0.15 0.2 0.25 0.3 0.35
t/s
(a)ȱ
Figure 7. Cont.
386
Energies 2018, 11, 1861
400
300
200
I/A
100
0
0.15 0.2 0.25 0.3 0.35
t/s
(b)ȱ
Figure 7. The simulation results of circulation current: (a) M2 PC; (b) Improved multi-step M2 PC.
20
MMC2 MMC4
0
P/MW
-20
-40
-60
4 6 8 10 12 14
t/s
(a)ȱ
20
MMC2 MMC4
0
P/MW
-20
-40
-60
4 6 8 10 12 14
t/s
(b)ȱ
Figure 8. Cont.
387
Energies 2018, 11, 1861
20
MMC2 MMC4
0
P/MW
-20
-40
-60
4 6 8 10 12 14
t/s
(c)ȱ
Figure 8. Simulation waveforms of load fluctuation: (a) The active power of the receiving end controlled
by double closed-loop control (DCLC); (b) The active power of receiving end controlled by an MPC
method based on a finite control set (FCS-MPC); (c) The active power of the receiving end controlled
by the hybrid modulated model predictive control (HM2 PC).
22
MMC2 MMC4
21
U/KV
20
19
18
4 6 8 10 12 14
t/s
(a)ȱ
22
MMC2 MMC4
21
U/KV
20
19
18
4 6 8 10 12 14
t/s
(b)ȱ
22
MMC2 MMC4
21
U/KV
20
19
18
4 6 8 10 12 14
t/s
(c)ȱ
Figure 9. Simulation waveforms of load fluctuation: (a) The DC voltage controlled by DCLC; (b) the DC
voltage controlled by FCS-MPC; (c) the DC voltage controlled by the HM2 PC.
388
Energies 2018, 11, 1861
The HM2 PC strategy proposed in this paper is faster than DCLC FCS-MPC. The DC voltage under
control shows almost no fluctuation under load fluctuation, and the voltage fluctuation and power
fluctuation in steady state are the smallest among the three control modes.
4.3. Aimulating the Exit of the Main Control Station Due to Failure
In this simulation scenario, the MMC1 station and the MMC4 station maintain a constant load of
10 MW and 40 MW, respectively. Initially, the VSC1 station and the VSC3 station respectively issue
20 MW and 30 MW of active power. At 5 s, the main control station MMC1 exited due to a failure.
At this time, the MMC3 station became the new main control station and simultaneously delivered
power to the MMC2 station and the MMC4 station.
The comparison of the active power transmitted by the MMC2 station and the MMC4 station in
each coordinated control mode is shown in Figure 10, and the comparison of the DC voltage at each
end of the MTDC system is shown in Figure 11.
20
MMC2 MMC4
0
P/MW
-20
-40
2 3 4 5 6 7 8 9 10 11 12
t/s
(a)ȱ
20
MMC2 MMC4
0
P/MW
-20
-40
2 3 4 5 6 7 8 9 10 11 12
t/s
(b)ȱ
20
MMC2 MMC4
0
P/MW
-20
-40
2 3 4 5 6 7 8 9 10 11 12
t/s
(c)ȱ
Figure 10. Simulation of the operation during an exit of an input converter station: (a) The active
power of the receiving end controlled by DCLC; (b) the active power of the receiving end controlled by
FCS-MPC; (c) the active power of the receiving end controlled by HM2 PC.
389
Energies 2018, 11, 1861
22
MMC2 MMC4
21
P/MW
20
19
18
2 3 4 5 6 7 8 9 10 11 12
t/s
(a)ȱ
22
MMC2 MMC4
21
P/MW
20
19
18
2 3 4 5 6 7 8 9 10 11 12
t/s
(b)ȱ
22
MMC1 MMC2
21
P/MW
20
19
18
2 3 4 5 6 7 8 9 10 11 12
t/s
(c)ȱ
Figure 11. Simulation of the operation during an exit of the input converter station: (a) The DC voltage
controlled by DCLC; (b) the DC voltage controlled by FCS-MPC; (c) the DC voltage controlled by
HM2 PC.
In this simulation scenario involving a large disturbance where one end completely withdraws
from the four-terminal system, all three coordinated controls can still achieve three-terminal power
balance. However, the lack of voltage control capability in the master-slave control method causes an
overshoot of active power to almost reach the upper limit of the master station control. If the limit is
exceeded, it may cause a change in the control master station, thereby forcing the MMC4 station to
maintain the DC voltage by reducing the load power. The power adjustment speed of the multi-point
voltage control strategy based on an active power balance proposed in this paper performs better
than voltage drop control, achieving the minimum voltage fluctuation and power fluctuation in the
steady state.
390
Energies 2018, 11, 1861
simulator OP5600 (OPAL-RT technologies Inc, Montreal, QC, Canada) and the high frequency power
electronic devices are placed in the nanosecond real-time simulator OP7020 (OPAL-RT technologies
Inc., Montreal, QC, Canada) containing FPGA, which are connected to the external controller through
the I/O interface and communication protocol. Then, the control strategy proposed in this paper can
be rewritten into the form of C language and fed into the external controller (usually Digital Signal
Processor (DSP)). In addition, it can test different running scenarios by dynamically adjusting the
reference values of state quantities in the control subsystem of OP5600 in real time. In a nutshell,
experimental verification is the next research focus that needs to be overcome.
Upper Computer
Ethernet
Measured
Sample variables
AI
Switch control DO
commands
OP5600
DI
6/12 Cores Switch state
An External
Controller
PCI/E Link For The
Communication Flexible DC
Protocol System
Intelligent Fiber optic
signal
Interface
Box
(Measurement
OP7020 signals, switching
FPGA signals, etc)
Figure 12. A schematic diagram of the real-time controller hardware-in-the-loop test platform.
6. Conclusions
A hybrid modulated model predictive control (HM2 PC) strategy for modular-multilevel-converter
(MMC) multi-terminal direct current (MTDC) systems supplying power to passive networks or weak
AC systems was developed to improve the control performance of maintaining the DC voltage and
power balance of the proposed system. The proposed method, on the basis of fully preserving
the superiority of the traditional model predictive control method, reduces the amount of control
operations and has the characteristics of flexible structure, good robustness, and strong scalability.
Next, an improved multi-point DC voltage control strategy based on active power balanced
control is proposed, which is proved to have a fast transient response and includes the control target
directly in the cost function minimization algorithm. It has the further advantage of including a
suitable modulation scheme inside the cost function minimization algorithm, in order to maintain a
constant switching frequency equal to half the sampling frequency.
Finally, the MMC-MTDC system supplying power to passive networks or weak alternating
current systems under different operating conditions is simulated to analyze and demonstrate the
feasibility and effectiveness of the proposed control strategy. Besides, the scheme of experimental
verification is mentioned in detail.
391
Energies 2018, 11, 1861
Author Contributions: All of the authors contributed to this research. The Authors’ contributions are as follows:
Writing-Original Draft, Z.W.; Writing-Review & Editing, Z.W., J.C. and W.G.; Data Curation and Investigation,
Q.H.; Formal Analysis and Supervision, L.C.; Methodology and Resources, X.Y.
Funding: This work was supported by Science and Technology Project of State Grid (J2017037) and The National
Natural Science Foundation of China (for youth, 51707033).
Conflicts of Interest: The authors declare no conflict of interest.
References
1. Nami, A.; Liang, J.; Dijkhuizen, F.; Demetriades, G.D. Modular Multilevel Converters for HVDC Applications:
Review on Converter Cells and Functionalities. IEEE Trans. Power Electron. 2015, 30, 18–36. [CrossRef]
2. Ni, Y.X.; Vittal, V.; Kliemann, W.; Fouad, A.A. Nonlinear modal interaction in HVDC/AC power systems
with DC power modulation. IEEE Trans. Power Syst. 2015, 11, 2011–2017. [CrossRef]
3. Li, X.; Song, Q.; Liu, W.; Rao, H.; Xu, S.; Li, L. Protection of Nonpermanent Faults on DC Overhead Lines in
MMC-Based HVDC Systems. IEEE Trans. Power Deliv. 2013, 28, 483–490. [CrossRef]
4. Aleenejad, M.; Mahmoudi, H.; Ahmadi, R. Unbalanced Space Vector Modulation with Fundamental Phase
Shift Compensation for Faulty Multilevel Converters. IEEE Trans. Power Electron. 2016, 31, 7224–7233.
5. Guo, C.; Zhao, C. Supply of an Entirely Passive AC Network through a Double-Infeed HVDC System.
IEEE Trans. Power Electron. 2010, 25, 2835–2841.
6. Lesnicar, A.; Marquardt, R. An innovative modular multilevel converter topology suitable for a wide
power range. In Proceedings of the 2003 IEEE Bologna Power Tech Conference Proceedings, Bologna, Italy,
23–26 June 2003; Volume 3, p. 6.
7. Gnanarathna, U.N.; Gole, A.M.; Jayasinghe, R.P. Efficient Modeling of Modular Multilevel HVDC Converters
(MMC) on Electromagnetic Transient Simulation Programs. IEEE Trans. Power Deliv. 2015, 26, 316–324.
[CrossRef]
8. Zhang, L.; Harnefors, L.; Nee, H.P. Interconnection of two very weak ac systems by VSC-HVDC links using
power-synchronization contro. IEEE Trans. Power Syst. 2011, 26, 344–355. [CrossRef]
9. Aleenejad, M.; Mahmoudi, H.; Moamaei, P.; Ahmadi, R. A New Fault-Tolerant Strategy Based on a Modified
Selective Harmonic Technique for Three-Phase Multilevel Converters with a Single Faulty Cell. IEEE Trans.
Power Electron. 2016, 31, 3141–3150. [CrossRef]
10. Aleenejad, M.; Mahmoudi, H.; Ahmadi, R. A Multi-Fault Tolerance Strategy for Three Phase Cascaded
H-Bridge Converters Based on HalfWave Symmetrical Selective Harmonic Elimination Technique.
IEEE Trans. Power Electron. 2016, 32, 7980–7989. [CrossRef]
11. Zhang, L.; Harnefors, L.; Nee, H.P. Modeling and Control of VSC-HVDC Links Connected to Island Systems.
IEEE Trans. Power Syst. 2011, 26, 783–793. [CrossRef]
12. Wang, L. Model Predictive Control System Design and Implementation Using MATLAB; Springer Science &
Business Media: London, UK, 2009.
13. Yu, F.; Lin, W.; Wang, X.; Xie, D. Fast Voltage-Balancing Control and Fast Numerical Simulation Model for
the Modular Multilevel Converter. IEEE Trans. Power Deliv. 2015, 30, 220–228. [CrossRef]
14. Saad, H.; Guillaud, X.; Mahseredjian, J.; Dennetière, S.; Nguefeu, S. MMC Capacitor Voltage Decoupling and
Balancing Controls. IEEE Trans. Power Deliv. 2015, 30, 704–712. [CrossRef]
15. Moon, J.W.; Kim, C.S.; Park, J.W.; Kang, D.W.; Kim, J.M. Circulating Current Control in MMC Under the
Unbalanced Voltage. IEEE Trans. Power Deliv. 2013, 28, 1952–1959. [CrossRef]
16. Rodriguez, J.; Cortes, P. Predictive Control of Power Converters and Electrical Drives; John Wiley & Sons:
Hoboken, NJ, USA, 2012.
17. Preindl, M.; Bolognani, S. Optimal State Reference Computation with Constrained MTPA Criterion for PM
Motor Drives. IEEE Trans. Power Electron. 2015, 30, 4524–4535. [CrossRef]
18. Akter, M.P.; Mekhilef, S.; Tan, N.M.; Akagi, H. Model Predictive Control of Bidirectional AC-DC Converter
for Energy Storage System. J. Electr. Eng. Technol. 2015, 10, 165–175. [CrossRef]
19. Narimani, M.; Wu, B.; Yaramasu, V.; Cheng, Z.; Zargari, N.R. Finite Control-Set Model Predictive
Control (FCS-MPC) of Nested Neutral Point-Clamped (NNPC) Converter. IEEE Trans. Power Electron.
2015, 30, 7262–7269. [CrossRef]
392
Energies 2018, 11, 1861
20. Kouro, S.; Cortés, P.; Vargas, R.; Ammann, U.; Rodríguez, J. Model Predictive Control-A Simple and Powerful
Method to Control Power Converters. IEEE Trans. Ind. Electron. 2009, 56, 1826–1838. [CrossRef]
21. Geyer, T.; Papafotiou, G.; Morari, M. Model Predictive Direct Torque Control-PartI: Concept, Algorithm,
and Analysis. IEEE Trans. Ind. Electron. 2009, 56, 1894–1905. [CrossRef]
22. Papafotiou, G.; Kley, J.; Papadopoulos, K.G.; Bohren, P.; Morari, M. Model Predictive Direct Torque
Control—Part II: Implementation and Experimental Evaluation. IEEE Trans. Ind. Electron. 2009, 56, 1906–1915.
[CrossRef]
23. Cortés, P.; Ortiz, G.; Yuz, J.I.; Rodríguez, J.; Vazquez, S.; Franquelo, L.G. Model Predictive Control of an
Inverter With Output, Filter for UPS Applications. IEEE Trans. Ind. Electron. 2009, 56, 1875–1883. [CrossRef]
24. Qin, J.; Saeedifard, M. Predictive Control of a Modular Multilevel Converter for a Back-to-Back HVDC
System. IEEE Trans. Power Deliv. 2012, 27, 1538–1547.
25. Mariethoz, S.; Fuchs, A.; Morari, M. A VSC-HVDC Decentralized Model Predictive Control Scheme for Fast
Power Tracking. IEEE Trans. Power Deliv. 2014, 29, 462–471. [CrossRef]
26. Preindl, M.; Schaltz, E.; Thogersen, P. Switching Frequency Reduction Using Model Predictive Direct Current
Control for High-Power Voltage Source Inverters. IEEE Trans. Ind. Electron. 2011, 58, 2826–2835. [CrossRef]
27. Xia, C.; Liu, T.; Shi, T.; Song, Z. A Simplified Finite-Control-Set Model-Predictive Control for Power
Converters. IEEE Trans. Ind. Inform. 2014, 10, 991–1002.
28. Zhang, Y.; Tai, N.; Xu, B. Fault Analysis and Traveling-Wave Protection Scheme for Bipolar HVDC Lines.
IEEE Trans. Power Deliv. 2012, 27, 1583–1591. [CrossRef]
29. Rashwan, A.; Sayed, M.A.; Mobarak, Y.; Shabib, G.; Senjyu, T. Predictive Controller Based on Switching State
Grouping for a Modular Multilevel Converter with Reduced Computational Time. IEEE Trans. Power Deliv.
2017, 32, 2189–2198. [CrossRef]
30. Bathurst, G.N.; Watson, N.R.; Arrillaga, J. Modeling of bipolar HVDC links in the harmonic domain.
IEEE Trans. Power Deliv. 2002, 15, 1034–1038.
31. Ilves, K.; Harnefors, L.; Norrga, S.; Nee, H.P. Predictive Sorting Algorithm for Modular Multilevel Converters
Minimizing the Spread in the Submodule Capacitor Voltages. IEEE Trans. Power Electron. 2015, 30, 440–449.
[CrossRef]
32. Mahmoudi, H.; Aleenejad, M.; Ahmadi, R. A New Multiobjective Modulated Model Predictive Control
Method with Adaptive Objective Prioritization. IEEE Trans. Ind. Appl. 2017, 53, 1188–1199. [CrossRef]
© 2018 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access
article distributed under the terms and conditions of the Creative Commons Attribution
(CC BY) license (http://creativecommons.org/licenses/by/4.0/).
393
energies
Article
Low-Harmonic DC Ice-Melting Device Capable of
Simultaneous Reactive Power Compensation
Jiazheng Lu, Siguo Zhu *, Bo Li, Yanjun Tan, Xiudong Zhou, Qinjun Huang, Yuan Zhu and
Xinguo Mao
State Key Laboratory of Disaster Prevention and Reduction for Power Grid Transmission and Distribution
Equipment, State Grid Hunan Electric Company Limited Disaster Prevention and Reduction Center,
Changsha 410007, China; [email protected] (J.L.); [email protected] (B.L.);
[email protected] (Y.T.); [email protected] (X.Z.); [email protected] (Q.H.);
[email protected] (Y.Z.); [email protected] (X.M.)
* Correspondence: [email protected]; Tel.: +86-0731-8633-2078
Abstract: As a result of the high efficiency of ice-melting and the small power supply capacity,
DC ice-melting devices are widely used in relation to transmission lines in the power grid.
However, it needs to consume reactive power when ice-melting, and voltage fluctuation of the
substation may be caused when the demand for reactive power is large. It also generates a large
number of 5th and 7th harmonics when ice-melting. In this paper, combined with the demand for
ice-melting for transmission lines and the dynamic reactive power of substations, a low-harmonic DC
ice-melting device capable of simultaneous reactive power compensation is studied. The function of
ice-melting and reactive power compensation can be operated simultaneously and the rectifier’s main
harmonics can be eliminated. The simulation and experimental research on the device was carried out
in the 500 kV Chuanshan substation. The actual ice melting was carried out on the 500 kV Chuansu I
line and took only 68 min to melt the ice. The 500 kV bus voltage had no negative deviation, and the
positive deviation decreased from +3.09% to +1.57% within 24 h of testing. The results prove the
feasibility of the proposed DC ice-melting device in this paper.
1. Introduction
Winter icing of transmission lines is one of the natural disasters of the power system. The rare
long-term freezing disaster in early 2008 caused serious damage to the power grid in southern China,
resulting in a large number of tower collapses, line interruptions, substation outages, and so on,
which caused huge losses in many southern provinces of China.
For transmission line icing, manual deicing or improving line anti-icing designs were the main
methods up until recently, but efficiency was low or investment was high. In order to cope with
the impact of more and more frequent ice disasters on power system facilities, research into various
ice-melting technologies has been receiving more and more attention [1–5].
Among them, DC current ice-melting has the advantages of high efficiency, a wide ice-melting
range for different transmission lines, and small power supply. A previous study [6] proposes
a diode-based uncontrolled rectifier DC ice-melting device, which only has the function of
ice melting, and which is only used during the covering-ice period of transmission lines in winter.
However, it has low utilization rate, and consumes system reactive power when ice-melting,
which affects voltage stability. Another study [7] proposes a Static Var Compensator (SVC) type DC
ice-melting device, which can run in two modes: DC ice-melting or SVC reactive power compensation.
However, the ice-melting and reactive power compensation cannot run at the same time and it cannot
meet the reactive demand of ice melting. Further more, the harmonics of ice-melting are large,
and a huge filter device is needed. Further studies [8–12] propose a new modular multi-level
DC ice-melting device, which combines the dynamic reactive power compensation capability of
a chain Static Var Generator (SVG) with the four-quadrant operation capability of a half-bridge
modular multi-level converter (MMC). It can output DC voltage at the same time to meet the DC
ice-melting demand, but the reactive power compensation and DC ice-melting need to be designed in
the same capacity. The cost is high, and it is still in the theoretical research stage.
In view of the above problems associated with the ice-melting device, this paper proposes a
low-harmonic DC ice-melting device that can compensate for simultaneous reactive power when
ice melting. The harmonics injected into the power grid are small without a filtering device when
ice melting. The device itself achieves a reactive power balance ensuring grid voltage stability.
The paper is organized as follows:
Firstly, the topology of the low-harmonic DC ice-melting device with simultaneous reactive power
compensation is proposed. The SVG and the ice-melting rectifier share the ice-melting transformer,
which eliminates the SVG’s connection reactance and reduces the SVG’s output voltage and
the insulation design. The design enables simultaneous operation of ice melting and reactive
power compensation.
Secondly, the output voltage ripple characteristics of the low-harmonic DC ice-melting device
is analyzed. The 12-pulse rectification structure is adopted, and the ripple factor value is only 0.994,
which effectively reduces the output DC current fluctuation.
Thirdly, using the Fourier series, the harmonics injected into the power grid are mainly 5th and
7th harmonic currents when ice-melting. Increasing the number of power modules and the triangular
carrier frequency can effectively eliminate the SVG’s lower harmonic.
Fourthly, injecting low-order harmonic multi-carrier phase-shift modulation algorithm which
injects 5th and 7th harmonics into a modulated wave is put forward. Using the simultaneous operation
of ice melting and reactive power compensation, the algorithm can eliminate the harmonic injected
into the grid when ice melting.
Finally, the simulation and experimental research on the low-harmonic DC ice-melting device
which was built in the 500 kV Chuanshan substation is carried out. The results verify that DC
ice-melting has low-harmonic characteristics and that the reactive power compensation function can
effectively improve grid voltage stability.
395
Energies 2018, 11, 2596
5 5 5
' ' '
69*
$SKDVH
.
%SKDVH
a
5HFWLILHU
.
$&
N9 < &SKDVH
7UDQVIRUPHU .
7UDQVPLVVLRQOLQHV
,VRODWLRQ6ZLWFK
5HFWLILHU
69*
The topology shown in Figure 1 can make full use of the transformer, providing dynamic reactive
power support for the grid system during daily operation. The SVG can also eliminate harmonics and
reactive power generated by the rectifier during the ice-melting operation mode.
49.6 f · IWΣDρK
Ukz % = , (1)
etH × 106
where f —Frequency (Hz); I—Rated current (A); W—Coil number (Turn); et—Every potential (V);
H—Average reactance height of two coils (m); ΣD—Magnetic flux leakage area (m2 );
ρ—Rockwell coefficient; K—Additional reactance coefficient, generally take 1.
The SVG’s output voltage is connected to the grid after being boosted by the transformer,
which reduces the SVG’s insulation voltage design difficulty [17,18], reduces the number of each phase
power modules connected in series, and simplifies the design of the control system. In order to improve
the reactive output current and meet the demand for large-capacity reactive power compensation
above 100 MVar, the SVG’s power modules adopt dual IGBT (Insulated Gate Bipolar Transistor)
parallel structure. The parallel IGBT adopts the same control pulses.
396
Energies 2018, 11, 2596
7KUHHZLQGLQJLFHPHOWLQJWUDQVIRUPHU
[\
1\
\\
$ ; ]\
% <
= [G
&
\G
1G
]G
69* 69*
8$ 60 8% 60 8& 60 8$ 60 8% 60 8& 60
)XOOEULGJHVXEPRGXOH
8GF
6 6 6 6
8L˄M˅
397
Energies 2018, 11, 2596
UR
γu = , (7)
Ud0
The ripple factor values of the output voltages of different pulse wave rectifiers obtained by
Equation (10) are shown in Table 1.
m γu (%)
3 18.27
6 4.18
12 0.994
∞ 0
It can be seen from Table 1, the more the pulse wave number of the rectifier, the smaller the output
voltage ripple value. The 12-pulse rectification structure of the ice-melting device can greatly reduce
the voltage ripple factor value and reduce the fluctuation of the output DC current, which is useful to
facilitate line ice-melting.
398
Energies 2018, 11, 2596
& '
iadϕ = 2
π Id sin ωt + ∑k=1,2,··· 1
6k −1 sin(6k − 1)ωt + 1
6k +1 sin(6k + 1)ωt , (12)
LD\ LDG
,G ,G
It can be obtained from Equations (11) and (12): the number of harmonics on the AC side of
the rectifier of the low-harmonic DC ice-melting device is 5, 7, 11, . . . , 6k ± 1 times, k = 1, 2, 3, . . . .
The RMS of the fundamental current and each harmonic are:
√
I1 = √π6 Id
, (13)
In = nπ6 Id
The RMS value of each harmonic is inversely proportional to the harmonic order. The ratio
of the RMS value to the fundamental value is the reciprocal of the harmonic order. The higher the
harmonic order, the smaller the harmonic amplitude, so the harmonics injected into the grid during the
ice-melting are mainly the 5th and 7th harmonic currents, which are 0.156Id and 0.111Id , respectively.
Uug nπ mnπ
Udc = Nm sin ωt+ ∑n∞=1 4
nπ cos 2 sin 2 sin ωt ·[cos nθ1 . . . + cos nθ N ] cos( nωc t)+
nπ mnπ (14)
∑∞
n =1
4
nπ cos 2 ·sin 2 sin ωt [sin nθ1 . . . + sin nθ N ] sin(nωc t),
where Udc is the power module DC bus voltage, m is the modulation degree, ω is the sinusoidal
modulation wave angle frequency, ω c is the carrier triangle wave angular frequency, and θ k (k = 1, 2,
. . . , N) is the power module carrier phase-shifted angle.
When n is an odd number, cos nπ 2 = 0.
When n is even, take the carrier ratio: kc = f c / f .
fc is the triangular carrier frequency and f is the sinusoidal modulation wave frequency.
among them:
A = cos nθ1 + cos nθ2 . . . + cos nθn
, (17)
B = sin nθ1 + sin nθ2 . . . + sin nθn
399
Energies 2018, 11, 2596
The control method of each power module with three-phase AC input and the single-phase
AC output adopts a sinusoidal pulse width modulation method. The power modules of the same
phase have the same carrier frequency, but the phases are sequentially different by 1/N carrier period,
as shown in Figure 4a.
W
$
WSZ
WPV W
(a) (b)
Figure 4. Modulation: (a) Carrier phase-shifted modulation (Different colors represent different
carriers); (b) sine pulse width modulation.
The pulse calculation method of each power module adopting sinusoidal pulse width modulation
methodis shown in Figure 4b.
The formula for calculating the pulse width is:
where T Δ is the period of the triangular carrier, m1 is the modulation ratio of the sine wave and the
triangular wave.
400
Energies 2018, 11, 2596
In each power module of Figure 2, the power devices IGBT S11 and S21 are connected in parallel,
S12 and S22 are connected in parallel, S13 and S23 are connected in parallel, and S14 and S24 are connected
in parallel. The two parallel IGBT pulse control signals are the same, and the power module upper
and lower arms S11 and S12 , S13, and S14 pulse control signals are complementary. In order to avoid
solving complex transcendental equations, the power switching device pulse control signal is obtained
by using the regular sampling method. The calculation principle is shown in Figure 5a.
$ 7ǻ 7ǻ
$
șL W W
șL
$
$
WJ WJ
WG W
W
WG
(a) (b)
Figure 5. Pulse control signal calculation principle: (a) S11 ; (b) S13 .
In Figure 5a, θ i is the angle value of the midpoint sampling time of the triangular wave.
TΔ
tg = (1 − m1 sin θi ), (20)
4
3TΔ
td = (1 + m1 sin θi ), (21)
4
The calculation results of Equations (20) and (21) are the offset time between the start and
stop times of each pulse control signal of S11 in the power module and the corresponding triangle
wave midpoint.
In Figure 5b:
T
t g = Δ (1 + m1 sin θi ), (22)
4
3T
td = Δ (1 − m1 sin θi ), (23)
4
The calculation results of Equations (22) and (23) are the offset time between the start and
stop times of each pulse control signal of S13 in the power module and the corresponding triangle
wave midpoint.
In order to eliminate the 5th and 7thharmonic currents injected into the grid during the
ice-melting [22–24], the 5th and 7th harmonic voltages are modulated into the power module
modulation wave of SVG1 and SVG2. The harmonic amplitudes are k1 and k2, respectively, so that
the generated harmonic current is equal to the amplitude of the harmonic current injected into grid
when ice-melting, and the direction is opposite. After the 5th and 7th harmonic voltages are injected
into the modulated wave of the left and right bridge arms of each power module, the waveform of the
modulated wave is as shown in Figure 6. The calculation formulas of the modulated wave of the left
and right bridge arms are as shown in Equation (24):
f 1 (t) = m sin ωt + k1m sin 5ωt + k2m sin 7ωt
(24)
f 2 (t) = −m sin ωt − k1m sin 5ωt − k2m sin 7ωt
401
Energies 2018, 11, 2596
WV
According to Equations (14)–(17) and (24), after the 5th and 7th harmonics are injected, the phase
voltages of each phase of SVG1 and SVG2 are:
where k1 and k2 are obtained by detecting the 5th and 7th harmonic currents injected into the grid by
the ice-melting rectifier and performing Fourier decomposition.
The principle of IGBT control pulse generation in each power module of the SVG is shown in
Figure 7 [25–29].
7ULDQJXODUZDYH
JHQHUDWRU
7ǻ1
P
VLQȦW î 7ǻ1
'ULYH
FLUFXLW
VLQȦW î N
î
7ǻ1
VLQȦW î N
402
Energies 2018, 11, 2596
At the 500 kV voltage level of Hunan Power Grid, it can be found that the area with low voltage
transient instability is concentrated in the south of the Hunan Province. The local voltage distribution
map of southern Hunan is enlarged as Figure 8. A low voltage problem in a steady state and a
voltage instability problem in the disturbed state exist in the southern Power Grid of Hunan Province.
With high-speed rail, electric irons, and other impact loads, the dynamic reactive power demand
is large in the Chuanshan substation. Therefore, it is necessary to install a dynamic reactive power
compensation device of a certain capacity in southern Hunan.
&KDQJ\DQSX *XWLQJ
VXEVWDWLRQ VXEVWDWLRQ
&KXDQVKDQ
VXEVWDWLRQ <RX[LDQ
9ROWDJH
FKURPDWRJUDSK\
SRZHUSODQW
=RQJ\XDQ
VXEVWDWLRQ
=L[LD 6XGDQ
VXEVWDWLRQ VXEVWDWLRQ
Combined with the demand for ice-melting of the lines in the Chuanshan substation and
the dynamic reactive demand in southern Hunan, a low-harmonic DC ice-melting device with
simultaneous reactive power compensation was installed in the Chuanshan substation to solve
the problem of dynamic reactive power and line ice-melting at the same time. The ice-melting
capacity is 120 MW, and the reactive power compensation capacity of SVG1 and SVG2 are all 50 MVar.
The ice-melting transformer has a rated capacity of 120 MVA, a rated input voltage of 35 kV, a rated
output voltage of 17.1 kV, and a short-circuit impedance of 15%. The ice-melting rectifier has a
rated capacity of 120 MW, a rated output DC voltage of 21 kV, and a rated output DC current of
5700 A. SVG1 and SVG2 have a rated output voltage of 17.1 kV and a rated output current of 1688 A.
The number of power modules per phase is 20, which is half the number of power modules compared
with the 35 kV grid-connected without a transformer. This greatly improves the stability of the SVG.
5.1.1. DC Ice-Melting
Taking the DC ice-melting of the 500 kV Chuangu line as an example, its DC resistance per phase
was 1.88 Ω, the line length was 130.3 km, and the wire type was 2 × LGJ–500. When ice melting,
the A phase and C phase are connected in a series, the output voltage of the ice-melting transformer is
17.1 kV, and the 12-pulse rectifier is connected in parallel by two bridges. During the simulation, it was
403
Energies 2018, 11, 2596
possible to obtain an output DC voltage of the ice-melting device of 18.9 kV, an output DC current
of 5685 A, and the voltage and current waveforms are shown in Figure 9a,b. The ripple factor value
of the output voltage is small in Figure 9a and the output current waveform is smooth in Figure 9b.
The actual output is consistent with the previous theoretical analysis.
XN9
LN$
WV WV
(a) (b)
Figure 10 is a low-order harmonic simulation analysis of the current waveform of the input side
of the ice-melting rectifier when ice-melting. When the rectifier is working, it will generate large 5th
and 7th harmonics on its input side, but it can be seen from Figure 5 that the 5th and 7th harmonics in
the input current are effectively eliminated by the SVG1 and SVG2 connected in parallel to the input
side of the rectifier, and the content is less than 0.5%.
LN$
+DUPRQLFQWK
Figure 10. Low-order harmonic analysis of input current of ice-melting rectifier.
X9
XN9
WPV
WPV
(a) (b)
Figure 11. The output voltage waveform: (a) single power module; (b) five power modules.
404
Energies 2018, 11, 2596
Arbitrarily selecting five power modules connected in the A phase of SVG1 or SVG2 to simulate,
the output of the eleven-level voltage waveform is as shown in Figure 11b. The output level of SVG is
equal to “2n + 1” where n is the number of power module per phase, n = 1, 2, 3.....
N
X9
N
L$
L$
L$
L$
405
Energies 2018, 11, 2596
melted in series which took about 33 min to melt the ice. The output voltage, current and line falling
ice is as shown in Figure 14a when ice-melting.
&RROLQJV\VWHP
7UDQVIRUPHU
5HFWLILHU 69*69*
Figure 13. Low-harmonic DC ice-melting device in 35 kV Chuanshan substation.
,FHRII
PP
WPV
(a) (b)
Figure 14. Actual ice melting: (a) (1) Ice-melting voltage; (2) current; and (3) falling ice. (b) Output DC
voltage waveform.
The output voltage of the ice-melting is shown in Figure 14b. The voltage ripple number
is 12 in each cycle, and the output voltage ripple value is about 0.99, which is consistent with
the theoretical calculation. When ice-melting, SVG1 and SVG2 run in parallel with the injected
low-harmonic multi-carrier phase-shift modulation algorithm. The 5th and 7th harmonic currents
injected into the grid by the rectifier are effectively eliminated as shown in Figure 15.
LN$
+DUPRQLFQWK
406
Energies 2018, 11, 2596
The single power module’s carrier frequency is 300 Hz in SVG1 and SVG2, the output voltage is
about 482 V. The output three-level voltage waveform of each power module is as shown in Figure 16a.
The SVG’s A phase output voltage waveform is as shown in Figure 16b.The actual test results are
consistent with the previous simulation results.
XN9
X9
WPV WPV
(a) (b)
Figure 16. The output voltage waveform: (a) Single power module; (b) one-phase.
When the inductive reactive power requirement of the substation’s power system is reduced
from 80 MVar to 20 MVar, the single SVG output reactive power is reduced from 40 MVar to 10 MVar.
The output current waveforms of the A and C phase are shown in Figure 17a. When the system
inductive reactive power requirement is increased from 20 MVar to 80 MVar, the single SVG output
reactive power is increased from 10 MVar to 40 MVar, and the A and C phase output current waveforms
are as shown in Figure 17b.
PDJQLILFDWLRQ PDJQLILFDWLRQ
N N
N N
N N
N N
L$
L$
N N
N N
N N
N N
WV WV
(a) (b)
Figure 17. Output two-phase current waveform: (a) 40 MVar to 10 MVar; (b) 10 MVar to 40 MVar.
When the reactive power requirement of the power system changes from 80 MVar sensibility to
−80 MVar capacitive, the single SVG output reactive power is changed from 40 MVar to −40 MVar,
and the A and C phase output current waveforms are shown in Figure 18.
The SVG output reactive response time is less than 10 ms which can well meet the reactive power
demand of power system according to the Figures 17 and 18.
After the low-harmonic DC ice-melting device in Chuanshan substation was put into operation,
the power quality of Chuanshan substation was tested for 24 h using the power quality tester according
to the test procedures. The 500 kV bus voltage had no negative deviation, and the positive deviation of
500 kV bus voltage was about 0.80–2.0% within 24 h of testing, as shown in Figure 19. The ninety-five
percent probability of the positive deviation value (phase B) was about 1.57%, which was 1.52% lower
than the 3.09% when there was no timely reactive power compensation at runtime.
So the low-harmonic DC ice-melting device capable of simultaneous reactive power compensation
can effectively improve the voltage stability in southern Hunan Province.
407
Energies 2018, 11, 2596
PDJQLILFDWLRQ
N
N
N
N
L$
N
N
N
N
WV
Figure 18. 40 MVar to −40 MVar output two-phase current waveform.
$SKDVH
9ROWDJHGHYLDWLRQ
%SKDVH
&SKDVH
WKP
Figure 19. 500 kV bus voltage deviation.
6. Discussion
The simulated and measured results in Section 5 can be explained as follows:
The topology of a low-harmonic DC ice-melting device capable of simultaneous reactive power
compensation is feasible. The SVG uses transformer leakage reactance instead of connecting reactance.
It can realize the simultaneous operation of ice-melting and reactive power compensation. The running
harmonics are small, and no filtering device is needed.
The twelve-pulse rectification structure in the low-harmonic DC ice-melting device can effectively
reduce the fluctuation of output DC current and the ripple factor value is only 0.994.
The ice-melting and SVG reactive power compensation are simultaneously operated, and the
injected low-harmonic multi-carrier phase-shift modulation algorithm can effectively eliminate the 5th
and 7th harmonics mainly generated during ice melting without the need of a filter device.
After the SVG was put into operation in 500 kV Chuanshan substation, the 500 kV bus voltage had
no negative deviation and the positive deviation decreased from 3.09% to 1.57% within 24 h of testing,
which effectively improves the voltage stability in southern Hunan Province, China.
7. Conclusions
In this paper, a topology of a low-harmonic DC ice-melting device capable of simultaneous
reactive power compensation has been proposed. The ice-melting device is mainly composed of
a transformer, SVG1, SVG2, and an ice-melting rectifier. The two SVGs are connected to the two
low-voltage winding sides of the transformer, which is also connected to the rectifier. The SVG can
effectively absorb harmonics generated by the rectifier and improve the voltage stability.
The simulation and experimental research is carried out. The results verify the feasibility and
effectiveness of the low-harmonic DC ice-melting device which provides an effective method for the
research and development of the DC ice-melting device.
408
Energies 2018, 11, 2596
Author Contributions: S.Z. carried out the experiments, analyzed the test results, and wrote this paper. J.L. gave
input to the analysis of test results. B.L., Y.T. and X.Z. carried out the experimental set up. Q.H., Y.Z. and X.M.
carried out the simulation research.
Funding: This research was funded by State Grid Corporation of China Science and Technology Program,
grant number [2016KJ0072].
Acknowledgments: The authors gratefully acknowledge the contributions of all members of the ice-melting
research team in State Grid Hunan Electric Power Corporation Limited for their work on this paper.
Conflicts of Interest: The authors declare no conflict of interest.
References
1. Lu, J.; Zeng, M.; Zeng, X.; Fang, Z.; Yuan, J. Analysis of ice-covering characteristics of China Hunan power
grid. IEEE Trans. Ind. Appl. 2015, 51, 1997–2002. [CrossRef]
2. Lu, J.Z.; Zhu, S.G.; Li, B.; Zhang, H.X.; Tan, Y.J.; Zhu, Y. Influence of STATCOM System on the DC-icing
Rectifier Transformers’ DC Magnetization and Suppression Method. High Volt. Eng. 2016, 42, 1624–1629.
3. Long, J.Z.; Zheng, L.J.; Cai, L.H.; Yong, H.F. Analysis of the causes of tower collapses in Hunan during the
2008 ice storm. High Volt. Eng. 2008, 34, 2468–2474.
4. Volat, C.; Farzaneh, M.; Leblond, A. De-icing/anti-icing techniques for power lines: Current methods and
future direction. In Proceedings of the 11th International Workshop on Atmospheric Icing of Structures,
Montreal, QC, Canada, 12–16 June 2005; pp. 1–11.
5. Fan, S.; Jiang, X.; Sun, C.; Zhang, Z.; Shu, L. Temperature characteristic of DC ice-melting conductor.
Cold Reg. Sci. Technol. 2011, 65, 29–38. [CrossRef]
6. Tan, Y.J.; Lu, J.Z.; Fang, Z.; Li, B.; Zhang, H.X. Study of Mobile DC De-icing Equipment Based on Uncontrolled
Rectification. Cent. China Electr. Power 2011, 24, 31–34.
7. Chun, L.C. Application research of SVC melting technology in 220 kV substation. Yunnan Electr. Power 2010,
38, 1–2.
8. Mei, H.; Liu, J. A novel dc ice-melting equipment based on modular multilevel cascade converter.
Autom. Elect. Power Syst. 2013, 37, 96–102.
9. Zhao, Q. A Novel DC Ice-melting Device Based on MMC with Hybrid Sub-module. South. Power Syst. Technol.
2015, 9, 9–36.
10. Guo, Y.; Xu, J.; Guo, C.; Zhao, C.; Fu, C.; Zhou, Y.; Xu, S. Control of full-bridge modular multilevel converter
for dc ice-melting application. In Proceedings of the11th IET International Conference on AC and DC Power
Transmission, Birmingham, UK, 10–12 February 2015; pp. 1–8.
11. Fan, R.; Sun, M.; He, Z.Y.; Yan, S. Design and system test of movable DC De-icer for Jiangxi power grid.
Autom. Electr. Power Syst. 2009, 33, 67–71.
12. Jin, B.H.; Nian, X.H.; Fan, R.X.; Liu, D.; Deng, M. Research of line full controlled ice-melting DC power
supply with control and change strategy. Autom. Electr. Power Syst. 2012, 36, 86–91.
13. Li, S.; Wang, Y.; Li, X.; Wei, W.; Zhao, G.; He, P. Review of de-icing methods for transmission lines.
In Proceedings of the 2010 International Conference on Intelligent System Design and Engineering
Application, Changsha, China, 13–14 October 2010; pp. 310–313.
14. Wang, J.; Fu, C.; Chen, Y.; Rao, H.; Xu, S.; Yu, T.; Li, L. Research and application of DC de-icing technology in
China southern power grid. IEEE Trans. Power Deliv. 2012, 27, 1234–1242. [CrossRef]
15. Wang, C.; Wen, J.; Li, S.; Ma, X.; Wang, J. Design on DC de-icing schemes for high voltage transmission line.
In Proceedings of the 2010 5th International Conference on Critical Infrastructure (CRIS), Beijing, China,
20–22 September 2010; pp. 1–5.
16. Lesnicar, A.; Marquardt, R. An innovative modular multilevel converter topology suitable for a wide
power range. In Proceedings of the 2003 IEEE Bologna Power Tech Conference Proceedings, Bologna, Italy,
23–26 June 2003.
17. Latiff, N.A.A.; Illias, H.A.; Bakar, A.H.A.; Dabbak, S.Z.A. Measurement and Modelling of Leakage Current
Behaviour in ZnO Surge Arresters under Various Applied Voltage Amplitudes and Pollution Conditions.
Energies 2018, 4, 875. [CrossRef]
18. Lu, J.; Xie, P.; Zhen, F.; Hu, J. Electro-Thermal Modeling of Metal-Oxide Arrester under Power Frequency
Applied Voltages. Energies 2018, 11, 1610. [CrossRef]
409
Energies 2018, 11, 2596
19. Perez, M.A.; Bernet, S.; Rodriguez, J.; Kouro, S.; Lizana, R. Circuit topologies, modeling, control schemes,
and applications of modular multilevel converters. IEEE Trans. Power Electron. 2015, 30, 4–14. [CrossRef]
20. Zeng, R.; Xu, L.; Yao, L.; Williams, B.W. Design and operation of a hybrid modular multilevel converter.
IEEE Trans. Power Electron. 2015, 30, 1137–1146. [CrossRef]
21. Li, X.; Song, Q.; Liu, W.; Xu, S.; Zhu, Z.; Li, X. Performance analysis and optimization of circulating current
control for modular multilevel converter. IEEE Trans. Ind. Electron. 2016, 63, 716–727. [CrossRef]
22. Zhang, M.; Huang, L.; Yao, W.; Lu, Z. Circulating harmonic current elimination of a CPS-PWM-based
modular multilevel converter with a plug-in repetitive controller. IEEE Trans. Power Electron. 2014, 29,
2083–2097. [CrossRef]
23. Konstantinou, G.; Ciobotaru, M.; Agelidis, V. Selective harmonic elimination pulse-width modulation of
modular multilevel converters. IET Power Electron. 2013, 6, 96–107. [CrossRef]
24. Tu, Q.; Xu, Z. Impact of sampling frequency on harmonic distortion for modular multilevel converter.
IEEE Trans. Power Deliv. 2011, 26, 298–306. [CrossRef]
25. Li, B.; Yang, R.; Xu, D.; Wang, G.; Wang, W.; Xu, D. Analysis of the phase-shifted carrier modulation for
modular multilevel converters. IEEE Trans. Power Electron. 2015, 30, 297–310. [CrossRef]
26. Townsend, C.D.; Summers, T.J.; Betz, R.E. Phase-shifted carrier modulation techniques for cascaded H-bridge
multilevel converters. IEEE Trans. Ind. Electron. 2015, 62, 6684–6696. [CrossRef]
27. Hagiwara, M.; Akagi, H. Control and analysis of the modular multilevel cascade converter based on
double-star chopper-cells (MMCCDSCC). IEEE Trans. Power Electron. 2011, 26, 1649–1658. [CrossRef]
28. Huneault, M.; Langheit, C.; Benny, J.; Audet, J.; Richard, J.C. A dynamic programming methodology
to develop de-icing strategies during ice storms by channeling load currents in transmission networks.
IEEE Trans. Power Deliv. 2005, 20, 1604–1610. [CrossRef]
29. Hagiwara, M.; Akagi, H. Control and Experiment of Pulse width-Modulated Modular Multilevel Converters.
IEEE Trans. Power Electron. 2009, 24, 1737–1746. [CrossRef]
© 2018 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access
article distributed under the terms and conditions of the Creative Commons Attribution
(CC BY) license (http://creativecommons.org/licenses/by/4.0/).
410
energies
Article
Modified State-of-Charge Balancing Control
of Modular Multilevel Converter with Integrated
Battery Energy Storage System
Yajun Ma, Hua Lin *, Zhe Wang and Zuyao Ze
State Key Laboratory of Advanced Electromagnetic Engineering and Technology, School of Electrical
and Electronic Engineering, Huazhong University of Science and Technology, Wuhan 430074, China;
[email protected] (Y.M.); [email protected] (Z.W.); [email protected] (Z.Z.)
* Correspondence: [email protected]; Tel.: +86-159-7219-3510
Abstract: Modular multilevel converter with integrated battery energy storage system (MMC-BESS)
has been proposed for energy storage requirements in high-voltage applications. The state-of-charge
(SOC) equilibrium of batteries is essential for BESS to guarantee the capacity utilization.
However, submodule voltage regulation can lead to over-modulation of individual submodules,
which will limit the efficiency of SOC balancing control. Focusing on this problem, a modified SOC
balancing control method with high efficiency is proposed in this paper. The tolerance for battery power
unbalance is defined to quantize the convergence of SOC balancing control. Both the DC component
and AC component are considered while regulating submodule voltage. The linear programming
method is introduced to realize the maximum tolerance for battery power unbalance in different
operation modes. Based on the analysis, by choosing appropriate submodule voltage regulation
method, the efficiency of SOC balancing control is improved greatly. In addition, the SOC controller
is also optimally designed to avoid over-modulation of submodules. Finally, the detailed simulation
and experiment results verify the effectiveness of the analysis and proposed control strategy.
Keywords: battery energy storage system (BESS); modular multilevel converter (MMC);
state-of-charge (SOC) balancing control; tolerance for battery power unbalance
1. Introduction
In recent years, renewable resources are becoming more and more important, but they have
great impact on grid due to their stochastic nature, reducing the voltage and frequency stability [1,2].
Battery energy storage system (BESS) is necessary and effective in these applications to improve
the stability [3]. As the interface between batteries and grid, many researches focus on medium
and high-voltage power conversion system (PCS).
Due to the advantages in medium and high-voltage applications, modular multilevel converters
(MMC) has been used in BESS (MMC-BESS). Batteries can be directly connected with the DC bus in
a centralized manner [4]. However, the series connection of massive batteries reduces the reliability
and increases the complexity of energy management. In [5–7], batteries are integrated into submodules
of MMC, constituting a modularized and distributed PCS. Compared with the centralized structure,
the reliability and flexibility of distributed structure are greatly improved. Hence, it is more applicable
to medium and high-voltage applications [8]. Most importantly, MMC-BESS is not only a pure
PCS, but also a three-port converter. As an example, Figure 1 is the structure diagram of wind
energy system. By integrating batteries into MMC, the original PCS is eliminated, which simplifies
the whole configuration and lowers the costs. In addition, BESS can coordinate the operation of AC
and DC side while transferring power among them [9]. Figure 1b is the topology of MMC-BESS,
consisting of three phases, each with two arms. In submodule A, batteries are directly connected with
submodules [10,11]. However, low-frequency current ripple can flow into batteries, which leads to
additional heat generation and temperature rise of batteries. That will accelerate the degradation
of batteries, resulting in significant reduction of battery life span [12,13]. Then a DC/DC converter
(isolated or non-isolated) is used to filter the low-frequency current in submodule B [14–16]. The main
advantages of non-isolated DC/DC are the simple structure and low cost. The isolated DC/DC
can achieve the electrical isolation between batteries and MMC, which is utilized to meet some
special requirements of batteries, such as grounding. At the same time, the DC/DC converter offers
an additional control degree of freedom (DOF). Therefore, the capacitor voltage can be directly
controlled by the DC/DC converter with traditional dual closed-loop control structure. Compared with
the methods based on traditional MMC [17,18], the capacitor voltage balancing control is greatly
simplified, and this paper also prefers this control structure.
idc
uku
Pkbu
iku
Ra La Rg Lg
uk
ik
ikc
ikl
Pkbl ukl
ȱ
Figure 1. Wind energy generation system: (a) structure of offshore wind farm; (b) topology of MMC-BESS.
For the massive submodules of MMC-BESS, the state-of charge (SOC) of each submodule will
inevitably be different. The capacity utilization of the whole BESS is limited by the submodules
with highest or lowest SOC due to the over-charge or over-discharge of them. Therefore it is
essential to maintain the SOC equilibrium of all submodules [19]. The SOC balancing control is
usually divided into three levels, including SOC balance among phases, SOC balance between arms
and SOC balance within arms. In [20], the zero-sequence voltage is injected to balance the SOC
among phases. However, the calculation of zero-sequence voltage is too complex. In [21,22], the DC
and fundamental circulating current are regulated to balance the SOC among phases and between arms
respectively. The SOC within arms is balanced by regulating the submodule voltage, which contains
both the DC component and AC component. So there are two dimensions to regulate the submodule
voltage. In [23], only AC component of submodule voltage is regulated to balance SOC. In [24],
the DC component is regulated to balance SOC in AC-side fault mode and the AC component is
regulated to balance SOC in DC-side fault mode. In [25], a power factor is introduced to regulate both
the DC component and AC components. However, the problem is that the regulation of submodule
voltage can lead to over-modulation of submodules when the battery power unbalance exceeds
certain limit. To avoid the over-modulation of submodules, the gain of SOC controller should be
limited [17,22]. However, that will seriously limit the SOC convergence rate of the whole BESS.
To guarantee appropriate SOC convergence, the key is to improve the tolerance for battery power
unbalance, which is closely related to the submodule voltage regulation method. However the methods
above only investigate some special cases, which are not necessarily optimal in any case. More seriously,
the SOC may not converge in some case. For example in [15], the SOC will not converge when the power
only transfers between DC side and batteries. Therefore, this paper aims to investigate the submodule
voltage regulation method to optimize the SOC balancing control.
412
Energies 2019, 12, 96
In this paper, capacitor voltage is controlled by the DC/DC converter with traditional dual
closed-loop structure. Carrier phase shifted modulation (CPS-PWM) is used to generate switching
signals. By analyzing the power flow of MMC-BESS, the factors that limit the SOC convergence
rate are investigated in detail. Then the tolerance for battery power unbalance is defined to
quantize the convergence of SOC balancing control. Both the DC and AC components are taken
into account when regulating submodule voltage. Linear programming method is introduced to reach
the maximum tolerance in different operation modes. One the basis, a modified SOC balancing control
method with high efficiency is proposed by optimizing the submodule voltage regulation method.
Finally, a downscaled prototype is built to verify the analysis and proposed method.
The rest of this paper is organized as follows: the power flow and principles of SOC balancing
control are introduced in Section 2. The submodule voltage regulation method is investigated
in Section 3. On the basis, optimized SOC balancing control strategy is proposed in Section 4.
Then the detailed simulation and experiment results are given in Section 5. Finally, the conclusions are
presented in Section 6.
where Ikc0 is the dc circulating current; Ikc1 and γk1 are the amplitude and phase of fundament
circulating current.
Just like the traditional MMC, the following basic relations still exist for arm voltages and currents
uku = 12 Vdc − vkc − vk , iku = ikc + 21 ik
ukl = 12 Vdc − vkc + vk , ikl = ikc − 12 ik
(2)
vkc = R a ikc + L a didtkc
vk = ( R g + 12 R a )ik + ( L g + 12 L a ) didtk + uk
where vkc and vk are the voltages required to drive circulating current and AC-side current respectively.
In this way, the system is divided into two parts: one part is only related to circulating current
and the other part is only related to AC-side current.
Ignoring power losses, the absorbed average power of arms can be calculated according to the arm
voltages and currents in (1) and (2).
⎧
⎪ 1 1 1 1
⎨ Pku = 2 Vdc Ikc0 − 2 Vk Ikc1 cosγ1 − 2 × 2 Vk Ik cosϕ + Pkbu
⎪
( )* + ( )* + ( )* + (3)
⎪
⎪ 0.5Pkdc PkΔ 0.5Pkac
⎩
Pkl = 12 Vdc Ikc0 + 12 Vk Ikc1 cosγ1 − 12 × 12 Vk Ik cosϕ + Pkbl
413
Energies 2019, 12, 96
where ϕ is the power factor angle; Vk , Ik are the amplitude of vk and ik . The DC circulating
current transfers the same power from DC bus to upper and lower arm, which is denoted by Pkdc .
The fundamental circulating current transfers the same power PkΔ from upper arm to lower arm.
Ac-side current absorbs the same power from both upper and lower arm, which is denoted by Pkac .
To maintain the power balance of arms, the absorbed active power should be equal to zero,
hence the total battery power injected into arms can be calculated as
Pkbu = 12 ( Pkac − Pkdc ) + PkΔ
(4)
Pkbl = 12 ( Pkac − Pkdc ) − PkΔ
According to Equations (3) and (4), the power flow among phases and between arms is shown in
Figure 2a, in which Pdc is the total power of dc-bus. The power flowing into AC-side for each phase is
usually the same. The power absorbed from DC bus by each phase can be controlled by regulating
the dc circulating current. Therefore the total battery power injected into each phase is controllable.
The power flowing from upper arm to lower arm can be controlled by regulating the fundamental
circulating current. Therefore, the battery power distribution between upper and lower arm can be
controlled arbitrarily. In this way, the power injected into arms can be controlled independently.
ikj
S kj ikj
0.5 Pdc 0.5Padc 0.5Pbdc 0.5 Pcdc Pkbj
ukcj ukj
Pkj
Pabu Pbbu Pcbu
i
Pkbj
S kji ikj ikj
0.5 Paac 0.5 Pbac 0.5Pcac
i
Pȧ Pḃ Pċ u kcj
ukji Pkji Pkj ukj
0.5Paac 0.5 Pbac 0.5Pcac
Pabl Pbbl Pcbl S kjN ikj
PkbjN ikj Pkji
N
ukcj ukjN
0.5 Pdc
0.5Padc 0.5Pbdc 0.5Pcdc
Figure 2. Power flow of MMC-BESS: (a) power flow among phases and between arms; (b) power flow
among submodules within arms.
In this paper, capacitor voltage of each submodule is controlled by the DC/DC converter
with traditional dual closed-loop control structure, which makes the DC/DC side of submodule
as a controlled voltage source, offering stable voltage for the MMC side. Then the arm can be equivalent
to Figure 2b, in which Skji , ui , and ui are the switching function, capacitor voltage and submodule
kcj kj
i and Pi are the power absorbed from batteries and MMC side, which are
voltage respectively. Pkbj kj
balanced in steady state. Therefore, the battery power injected into each submodule is
T
1
i
Pkbj = − Pkji = − uikj ikj dt (5)
T
0
where T is the fundamental frequency period. For submodules connected in series within arms,
the currents flowing through them are the same. The total battery power injected into arms can be
flexibly allocated to submodules through regulating the DC and AC components of submodule voltage.
Combination with the DC power control, AC power control and balance power control, the battery
power injected into each submodule can be controlled independently.
414
Energies 2019, 12, 96
Storaged charges
SOC = Nominal capacity × 100%
t (6)
SOC (t) = SOC (t0 ) + E1bat t0 Pbat dt
where Pbat is the battery power; Ebat is the nominal energy, which can be calculated by multiplying
the battery voltage and its capacity.
Figure 3 is the general control structure of MMC-BESS. Capacitor voltage is controlled by
the DC/DC converter. The notch filter is used to filter capacitor voltage ripples, which can introduce
low-frequency current ripples into batteries. The AC-side power control adopts typical control structure
in dq frame just like the two-level voltage source converter [26]. The SOC balancing control is divided
into three levels, including SOC balance among phases, SOC balance between arms and SOC balance
within arms. SOCikj is the SOC of the ith submodule. SOCkj , SOCk , and SOCBESS are the average SOC
of arms, phases, and the whole BESS respectively.
1 1 1 N
SOCBESS = ∑
3 k= a,b,c
SOCk , SOCk = (SOCku + SOCkl ), SOCkj = ∑ SOCkj
2 N i =1
i
(7)
According to (6), the three-level SOC balancing control can be realized by regulating the battery
power injected into phases, arms, and submodules respectively. In Figure 3, K1 , K2 , K3 are
the corresponding proportional controllers, and the battery power injected into each phase, arm,
and submodule is
1 1 1
Pkb = P + Δ Pkb , Pkbj = Pkb + Δ Pkbj , Pkbj
i
= Pkbj + Δ Pkbj
i
(8)
3 b 2 N
The battery power injected into each phase and arm is controlled by regulating the dc
and fundamental circulating current. In Figure 3, the output of circulating current control v∗kc is
the reference of vkc , which is used to drive the circulating current. The reference of dc circulating
current is
∗ 1 1
Ikc0 = ( P − Δ Pkb ) (9)
Vdc 3 dc
415
Energies 2019, 12, 96
To prevent the fundamental circulating current from flowing into DC side, fundamental circulating
current should contains no zero-sequence component, and the reference is given as [9,17]
⎡ ⎤ ⎡ ⎤⎡ ⎤
i∗ sin ω t − cos ω t cos ω t Δ Pabu − Δ Pabl
⎢ ∗ac1 ⎥ 1 ⎢ ⎥⎢ ⎥
⎣ ibc1 ⎦ = √ ⎣ cos(ω t − 2π/3) sin(ω t − 2π/3) − cos(ω t − 2π/3) ⎦⎣ Δ Pbbu − Δ Pbbl ⎦ (10)
∗ 3Vk
icc1 − cos(ω t + 2π/3) cos(ω t + 2π/3) sin(ω t + 2π/3) Δ Pcbu − Δ Pcbl
In Figure 3, the battery power injected into submodules is controlled by regulating the submodule
voltage. As an example, with the method in [20,25], the submodule voltage is calculated as
where Δ uikj is the voltage increment to regulate the battery power injected into submodules.
For half-bridge submodule used in this paper, the submodule voltage should be between 0
and Vdc /N. However, the voltage increment can easily result in uikj > Vdc /N or uikj < 0, which exceeds
the output range of submodules. Then over-modulation of submodules occurs, leading to massive
harmonics. To solve the problem, the gain of SOC controller should be limited, and the following
relation exists
K3 (SOCkj − SOCkji )
1−m
≤ (12)
Pkbj /N 1+m
where m = 2Vk /Vdc is the modulation ratio of MMC-BESS. When the modulation ratio m is relatively
large, the allowed K3 is very small, which limits the convergence rate of SOC balancing control.
More seriously, the SOC may not converge in some case, decreasing the capacity utilization of the whole
BESS. Therefore, it is essential to ensure appropriate SOC convergence rate.
K3
λikj = (SOCkj − SOCkj
i
) (14)
Pkbj
416
Energies 2019, 12, 96
Submodule voltage contains dc component and ac component, so there are two dimensions to
regulate submodule voltage. Then the voltage increment Δ uikj is given as
1 i 1
Δ uikj = α V + βi u (15)
2N kj dc N kj k
where αikj and βikj are defined as the DC factor and AC factor, which are used to regulate the DC
and AC component of voltage respectively.
Substituting (15) into (5), the submodule power regulated by the dc factor and ac factor is
1 i 1 i
i
Δ Pkj = α P − β ( P + 2PkΔ ) (16)
2N kj kdc 2N kj kac
In steady state, the total active power absorbed by submodule should be equal to zero.
According to (14) and (16), the submodule voltage regulation should satisfy the relation
1 i 1 i
− λikj Pkbj = α P − β ( P + 2PkΔ ) (17)
2N kj kdc 2N kj kac
Increasing K3 can improve the convergence rate of SOC, but it requires more power regulation to
balance the submodule power. In different operation modes, the contribution of DC factor and AC
factor to power regulation is different. Choosing appropriate DC and AC factor can increase the power
regulation capability, meaning that the allowed SOC convergence rate can be improved.
To facilitate the analysis, the Equation (17) can be rewritten as
1 ξ kj
− λikj = βi − αi (18)
1 − ξ kj kj 1 − ξ kj kj
where Pkdc
Pkac +2PkΔ , j=u
ξ kj = Pkdc (19)
Pkac −2PkΔ , j=l
ξ kj is the power ratio of dc power and ac power in arms, which can denote the operation mode of
MMC-BESS. To improve the SOC convergence rate, the range of allowed battery power unbalance
degree should be as large as possible.
To avoid over-modulation of submodules, we find the following constraints
⎧
⎨ (1 + αi ) + 1 + βi m ≤ 2
kj kj (20)
⎩ (1 + αi ) − 1 + βi m ≥ 0
kj kj
In addition to constrain in (18), the dc factor and ac factor also should locate at the shadow area in
Figure 4. S1 , S2 , S3 , and S4 are the boundaries of the shadow area according to constrains in (20).
417
Energies 2019, 12, 96
/
) /
% O) O)
6 ( % O) O)
/ ) 6
6 6
$ O( O(
$ O( O(
AC factor Άkji
AC factor Άkji
/
/
/
6
6
( 6
6
DC factor ΅kji DC factor ΅kji
D E
/ % O) O) / % O) O)
/ (
(
6
) 6 $ O( O(
6
6
$ O( O(
AC factor Άkji
AC factor Άkji
/
/
/
6
6
6
6 )
DC factor ΅kji DC factor ΅kji
F G
Figure 4. Choosing appropriate DC and AC factor for maximum tolerance in different conditions:
(a) when 0 < ηkj ≤ 1; (b) when n (c) when −1 < ηkj ≤ 0; (d) when ηkj ≤ −1.
By regulating ηkj , the allowed range of battery power unbalance degree can be improved,
and the SOC convergence rate can also be improved.
Linear programming method is the typical method to study the extremum of linear objective
function under linear constraints. In this paper, linear programming method is used to study
the extremum of allowed unbalance degree.
According to the principles of linear programming method, the objective function is defined as
1 ξ kj
L : −λ = β − α (22)
1 − ξ kj 1 − ξ kj
The line L1 intersects with L at point (−λ, −λ), which can represent the unbalance degree.
For a larger unbalance degree, the intersection should be far away from the origin.
The Line L2 in Figure 4 is defined as
L2 : β = ηkj α (24)
418
Energies 2019, 12, 96
The line L2 denotes the ratio of DC factor and AC factor. The line segment EF is the intersection of
L2 and the shadow area. Therefore, the DC and AC factor should locate at the line segment EF.
(1) When 0 < η kj ≤ 1, E and F locate at S1 and S2 as shown in Figure 4a. The coordinates of E and F
are calculated as
1−m 1−m 1−m 1−m
E( ,η ), F ( ,η ) (25)
mηkj − 1 kj mηkj − 1 ηkj m + 1 kj ηkj m + 1
(2) When η kj > 1, E and F locate at S2 and S3 as shown in Figure 4b. The coordinates of E and F are
calculated as
1+m 1+m 1−m 1−m
E(− , −ηkj ), F ( ,η ) (26)
mηkj + 1 mηkj + 1 ηkj m + 1 kj ηkj m + 1
(3) When −1 < η kj ≤ 0, point E and F still locate at S1 and S2 as shown in Figure 4c, and the coordinates
of E and F are the same as Equation (25).
(4) When η kj ≤ −1, E and F locate at S1 and S4 as shown in Figure 4d. The coordinates of E and F are
According to the principles of linear programming method, it is obvious that λ reaches maximum
or minimum values when L1 passes through the point E or F. The point A (λE , λE ) and B (λF , λF )
are the corresponding intersections of the line L1 and L. Then substituting (25)–(27) into (22),
the unbalance degree λE and λF can be calculated.
In Figure 4, one of the point A and B locates at the first quadrant, and the other point locates
at the third quadrant. It means that the maximum values of λ must be positive and the minimum
values of λ must be negative. Therefore, we find the relations
λ p = max (λ E , λ F )
(28)
λn = min(λ E , λ F )
where λp denotes the tolerance for positive battery power unbalance degree, and λn denotes
the tolerance for negative battery power unbalance degree.
Considering that the battery power unbalance degree can be negative or positive for submodules
within one arm, the tolerance for battery power unbalance is defined as
ψkj = min λ p , |λn | (29)
If the battery power unbalance degree does not exceed the tolerance, over-modulation will not
occur, which can ensure the normal operation of MMC-BESS.
According to (29), the tolerance for battery power unbalance is calculated as shown in Figure 5,
which can be divided into several cases according to the power ratio.
419
Energies 2019, 12, 96
7ROHUDQFHIRUEDWWHU\SRZHUXQEDODQFH
7ROHUDQFHIRUEDWWHU\SRZHUXQEDODQFH
[ [
[ [
[
[
[
[ [
[
[
[
Ratio of DC factor and AC factorkj Ratio of DC factor and AC factor kj
D E
7ROHUDQFHIRUEDWWHU\SRZHUXQEDODQFH
7ROHUDQFHIRUEDWWHU\SRZHUXQEDODQFH
[ [
[ [
[ [
[ [
[ [
Ratio of DC factor and AC factor kj Ratio of DC factor and AC factor kj
F
G
Figure 5. Power regulation capability of submodules when m = 0.8: (a) when power ratio 0 < ξ kj ≤ 1;
(b) when power ratio ξ kj > 1; (c) when power ratio ξ kj ≤ −1/m; (d) when power ratio −1/m < ξ kj ≤ 0.
1. In Figure 5a, the power ratio 0 < ξ kj ≤ 1. The power regulation capability increases when
the absolute value of weighting ratio η kj increases. Apparently as weighting ratio approaches
infinity, the tolerance reaches the maximum value.
2. In Figure 5b, the power ratio ξ kj > 1. The tolerance for battery power unbalance reaches
the maximum value when η kj is equal to zero.
According to Figure 4, when the power ratio ξ kj = −1/m, the slope of L is the same to the boundary
S2 . When L passes through point F, the intersection of L and L1 is a fixed point, meaning that the power
regulation capability is a fixed value. It can be calculated according to Equations (23) and (24).
1 1−m
ψkj (ξ kj = − )= (30)
m 1+m
3. For the case ξ kj < −1/m, the tolerance for battery power unbalance reaches the maximum value
when η kj is equal to zero as shown in Figure 5c. For the case −1/m < ξ kj ≤ 0, the tolerance reaches
the maximum value when η kj approaches infinity as shown in Figure 5d.
In addition, note that all the curves in Figure 5 passes through a fixed point. The tolerance for
unbalanced power has no relation with the power ratio. According to Figure 4, when the weighting
ratio is equal to 1, the point B and F coincide together, so that the power regulation capability will not
change, and can be calculated as
1−m
ψkj (ηkj = 1) = (31)
1+m
420
Energies 2019, 12, 96
1. When −1/m < ξ kj ≤ 1, only ac component needs to be regulated, so that the DC factor and AC
factor are
αikj = 0
. (32)
βikj = (1 − ξ kj )λikj
Then according to the analysis in Section 3.2, the tolerance for battery power unbalance can be
calculated as
1−m
ψkj = (33)
m(1 − ξ kj )
2. When ξ kj > 1 or ξ kj ≤ −1/m, only DC component needs to be regulated, so that the DC factor
and AC factor are ⎧
⎨ αi = ξ kj −1 λi
kj ξ kj kj
(34)
⎩ βi = 0
kj
With the same method, the tolerance for battery power unbalance is
ξ kj
ψkj = (1 − m ) (35)
ξ kj − 1
On the basis, the modified SOC balancing control within arms is shown in Figure 6.
First, the unbalance degree is calculated according to (13). Then according to the power ratio, the DC
and AC factor are calculated. The reference of submodule voltage is given by adding the voltage
increment Δ uikj into the original submodule voltage. At last, CPS-PWM generates switching signals to
control the state of submodules.
Pkbj d [ d
m
N
'Pkbji Pkbji Okbj
i
D kbj
i
E kbj
i
SOCkj K ̇ukji ukji
Pkbj [ m
SOCkji
or [ !
ukj
Figure 7a shows the comparisons of tolerance for battery power unbalance when η takes some
special values. In [19,25], a power factor is introduced to distribute submodule voltage, which can be
equivalent to the case η = 1. The tolerance for battery power unbalance is a fixed value, but it is
too small for near all power ratio, which seriously limits the convergence rate of SOC balancing
control. For the case η = 0, only AC component is redistributed. However, the tolerance becomes
too small when the power ratio is relatively large. For the case 1/η = 0, only DC component is
421
Energies 2019, 12, 96
regulated, but the tolerance is too small when the power ratio is around zero. For the modified
method, the weighting ratio changes with power ratio, and the tolerance reaches maximum for all
operation modes.
7ROHUDQFHIRUSRZHUXQEDODQFH
7ROHUDQFHIRUSRZHUXQEDODQFH
3URSRVHGPHWKRG
P
K P
K P
K
3RZHUUDWLR 3RZHUUDWLR
D E
Figure 7. Tolerance for battery power unbalance: (a) comparison of different submodule voltage
regulation methods; (b) influence of modulation ratio.
Figure 7b shows the relation between modulation ratio and tolerance for battery power unbalance.
With the increase of modulation ratio, the tolerance sharply decreases. To avoid the over-modulation
of submodules, the gain of controller should be limited as
K3 Δ SOCkj_max ≤ ψkj Pkbj (36)
where
i
Δ SOCkj_max = max (SOCkj − SOCkj ) (37)
Note that the power ratio and maximum SOC unbalance of six arms are different, meaning that
the controller K3 may be different for different arms. To simplify the whole SOC balancing control
structure, K3 should take the same value, which should satisfy the relations
1
K3 ≤ min( ψkj Pkbj ) (39)
Δ SOCkj_max
In this way, over-modulation of submodules can be avoided, and the convergence rate of SOC
balancing control can be improved greatly.
422
Energies 2019, 12, 96
Figure 8 is the simulation results of traditional SOC balancing control method used in [25].
The power of AC side and DC side are: Pdc = 4.8 KW, Pac = 9.6 KW. Figure 8a is the SOC
of 24 submodules in MMC-BESS. At time T = 20 s, the SOC balancing control is added to the system,
and then the SOC starts to converge. However the convergence rate is too small for the whole BESS.
Figure 8b shows the average SOC of six arms, which can denote the SOC balancing control among
phases and between arms. Figure 8c,d are the SOC of upper and lower arm in phase A. It is obvious
that the convergence rate of whole BESS is mainly limited by SOC balancing control within arms.
The analysis in Section 3.2 indicates that the tolerance for battery power unbalance is limited in 11%
when m = 0.8. In Figure 8e, the maximum power unbalance is 10% and over-modulation almost
occurs as shown in Figure 8f. It means that the SOC convergence rate has already reached the limit,
however the SOC convergence of the whole BESS is still so poor.
423
Energies 2019, 12, 96
62&RIVXEPRGXOHV $YHUDJH62&RIVL[DUPV
62&
62&
$GG62&EDODQFLQJ
FRQWUROWRWKHV\VWHP
7LPHV 7LPHV
D E
62&RIORZHUDUPLQSKDVH$
62&RIXSSHUDUPLQSKDVH$
62&
62&
7LPHV 7LPHV
F G
0RGXODWLRQZDYHVRIXSSHUDUPLQSKDVHD
O
%DWWHU\FXUUHQW$
O
7LPHV 7LPHV
H I
Figure 8. Simulation results of traditional SOC balancing control: (a) SOC of all submodules;
(b) average SOC of six arms; (c) SOC of upper arm in phase a; (d) SOC of lower arm in phase a;
(e) battery current of phase arm in phase a; (f) modulation waves of upper arm in phase A.
Figure 9 is the simulation results of the proposed SOC balancing control, and the power
configuration is the same as the simulation in Figure 8. The SOC of all submodules is shown in
Figure 9a. At time T = 20 s, the SOC balancing control is added to the control system, and then the SOC
of the whole BESS converges to the same value at around T = 200 s. Figure 9b shows the average SOC
of six arms. Figure 9c,d are the SOC of upper and lower arm in phase A. In Figure 8, the tolerance
for battery power unbalance is about 50%, and the control design is according to (39). At T = 20 s,
the difference of SOC among submodules is the greatest, but the battery power unbalance is still
limited into the allowed values and over-modulation does not occur.
424
Energies 2019, 12, 96
62&RIVXEPRGXOHV $YHUDJH62&RIVL[DUPV
62&
62&
$GG62&EDODQFLQJ
FRQWUROWRWKHV\VWHP
7LPHV 7LPHV
D E
62&RIXSSHUDUPLQSKDVH$ 62&RIORZHUDUPLQSKDVH$
62&
62&
7LPHV 7LPHV
F G
0RGXODWLRQZDYHVRIXSSHUDUPLQSKDVHD
O %DWWHU\FXUUHQWRIXSSHU
SKDVHDUPLQSKDVH$
&XUUHQW$
O
7LPHV 7LPHV
H I
Figure 9. Simulation results of the modified SOC balancing control: (a) SOC of all submodules;
(b) average SOC of all phase arms; (c) SOC of upper arm in phase a; (d) SOC of lower arm in phase a;
(e) battery current of phase arm in phase A; (f) modulation waves of upper arm in phase A.
Compared with the traditional method, the proposed SOC balancing control method improves
the tolerance for battery power unbalance. Therefore, the efficiency of SOC balancing control can be
greatly improved and over-modulation also can be effectively avoided.
425
Energies 2019, 12, 96
Figure 11 is the steady-state waveforms of MMC-BESS, and the BESS works in charging mode.
Figure 11a is the ac-side current, and Figure 11b shows the circulating current of three phases.
Circulating current contains DC component and fundamental frequency component. The dc circulating
currents of phase A, B, and C are different, which are controlled to balance the SOC among legs.
Fundamental frequency circulating currents are injected to balance the SOC between phase arms.
Figure 11c,d show the submodule capacitor voltages and battery currents of upper arm and lower
arm in phase A. The ripples of capacitor voltage are filtered by the notch filter, so there is nearly no
low-frequency component in the battery current. The maximum battery power unbalance degree is
about 40%, which is much greater than the allowed unbalance degree in traditional method.
Figure 12 is the experiment result of optimized SOC balancing control proposed in this paper.
The SOC of 12 submodules is between 76–82% at T = 0, and the SOC of all submodules converges
to 70% at T = 40 min. Figure 13 is the experiment result of traditional SOC balancing control. The SOC
of 12 submodules is between 55–60% at T = 0. Figures 12a and 13a shows the SOC of all submodules.
it is obvious that the convergence of proposed method is much better than that of traditional
method. Figures 12b and 13b denote the SOC balancing control among phases and between arms.
The convergence of the two methods are basically the same. In Figure 12c,d and Figure 13c,d, the SOC
balancing control within arms of the proposed method is much faster than that of traditional method.
That is why the efficiency of the proposed method is much higher than that of traditional method.
426
Energies 2019, 12, 96
AcȬsideȱcurrent Circulatingȱȱcurrent
(a) (b)
UpperȱarmȱofȱphaseȱA LowerȱarmȱofȱphaseȱA
Capacitorȱvoltage SM1 [8V/div] Capacitorȱvoltage SM1 [8V/div]
Oau
Batteryȱcurrent SM1[0.5A/div] Batteryȱcurrent
Oau SM1[0.5A/div]
O
au SM2[0.5A/div]
SM2[0.5A/div]
[50ms/div] [50ms/div]
(c) (d)
Figure 11. Steady-state waveforms of MMC-BESS with optimized SOC balancing control method:
(a) AC-side current; (b) circulating current; (c) capacitor voltage and battery current of upper arm in
phase A; (d) capacitor voltage and battery current of lower arm in phase A.
62&RIVXEPRGXOHV $YHUDJH62&RIVL[DUPV
62&
62&
7LPHPLQ 7LPHPLQ
(a) (b)
SOC of upper arm in phase A SOC of lower arm in phase A
SM1 SM1
62&
62&
SM2 SM2
7LPHPLQ 7LPHPLQ
(c) (d)
Figure 12. Experiment results of modified SOC balancing control method: (a) SOC of all submodules;
(b) average SOC of phase arms; (c) SOC of upper arm in phase A; (d) SOC of lower arm in phase A.
427
Energies 2019, 12, 96
62&RIVXEPRGXOHV $YHUDJH62&RIVL[DUPV
62&
62&
7LPHPLQ 7LPHPLQ
(a) (b)
62&
62&
SM2
SM2
7LPHPLQ 7LPHPLQ
(c) (d)
Figure 13. Experiment results of traditional SOC balancing control method: (a) SOC of all submodules;
(b) average SOC of phase arms; (c) SOC of upper arm in phase A; (d) SOC of lower arm in phase A.
6. Conclusions
This paper mainly focuses on the SOC balancing control of MMC-BESS, aiming to improve
the efficiency of SOC balancing control. The investigation indicates that the battery power unbalance
can lead to the over-modulation of submodules, limiting the efficiency of SOC balancing control.
Then the tolerance for battery power unbalance is defined to quantize the convergence of SOC
balancing control. The submodule voltage regulation method is studied in detail by introducing
the DC factor and AC factor. The linear programming method is introduced to reach the maximum
tolerance in different operation modes. Based on the analysis, by choosing appropriate submodule
voltage regulation method, the efficiency of SOC balancing control is improved greatly. To avoid
over-modulation of submodules, the controller of SOC balancing control is also optimally designed.
In this way, the convergence rate of SOC is greatly improved compared with traditional method.
Finally, the analysis and proposed SOC balancing method are verified through detailed simulation
and experiment results.
Author Contributions: Y.M. proposed the main idea, performed the theoretical analysis, and wrote the paper.
H.L. contributed the experiment materials and gave some suggestions. Z.W. and Z.Z. performed the experiments.
Funding: This research was funded by National Natural Science Foundation of China, grant number 51741703.
Conflicts of Interest: The authors declare no conflict of interest.
References
1. Qian, H.; Zhang, J.; Lai, J.S.; Yu, W. A high-efficiency grid-tie battery energy storage system. IEEE Trans.
V
Power Electron. 2011, 26, 886–896. [CrossRef]
2. Alipoor, Y.; Miura, Y.; Ise, T. Power System Stabilization Using Virtual Synchronous Generator with
Alternating Moment of Inertia. IEEE J. Emerg. Sel. Top. Power Electron. 2015, 3, 451–458. [CrossRef]
3. Jiang, Q.Y.; Gong, Y.Z.; Wang, H.J. A battery energy storage system dual-layer control strategy for mitigating
wind farm fluctuations. IEEE Trans. Power Syst. 2013, 28, 3263–3273. [CrossRef]
4. Baruschka, L.; Mertens, A. Comparison of cascaded H-bridge and modular multilevel converters for
BESS application. In Proceedings of the Energy Conversion Congress and Exposition, Phoenix, AZ, USA,
17–22 September 2011; pp. 909–916. [CrossRef]
428
Energies 2019, 12, 96
5. Soong, T.; Lehn, P.W. Evaluation of emerging modular multilevel converters for BESS applications.
IEEE Trans. Power Deliv. 2014, 29, 2086–2094. [CrossRef]
6. Trintis, I.; Munk-Nielsen, S.; Teodorescu, R. A new modular multilevel converter with integrated energy
storage. In Proceedings of the IECON 2011-37th Annual Conference on IEEE Industrial Electronics Society,
Melbourne, Australia, 7–10 November 2011; pp. 1075–1080. [CrossRef]
7. Coppola, M.; Del Pizzo, A.; Iannuzzi, D. A power traction converter based on modular multilevel
architecture integrated with energy storage devices. In Proceedings of the Electrical Systems for Aircraft,
Railway and Ship Propulsion (ESARS), Pittsburgh, PA, USA, 14–18 September 2014; pp. 1–7. [CrossRef]
8. Hillers, A.; Stojadinovic, M.; Biela, J. Systematic comparison of modular multilevel converter topologies for
battery energy storage systems based on split batteries. In Proceedings of the 17th Europe Conference Power
Electronics, Geneva, Switzerland, 8–10 September 2015; pp. 1–9. [CrossRef]
9. Soong, T.; Lehn, P.W. Internal Power Flow of a Modular Multilevel Converter with Distributed Energy
Resources. IEEE J. Emerg. Sel. Top. Power Electron. 2014, 2, 1127–1138. [CrossRef]
10. Gao, F.; Zhang, L.; Zhou, Q. State-of-charge balancing control strategy of battery energy storage system based
on modular multilevel converter. In Proceedings of the IEEE Energy Conversion Congress and Exposition,
Pittsburgh, PA, USA, 14–18 September 2014; pp. 2567–2574. [CrossRef]
11. Zhang, L.; Gao, F.; Li, N. Interlinking modular multilevel converter of hybrid AC-DC distribution system with
integrated battery energy storage. In Proceedings of the IEEE Energy Conversion Congress and Exposition,
Montreal, QC, Canada, 20–24 September 2015; pp. 70–77. [CrossRef]
12. Bala, S. The effect of low frequency current ripple on the performance of a Lithium Iron Phosphate (LFP)
battery energy storage system. In Proceedings of the IEEE Energy Conversion Congress and Exposition,
Raleigh, NC, USA, 15–20 September 2012; pp. 3485–3492. [CrossRef]
13. Puranik, I.; Zhang, L.; Qin, J. Impact of Low-Frequency Ripple on Lifetime of Battery in MMC-based Battery
Storage Systems. In Proceedings of the IEEE Energy Conversion Congress and Exposition, Portland, OR, USA,
23–27 September 2018; pp. 2748–2752. [CrossRef]
14. Novakovic, B.; Nasiri, A. Modular multilevel converter for wind energy storage applications. IEEE Trans.
Ind. Electron. 2017, 64, 8867–8876. [CrossRef]
15. Ma, Y.J.; Lin, H.; Wang, Z.; Wang, T. Capacitor voltage balancing control of modular multilevel converters
with energy storage system by using carrier phase-shifted modulation. In Proceedings of the IEEE Applied
Power Electronics Conference and Exposition, Tampa, FL, USA, 26–30 March 2017; pp. 1821–1828. [CrossRef]
16. Soong, T.; Lehn, P.W. Assessment of Fault Tolerance in Modular Multilevel Converters with Integrated
Energy Storage. IEEE Trans. Power Electron. 2016, 31, 4085–4095. [CrossRef]
17. Hagiwara, M.; Akagi, H. Control and experiment of pulse width-modulated modular multilevel converters.
IEEE Trans. Power Electron. 2009, 24, 1737–1746. [CrossRef]
18. Adam, G.P.; Anaya-Lara, O.; Burt, G.M. Modular multilevel inverter: Pulse width modulation and capacitor
balancing technique. IET Power Electron. 2010, 3, 702–715. [CrossRef]
19. Han, W.; Zou, C.; Zhou, C. Estimation of cell SOC evolution and system performance in module-based
battery charge equalization systems. IEEE Trans. Smart Grid 2018. [CrossRef]
20. Vasiladiotis, M.; Rufer, A. Analysis and Control of Modular Multilevel Converters with Integrated Battery
Energy Storage. IEEE Trans. Power Electron. 2015, 30, 163–175. [CrossRef]
21. Quraan, M.; Tricoli, P.D.; Arco, S. Efficiency assessment of modular multilevel converters for battery electric
vehicles. IEEE Trans. Power Electron. 2017, 32, 2041–2051. [CrossRef]
22. Quraan, M.; Yeo, T.; Tricoli, P. Design and control of modular multilevel converters for battery electric
vehicles. IEEE Trans. Power Electron. 2016, 31, 507–517. [CrossRef]
23. Zhang, L.; Tang, Y.; Yang, S. Decoupled Power Control for A Modular Multilevel Converter-Based Hybrid
AC-DC Grid Integrated with Hybrid Energy Storage. IEEE Trans. Ind. Electron. 2018. [CrossRef]
24. Chen, Q.; Li, R. Analysis and Fault Control of Hybrid Modular Multilevel Converter with Integrated Battery
Energy Storage System. IEEE J. Emerg. Sel. Top. Power Electron. 2017, 5, 64–79. [CrossRef]
429
Energies 2019, 12, 96
25. Liang, H.; Guo, L.; Song, J. State-of-Charge Balancing Control of a Modular Multilevel Converter with
an Integrated Battery Energy Storage. Energies 2018, 11, 873. [CrossRef]
26. Debnath, S.; Qin, J.; Saeedifard, M. Control and stability analysis of modular multilevel converter under
low-frequency operation. IEEE Trans. Ind. Electron. 2015, 62, 5329–5339. [CrossRef]
© 2018 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access
article distributed under the terms and conditions of the Creative Commons Attribution
(CC BY) license (http://creativecommons.org/licenses/by/4.0/).
430
energies
Article
Multi-Level Open End Windings Multi-Motor Drives
Salvatore Foti 1, *, Antonio Testa 1 , Salvatore De Caro 1 , Tommaso Scimone 1 , Giacomo Scelba 2
and Giuseppe Scarcella 2
1 DI, University of Messina, 98122 Messina, Italy; [email protected] (A.T.); [email protected] (S.D.C.);
[email protected] (T.S.)
2 DIEEI, University of Catania, 95131 Catania, Italy; [email protected] (G.S.);
[email protected] (G.S.)
* Correspondence: [email protected]
Abstract: A multi-level open-end winding converter topology for multiple-motor drives is presented
featuring a main multi-level inverter processing the power delivered to the motors and an active filter
based on an auxiliary two-level inverter. The main inverter operates at the fundamental frequency in
order to achieve low switching power losses, while the active filter is Pulse Width Modulation (PWM)
operated to suitably shape the motor currents. The proposed configuration features less phase current
distortion than conventional multi-level inverters operating at the fundamental frequency, while
achieving a higher efficiency compared to PWM multi-level inverters. Experimental results confirm
the effectiveness of such a configuration on both multiple motors-single converter and multiple
motor-multiple converter drives.
Keywords: multilevel converter; multi-motor drive; harmonic mitigation; active filter; open end
winding motor; high efficiency drive; high reliability applications
1. Introduction
A Multiple Motor Drive (MMD) is composed of some electric motors sharing the load torque [1–5].
Such a configuration costs less than a set of single motor drives, as some resources are shared between
the units. Further, compared to a single drive, it is easily expandable by adding new units, moreover,
the intrinsic redundancy may be used to mitigate the effects of some kinds of converter and motor
faults. MMD are common in paper and textile industry and ironworks, as well as in several industry
applications demanding synchronization between two or more axes, high levels of reliability and/or
easy expandability. MMD systems can be grouped into two classes, namely: Multiple Motors Fed by a
Single Multi-level Converter (MMSC) and Multiple Motors Fed by Multiple Multi-level Converters
(MMMC). A single inverter on MMSC delivers power to all the machines, thus leading to only
an approximatively proportional load sharing. On MMMC a common DC bus supplies a set of
inverters, each one powering a single motor. In this case, the torque produced by each motor can be
independently controlled, while retaining a common power entry and braking system.
Induction Motor (IM) based MMMCs are frequently used on rail mounted, or rubber tired, gantry
cranes, equipping hoist, trolley and leg drives [6–8]. On leg drives MMMCs provide the ground to cope
with different wheel diameter, unequal wheels’ adhesion and slipping of transmission devices. MMDs
also often equip electric locomotives, powering the axles through spur gearings [9–12]. Dual-Voltage
Source Inverter (VSI)/Dual-IM and Mono-VSI/Dual-IM configurations are used with induction
motors. The first, being of the MMMC type, comprises two induction motors supplied through
two power converters. Such a configuration features a higher level of robustness toward inverter
faults. Moreover, critical operations caused by pantograph detachment, loss of wheel adherence and
stick-slip perturbation may be faced thanks to a fully independent control of the torque delivered
by single machines. In recent years, MMMC has also become a viable alternative to single drives on
powertrains of electrical and hybrid vehicles, featuring higher flexibility, reliability and transmission
efficiency, while helping to increase the available inner space [13,14].
A straightforward way to control the speed of a MMMC is based on the common speed reference
technique, providing a common speed reference signal to the speed controller of each unit. A torque
follower control approach is however preferable, due to concerns regarding the control precision and
system flexibility. According to such a technique, as shown in Figure 1, a single speed command is
provided to a master unit, which in turns sends the torque references to the other drives [6]. Torque
and flux regulation on single units is generally based on the traditional Indirect Field Oriented Control
(IFOC) technique or Direct Torque Control strategy.
9D
7H &XUUHQW 9E 3:0 ,19 ,0
.
FRQWURO
9F a
ȦU
9D
ȦU - 7H &XUUHQW 9E 3:0 ,19 ,0
+ 3, .
FRQWURO 9F a
ȦU
ȦU
9DQ
7HQ &XUUHQW 9EQ 3:0 ,19Q ,0Q
.Q
FRQWURO
9FQ a
ȦU
Figure 1. Common speed reference control of a Multiple Motors fed by Multiple Converters
(MMMC) system.
In recent years, Multi-Level Inverters (MLIs) have been introduced on multi-motor drives. in
order to generate almost sinusoidal output voltages using low frequency switching power devices,
thus achieving high efficiency and electromagnetic compatibility. In addition, power devices are
tasked with withstanding a fraction of the total DC input voltage, resulting in a remarkable reduction
of dv/dt stresses and switches voltage ratings. However, in order to achieve a comparable phase
current Total Harmonic Distortion (THD), MLI topologies working at low switching frequency could
require many more power devices than conventional Pulse Width Modulation (PWM) operated bridge
inverters. Cost concerns lead to limitation of the number of power devices, resulting in torque ripple
and additional losses. These can be addressed by selective harmonic elimination or PWM techniques,
as well as, by the addition of line reactors and tuned harmonic filters. Active power filters may
also be exploited as they are able to provide a more flexible and effective attenuation of current
harmonics [15–24].
An Open-end Winding (OW), multi-level, configuration for MMD applications is proposed in
this paper; it features null neutral point fluctuations, low phase current ripple and improved DC bus
voltage utilization [25–29]. A distinctive characteristic of the proposed configuration is the asymmetry,
because that the two inverters are not of the same type and only one of the two provides power to the
motors. In fact, a main multi-level inverter processes the power delivered to the motors, while an active
filter, based on an auxiliary two-level inverter (TLI), shapes the phase current. Moreover, the main
inverter operates at the fundamental frequency in order to achieve low switching power losses, while
the active filter is PWM operated. Finally, the DC bus voltage of the two-level inverter is remarkably
lower than that of the main inverter [30–36]. The proposed MMD OW configuration features a higher
global efficiency and lower current THD than an equivalent PWM operated multi-level inverter for
multi-motor drives [37], exploiting a specific control strategy combining low switching frequency
432
Energies 2019, 12, 861
modulation on the MLI and high frequency PWM on the TLI. Finally, it can be used either on either
multiple motors-single converter or multiple motor-multiple converter drives.
2l − n + 1
VMLI_stepi = V (1)
2(n − 1) DC
5RWRU
SRVLWLRQ
6WHS TU
9'&¶ 90/,BVWHS ,0
9 0/,D
6WHS 0/, 5DLO
9 0/,E
0RGXODWLRQ
9 0/,F
LD
LE 9P
LF 3:0
9 7/,D 7/,
9 3:0
9
7/,E
7/,F
97/,
9'&¶¶ 9P
,0
LD
LE ȦU
LF
5RWRU
TU SRVLWLRQ
Figure 2. Proposed Open-end Winding (OW) Multi-level inverter (MLI) + Two Level Inverter (TLI)
Multiple Motors Fed by a Single Multi-level Converter (MMSC) configuration.
In the same way, the i-phase TLI output voltage VTLIi is given by:
(2l − 1)
VTLIi = VDC (2)
2
where l” = 0, 1 is the i-phase TLI actual output voltage level.
The voltage Vmi across a generic ‘i’ motor phase winding, is finally given by:
433
Energies 2019, 12, 861
where V n n” is the voltage across the mid points n and n” of the two DC buses, which is given by:
1 1
Vn n = (VMLIa + VMLIb + VMLIc ) + (VTLIa + VTLIb + VTLIc ) (4)
3 3
The phase voltage Vmi takes the zero level and further 4(n + 1) non-zero levels when VDC ” =
VDC /[2(n − 1)], while, some additional non zero levels become available if VDC ” < VDC /[2(n −
1)] [31].
The voltage levels which the proposed asymmetrical hybrid multilevel inverter configuration may
take are more numerous than those of conventional Neutral Point Clamped (NPC) or Flying Capacitor
(FC) MLI topologies with the same amount of power switches. In other words, the same phase voltage
THD can be achieved with the proposed MMSC configuration using fewer power devices. Moreover,
the proposed configuration features a switching frequency which is that of the TLI, although the main
inverter switches at the fundamental frequency [37]. This leads to use power devices optimized for
low switching frequency operation (i.e., featuring a low on-state voltage drop) in the MLI, and power
devices suitable for high switching frequency in the TLI.
A suitable motor phase voltage modulation strategy was formulated taking into account the
specific features of the proposed topology, according to the scheme in Figure 3.
The TLI is tasked with compensating low frequency phase voltage harmonics generated by the
MLI, which is step driven to reduce the switching power losses. Unwanted low frequency voltage
harmonics can be suppressed by setting the voltage reference V*TLIi of the TLI to:
∗ ∗ ∗
VTLIi = VMLI_stepi − VMLIi (5)
where: V*MLIi is the fundamental harmonic of the ith motor phase reference voltage V*MLI_stepi . Both
quantities are depicted in Figure 4 for the case of a seven-level VMLI_stepi waveform.
9 0/,L
9'&ƍ
90/,BVWHSL
W
9'&ƍ
Q
9'&ƍ
9 7/,L
W
434
Energies 2019, 12, 861
The voltage ratio KV = VDC ”/VDC is a key parameter, because it impacts on the number of
inverter voltage levels, on the THD of phase voltages and currents, on the maximum motor phase
voltage amplitude and finally, on the ratings of TLI power devices.
The phase voltage Vmi is the difference between VMLIi and VTLIi , hence, its space vector diagram
can be obtained by combination of the voltage space vector diagrams of the MLI and TLI. The simplest
MMSC structure which can be obtained with the proposed approach consists of a Three-Level inverter
(3LI) and a TLI (3LI+TLI).
The phase voltage of each inverter leg of the 3LI can assume three statuses namely: P, O and N. P
denotes that the inverter phase voltage VMLIi = VDC , while O indicates that VMLIi = 0, and N that VMLIi
= −VDC . The 3LI topology is basically composed of two cells, each one supplied at VDC /2, hence each
leg may take three switching states, resulting in 33 = 27 possible inverter switching state combinations.
Each space vector can be categorized into zero voltage, small voltage, medium voltage and large
voltage on the basis of its magnitude. These are tabulated in Table 1. The TLI instead features 23 = 8
inverter states, leading to 7 voltage vectors. As shown in Figure 5, the 3LI+TLI voltage space vector
diagram is obtained by composition of the voltage space vector diagrams of the TLI and the 3LI. The
number of available voltage vectors and voltage levels depends on KV , as listed in Table 2, affecting
both the THDV and the peak amplitude Vmpk of the phase voltage Vmi . In particular, Vmpk increases
with KV , while a minimum THDV is achieved for VDC ” = VDC /[(n − 1)], [24], thus, the considered
3LI+TLI system gets the minimum THDV for VDC ” = VDC /2. However, Vmpk maximization must be
also taken into consideration, thus, a useful figure of merit in determining the optimal value of KV is
Kp = Vmpk /(VDC × THDV ), which, according to Table 3, is maximized when VDC ” = VDC /2. When
VDC ” is reduced below VDC /2, Kp and Vmpk decrease, while the number of voltage levels and voltage
vectors increases, as well as THDV . However, the voltage rating of TLI power devices is lowered. For
KV = 1/8, the 3LI+TLI is equivalent to conventional six-level NPC or FC inverter structures, which
however require six more power devices. By setting VDC ” over VDC /2, a higher Vmpk is obtained,
while the number of voltage levels and voltage vectors is lowered, worsening THDV and Kp . Moreover,
when VDC ” = VDC , the voltage rating of the TLI switches becomes equal to that of MLI devices.
Table 1. Switching states and voltage vector of Three Level Inverter (3LI).
Table 2. Power converter specifications vs. KV for Three Level Inverter + Two Level Inverter (3LI+TLI).
435
Energies 2019, 12, 861
9 '&
9 '& 131 231 331
9 '& 131
13 231 331
31
9 '&
9P 132
32
2
121
232 332
221
321
3
9P 132 232 332 321
121 221
9'& 333
9'& 333
133
3 233 111 322 311
1
122 211 133 233 111 322 311
1
222
122 222 211
223 212
123
23 112 323 312
1 212
223
9'& 123 112 323 312
9 9'&
113 213 313 '&
113
11 213 313
13
3
9'& 9'& 9'&
(a) (b)
9 '&
9 '& 9 '&
9 '&
131 231 331 131
13 231 331
31
9P 9
9'&
132 232 332 321 P
132 232 332 321
121 221 121 221
9'& 333 333
111
133 233 111 322 311 133 233 322 311
122 222
22 211
122 222 211
223 212
223 212 123 112 323
1 312
123 112 323 312
12
12
113
11 213 313
13
113 213 313
9'& 9'&
9'&
9'&
9'&
9'&
(c) (d)
Figure 5. Phase voltage space phasor diagram (a) VDC ”/VDC = 1/8; (b) VDC ”/VDC = 1/4;
(c) VDC ”/VDC = 1/2; (d) VDC ”/VDC = 1.
According to the proposed approach no active power is delivered to the two IM motors from the
TLI. In practice, power devices and motors power losses in the TLI would cause a progressive discharge
of the floating capacitor of the TLI DC-bus. Being floating, such a capacitor can only be charged by
diverting to it a small quantity of the active power delivered by the MLI to the motors [32–44]. As
shown in the control scheme of Figure 6, this is achieved by slightly modifying the TLI reference
voltages. Specifically, two additional terms VdCap and VqCap are introduced to control the mean current
436
Energies 2019, 12, 861
flowing through the DC bus capacitor. Since the TLI is not tasked with supplying reactive power to
the load, VdCap can be straightforwardly related to VqCap , by:
3 i
Q= V i − VdCap iq = 0 ⇒ VdCap = d VqCap (6)
2 qCap d iq
The active power P required to hold VDC ” constant is obtained by a PI controller processing the error
between the reference DC bus voltage VDC ”* and the actual voltage VDC ”.
3 K
P= V iq + VdCap id = (V DC ∗ − V DC ) K pVDC + iVDC (7)
2 qCap s
where s is the Laplace operator, and KpVDC and KiVDC are, respectively, the proportional and integral
gain of the PI controller. By introducing Equation (6) into Equation (7), the dq-axes voltage reference
components VqCap and VdCap are obtained:
2 Piq 2 Pid
VqCap = VdCap = (8)
3 i2q + i2d 3 i2q + i2d
0/,UHIHUHQFHYROWDJHV 9'&ƍ
ȦUH 9 90/,BVWHS
T0/, TGR ,0 5DLO
( T /VȦȜUHL G + 9 0/,D 6WHS 0/,
9 G0/,
9 0/,E 0RGXODWLRQ
+
( G /.ȦȜUHL T DEF 9 0/,BVWHSD
S LD
9 0/,F LE 9P
TȜUH 9 0/,BVWHSE LF
L G 7/,&XUUHQW&RQWURO 9 0/,BVWHSF
- LG
S
9 G7/,U TGR +-
+
3, 9 9 7/,
ȦU L T
+ 7/,UBD - +-+ 7/,D
3:0
+
3, 9 97/,
DEF 9 7/,UBE 9
-
+ T7/,U 7/,E
- 3, ++
-
ȦU -
LT 9 7/,UBF
-
9 7/,F
9P
9FDSBE 9FDSBF 9'&ƍƍ
3 9FDSBD ,0
9'&ƍƍ 9 T&DS 9 TFDS TGR LT TGR LD
9'&ƍƍ 3 ¨§ L G · LE
L ¸
-
SS 3, 9 GFDS LG
+
¨© T L T ¸¹ DEF
DEF LF ȦU
ȦUH 9 G&DS
LG
9 T&DS TȜUH
LT TȜUH LT
ZOUH ZUH ȦUH 0RWLRQ
7/,'&%XVYROWDJHFRQWURO WU LG
2EVHUYHU
SSSROHSDLUV TȜUH TOUH ³Z OUH GW
The two additional terms are then transformed to the abc stationary frame and added to the TLI
voltage references obtained from Equation (5). Due to the floating capacitor recharging, the phase
current typically increases by less than 1.5% of the rated current. The considered 3LI+TLI topology
requires a specific control system which is schematized in Figure 6. It consists of two subsystems,
acting on the two inverters. The MLI is voltage controlled, thus, the q, d axes voltage references VdqMLI *
are made equal to the motors back EMF components Ê*q and Ê*d , which in turn are estimated by
Êq∗ = Ls ωλre id∗
(9)
Êd∗ = − Lk ωλre iq∗
⎧ ∗
⎨ ω = Rr i∗q + ω
λre Lr i d r
(10)
⎩ L = − Ls Lr − L2m
k Lr
where: ω λre is the rotor flux angular frequency, ω r is the rotor speed of the two machines, and Ls , Lr
and Lm are respectively the stator, rotor and magnetizing inductances.
As shown in Figure 6, the TLI features a feedback current control, in order to improve the shape
of the current waveform and the system dynamic response. The outputs V*dqTLIr_i of the TLI current
control loop are transformed to the abc stationary frame and then added to other voltage reference
437
Energies 2019, 12, 861
components, dealing with compensation of low order stator voltage harmonics and VDC ” stabilization,
this allows us to obtain the voltage references for the PWM modulator, which are given by:
∗ ∗ ∗ ∗
VTLIi = VTLIr_i + VMLI_stepi − VMLIi + Vcap_i (11)
The currents flowing through the two stator windings cannot individually be controlled. However,
even load torque sharing is obtained when considering two identical motors with a high-stiffness
mechanical coupling. Whenever these conditions are not verified, torque and current unbalance may
yield to a system instability. In this case, the TLI current control structure needs to be modified as
suggested in references [45–51].
6WHS
9'&¶ 90/,BVWHS ,0
9 0/,D
6WHS 0/, 5DLO
9 0/,E
0RGXODWLRQ
9 0/,F
LD
LE 9P
9 7/,D LF
9 7/,E 7/,
9 7/,F 3:0 97/,
9 7/,G
9 7/,H
9'&¶¶ 9P
,0
LF
LE ȦU
LD
5RWRU
TU SRVLWLRQ
438
Energies 2019, 12, 861
0/,UHIHUHQFHYROWDJHV 90/,
ȦUH 9 9'&ƍ
T0/, TGR 9 0/,D ,0 5DLO
(T /VȦȜUHL G +
9 0/,E 6WHS 0/,
9 G0/, 0RGXODWLRQ
(G /.ȦȜUHL + DEF 9 0/,F 9 0/,BVWHSD
T + - S LD
9 0/,BVWHSE LE 9P
7/,&XUUHQW&RQWURO TȜUH + -
LF
L G 9 0/,BVWHSF
L G - LG
+ - B S
9 G7/,U TGR 9 7/,UBD 9 7/,D
+ 3, +
9 7/,UBE 9 7/,E
L T + 9 T7/,U
+
+ 9 7/,F
7/,
97/,
. 3, DEF
9 7/,UBF
+
9 7/,G 3:0
-
LT - -+ 9 7/,H
L
-
ȦU T 9'&ƍƍ
- LG 9P
+
3, L G 9 G7/,U TGR 9 7/,UBD
- 3, ,0
ȦU +
9 7/,UBE
.
L T + 9 T7/,U TGR LD
3, DEF
9 LT
-
LT
7/,UBF
LE LD
LG LE ȦU
TȜUH 9FDSBD
SS DEF LF LF
ȦUH 3 9FDSBE TȜUH
9'&ƍƍ 9 T&DS 9 TFDS TGR 5RWRU
ƍƍ
SSSROHSDLUV 9'& - 3 ¨§ L G · 9FDSBF SRVLWLRQ
3, L ¸ 9 GFDS LTL
+
¨© T L T ¸¹ DEF
TGR LD ZOUHL ZUH
7HQ LT WUL LGL ȦUH 0RWLRQ
. LG LE
9 G&DS
9 T&DS TȜUH LG
7HQ 7HQ
³Z
DEF 2EVHUYHU
LT LF TOUHL OUHLGW
. . TȜUH L
7/,'&%XVYROWDJHFRQWURO
According to such an approach [46], the five-leg TLI voltage references are given by:
∗
VTLIa ∗
= VTLIr_a1 ∗
+ VTLIr_c2 ∗
+ VMLI_stepa ∗
− VMLIa
∗ ∗ ∗ ∗ ∗
VTLIb = VTLIr_b1 + VTLIr_c2 + VMLI_stepb − VMLIb
∗
VTLIc ∗
= VTLIr_c1 ∗
+ VTLIr_c2 ∗
+ VMLI_stepc ∗
− VMLIc (12)
∗ ∗ ∗ ∗ ∗
VTLId = VTLIr_a2 + VTLIr_c1 + VMLI_stepa − VMLIa
∗ ∗ ∗ ∗ ∗
VTLIe = VTLIr_b2 + VTLIr_c1 + VMLI_stepb − VMLIb .
Since both motors are connected to a single MLI, voltage harmonic compensation is exerted by
acting on the TLI a, b, d and e phase voltage references.
The average values of q-d back EMF components Ê*q and Ê*d are estimated from Equations (9)
and (10), by assuming:
id∗ = id1
∗ ∗
= id2 (13)
∗
iq1 = K1 iq∗ ∗
iq2 = K2 iq∗ (14)
where:
Te2n
K1 = K2 = ( 1 − K1 ) (15)
Te1n + Te2n
By assuming the use of two identical motors, the q-axis current references can be imposed as:
∗ ∗
iq1 = iq2 = 0.5iq∗ (16)
439
Energies 2019, 12, 861
The inverter power losses, consisting of the switching losses PswMLI , PswTLI and conduction losses
PcMLI , PcTLI were calculated as in [31]:
The motor joule losses Pjoule and motor iron losses Piron are given by:
E2
Pjoule = RS iS 2 + Rr ir 2 Piron = (18)
Rfe
The induction motors parameters are listed in Table 4, while technical data of the IGBT used in
the MLI and the MOSFET used in the TLI are summarized in Tables 5 and 6, respectively. The systems
were run at ω r = 100 rad/s.
Pn (HP) Vn (V) pp Ls (mH) Lr (H) Lm (H) Rs (Ω) Rfe (Ω) Rr (Ω) J (Kg·m2 )
3 400 2 0.32 0.32 0.31 2.6 902 2.7 0.016
VDSS (V) IDSS (A) Tj (◦ C) RDS(on) (mΩ) ton (ns) toff (ns)
150 20 175 32 8.9 17.2
Figure 9 deals with power losses estimation for the three considered cases, taking into account
the motor (core and winding) and inverter (switching and conduction) power losses and considering
the first ninety harmonics of the stator current and voltage.
Figure 9. Motor iron losses Piron , motor joule losses Pjoule , MLI conduction losses PCMLI , MLI switching
losses PswMLI , TLI conduction losses PCTLI and TLI switching losses PswTLI : (a) 3LI step modulated;
(b) 3LI PWM modulated; (c) 3LI+TLI configuration.
When the step modulated 3LI feeds the two wye connected induction motors, as shown in
Figure 9a, power losses largely consist of motor joule losses, because the motor currents are affected
by low-order harmonics components. When the 3LI PWM modulated feeds the two wye connected
induction motors, as shown in Figure 9b, motor joule losses are still dominant, but higher switching
losses occurs. Finally, the 3LI+TLI configuration is considered. Since the MLI is step modulated and
440
Energies 2019, 12, 861
the phase motor current waveform is made close to a sinusoidal one by the active power filter, motor
and MLI inverter losses are considerably reduced, especially at heavier loads.
The 3LI+TLI topology features a higher efficiency at medium and high loads, while at low loads
its efficiency is comparable with that of the PWM driven 3LI. Based on computed motor and inverter
losses, total efficiency was evaluated in the three considered cases, as shown in Figure 10.
Figure 10. Total efficiency of the MMSC: (a) 3LI step operated; (b) 3LI PWM operated;
(c) 3LI+TLI configuration.
A comparison between the performance of the 3LI+TLI5 topology and that of a conventional
system consisting of two PWM operated 3LIs supplying two wye connected induction motors was also
accomplished. The results shown in Figure 11, confirming that the 3LI+TLI5 MMMC is more efficient
than the conventional one, especially at heavy loads.
(IILFLHQF\ (IILFLHQF\
/RDGWRUTXH SX /RDGWRUTXH SX
(a) (b)
Figure 11. Total efficiency of the system: (a) 3LI PWM operated; (b) 3LI+TLI5 configuration.
5. Experimental Tests
The proposed multi-motor drive configurations were experimentally validated using two
induction motors, the technical specifications of which are shown in Table 4. The MLI was equipped
with an IGBT with parameters shown in Table 5 while the TLI consisted of a MOSFET, detailed in
Table 6. Figure 12 shows the test rig. The first prototype featured an MMSC configuration, tailored
around a five level NPC main inverter (5LI+TLI). The second prototype was still an MMSC system,
but equipped with a three level NPC main inverter (3LI+TLI). The third prototype is instead a MMMC
system composed of a five level NPC main inverter and a five-leg, two-level (5LI+TLI5) auxiliary
inverter. All the three prototypes are field oriented controlled by a dSPACE board featuring a 100 μs
update time. On each drive configuration two induction motors were present with mechanical coupling
between them in order to operate them at the same rotational speed. Moreover, the TLI was PWM
operated at fswTLI = 10 kHz, with a 1 μs dead time. The DC bus voltage VDC of the MLIs was 400 V,
while VDC ” was set at 50 V when a 5LI was used and at 100 V when a 3LI was used. A controllable
mechanical load was realized by exploiting a conventional 3 HP vector controlled induction motor
drive, detailed in Table 4.
A steady state test on a conventional step operated 5LI supplying two wye connected induction
motors is shown in Figure 13. The test was performed at ω r = 50 rad/s and with no load. A remarkable
stator current distortion was obtained, due to the low switching frequency. Figure 14 deals with
441
Energies 2019, 12, 861
the same test but using the 5LI+TLI MMSC topology instead of the conventional configuration. The
distortion of the motors phase current was remarkably reduced, however; the efficiency was also
slightly reduced, being 80% for the 5LI and 76% for the 5LI+TLI system.
¶¶
,5)63%)
9'&
9$ &
¶¶
'&3RZHU 9'& '&3RZHU
,*%7*:1&9' 6XSSO\
6XSSO\ 9$ &
9'&¶ 6: 9GF 6:
G6SDFH G6SDFH
9GF¶ 6:
¶
9GF Q LDEFP 7/, 7/,
97/,DEF OHJV OHJV L DEFV
9 0/,DEF
/,
/RDG,19
/RZ )UHTXHQF\
FRPPDQGVLJQDO
ZUP
3:0FRPPDQG (QFRGHU
VLJQDO
,0 ,0 /RDG (QFRGHU
FXUUHQWDQG
YROWDJHVLJQDOV 2SHQ HQG:LQGLQJ
Figure 12. Experimental setup of OW MMSC.
UDGV ȦU
9PD 9
Figure 13. Conventional configuration, both motors are wye-connected and fed by a step operated
5MLI: steady state test at ω r = 50 rad/s and with no load. Motor speed ω r , a-phase motor Vma , motor
currents iam1 and iam2 .
UDGV ȦU
9PD
9
7+'L
LDP
LDP
PV 7+'L $
Figure 14. 5LI+TLI MMSC: steady state test at ω r = 50 rad/s. Motor speed ω r , a-phase motor Vma ,
motor currents iam1 and iam2 .
442
Energies 2019, 12, 861
A comparison between the 3LI+TLI and 5LI+TLI MMSC configurations is provided in Figure 15.
A steady state test (ωr1 = ωr2 = 50 rad/s) performed using the MMMC 5LI+TLI5 system is displayed
in Figure 16. The c phase current of the TLI is higher than the currents of the other four phases, as it is
given by the combination of the c phase currents of both motors.
9PD 9
LDP
7+'L
$
97/,D
9
9 7/,D PV
(a)
9
9PD
7+'L
LDP $
97/,D
9
9 7/,D PV
(b)
Figure 15. (a) MMSC (3LI+TLI); (b) MMSC (5LI+TLI). Steady state test, stator voltage Vma , stattor
current iam1 , TLI output voltage VTLIa and TLI voltage reference V*TLIa .
UDGV ȦU
9PD 9
7+'L
$
7+'L
PV
(a)
7+'L
LFP
Figure 16. 5LI+TLI5 MMMC, Steady state test at ω r = 50 rad/s. (a) Motor speed ω r , a-phase motor
Vma , motor currents iam1 and iam2 ; (b) motor currents iam1 and iam2 and common-leg c-phase current ic .
Speed reversals from ωr = −40 rad/s to ωr = 40 rad/s accomplished by the 5LI+TLI MMSC and
the 5LI+TLI5 MMMC prototypes, are shown in Figure 17. The drives feature a good dynamic response
443
Energies 2019, 12, 861
and an effective floating capacitor voltage control. The torque load was evenly shared between the
two motors.
UDGV
ȦU
LT
$
LT
9'&
PV 9
(a)
ȦU
UDGV
LT
LT $
9'&
PV 9
(b)
Figure 17. (a) 5LI+TLI5 MMSC; (b) 5LI+TLI5 OW MMMC: speed reversal with idref = 2 A. Motor speed
ω r , q-axes currents components iq1 and iq2 and TLI DC Bus voltage VDC ”.
In order to assess the capability of the 5LI+TLI5 configuration to individually control the torque
produced by the two motors, the previous test was repeated with uneven loading on the two machines.
As shown in Figure 18, 70% of the load torque was produced by IM1 and 30% by IM2. Figure 19 shows
the phase currents of IM1 and IM2 at the steady state for the MMMC. The steady state currents and
dynamical torque, as well as, and speed response are quite satisfactory.
ȦU UDGV
LT
LT $
9'&
PV 9
Figure 18. MMMC 5LI+TLI5: speed reversal with. idref = 2 A, iq1 = 0.7 iq and iq2 = 0.3 iq . Motor speed
ω r , q-axes currents components iq1 and iq2 and TLI DC Bus voltage VDC ”.
444
Energies 2019, 12, 861
UDGV ȦU
LDP
$ 7+'L
LDP $
7+'L
PV
Figure 19. MMMC 5LI+TLI5: Steady state at ω r = 50 rad/s and 50% of rated load, speed ω r , currents
iam1 and iam2 .
6. Conclusions
The paper has proposed a multi-level converter topology for multiple-motor drives based on
a special open-end winding configuration. Applications of such a topology to multiple motors -
single converter and multiple motor-multiple converter drives was also discussed. Specifically, two
configurations, an MLI+TLI Multi Motor Single Converter system and an MLI+TLI5 Multi Motor Multi
Converter system were presented and managed by purposely developed control strategies, combining
a low switching frequency modulation on the MLI and high frequency PWM on the TLI. As shown in
the paper, in both cases the proposed configurations produced much lower stator current distortion
when compared to conventional multi-motor drives equipped with MLI switching at the fundamental
frequency. Further, they generated lower power losses when compared to multi motor drives equipped
with PWM operated MLI. Although the paper considers only multi motor systems comprising two
identical induction machines, the proposed approach can be generalized for systems with an arbitrary
amount of motors; it can also be exploited for multi motor systems using synchronous machines, and
even for multi motor systems using a mix of machines of different sizes.
Author Contributions: Conceptualization, S.F., A.T., S.D.C., and G.S. (Giuseppe Scarcella); methodology, S.F.,
A.T., and G.S. (Giacomo Scelba); software, S.F., G.S. (Giacomo Scelba) and T.S.; validation, S.F., G.S. (Giacomo
Scelba) and T.S.; supervision, A.T., G.S. (Giacomo Scelba) and G.S. (Giuseppe Scarcella).
Funding: This research received no external funding.
Conflicts of Interest: The authors declare no conflict of interest.
Nomenclature
MMD Multiple Motor Drive
MMSC Multiple Motors fed by a Single Converter
MMMC Multiple Motors fed by Multiple Converters
IFOC Indirect Field Oriented Control
TLI Two-Level Inverter
3LI Three-Level inverter
TLI5 Five-leg two level inverter
3LI+TLI OW configuration including 3LI and TLI
3LI+TLI5 OW configuration including 3LI and TLI5
5LI+TLI OW configuration including 5LI and TLI
5LI+TLI5 OW configuration including 5LI and TLI5
THD Total Harmonic Distortion
n MLI voltage levels
VMLI_stepi i-phase MLI output voltage with respect to n
VTLIi i-phase TLI output voltage with respect to n”
445
Energies 2019, 12, 861
References
1. Levi, E.; Jones, M.; Vukosavic, S.N.; Toliyat, H.A. A novel concept of a multiphase, multimotor vector
controlled drive system supplied from a single voltage source inverter. IEEE Trans. Power Electron. 2004, 19,
320–335. [CrossRef]
2. Jeftenic, B.; Bebic, M.; Statkic, S. Controlled multi-motor drives. In Proceedings of the International
Symposium on Power Electronics, Electrical Drives, Automation and Motion SPEEDAM, Taormina, Italy,
23–26 May 2006; pp. 1392–1398.
3. Iyer, J.; Tabarraee, K.; Chiniforoosh, S.; Jatskevich, J. An improved V/F control scheme for symmetric load
sharing of multi-machine induction motor drives. In Proceedings of the Canadian Conference on Electrical
and Computer Engineering (CCECE), Niagara Falls, ON, Canada, 8–11 May 2011; pp. 1487–1490.
446
Energies 2019, 12, 861
4. Pulvirenti, M.; Scarcella, G.; Scelba, G.; Cacciato, M.; Testa, A. FaultTolerant AC Multidrive System. IEEE J.
Emerg. Sel. Top. Power Electron. 2014, 2, 224–235. [CrossRef]
5. Scelba, G.; Scarcella, G.; Pulvirenti, M.; Cacciato, M.; Testa, A.; de Caro, S.; Scimone, T. Current-Sharing
Strategies for Fault-Tolerant AC Multidives. IEEE Trans. Ind. Appl. 2015, 51, 3943–3953. [CrossRef]
6. Slutej, A.; Kolonic, F.; Jakopovic, Z. The new crane motion control concept with integrated drive controller for
engineered crane application. In Proceedings of the IEEE International Symposium on Industrial Electronics,
ISIE, Bled, Slovenia, 12–16 July 1999; pp. 1458–1461.
7. Mitrovic, N.; Petronijevic, M.; Kostic, V.; Jeftenic, B. Electrical Drives for Crane Application, Mechanical
Engineering; Gokcek, M., Ed.; InTech: London, UK, 2012; ISBN 978-953-51-0505-3.
8. Foti, S.; Testa, A.; de Caro, S.; Scimone, T.; Pulvirenti, M. Sensorless field oriented control of multiple-motors
fed by multiple-converters systems. In Proceedings of the IEEE International Symposium on Sensorless
Control for Electrical Drives (SLED), Catania, Italy, 18–19 September 2017; pp. 237–242.
9. Matsumoto, Y.; Ozaki, S.; Kawamura, A. A novel vector control of single-inverter multiple-induction-motors
drives for Shinkansen traction system. In Proceedings of the 16th Annual Applied Power Electronics
Conference and Exposition, (APEC 2001), Anaheim, CA, USA, 4–8 March 2001; pp. 608–614.
10. Peña-Eguiluz, R.; Pietrzak-David, M.; DeFornel, B. Comparison of several control strategies for parallel
connected dual induction motors. In Proceedings of the VIII IEEE International Power Electronics Congress,
2002. Technical Proceedings. CIEP 2002, Guadalajara, Mexico, 24–24 October 2002.
11. Mabrouk, W.B.; Belhadj, J.; Pietrzak-David, M. Synthesis and Analysis of one Bogie Induction Railway
Traction System. In Proceedings of the on 13th European Conference on Power Electronics and Applications,
Barcelona, Spain, 8–10 September 2009; pp. 1–9.
12. Achour, T.; Pietrzak-David, M. Service Continuity of an IM Distributed Railway Traction with a Speed Sensor
Fault. In Proceedings of the 14th European Conference on Power Electronics and Applications, Birmingham,
UK, 30 August–1 September 2011; pp. 1–8.
13. Cui, S.; Han, S.; Chan, C. Overview of multi-machine drive systems for electric and hybrid electric vehicles. In
Proceedings of the IEEE Conference and Expo Transportation Electrification Asia-Pacific (ITEC Asia-Pacific),
Beijing, China, 31 August–3 September 2014; pp. 1–6.
14. Arnet, B.; Jufer, M. Torque control on electric vehicles with separate wheel drives. In Proceedings of the EPE
Conference, Trondheim, Norway, 8–10 September 1997; pp. 659–664.
15. Du, Z.; Tolbert, L.M.; Chiasson, J.N. Active harmonic elimination for multilevel converters. IEEE Trans.
Power Electron. 2006, 21, 459–469.
16. Tolbert, L.M.; Chiasson, J.N.; Du, Z.; McKenzie, K.J. Elimination of Harmonics in a Multilevel Converter
with Non equal DC Sources. IEEE Trans. Ind. Appl. 2005, 41, 75–82. [CrossRef]
17. Fong, Y.C.; Cheng, K.W.E. An adaptive modulation scheme for fundamental frequency switched multilevel
inverter with unbalanced and varying voltage sources. In Proceedings of the Power Electronics Systems and
Applications (PESA), Hong Kong, China, 15–17 December 2016; pp. 1–6.
18. Edpuganti, A.; Rathore, A.K. Fundamental Switching Frequency Optimal Pulsewidth Modulation of
Medium-Voltage Cascaded Seven-Level Inverter. IEEE Trans. Ind. Appl. 2015, 51, 3485–3492. [CrossRef]
19. Corzine, K.A.; Sudhoff, S.D.; Whitcomb, C.A. Performance characteristics of a cascaded two-level converter.
IEEE Trans. Energy Convers. 1999, 14, 433–439. [CrossRef]
20. Li, L.; Czarkowski, D.; Liu, Y.; Pillay, P. Multi-level selective harmonic elimination PWM technique in
serie-connected voltage inverters. IEEE Trans. Ind. Appl. 2000, 36, 160–170. [CrossRef]
21. Napoles, J.; Leon, J.I.; Portillo, R.; Franquelo, L.G.; Aguirre, M.A. Selective Harmonic Mitigation Technique
for High Power Converters. IEEE Trans. Ind. Electron. 2009, 57, 2197–2206. [CrossRef]
22. Haitham, A.R.; Holtz, J.; Rodriguez, J.; Baoming, G. Medium Voltage Multilevel Converters-State of the Art,
Challenges, and Requirements in Industrial Applications. IEEE Trans. Ind. Electron. 2010, 57, 2581–2596.
23. Lai, J.-S.; Peng, F.Z. Multi-level converters-A new breed of power converters. IEEE Trans. Ind. Appl. 1996, 32,
509–517.
24. Davari, P.; Yang, Y.; Zare, F.; Blaabjerg, F. A novel harmonic elimination approach in three-phase multi-motor
drives. In Proceedings of the IEEE Energy Conversion Congress and Exposition (ECCE), Montreal, QC,
Canada, 20–24 September 2015; pp. 7001–7008.
447
Energies 2019, 12, 861
25. Sivakumar, K.; Das, A.; Ramchand, R.; Patel, C. A Hybrid Multilevel Inverter Topology for an Open-End
Winding Induction Motor Drive Using Two-Level Inverters in Series with a Capacitor-Fed H-Bridge Cell.
IEEE Trans. Ind. Electron. 2010, 57, 3707–3714. [CrossRef]
26. Boller, T.; Holtz, J.; Rathore, A.K. Optimal pulse width modulation of a dual 3LI system operated from a
single dc link. IEEE Trans. Ind. Appl. 2012, 48, 1610–1615. [CrossRef]
27. Mondal, G.; Sivakumar, K.; Ramchand, R.; Gopakumar, K.; Levi, E. A Dual Seven-Level Inverter Supply for
an Open-End Winding Induction Motor Drive. IEEE Trans. Ind. Electron. 2008, 56, 1665–1673. [CrossRef]
28. Somasekhar, T.; Gopakumar, K.; Bajiu, M.R.; Mohapatra, K.K.; Umanand, L. A multilevel inverter system for
an inductor motor with open-end windings. IEEE Trans. Ind. Electron. 2005, 52, 824–836. [CrossRef]
29. Edpuganti, A.; Rathore, A.K. New Optimal Pulse Width Modulation for Single DC-Link Dual-Inverter Fed
Open-End Stator Winding Induction Motor Drive. IEEE Trans. Power Electron. 2014, 30, 4386–4393.
30. Foti, S.; Testa, A.; Scelba, G.; de Caro, S.; Cacciato, M.; Scarcella, G.; Bazzano, D.; Scimone, T. A new approach
to improve the current harmonic content on open-end winding AC motors supplied by multi-level inverters.
In Proceedings of the IEEE Energy Conversion Congress and Exposition (ECCE), Montreal, QC, Canada,
20–24 September 2015; pp. 4040–4047.
31. Foti, S.; Testa, A.; Scelba, G.; de Caro, S.; Cacciato, M.; Scarcella, G.; Scimone, T. An Open End Winding Motor
Approach to mitigate the phase voltage distortion on Multi-Level Inverters. IEEE Trans. Power Electron. 2018,
33, 2404–2416. [CrossRef]
32. De Caro, S.; Foti, S.; Scimone, T.; Testa, A.; Cacciato, M.; Scarcella, G.; Scelba, G. THD and efficiency
improvement in multi-level inverters through an open end winding configuration. In Proceedings of the
2016 IEEE Energy Conversion Congress and Exposition (ECCE), Milwaukee, WI, USA, 18–22 September
2016; pp. 1–7.
33. Foti, S.; Scelba, G.; Testa, A.; Sciacca, A. An Averaged-Value Model of an Asymmetrical Hybrid Multi-Level
Rectifier. Energies 2019, 12, 589. [CrossRef]
34. Foti, S.; de Caro, S.; Scelba, G.; Scimone, T.; Testa, A.; Cacciato, M.; Scarcella, G. An Optimal Current
Control Strategy for Asymmetrical Hybrid Multilevel Inverters. IEEE Trans. Ind. Appl. 2018, 54, 4425–4436.
[CrossRef]
35. De Caro, S.; Foti, S.; Scimone, T.; Testa, A.; Cacciato, M.; Pulvirenti, M.; Russo, S. Over-voltage mitigation on
SiC based motor drives through an open end winding configuration. In Proceedings of the 2017 IEEE Energy
Conversion Congress and Exposition (ECCE), Cincinnati, OH, USA, 1–5 October 2017; pp. 4332–4337.
36. Foti, S.; Testa, A.; Scelba, G.; Cacciato, M.; de Caro, G.S.S.; Scimone, T. Overvoltage mitigation in open-end
winding AC motor drives. In Proceedings of the 2015 IEEE ICRERA, Palermo, Italy, 22–25 November 2015;
pp. 235–238.
37. Scelba, G.; Scarcella, G.; Foti, S.; Testa, A.; de Caro, S.; Scimone, T. An Open-end Winding approach to the
design of multi-level multi-motor drives. In Proceedings of the IECON 2016—42nd Annual Conference of
the IEEE Industrial Electronics Society, Florence, Italy, 23–26 October 2016; pp. 5026–5032.
38. Haque, R.U.; Toulabi, M.S.; Knight, A.M.; Salmon, J. Wide speed range operation of PMSM using an open
winding and a dual inverter drive with a floating bridge. In Proceedings of the IEEE Energy Conversion
Congress and Exposition (ECCE), Denver, CO, USA, 15–19 September 2013; pp. 3784–3791.
39. Cacciato, M.; Consoli, A.; Finocchiaro, L.; Testa, A. High frequency modeling of bearing currents and shaft
voltage on electrical motors. In Proceedings of the Eighth International Conference on Electrical Machines
and Systems, Nanjing, China, 27–29 September 2005; pp. 2065–2070.
40. Cacciato, M.; Cavallaro, C.; Scarcella, G.; Testa, A. Effects of connection cable length on conducted EMI in
electric drives. In Proceedings of the IEEE International Electric Machines and Drives Conference, Seattle,
WA, USA, 9–12 May 1999; pp. 428–430.
41. Cacciato, M.; De Caro, S.; Scarcella, G.; Scelba, G.; Testa, A. Improved space-vector modulation technique for
common mode currents reduction. IET Power Electron. 2013, 6, 1248–1256. [CrossRef]
42. Foti, S.; Testa, A.; Scelba, G.; Sabatini, V.; Lidozzi, A.; Solero, L. Asymmetrical hybrid unidirectional T-type
rectifier for high-speed gen-set applications. In Proceedings of the IEEE Energy Conversion Congress and
Exposition (ECCE), Cincinnati, OH, USA, 1–5 October 2017; pp. 4887–4893.
43. Scelba, G.; Scarcella, G.; Foti, S.; De Caro, S.; Testa, A. Self-sensing control of open-end winding PMSMs fed
by an asymmetrical hybrid multilevel inverter. In Proceedings of the IEEE International Symposium on
Sensorless Control for Electrical Drives (SLED), Catania, Italy, 18–19 September 2017; pp. 165–172.
448
Energies 2019, 12, 861
44. De Caro, S.; Foti, S.; Scelba, G.; Scimone, T.; Testa, A. A six-level asymmetrical Hybrid Photovoltaic Inverter
with inner MPPT capability. In Proceedings of the 6th International Conference on Clean Electrical Power
(ICCEP), Santa Margherita Ligure, Italy, 27–29 June 2017; pp. 631–635.
45. Dujic, D.; Jones, M.; Vukosavic, S.N.; Levi, E. A general PWM method for a (2n+1)-leg inverter supplying n
three-phase machines. IEEE Trans. Ind. Electron. 2009, 56, 4107–4118. [CrossRef]
46. Rifkin, S. Adjustable-Voltage Hoist Drives for Cranes. IEEE Electr. Eng. 1956, 75, 620–623. [CrossRef]
47. Myles, A.H.; Davies, M.C.; Srnka, L.J. DC magnetic crane hoist control for AC powered cranes. Trans. Am.
Inst. Electr. Eng. Part I Commun. Electron. 1960, 79, 207–211.
48. Ruxi, W.; Yue, W.; Qiang, D.; Yanhui, H.; Zhaoan, W. Study of control methodology for single inverter
parallel connected dual induction motors based on the dynamic model. In Proceedings of the 2006 37th IEEE
Power Electronics Specialists Conference, Jeju, Korea, 18–22 June 2017; pp. 1–7.
49. Matsuse, K.; Kouno, Y.; Kawai, H.; Yokomizo, S. A speed-sensorless vector control method of
parallel-connected dual induction motor fed by a single inverter. IEEE Trans. Ind. Appl. 2002, 38, 1566–1571.
[CrossRef]
50. Kelecy, P.M.; Lorenz, R.D. Control methodology for single inverter, parallel connected dual induction motor
drives for electric vehicles. In Proceedings of the Power Electronics Specialists Conference, PESC ’94 Record,
25th Annual IEEE, Taipei, Taiwan, 20–25 June 1994; Volume 2, pp. 987–991.
51. Dixit, A.; Mishra, N.; Sinha, S.K.; Singh, P. A review on different PWM techniques for five leg voltage source
inverter. In Proceedings of the IEEE-International Conference On Advances In Engineering, Science And
Management (ICAESM), Nagapattinam, Tamil Nadu, India, 30–31 March 2012; pp. 421–428.
52. Tabbache, A.; Rebaa, K.; Marouani, K.; Benbouzid, M.E.H.; Kheloui, A. Independent control of two
induction motors fed by a five legs PWM inverter for electric vehicles. In Proceedings of the 2013 4th
International Conference on Power Engineering, Energy and Electrical Drives, Istanbul, Turkey, 13–17 May
2013; pp. 629–634.
53. Pradabane, S. A New SVPWM for Dual-Inverter fed Three-level Induction Motor Drive. In Proceedings of
the 2013 4th International Conference on Green Computing, Communication and Conservation of Energy,
Chennai, India, 12–14 December 2014; pp. 514–518.
© 2019 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access
article distributed under the terms and conditions of the Creative Commons Attribution
(CC BY) license (http://creativecommons.org/licenses/by/4.0/).
449
energies
Article
On PWM Strategies and Current THD for Single- and
Three-Phase Cascade H-Bridge Inverters with
Non-Equal DC Sources
Zhansen Akhmetov 1 , Manel Hammami 2 , Gabriele Grandi 2, * and Alex Ruderman 1
1 Department of Electrical and Computer Engineering, Nazarbayev University, 010000 Astana, Kazakhstan;
[email protected] (Z.A.); [email protected] (A.R.)
2 Department of Electrical, Electronic, and Information Engineering, Univ. of Bologna, 40136 Bologna, Italy;
[email protected]
* Correspondence: [email protected]; Tel.: +39-051-20-93571
Abstract: Cascade H-bridge (CHB) inverter is an attractive choice for integration of DC sources of
different nature, e.g., for distributed generation with energy storage, photovoltaic generation, etc. In
general, non-equal DC voltage sources can affect the total harmonic distortion (THD) of the CHB by
introducing undesirable low-frequency subharmonics. This paper investigates different level-shifted
(LS) and phase-shifted (PS) pulse width modulation (PWM) strategies for single- and three-phase
cascade H-bridge inverters with non-equal DC sources from the load current THD minimization
perspective. The best current quality is provided by LS PWM, as reported in the literature. The paper
provides a simple time domain explanation of LS PWM superiority. However, PS PWM may be
a preferable choice for practical applications due to fair power and loss sharing across individual
H-bridges. The paper explains how to obtain the best current quality by PS PWM carriers’ order
arrangement (DC sources switching sequence selection).
Keywords: multilevel inverters; total harmonic distortion; level-shifted PWM; phase-shifted PWM
1. Introduction
Nowadays, multilevel inverters (MLIs) are widely used, since they offer improved output
waveforms, smaller grid filter size, lower total harmonic distortion (THD), and reduced electromagnetic
interference (EMI), compared to their two-level inverter counterparts [1–6]. In particular, MLIs are
particularly suitable for medium- and high-voltage applications for both single- and three-phase systems,
thanks to the possibility to work with high-voltage levels by adopting low-voltage-rated devices.
The basic multilevel converter topologies are cascade H-bridge (CHB), neutral-point-clamped
(NPC), flying capacitor (FC), and modular multilevel converter (MMC) [5,6]. These kinds of converters
are also adopted in photovoltaic applications due to the aforementioned advantages.
Many recently published papers deal with the estimation of voltage and current THD in
multilevel inverters. In most of the cases, they are based on voltage frequency spectra numerical
calculations/measurements (fast Fourier transform, FFT). The scientific community has shown a
significant interest in voltage and current THD analyses for both multilevel pulse width modulation
(PWM) and staircase modulation over the past years. Analytical solutions for the voltage THD of
multilevel PWM single- and three-phase inverters were obtained in [7] in asymptotic approximation
(high switching-to-fundamental frequency ratio). Experimental tests have been carried out in [8] to
verify the calculation and analytical developments of voltage and current THDs in the case of three-,
five-, and seven-level single-phase PWM inverters.
Cascade H-Bridge converter is a mature multilevel topology adopted for different applications
with multiple DC sources [1–4].
A single-phase CHB inverter topology and related phase-shifted (PS) and level-shifted (LS) PWM
are demonstrated in Figure 1. For LS PWM, apparent switching frequency equals the carrier one. For
PS PWM, the apparent switching frequency is that of an individual H-bridge (double carrier frequency)
times the number of H-bridges [9].
Current THD theoretical calculations for a single-phase multilevel PWM inverter with uniform
voltage level distribution and inductance-dominated RL-load is addressed in [8]. The approach of [8]
is applicable to a CHB inverter with equal DC sources.
With respect to a CHB inverter having equal DC sources, a CHB inverter with non-equal DC
voltages can affect current quality by introducing undesirable subharmonic content that may violate
the grid-codes [10].
This paper considers LS and PS PWM applied to single- and three-phase CHB inverters with
non-equal DC sources in the context of current THD minimization. Though a converter RL-load is
considered, the results are applicable to grid-connected applications as well [8].
The paper starts with a generalization of asymptotic current THD formulas for a single-phase
multilevel inverter with uniform levels [8] for non-uniform voltage level distribution. The results
are applicable to a single-phase CHB inverter with LS PWM and non-equal DC sources. In addition,
minimal current THD requires matching LS PWM bands to DC source voltages that may be difficult
to implement in real-life applications. For a single-phase CHB inverter with PS PWM and non-equal
DC sources, the optimal current THD for more than three sources is achieved by a proper selection of
carrier order (DC sources switching sequence), as recently shown in [11,12].
For a three-phase CHB inverter, theoretical current THD consideration becomes too complicated.
Therefore, current THD is analyzed by MATLAB–Simulink simulations.
The major contributions of this paper may be formulated as follows. Theoretical current
THD calculation methodology for non-uniform voltage levels allows evaluating current THD for a
single-phase CHB inverter with non-equal DC sources and LS PWM. Though it is difficult to implement
LS PWM in practice (PWM band matching to DC source voltages is required), the calculated current
THD gives a theoretical limit.
For a three-phase CHB inverter with more than three DC sources per phase, the single-phase
current THD optimal DC source switching sequences reported in [11,12] also work well. Swapping the
carriers among the different phases (changing the carriers order) could be considered as an additional
degree of freedom that may be used to improve the current THD.
C C C C
V REF
t
− VREF
−
V REF
t
−
Figure 1. Single-phase cascade H-bridge (CHB) inverter: (a) topology example for four H-bridges;
(b) phase-shifted (PS) pulse width modulation (PWM) carriers; (c) level-shifted (LS) PWM
carrier arrangement.
451
Energies 2019, 12, 441
The paper is organized as follows. Section 2 presents the current THD calculation methodology
for non-uniform voltage levels applicable to a single-phase cascade inverter in the case of LS PWM
and non-equal DC sources. The analysis of the current THD with PS PWM and non-equal DC sources
for the cascade H-bridge inverter is presented in Section 3. The analysis of current THD has been
extended to a three-phase cascade H-bridge inverter with non-equal DC sources and presented in
Section 4. Section 5 presents the conclusion.
2. Current THD for a Single-Phase CHB Inverter with LS PWM and Non-Equal DC Sources
Current THD for a single-phase CHB inverter with LS PWM and equal DC sources can be
calculated as suggested in [8] for uniformly distributed voltage levels. In this section, the results of [8]
are generalized to acquire non-equal DC sources. For the best harmonic performance (minimal current
THD), LS modulation bands must be adjusted to match non-equal DC source voltages (Figure 2).
V REF
t
−
Figure 2. Four H-bridge CHB inverter LS PWM bands adjusted to match non-equal DC sources V1 >
V2 > V3 > V4.
where L and R are load inductance and resistance; ff and fAS – fundamental frequency and apparent
switching frequency; n-level count (the number of H-bridges increased by one).
For n-level CHB inverter with (n − 1) H-bridges with non-equal sources and LS PWM
band matching (Figure 2), the current ripple normalized mean square (NMS) is found using the
general formula
1 n −3 ci bn − 2
6π i∑
N MSnNE (m) =
AC
+ , (2)
=0 a i +1 − a i 1 − a2n−2
2 2
where ai , 0 < ai < 1, is “voltage level”, i, 0 ≤ i ≤ n − 1, is the ratio of respective sum of DC source
voltages to the total DC voltage (a0 = 0, an−1 = 1)
∑ij=1 Vj
ai = , (3)
Vtotal
where Vtotal = ∑nj=−11 Vj is the total DC voltage and m is the modulation index (0 < m < 1);
1
a2n−2 2 2 πan−2 πa2
2
a n −2 π 3πm4
bn − 2 = qn−2 asin + d n −2 1 − 2 +m + πan−2 + + + n−2 , (4)
m m 4 4 16 2
1 1
ai a a2i 2
a2i+1 2
ci = qi asin − asin i+1 + di 1 − + hi 1 − . (5)
m m m2 m2
452
Energies 2019, 12, 441
3 m2 2
q i = − m4 − ai + 4ai ai+1 + a2i+1 − a2i a2i+1 ; (6)
8 2
23 4 a3 a2 a
d i = − m3 ai + ai+1 + m i − 3ai i+1 − 2a2i i+1 ; (7)
24 3 12 2 3
4 23 a3 a2 a
h i = m3 ai + ai+1 + m − i+1 + 2ai i+1 + 3a2i i+1 . (8)
3 24 12 3 2
3NE ( m ) =
NMSAC
⎧ 1
⎪
⎪ 2 3
23 a m3 − a1 m a2 2
− − 38 m4 − m2 a21 asin( m1 )− 43 a1 m3 +
a
⎪
⎪ 24 1 1− 1
⎪
⎪
12 m2
⎪
⎪ 6πa21
⎪
⎪
⎨ 2 πa2
( )−a21 a22 asin( m1 )+m2
a π
− 38 m4 − m2 a21 +4a1 a2 + a22 4 + πa1 + 4
1 (9)
⎪ +
⎪
⎪ 6π (1− a21 )
⎪
⎪
⎪
⎪ 2
3πm4 + πa1 + a3 a22 a2
1
2
⎪
⎪ −m3 ( 23
24 a1 + 3 a2 ) + m
4
12 −3a1
1 2 a2
2 −2a1 3 1− 1
⎪
⎩ +
16 2 m2
.
6π (1− a21 )
For a three H-bridge (4-level) CHB with non-equal DC source voltages, V 1 = V 2 = V 3 , output
voltage levels become a0 = 0; a1 = V +V 1
; a2 = V V+1V+2V+2V3 ; a3 = V1 +V2 +V3
V1 +V2 +V3 = 1.
1 V2 +V3 1
Current ripple NMS for non-equal sources
⎧ 1
⎪
⎪ a2 2
⎪
⎪ −q0 asin( m1 )+d0 +h0 1−
a 1
⎪
⎪ m2
+
⎪
⎪ a21 ∗6∗π
⎪
⎪
⎪
⎨ a2
1
2 a22
1
2
q1 (asin( m1 )−asin( m2 ))+d1
a a
1− 12 + h1 1−
AC
N MS4NE (m) = m m2 (10)
⎪
⎪ + +
⎪
⎪ ( a22 −a21 )∗6∗π
⎪
⎪ 1
⎪
⎪ a2 2 a22 4 πa22
⎪
⎪ q2 asin( m2 )+d2
a
1− 2 + m2 π π
4 + πa2 + 4 + 3πm
16 +
⎪
⎩ m2 2
,
(1−a22 )∗6∗π
where coefficients q0 , d0 , h0 , q1 , d1 are calculated using Formulas (6)–(8). For example, for a four
H-bridge (5-level) CHB inverter current ripple NMS for non-equal sources from (2),
⎧
⎪
⎪ a2
1
2
⎪
⎪ −q0 ∗asin( m1 )+d0 +h0 ∗ 1−
a 1
⎪
⎪ m2
⎪
⎪ +
⎪
⎪ a21 ∗6∗π
⎪
⎪ 1 1
⎪
⎪ q1 (asin( m1 )−asin( m2 ))+d1
a a a2 2 a22 2
⎪
⎪ 1− 12 + h1 ∗ 1−
⎪
⎨
m m2
+
( a22 −a21 )∗6∗π
AC
N MS5NE (m) = 1 1 (11)
⎪
⎪ a2 2 a2 2
⎪
⎪ q2 (asin( m2 )−asin( m3 ))+d2
a a
1− 22 + h2 ∗ 1− 32
⎪
⎪ m m
+
⎪
⎪ ( a23 −a22 )∗6∗π
⎪
⎪
⎪
⎪ 1
⎪
⎪ a2 2 a2 4 πa23
q3 ∗asin( m3 )+d3 ∗
a
⎪
⎪ 1− 32 + m2 π 43 +πa3 + π4 + 3πm
16 +
⎪
⎩
m 2
.
(1−a23 )∗6∗π
Theoretical current THD results obtained using (1), (2) are in good agreement with simulated
ones. Calculations and simulations across this paper are carried out for the following parameters: load
resistance R = 1 Ω, load inductance L = 1 mH, fundamental frequency ff = 50 Hz, apparent switching
frequency fAS = 4000 Hz and nominal DC source voltage V = 100 V.
453
Energies 2019, 12, 441
Figure 3a,b present theoretical current THD according to (1), (2), (11) for a single-phase 4-bridge
CHB for three cases: non-equal sources arranged in ascending order (a1 = 0.2; a2 = 0.45; a3 = 0.7);
non-equal sources arranged in descending order (a1 = 0.3; a2 = 0.55; a3 = 0.8); uniform voltage levels
(equal sources, a1 = 0.25; a2 = 0.5; a3 = 0.75).
(a) (b)
Figure 3. Total harmonic distortion (THD) for LS PWM: (a) 0.1 < m < 1; (b) 0.7 < m < 1.
For relatively large modulation indices m > 0.8, that is typical for grid-tied applications, current
THDs for all three cases are close to each other. The lowest THD is achieved for non-equal sources
arranged in descending order (V 1 > V 2 > V 3 > V 4 ).
For relatively small modulation indices m < 0.3, the lowest THD is achieved for the non-equal
sources arranged in ascending order (V 1 < V 2 < V 3 < V 4 ).
Figures 4–6 show current THD simulation results for m = 0.9 that are in good agreement with
theoretical ones (Figure 3). Theoretical current THD values are typically slightly lower than those
obtained from simulation due to theoretical assumptions.
Figure 4. THD for LS PWM a1 = 0.2, a2 = 0.45, a3 = 0.7, and m = 0.9.
454
Energies 2019, 12, 441
The LS PWM considered in this section provides better current THD compared with PS PWM for
single-phase and especially for three-phase CHB inverters. However, the known drawback of LS PWM
is an uneven power and loss distribution across different H-bridges. For equal DC sources, the remedy
may be H-bridge rotation. For non-equal DC sources, the best THD performance requires LS PWM
band adjustment in accordance with true DC source voltage magnitudes (Figure 2) that may become
problematic. If there is no match between non-equal DC sources and LS PWM bands, current THD is
compromised, and the linearity of CHB inverter as reference signal “voltage amplifier” is violated.
3. Current THD for a Single-Phase CHB Inverter with PS PWM and Non-Equal DC Sources
For a single-phase CHB inverter with PS PWM and equal DC sources (uniform levels), current
THD for inductance-dominated RL-load may be calculated according to [8]. Current THD theoretical
formulas are based on asymptotic assumption, meaning that the apparent PWM frequency is much
larger than the fundamental AC one.
In theory, the same formula for current THD for uniform voltage levels is applicable to both LS
and PS PWM. In real life, current THD for PS PWM may be larger than that for LS PWM, that is better
predicted by asymptotic formulas.
For LS PWM, voltage and current spectra show distinct apparent switching frequency
(Figures 4–6). For PS PWM, the spectrum around apparent switching frequency is spread. This
happens because, at reference level crossings, PWM voltage for PS PWM is shifted by half a PWM
period. This effect has almost no impact on voltage THD for uniform levels—for a single-phase CHB
inverter with equal sources, voltage THD is practically the same for both LS and PS PWM, and this is
because voltage ripple mean square on respective PWM periods is practically the same [7].
455
Energies 2019, 12, 441
The effect of PWM voltage half a period shift at reference level crossings, in fact, presents a
low-frequency disturbance that may have a negative impact on current THD. This is because current
ripple can be considered as voltage ripple integral for an inductance-dominated load [8], and it is
deteriorated by the low-frequency “voltage irregularities”. On the one hand, this adverse effect
increases with level count increase (more reference voltage crossings). On the other hand, it reduces
with apparent switching frequency increase (more switching between adjacent levels) and RL-load
time constant increase (better low-frequency filtering).
Figure 7 shows current THD for a four H-bridge CHB inverter with equal sources and PS PWM.
Compared with LS PWM for the same modulation index m = 0.9 (Figure 6), the switching frequency
spectrum is spread, and the THD value is slightly larger.
Figure 7. Four H-bridge CHB inverter current THD for PS PWM and equal sources.
In the recent papers [11] and [12], asymptotic formulas of [8] are generalized for a single-phase
CHB inverter with PS PWM and non-equal DC sources. Moreover, it is shown that for more than three
H-bridges, there are extreme DC source (H-bridge) switching sequences (carrier orders in Figure 1b
that minimize (maximize) current THD.
Suppose DC source voltages are sorted in the ascending order
and DC source switching sequences on a PWM period are denoted by number sequences like 1234
(Figure 8). In the case of three CHB cells, there are six different sequences in total, and only one
sequence could be considered with respect to the THD, which is the 123. In fact, the sequences 123,
231, and 312 have the same THD due to circular permutation equivalence. Similarly, 321, 132, and 213
have the same THD due to the reversal circular permutation. In the following, “1” is always placed
first to eliminate circular permutation redundancy.
456
Energies 2019, 12, 441
C C C C C C C C
V REF V REF
t t
− VREF − VREF
− −
C C C C C C C C
V REF V REF
t t
− VREF − VREF
− −
Figure 8. Four H-bridge CHB inverter switching sequences: (a) 1234, (b) 4123, (c) 3412 and (d) 2341 are
equivalent under asymptotic assumption by circular permutation.
In the case of four CHB cells, only three different sequences can be considered which are 1234,
1324, and 1243. The other sequences are equivalent within circular permutation (Figure 8) and order
reversal. The number of all possible DC source switching sequences for the different numbers of
H-bridge cells are summarized in Table 1. It can be noticed that in the case of four and more CHB cells,
the THD with PS PWM is strictly dependent on the DC sources switching sequences.
Cells 4 5 6 7 8 9 10
Sequences 3 12 60 360 2520 20160 181440
As shown in [11,12], for four H-bridges, the best and worst sequences from the current THD
perspective become 1423 and 1243. The switching sequences for the different numbers of H-bridge
cells are given in Table 2 with respect to the best and the worst cases.
Cells 5 6 7 8 9
Worst 12453 124653 1246753 12468753 124689753
Best 15234 162435 1725436 18264537 192745638
Figures 9 and 10 present current THD for a single-phase CHB inverter with PS PWM for the best
and worst switching sequences, respectively. Normalized non-equal voltages amount to v1 = 0.8; v2
= 0.933; v3 = 1.067; v4 = 1.2 p.u. (1.0 p.u. corresponds to 100 V). It is clearly seen that the best source
switching sequence, 1423, provides the minimal current THD of 0.77% (1.04% for the worst sequence).
However, the minimal THD of this PS PWM is worse than 0.6% for equal DC sources (for LS PWM
with optimal bands adjustment, it is even better—0.57%).
457
Energies 2019, 12, 441
Figure 9. Four H-bridge CHB THD for PS PWM and non-equal sources best switching sequence 1423.
Figure 10. Four H-bridge CHB THD for PS PWM and non-equal sources worst switching sequence 1243.
Current THD was also calculated for a single-phase CHB inverter with six H-bridges and PS PWM
for the best and worst switching sequences, respectively. Normalized non-equal voltages were selected
as v1 = 0.80; v2 = 0.88; v3 = 0.96; v4 = 1.04; v5 = 1.12; v6 = 1.20 p.u. Current THD for the best switching
sequence 162435 was found as 0.47%, and the same for the worst sequence—1.29% (compared with
0.4% for equal DC sources).
Current THD values for different cases of single-phase four H-Bridge CHB inverter PWM for m =
0.9, R = 1 Ω, L = 1 mH are compared in Table 3.
In general, there was a good agreement between theoretically calculated and simulated values.
For uniform levels, simulated current THD for PS PWM was slightly larger than for LS PWM due to
the unaccounted effect of PS PWM voltage half a period shift at reference level crossings (Section 2).
Current THD values for different cases of single-phase six H-Bridge CHB inverter PWM for m =
0.9, R = 1 Ω, L = 1 mH are compared in Table 4.
458
Energies 2019, 12, 441
For Table 4, again, there is a good agreement between theoretically calculated and simulated
current THD values. The relative difference between calculated and simulated current THD values
for PS PWM is larger compared to the four H-bridge inverter because there are more unaccounted
low-frequency disturbances due to PWM voltage half a period shift at reference level crossings.
t t
t
t
t t
Figure 11. Different PWM phase voltages synchronization for LS PWM: (a) voltage pulses of the same
polarity; (b) voltage pulses of opposite polarities.
459
Energies 2019, 12, 441
For PS PWM, due to the effect of voltage half a PWM period shift at reference level crossings,
for some portions of a fundamental period different phase, PWM voltage synchronization may be
as in Figure 12 (Figure 12b is obtained from Figure 11b by half a PWM period shift). This kind of
synchronization results in reduced line voltage quality due to non-nearest level switching.
sĂ sĂ
t t
sď sď t
t
sĂď sĂď
t t
;ĂͿ ;ďͿ
Figure 12. Different PWM phase voltages possible synchronization for PS PWM: (a) voltage pulses of
the same polarity; (b) voltage pulses of opposite polarities.
Theoretical asymptotic time domain analysis of a three-phase CHB inverter voltage and current
quality becomes a complicated task. Therefore, current THD values in this section were obtained
by simulation for inverter Y-connected balanced RL-load and relatively large modulation index m =
0.85 that is characteristic for grid-tied applications. Voltage references were selected pure sinusoidal
without any zero-sequence insertion.
For LS PWM and equal DC sources, line voltage and current THD are shown in Figures 13 and 14;
the same for PS PWM—in Figures 15 and 16. It is clearly seen that for PS PWM, for some parts of the
fundamental period, the line voltage is of the non-nearest switching type that results in current THD
increase from 0.23% (in case of LS PWM) to 0.44%.
Figure 13. Three-phase four H-bridge CHB inverter line voltage for LS PWM and equal sources.
460
Energies 2019, 12, 441
Figure 14. Three-phase four H-bridge CHB inverter current THD for LS PWM and equal sources.
Figure 15. Three-phase four H-bridge CHB line voltage for PS PWM and equal sources.
Figure 16. Three-phase four H-bridge CHB current THD for PS PWM and equal sources.
Next, consider non-equal DC sources. In this paper, for the sake of simplicity, we assume the
same non-equal sources in all three phases. Specifically, for a four H-bridge CHB inverter, normalized
voltages v1 = 0.8; v2 = 0.933; v3 = 1.067; v4 = 1.2 p.u. (1.0 p.u. corresponds to 100 V).
For the four H-bridge CHB inverter with LS PWM and phase DC sources arranged in the optimal
descending order, line voltage and current THD are given in Figures 17 and 18. Again, this excellent
461
Energies 2019, 12, 441
current quality is achieved for ideal matching of LS PWM bands to DC sources that may be difficult to
implement in practice.
The results for PS PWM for the best phase sources switching sequence are given in Figures 19
and 20, and for the worst switching one, in Figures 21 and 22.
For PS PWM, there is another degree of freedom which is carriers’ synchronization in different
phases. The results of Figures 19–22 were obtained assuming the same carriers for all three phases. For
example, for the best sequence, the carrier sequences in three phases are (1423; 1423; 1423). However,
the carriers in different phases can be shifted using circular permutation without violating phase
switching sequence optimality, e.g., (1423; 3142; 2314).
Figure 17. Three-phase four H-bridge CHB line voltage for LS PWM and non-equal sources.
Figure 18. Three-phase four H-bridge CHB current THD for PS PWM and non-equal sources.
If the number of sources in CHB inverter phase is not a multiple of 3, then such carriers’
manipulation will always make voltages and currents non-symmetric, and current THDs in different
phases will be unequal. The authors have an example showing that current THD in each phase may
become less than the one obtained when using the same carrier sequence in three phases.
462
Energies 2019, 12, 441
Figure 19. Three-phase four H-bridge CHB line voltage for PS PWM and best switching of
non-equal sources.
Figure 20. Three-phase four H-bridge CHB current THD for PS PWM and best switching of
non-equal sources.
Figure 21. Three-phase four H-bridge CHB line voltage for PS PWM and worst switching of
non-equal sources.
463
Energies 2019, 12, 441
Figure 22. Three-phase four H-bridge CHB current THD for PS PWM and worst switching of
non-equal sources.
5. Conclusions
This paper investigated several aspects of carrier-based PWM strategies of single- and three-phase
CHB inverters with non-equal DC source voltages in the context of current THD minimization. Though
the results are demonstrated for inductance-dominated RL-load, they are applicable to grid-tied
applications as well.
Here are the main outcomes:
1 Asymptotic current THD formulas for a single-phase multilevel inverter with uniform voltage
level distribution [8] were generalized to acquire non-uniform voltage levels. The generalized
formulas are applicable to a single-phase CHB inverter with non-equal DC source voltages and
LS PWM with PWM bands matching voltage values. While it may be difficult to implement LS
PWM bands matching in real-life applications, obtained current THD values are theoretically
minimal, and can be only compromised by PS PWM.
2 Provided is a simple time domain explanation of superiority of LS PWM over PS PWM from
a voltage and current THD perspective. It is based on recognition of the effect of PS PWM
voltage half a period shift at reference level crossings. While this effect has a minor impact
for single-phase CHB inverters with PS PWM, it causes a significant deterioration of voltage
and current THD for three-phase CHB inverters with PS PWM (non-nearest level switching)
because source phase voltage synchronization becomes different from the optimal one provided
by LS PWM.
3 For a three-phase CHB inverter with PS PWM and more than three unequal DC sources per phase,
simulations demonstrated that the best (worst) current THD is obtained by phase switching
performed according to the best (worst) DC sources switching sequences for a single-phase CHB
inverter, as recently suggested in [11,12]. There is another degree of freedom to be potentially
exploited, that is, different carrier sequences in three converter phases by circular permutation of
optimal ones.
Future research must address the impact of zero-sequence insertion into reference voltages. At a
glance, the classic third harmonic correction may deteriorate current THD in CHB inverter as opposed
to its positive effect on current THD in a three-phase two-level inverter.
Author Contributions: Conceptualization, Z.A. and A.R.; Methodology and Validation, Z.A., A.R., M.H., and
G.G.; Formal Analysis, A.R., and G.G.; Investigation, Z.A. and M.H.; Writing-Original Draft Preparation, Z.A. and
A.R.; Writing-Review & Editing, M.H. and G.G.; Supervision, A.R., and G.G.; Funding Acquisition, G.G.
Funding: This research received no external funding.
Conflicts of Interest: The authors declare no conflict of interest.
464
Energies 2019, 12, 441
Abbreviations
The following abbreviations and symbols are used in this manuscript:
MLI multilevel inverters
EMI electromagnetic interferences
CHB cascade H-bridge
THD total harmonic distortion
LS level shifted
PS phase shifted
PWM pulse width modulation
NMS normalized mean square
ff fundamental frequency
fAS apparent switching frequency
NPC neutral-point-clamped
FC flying capacitor
MMC modular multilevel converter
FFT fast Fourier transform
References
1. Rodríguez, J.; Bernet, S.; Wu, B.; Pontt, J.O.; Kouro, S. Multilevel voltage-source-converter topologies for
industrial medium-voltage drives. IEEE Trans. Ind. Electron. 2007, 54, 2930–2945. [CrossRef]
2. Villanueva, E.; Correa, P.; Rodriguez, J.; Pacas, M. Control of a single-phase cascaded H-bridge multilevel
inverter for grid-connected photovoltaic systems. IEEE Trans. Ind. Electron. 2009, 56, 4399–4406. [CrossRef]
3. Buticchi, G.; Barater, D.; Lorenzani, E.; Concari, C.; Franceschini, G. A nine-level grid-connected converter
topology for single-phase transformerless PV systems. IEEE Trans. Ind. Electron. 2014, 61, 3951–3960.
[CrossRef]
4. Chavarria, J.; Biel, D.; Guinjoan, F.; Meza, C.; Negroni, J.J. Energy balance control of PV cascaded multilevel
grid-connected inverters under level-shifted and phase-shifted PWMs. IEEE Trans. Ind. Electron. 2013, 60,
98–111. [CrossRef]
5. Ricco, M.; Mathe, L.; Monmasson, E.; Teodorescu, R. FPGA-based implementation of MMC control based on
sorting networks. Energies 2018, 11, 2394. [CrossRef]
6. Ricco, M.; Mathe, L.; Teodorescu, R. New MMC capacitor voltage balancing using sorting-less strategy
in nearest level control. In Proceedings of the IEEE Energy Conversion Congress and Exposition (ECCE),
Milwaukee, WI, USA, 18–22 September 2016.
7. Ruderman, A.; Reznikov, B.; Busquets-Monge, S. New MMC capacitor voltage balancing using sorting-less
strategy in nearest level control. IEEE Trans. Ind. Electron. 2013, 60, 1999–2009. [CrossRef]
8. Reznikov, B.; Srndovic, M.; Familiant, Y.; Grandi, G.; Ruderman, A. Simple time averaging current quality
evaluation of a single-phase multilevel PWM inverter. IEEE Trans. Ind. Electron. 2016, 63, 3605–3615.
[CrossRef]
9. Malinowski, M.; Gopakumar, K.; Rodriguez, J.; Perez, M.A. A survey on cascaded multilevel inverters.
IEEE Trans. Ind. Electron. 2010, 57, 2197–2206. [CrossRef]
10. Institute of Electrical and Electronics Engineers (IEEE). IEEE Recommended Practice and Requirements for
Harmonic Control in Electric Power Systems; IEEE: Piscataway, NJ, USA, 2014.
11. Zhuldassov, N.; Ruderman, A. Single-phase PS-PWM cascaded H-bridge inverter current THD optimization
by unequal DC sources switching sequence selection. In Proceedings of the IEEE 9th International
Symposium on Power Electronics and Distributed Generation Systems, Charlotte, NC, USA, 25–28 June 2018.
12. Polichshuk, R.; Zhuldassov, N.; Ruderman, A.; Reznikov, B. On current THD extreme switching sequences
for a single-phase cascade H-bridge inverter with phase-shifted PWM and non-equal DC sources. In
Proceedings of the IEEE 18th International Conference on Power Electronics and Motion Control, Budapest,
Hungary, 26–30 August 2018.
13. McGrath, B.P.; Holmes, D.G. A comparison of multicarrier PWM strategies for cascaded and neutral
point clamped multilevel inverters. In Proceedings of the IEEE 31st Annual Power Electronics Specialists
Conference, Galway, Ireland, 18–23 June 2000.
465
Energies 2019, 12, 441
14. Omer, P.; Kumar, J.; Surjan, B.S. Comparison of multicarrier PWM techniques for cascaded H-bridge inverter.
In Proceedings of the IEEE Students’ Conference on Electrical, Electronics and Computer Science, Bhopal,
India, 1–2 March 2014.
15. Sochor, P.; Akagi, H. Theoretical and experimental comparison between phase-shifted PWM and level-shifted
PWM in a modular multilevel SDBC inverter for utility-scale photovoltaic applications. IEEE Trans. Ind. Appl.
2017, 53, 4695–4707. [CrossRef]
© 2019 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access
article distributed under the terms and conditions of the Creative Commons Attribution
(CC BY) license (http://creativecommons.org/licenses/by/4.0/).
466
energies
Article
Power Flow Analysis of the Advanced Co-Phase
Traction Power Supply System
Xiaoqiong He 1,2 , Haijun Ren 1 , Jingying Lin 1, *, Pengcheng Han 1 , Yi Wang 1 , Xu Peng 3 and
Zeliang Shu 1
1 School of Electrical Engineering, Southwest Jiaotong University, Chengdu 611756, China;
[email protected] (X.H.); [email protected] (H.R.); [email protected] (P.H.);
[email protected] (Y.W.); [email protected] (Z.S.)
2 National Rail Transit Electrification and Automation Engineering Technique Research Center,
Southwest Jiaotong University, Chengdu 611756, China
3 Aviation Engineering Institute, Civil Aviation Flight University of China, Guanghan 611756, China;
[email protected]
* Correspondence: [email protected]; Tel.: +86-028-6636-6731
Abstract: The development of the traction power supply system (TPSS) is limited by the existence
of the neutral section in the present system. The advanced co-phase traction power supply system
(ACTPSS) can reduce the neutral section completely and becomes an important research and
development direction of the railway. To ensure the stable operation of ACTPSS, it is necessary
to carry out an appropriate power analysis. In this paper, the topology of advanced co-phase
traction substation is mainly composed by the three-phase to single-phase cascaded converter. Then,
the improved PQ decomposition algorithm is proposed to analyze the power flow. The impedance
model of the traction network is calculated and established. The power flow analysis and calculation
of the ACTPSS with different locations of locomotive are carried out, which theoretically illustrates
that the system can maintain stable operation under various working conditions. The feasibility and
operation stability of the ACTPSS are verified by the simulations and low power experiments.
1. Introduction
By the end of 2018, the operation mileage of the China railway had already reached 124 thousands
kilometers. Among them is the high speed railway mileage, which reached 22 thousands kilometers.
There is no doubt that the China railway is of great importance to China’s transportation industry.
To the railway system, the traction power supply system (TPSS) is a crucial part that maintains stable
and safe operation of railways [1–3]. The existing TPSS is shown in the left of Figure 1. The power
supply distance of each traction substation is limited by the neutral sections, and the power supplied
by each traction substation is incapable of interconnection [4–7]. As a result, when the train is
running in regenerative braking mode, the power cannot be used by other locomotives because of
the neutral sections. Then, the power is transmitted to a three-phase grid through the transformer,
which causes the problem of large harmonic content and unbalanced voltage in three-phase power
network. Because of the regenerative braking energy consumption, a large number of economic losses
are caused [4]. Furthermore, the voltage range of the traction network is changed sharply, and the
negative sequence, reactive power, and harmonic problems are brought into the present TPSS when
the locomotives are under operation [8,9]. These problems influence the quality of the three-phase
power grid, the operation efficiency, and the stability of the TPSS. Moreover, the locomotives need to
decelerate and slide through the neutral section. In this way, the loss of speed and the decrease of the
operation safety are problems that restrict the development of railways [10,11].
3RZHUJULG 3RZHUJULG
ib
vc
ic vb
vb
$3&
va i
ic v c
a
<1G <QYG ica
WUDFWLRQWUDQVIRUPHU ib WUDFWLRQWUDQVIRUPHU
([LVWLQJWUDFWLRQSRZHUVXSSO\VXEVWDWLRQ &RSKDVHWUDFWLRQSRZHUVXSSO\VXEVWDWLRQ
i
([LVWLQJWUDFWLRQSRZHUVXSSO\V\VWHP &RSKDVHWUDFWLRQSRZHUVXSSO\V\VWHP
Figure 1. Traction power supply system. (left) The existing power supply substation, (right) the
co-phase power supply substation based on active power compensators (APC).
To solve these problems, a great deal of research has been done in China. The co-phase traction
power supply system (CTPSS) is proposed in [10], which is shown in the right of Figure 1. The active
power compensators (APC) is applied in the CTPSS [4]. Half of the neutral sections can be reduced,
and the power quality of the three-phase power grid can be improved to a certain extent [6]. The CTPSS
has been put into operation in Meishan, Sichuan province. Voltage source converter based high voltage
direct current transmission traction power supply system (VSC-Based HVDC TPSS) is proposed in [5].
Compared to TPSS, the power quality problems such as unbalance, reactive power, and harmonic
distortion are greatly improved. However, the stray current is generated by the HVDC TPSS, which is
harmful to the rail system, and the current supply voltage of the traction network (27.5 kV/50 Hz) is
not changed by CTPSS. If there is a line using DC system, the trains will not be able to run on both
systems at the same time.
In order to link all the traction networks of every different substation, the advanced traction
power substation system is proposed in literature [12]. The substation based on three-phase to
single-phase converter is adopted in this system [13–16]. In order to adapt to the voltage level of
three-phase grid voltage and the traction network voltage, the step-down transformer and step-up
transformer are added to the three-phase grid and the traction network side, respectively. The neutral
sections and problems of power quality in the traditional system can be avoided. However, it is
difficult to meet the existing substation requirement of capacity because the structure is limited by
the power electronic devices. The advanced co-phase traction power supply system (ACTPSS) based
on three-phase to single-phase cascaded converter is proposed in literature [7], as shown in Figure 2.
The ACTPSS achieves the interconnection of the whole traction network, thus all the neutral sections
are reduced by ACTPSS. The negative sequence, reactive power, and harmonic problems existent in
the traditional TPSS can be solved effectively [12,13]. Meanwhile, the voltage of the traction network
can be maintained in a relatively stable range, and regenerative braking energy can be better utilized.
Thus, the ACTPSS has become essential in the research and development of future TPSS.
Due to the interconnection of the whole traction network, the energy of the locomotive is mainly
supplied by the closest power supply arm, and the adjacent substations provide the remaining parts
of the energy. Therefore, the system capacity of the traction power supply system can be reduced.
To assess and manage the operation state of ACTPSS, the power flow analysis also needs to be
468
Energies 2019, 12, 754
researched. Criteria of voltage stability based on the existence of the power flow solvability was used
in the power distribution network [17]. Another voltage stability criterion was obtained based on the
volt-ampere characteristic of the branches in the system [18]. This power analysis research of the public
three-phase power grid provides a good theoretical basis for the power flow analysis of the traction
network. In the power supply model of auto transformer (AT) traction substation, the power flow and
voltage distribution in different working conditions of high-speed railway are analyzed by establishing
a general multi-conductor chain circuit model [19,20]. The influence of traction load on power quality
of the three-phase power grid was illustrated. These laid a good foundation for building the model of
the traction network [21,22]. In ACTPSS, no node voltage of the traction network is allowed to exceed
the prescribed voltage standard [23]. In this way, each traction substation supplies the power equitably
and stably. Furthermore, the voltage range of the traction network maintains steadily. Therefore, it is
necessary to carry out the power flow analysis of ACTPSS and assess the voltage variation degree of
the traction network so that the dispatchers can take correspondent measures.
In this paper, firstly, the structure of ACTPSS based on a three-phase to single-phase cascaded
converter is illustrated, and the corresponding control strategy and modulation strategy are given.
Secondly, on the basis of ACTPSS, the mathematical model of traction network impedance is established
by multi-conductor model, and the power flow analysis of the traction network is carried out by the
improved PQ decomposition algorithm. Thirdly, the stability performance of ACTPSS is verified
through the analysis of the power flow under different locomotive operation conditions. Finally,
the correctness of the theory analysis is verified through the simulation, and the operation reliability of
ACTPSS is verified through the low power experiment.
VXEVWDWLRQEDVHGRQWKHFDVFDGHG
VXEVWDWLRQEDVHGRQWKHFDVFDGHG
VXEVWDWLRQEDVHGRQWKHFDVFDGHG
0XOWLZLQGLQJVWHSGRZQWUDQVIRUPHU
7KHDGYDQFHGFRSKDVHWUDFWLRQ
7KHDGYDQFHGFRSKDVHWUDFWLRQ
7KHDGYDQFHGFRSKDVHWUDFWLRQ
7KUHHSKDVH/
13&UHFW LIL HU
7KUH HSKDVHWRVLQJOHSKDVH
7KUH HSKDVHWRVLQJOH
7KUH HSKDVHWRVLQJOH
7KUH HSKDVHWRVLQJOH
FRQYHUWHU
FRQYHUWHUn
FRQYHUWHUn
SKDVHFRQYHUWHU
SKDVHFRQYHUWHU
SKDVHFRQYHUWHUn
FDVFDGHGFRQYHUWHU
Ă
Ă
ILOWHU /13&LQYHUWHU
/& 6LQJOHSKDVH
7UDFWLRQQHWZRUN
Figure 2. The structure of the advanced co-phase traction power supply system (ACTPSS).
469
Energies 2019, 12, 754
The three-phase to single-phase converter is comprised of the three-phase 3L-NPC rectifier and the
single-phase 3L-NPC inverter. The three-phase 3L-NPC rectifier converts the power from three-phase
alternating current (AC) to direct current (DC), then the single-phase 3L-NPC inverter converts the
power from DC to single-phase AC. The output of the three-phase to single-phase cascaded converter
as the output of the traction substation is connected with the traction network. The amplitude,
the frequency, and the phase of the traction substation output voltage are controlled to be in accordance
with the traction network. The traction substations are paralleled with the traction network and
achieve the power interconnection of the whole system.
2.2. The Control Strategy and Modulation Strategy of Three-Phase 3L-NPC Rectifier
In order to ensure that the three-phase 3L-NPC rectifiers operate under unit power factor, P-Q
transformation, voltage, and current double closed loop control strategy is adopted [24]. The control
strategy and modulation strategy of the three-phase 3L-NPC rectifier are illustrated by Figure 3. Firstly,
the phase of input voltage vabc is extracted through phase lock loop (PLL). The locked phase is used as
the reference phase of input current iabc to achieve coordinate transformation from the three-phase
static coordinate (abc) to the two-phase rotating coordinate (dq). Under the two-phase rotating
coordinate, the active component and reactive component of the current are controlled, respectively.
The reference of the active component of the current is relative with the output voltage vdc , while the
reference of the reactive component of the current is 0. The Space Vector Pulse Width Modulation
(SVPWM) strategy is adopted as the modulation strategy for the rectifier.
VLQij aFRVij a
vD VLQij bFRVij b i dref v dc
vE VLQij cFRVij c 3,
3//
vF v dcref
ȦL
v sd
v id S S
iD id 6
DEF 3, GT
iE 9 S S
3
iF iq v iq : S S
GT 3, DEF 0
VLQij aFRVij a ȦL VLQij aFRVij a
VLQij bFRVij b i qref VLQij bFRVij b
VLQij cFRVij c VLQij cFRVij c
Figure 3. The control strategy and modulation strategy of the three-phase three-level neutral point
clamped (3L-NPC) rectifier.
2.3. The Control Strategy and Modulation Strategy of Single-Phase 3L-NPC Cascaded Inverter
The control strategy and modulation strategy of the single-phase 3L-NPC cascaded inverter are
shown in Figure 4. The double closed loop control strategy is applied in this paper. The outer loop
control strategy is designed to steady the output voltage. The inner loop control strategy is designed
to adjust the dynamic response of the system. The value of output voltage and inductance current are
detected to involve the control strategy.
The carrier phase shift strategy is used as the modulation strategy [25]. Every inverter model has
the same modulation wave produced by the controller, while the triangle angle waves are different.
The phase angle difference of two adjacent triangle angle waves is π/n, where the n represents the
number of the inverter models. The single-phase SVPWM strategy is used as the modulation strategy
to drive each inverter model.
470
Ă
Ă
Ă
Energies 2019, 12, 754
'RXEOHFORVHGORRSFRQWURO
u ref
K ip 3,
vm
7ULDQJOH 693:0 uab iL
FDUULHU
0RGXOH
vm
uab uR
7ULDQJOH 693:0 uab
FDUULHU C
0RGXOH Zr
Ă
Ă
Ă
vm
7ULDQJOH 693:0 uabn
FDUULHUn
0RGXOHn
&DUULHUSKDVHVKLIW
PRGXODWLRQVWUDWHJ\ &DVFDGHGLQYHUWHU /&/RZSDVVILOWHU $&WUDFWLRQORDG
Figure 4. The control strategy and modulation strategy of single-phase 3L-NPC cascaded inverter.
7UDFWLRQVXEVWDWLRQ
z ȍNP I 7UDFWLRQQHWZRUN
y 6NP
*1'
.
Figure 5. The original circuit model of the traction network.
According to Figure 5, it is known that the unit length impedance of traction network z can be
calculated by Equation (1):
· ·
U − U
z= · (1)
Il
·
In Equation (1), the voltage between the output port of the traction substation and ground is U,
·
the voltage of the locomotive load is U , the length of the traction network is l, and the current of the
·
traction network is I.
471
Energies 2019, 12, 754
It is known from Equation (1) that the z is nonlinear and cannot be calculated by formula flexibly.
It is assumed that the current of steel rail can flow into the ground instantly, or the current of the
ground can flow into the steel rail instantly, and the current can flow into the output port of the
traction substation with the same amplitude as well. Then, the admittance γ between the steel rail
and the ground can be considered to approach infinity, and the conduction current of steel rail can be
considered to tend to 0. Taking these assumptions as the simplification condition, Equation (2) can be
expressed as:
1 ·
lim (1 − k z ) I e−γ(l − x) + e−γx ≈ 0 (2)
γ→∞ 2
In Equation (2), k z = z12 /z2 . The mutual impedance is z12 , the self-impedances are z1 and z2 ,
and the distance between the locomotive and the traction substation is x.
· ·
Then, the current of the steel rail IT and the ground IG can be recognized as:
⎧
⎨ I· x = I· = k I·
T( ) T z
(3)
⎩ I· ( x ) = I· = (1 − k ) I·
G G z
The simplified impedance model of the traction network is illustrated by Figure 6 [26]. The model
is composed of two current loops. In the first loop, the current flows through the traction network and
the ground. In the second loop, the current flows through the steel rail and the ground. The second
current loop just reflects the induced current, which is far bigger than the conduction current.
According to the light of this simplified impedance model, the unit length impedance of the traction
network z can be figured out by the calculation of the self-impedance of the first and second loop.
7UDFWLRQVXEVWDWLRQ
z ȍNP I 7UDFWLRQQHWZRUN
/RFRPRWLYH
U z ȍNP U'
ORDG
z ȍNP 6WHHOUDLO
IT k z I
*1'
IG k z I
l .
According to the Carson theory [27], the ground can be recognized as virtual wire. Then, Equation (4)
can be expressed as: ⎧
⎪
⎪
D
z = r1 + 0.05 + j0.1446g R g Ω/km
⎪
⎨ 1 ε1
Dg
⎪ z 2 = r 2 + 0.05 + j0.1446g Rε2 Ω/km (4)
⎪
⎪
⎩ z = 0.05 + j0.1446g Dg Ω/km
12 d 12
In Equation (4), the r1 and Rg1 represent the effective resistance and equivalent radius of the first
loop, respectively; r2 and Rg2 represent the effective resistance and equivalent radius of the second
loop, respectively; the Dg represents the depth of the equivalent earth-return circuit; d12 is the center
distance between the conductor in the first and second loop.
Therefore, the z can be calculated as follow:
z12 2
z = z1 − (5)
z2
472
Energies 2019, 12, 754
According to Equation (5), the impedance of the traction network zl with the length l can be
expressed as follows:
zl = z × l (6)
ΔQ = LU −1 ΔU (8)
From Equations (7) and (8), it is known that the correction equation of the active power ΔP and
the reactive power ΔQ can be iterated, respectively. Compared with the 2n-order linear equations of
the Newton-Raphson algorithm, the PQ decomposition algorithm transforms it into two n-order linear
equations. The calculation time can be reduced sharply. However, in the iteration, the coefficient matrix
H and L, which belong to the asymmetric matrix, are changing constantly. Thus, it is necessary to
change coefficient matrices into the symmetric matrices so that the calculation can be further simplified.
Because of the relatively little voltage phase difference between two ports of the circuit, it can be
supposed as follows: ⎧
⎪
⎨ cos δij ≈ 1
Gij sin δij Bij (9)
⎪
⎩ Q U2 B
i i ii
473
Energies 2019, 12, 754
ΔP = UBUΔθ (12)
In Equations (12) and (13), the U is the diagonal matrix of the effective value of node voltage,
and the B represents the susceptance matrix.
By multiplying Equations (12) and (13) with U−1 , Equations (14) and (15) can be obtained
as follows:
U −1 ΔP = B UΔθ (14)
U −1 ΔQ = B ΔU (15)
In Equation (18), the X is the line reactance of the original model, the R is the line resistance
of the original model, and the unit of them is Ω. If we suppose that the real part of the Y is 0,
the transmission line reactance of the traction network can be sufficiently larger than the resistance,
and the condition Gij sin δij << Bij can be satisfied. To make sure that the power flow calculation will
not be wrong and the system can keep balance after the change of the impedance, the lacking power
part will be added by the other power sources in node i and node j. The way to add the power sources
474
Energies 2019, 12, 754
can be determined by Figure 7c. Combined with the node voltage and the modified Y , the power of
node i and node j can be illustrated as:
⎧
⎪
⎪ Pi = Ui G Uj cos θij − Ui + B Uj sin θij
⎨ Q = U G U sin θ + B U cos θ − U
⎪
i i j ij j ij i
(19)
⎪
⎪ Pj = Uj G Ui cos θij − Uj + B Ui sin θij
⎪
⎩
Q j = −Uj G Ui sin θij + B Ui cos θij − Uj
Figure 7. The models of the traction network. (a) The impedance model of the traction network; (b) the
parallel equivalent impedance model of the traction network; (c) the simplified equivalent impedance
model of the traction network.
In Equation (19), the G” is the conductance of the modified model, the B” is the susceptance
of the modified model, and the unit of them is S. When the condition Gij sinδij << Bij has been
satisfied, the subsequent calculation of the improved PQ decomposition algorithm is same as the
PQ decomposition algorithm. In the power flow calculation of the improved PQ decomposition
algorithm to the traction network, the locomotives are considered as the power sources, and the traction
substations are recognized as the equivalent node models of voltage source. The equivalent mathematic
model of ACTPSS, which can apply the improved PQ decomposition algorithm, is exhibited in Figure 8.
= = =1
66 66 1 66 1
475
Energies 2019, 12, 754
= = = = = =
Power flow calculation results of ACTPSS are listed in Table 2. In this paper, the voltage values of
node 4 and node 10 in the model are the lowest, which are 21.3758 kV. Obviously, 21.3758 kV is still
higher than 19 kV. At this condition, the locomotive can continue to run, which indicates that ACTPSS
proposed in this paper can ensure the locomotive operates normally.
Node Voltage Amplitude U (kV) Voltage Phase α (rad) Complex Power S (MVA)
1 27.500 0.000 25.484 + j10.218
2 27.500 0.000 21.159 + j6.625
3 27.500 0.000 25.484 + j10.218
4 21.3758 −0.35922 −9.6 + j(−1.37)
5 25.9499 −0.11363 −9.6 + j(−1.37)
6 24.3719 −0.20953 −9.6 + j(−1.37)
7 26.4185 −0.09387 −9.6 + j(−1.37)
8 24.3719 −0.20953 −9.6 + j(−1.37)
9 25.9499 −0.11363 −9.6 + j(−1.37)
10 21.3758 −0.35922 −9.6 + j(−1.37)
The line impedance exists in the traction network model. By using the node voltage and node
admittance matrix, it can be calculated that the total power of the system is 72.135 + j27.062 MVA,
the total consumption power of the system load is 67.2 + j9.595 MVA, and the total power loss of
the system is 4.935 + j17.472 MVA. The power loss of every line between two nodes is illustrated in
Table 3. The power losses are expressed in the form of complex power with the inductive reactive
power. Because the distance between the locomotive and the node is different, the power loss of the
line between the nodes is different.
476
Energies 2019, 12, 754
/RFRPRWLYH /RFRPRWLYH
ORDG ORDG
Two locomotives are located at point 1 and 2 in Figure 10. The locomotive is considered as
a single-particle model in the analysis. The output current of traction substations SS1 and SS2 are
iSS1 and iSS2 , respectively. The line impedances between the traction substations SS1 and SS2 to the
locomotive are ZSS1 and ZSS2 , respectively. The line impedance between point 1 and point 2 is Z12 .
The currents of locomotives 1 and 2 are i1 and i2 , respectively.
According to the Kirchhoff’s Voltage Law (KVL) and Kirchhoff’s Current Law (KCL):
· · · · ·
V SS1 − V SS2 = ZSS1 I SS1 + Z12 I 12 − ZSS2 I SS2 (20)
· · ·
I SS1 − I 12 = I1 (21)
· · ·
I 12 − I SS2 = I 2 (22)
Assuming that the output voltage of the SS1 and SS2 are VSS1 and VSS2 , and the currents I1 , I2 of
the locomotive are known, then Equations (21) and (22) can be simplified as:
· · · ·
· ( Z12 + ZSS2 ) I1 + ZSS2 I 2 V SS1 − V SS2
I SS1 = + (23)
ZSS1 + Z12 + ZSS2 ZSS1 + Z12 + ZSS2
· · · ·
· ZSS1 I1 + ( ZSS1 + Z12 ) I 2 V SS1 − V SS2
I SS2 = − (24)
ZSS1 + Z12 + ZSS2 ZSS1 + Z12 + ZSS2
In the actual condition, there must exist the voltage drop along the traction network. Therefore,
the power flow calculation of the traction network also needs a similar method. Generally, the power
loss of the traction network is ignored, and the power is also calculated by the voltage V. If we suppose
that V = VN ∠0◦ and S = VN I, then Equations (25) and (26) can be acquired after multiplying the
conjugate value of Equations (23) and (24) with the VN .
· · · · ·
Z12 + Z SS2 S1 + Z SS2 S2 V SS1 − V SS2 VN
SSS1 = · · · + · · · (25)
Z SS1 + Z12 + Z SS2 Z SS1 + Z12 + Z SS2
· · · · ·
Z SS1 S1 + Z SS1 + Z12 S2 V SS1 − V SS2 VN
SSS2 = · · · − · · · (26)
Z SS1 + Z12 + Z SS2 Z SS1 + Z12 + Z SS2
Based on Equations (25) and (26), it can be obtained that the output power of the traction substation
contains two parts. One part is decided by the parameter of the locomotive itself; the other is unrelated
to the parameter of itself, which is called the cyclic power.
477
Energies 2019, 12, 754
The simulation that sets three traction substations in the system is also achieved. In this simulation,
the locomotive runs from the start (0 km) to the end (150 km). When the locomotive is at seven different
locations, the output power of the traction substations are illustrated as shown in Table 4.
Fitting the data of Table 4, the relationship between the distance and the output power ratio of
each traction substation is expressed as Figure 11. It can be known by Figure 11 that the output power
is varied with the change of the distance between the locomotive and the substation. Compared with
the present traction substation, 10 percentages of the output power can be reduced by the traction
substation of ACTPSS (approximately), which could have significant economic influence on the China
railway system.
VXEVWDWLRQV
'LVWDQFH NP
Figure 11. The relationship between the location of the locomotive and the output power ratio of the
traction substation.
5.1. The Simulation Analysis of Three-Model Three-Phase to Single-Phase Cascaded Converter Based
on ACTPSS
The simulation of the three-model three-phase to single-phase cascaded converter based on
ACTPSS was built, and the feasibility of the control strategy and modulation strategy was verified.
The simulation parameters are exhibited in Table 5.
Parameters Value
The number of the cascaded model 3
The DC voltage of the single model 15 kV
The reference voltage of the traction network 27.5 kV
Power of the traction network 9.6 MW
The value of the capacitor in DC side 1 mF
The value of the fliter inductance 10 mH
The value of the fliter capacitor 10 μF
The carrier wave frequence of the inverter 1 kHz
478
Energies 2019, 12, 754
The output voltage waves of the three-phase 3L-NPC rectifiers are shown in Figure 12, and it can
be known that the voltages could achieve stability after about 0.17 s. As the output waves appeared,
the second-order ripple was suppressed by the LC filter. By the rectifiers, the steady and reliable DC
voltages could be obtained.
î
U GF 9 U GF 9 U GF 9
6WDUWXSVWDJH
7LPHtV
The output voltage and current waves of the three-model 3L-NPC cascaded inverter after filter are
illustrated by Figure 13a. The uR and iR are the output voltage and current after the filter, respectively.
In order to display the voltage and the current wave of output load properly and in the same scope,
the current waveform was expanded by 50 times, the output voltage and current waveform were
closed to the standard sine waves, and the output voltage that had little harmonic component and
high power factor could be provided by the cascaded inverter. The 5-level output voltage waves of the
three-inverter and the output voltage of the cascaded inverter are shown in Figure 13b. The uab is the
13-level output voltage of the three-model cascaded inverter, of which the effective value is 27.5 kV.
The feasibility and availability of the cascaded inverter’s control strategy and modulation strategy
have been verified by Figure 13.
2XWSXWYROWDJHDIWHUILOWHUu R 9 2XWSXWFXUUHQWDIWHUILOWHUi R $
[
7LPHtV
(a)
Figure 13. Cont.
479
Energies 2019, 12, 754
2XWSXWYROWDJHRIWKHFDVFDGHGLQYHUWHUu DE 9
9ROWDJHRIPRGHO 9 9ROWDJHRIPRGHO 9 9ROWDJHRIPRGHO 9
[
[
[
[
7LPHtV
(b)
Figure 13. The output voltage and current waves of 3L-NPC cascaded inverter. (a) The output voltage
and current wave of the three-model 3L-NPC cascaded inverter after filter; (b) the output voltage
waves of the three single-phase 3L-NPC inverter and the output voltage of 3L-NPC cascaded inverter.
Parameters Value
The number of the traction substation 3
The reference voltage of the traction network 27.5 kV
The value of the fliter inductance in network side 10 mH
The value of the fliter capacitor in network side 10 μF
The carrier wave frequence of the inverter 1 kHz
The locomotive 1 (R1 ) was set to run in 0.5–1.5 s, 2.5–3.5 s, and 4.5–7 s in the simulation, the
locomotive 2 (R2 ) was set to run in 1.5–2.5 s and 3.5–6.0 s, while the locomotive 3 (R3 ) was set to run in
2.5–5.0 s. The output current waves of the three traction substations and the current waves of the three
locomotives are shown in Figure 14.
The traction substation 1 (SS1) was connected with the traction network at 0.5 s, the start of the
system operation. The traction substation 2 (SS2) was connected with the traction network at 1.0 s,
and the traction substation 3 (SS3) at 2.0 s. In 0.5–1.0 s, only the R1 was under operation, and the
power was provided to the R1 only by the SS1, thus the current of the R1 was the same as the current
of the SS1 at this period. In 1.0–1.5 s, the power was supplied to the R1 by both the SS1 and the SS2.
In 1.5–2.0 s, only the R2 was under operation, and the power was supplied to the R2 by both the SS1
and the SS2. Because the distance between the R2 and the SS2 was shorter, the power supplied by the
SS2 was more than that supplied by the SS1. In 2.0–2.5 s, the power was supplied to the R2 by the SS1,
the SS2, and the SS3. Because the location of R2 was between the SS2 and the SS3, the power provided
by the SS1 was the least. In 2.5–3.0 s, the R1 and the R3 were under operation, and the power of them
was supplied by the three traction substations together. At this period, the R3 was on the right side of
the SS3, and the power provided by the SS3 was more than that supplied by the SS1 and the SS2.
480
Energies 2019, 12, 754
î
î
i 5 $ i 5 $
î
R ,QSXW R ,QSXW R R ,QSXW
7LPHt V
Figure 14. The current waves of the traction substations and locomotives in 0–3.5 s.
The output voltage waves of the traction substations and the voltage waves of locomotives in
0–3.5 s are exhibited in Figure 15. From the simulation results, it is clear that the output voltages of
the traction substations and the voltages of locomotives were adjusted properly when the traction
loads were input or excision. The voltages were maintained within the international prescribed scope,
from 19 kV to 29 kV, ensuring that the locomotives could be under the normal operation.
î
V 66 9 V 66 9 V 66 9
î
î
SS,QSXW SSǃSS,QSXW SSǃSSǃSS,QSXW
î
V 5 9
î
V 5 9
î
V 5 9
R ,QSXW R ,QSXW R R ,QSXW
7LPHt V
Figure 15. The voltage waves of the traction substations and the locomotives in 0–3.5 s.
The output current waves of the traction substations and the current waves of locomotives in
3.5–7.0 s are exhibited in Figure 16. In 3.5–4.5 s, the R2 and the R3 were under operation, and the power
of them was supplied by the three traction substation together. Because the distance between the R2 ,
the R3 , and the SS1 was longer, the power supplied by the SS1 was the least. In 4.5–5.0 s, the R1 , the
R2 , and the R3 were under operation, and the power of them was also provided by the three traction
substations together. Because the R3 was farther from the SS1 and the SS2 than from the SS3, the power
supplied from the SS3 to the R3 was the most. In 5.0–6.0 s, when the SS3 was excision because of
fault, the R1 and the R2 were still under operation and obtained the power from the SS1 and the SS2.
481
Energies 2019, 12, 754
In 6.0–7.0 s, the R1 was under operation and located between the SS1 and the SS2. The power was
supplied to the R1 by the SS1 and the SS2 equally.
î
i 66 $
î
i 66 $
î
i 66 $
SSSSSS,QSXW SSSS,QSXW
î
i 5 $
î
i 5 $
î
i 5 $
R R R
R R ,QSXW R R ,QSXW R ,QSXW
,QSXW
7LPHt V
Figure 16. The current waves of the traction substations and locomotives in 3.5–7 s.
The output voltage waves of the traction substations and the voltage waves of locomotives in
3.5–7.0 s are exhibited in Figure 17. From the simulation results, it is clear that the output voltages
of the traction substations and the voltages of locomotives were adjusted properly when the traction
loads were input or excision, and the voltages were maintained within the international prescribed
scope, from 19 kV to 29 kV, ensuring that the locomotives could be under the normal operation.
î
V 66 9 V 66 9 V 66 9
î
î
SSSSSS,QSXW SSSS,QSXW
î
V 5 9
î
V 5 9
î
V 5 9
R R R
R R ,QSXW R R ,QSXW R ,QSXW
,QSXW
7LPHt V
Figure 17. The voltage waves of the traction substations and locomotives in 3.5–7 s.
482
Energies 2019, 12, 754
The output active and reactive power of the traction substations are illustrated by Figure 18.
The converters inside the locomotives were controlled to operate with the unity power factor, thus the
locomotives could be considered the pure resistance load. Therefore, under the steady operation of the
locomotive, the reactive power was almost zero. When the locomotive started up or broke, the reactive
power was outputted to achieve the power balance of the traction network.
SRZHU
î
662XWSXW
SRZHU
î
662XWSXW
SRZHU
7LPHt V
Figure 18. The output active and reactive power of three traction substations.
(a) (b)
Figure 19. The output voltage waves of the three-model 3L-NPC cascaded converter. (a) The
relationship of the output voltage waves; (b) the output voltage waves in about one period (CH1:
the output voltage of cascaded converter; CH2: the voltage of the inverter 1; CH3: the voltage of the
inverter 2; CH4: the voltage of the inverter 3).
The output current waves of the three parallel traction substations and the load voltage wave are
exhibited in Figure 20. The same amplitude and phase of three current waves were obtained after about
50 ms to adjust. The current could be outputted by three traction substations equally. The feasibility of
the theoretical analysis and simulation could be verified by the results of the low power experiment.
483
Energies 2019, 12, 754
$GMXVWLQJVWDWH 6WDEOHVWDWH
(a) (b)
Figure 20. The output current waves of the three parallel traction substations and the load voltage
wave. (a) The waves under the adjusting state and stable state; (b) the relationship between the current
waves and the load voltage wave under the stable state (CH1: the output current of the SS1; CH2:
the output current of the SS2; CH3: the output current of the SS3; CH4: the voltage of load.).
6. Conclusions
In this paper, ACTPSS based on the three-phase to single-phase cascaded converter was studied
to solve the problems of power qualities and to cancel all the neutral sections in traditional TPSS. Based
on the research of ACTPSS, an improved PQ decomposition algorithm was proposed to calculate
the power flow of ACTPSS. As a result, the impedance model of the traction network was built and
analyzed. Then, the power flow situations under different operation conditions were analyzed. Finally,
simulation and experimental results were given to validate the proposed improved PQ decomposition
algorithm strategy. According to the aforementioned analysis and implementation, the following
advantages could be obtained:
(1) The induced current in the rail-earth loop was far greater than that in the conduction circuit.
As a result, when the distance between the locomotive and the substation was greater than 5 km, the
resulting impedance calculation error was less than 5%. Therefore, the simplified equivalent model of
the traction network was valid in the traction network impedance model of ACTPSS.
(2) The results showed that the minimum voltage of the traction network was higher than 19 kV,
which met the running requirements of locomotive load. The analyses indicated that the capacity of
the individual substation could be reduced by nearly 10%. The theoretical fundament of ACTPSS was
laid in this paper.
(3) The power losses of the ACTPSS between the nodes were calculated. According to the
calculation of the output power, the calculation results illustrated that the output power was affected
by the distance between the locomotive and the traction substation. The closer the distance between
the locomotive and the substation, the more power would output by the substation.
(4) On the basis of theoretical analysis, the correctness and validity of the proposed improved PQ
decomposition algorithm strategy were proven by the simulation and the experimental, which laid a
foundation for the application of ACTPSS.
Author Contributions: X.H. and H.R. analyzed the strategy and conceived the experiment; J.L. collected and
analyzed the data; P.H. performed the experiment; Y.W. and X.P. wrote the paper; and Z.S. contributed the
experiment prototype.
Acknowledgments: This work was supported by the National Natural Science Foundation of China (Grant
Nos. 51477144) and the National Rail Transit Electrification and Automation Engineering Technique Research
Center Open Project (Grant No. NEEC-2017-A01).
Conflicts of Interest: The authors declare no conflict of interest.
484
Energies 2019, 12, 754
References
1. Feng, C.; Zhu, Q.; Yu, B.; Zhang, Y. Complexity and vulnerability of high-speed rail network in China.
In Proceeddings of the 2017 36th Chinese Control Conference (CCC), Dalian, China, 26–28 July 2017;
pp. 10034–10039.
2. Zhang, J.; Wu, M.; Liu, Q. A Novel Power Flow Algorithm for Traction Power Supply Systems Based on the
Thévenin Equivalent. Energies 2018, 11, 126. [CrossRef]
3. Zhao, N.; Roberts, C.; Hillmansen, S.; Nicholson, G. A Multiple Train Trajectory Optimization to Minimize
Energy Consumption and Delay. IEEE Trans. Intell. Transp. Syst. 2015, 16, 2363–2372. [CrossRef]
4. Wang, H.; Li, Y.; Liu, H.; Wu, L.; Sun, Y. Transmission characteristics of harmonics and negative sequence
components of electrified railway in power system. In Proceeddings of the 2016 International Conference on
Smart Grid and Clean Energy Technologies (ICSGCE), Chengdu, China, 19–22 October 2016; pp. 301–306.
5. Shu, Z.; Xie, S.; Lu, K.; Zhao, Y.; Nan, X.; Qiu, D.; Zhou, F.; Gao, S.; Li, Q. Digital detection, control,
and distribution system for co-phase traction power supply application. IEEE Trans. Ind. Electron. 2013,
60, 1831–1839. [CrossRef]
6. Yang, X.; Hu, H.; Ge, Y.; Aatif, S.; He, Z.; Gao, S. An Improved Droop Control Strategy for VSC-Based MVDC
Traction Power Supply System. IEEE Trans. Ind. Appl. 2018, 54, 5173–5186. [CrossRef]
7. He, X.; Guo, A.; Peng, X.; Zhou, Y.; Shi, Z.; Shu, Z. A Traction Three-Phase to Single-Phase Cascade Converter
Substation in an Advanced Traction Power Supply System. Energies 2015, 8, 9915–9929. [CrossRef]
8. Xie, B.; Zhang, Z.; Li, Y.; Hu, S.; Luo, L.; Rehtanz, C.; Krause, O. Reactive Power Compensation and
Negative-Sequence Current Suppression System for Electrical Railways with YNvd-Connected Balance
Transformer—Part II: Implementation and Verification. IEEE Trans. Power Electron. 2017, 32, 9031–9042.
[CrossRef]
9. Zhang, D.; Zhang, Z.; Wang, W.; Yang, Y. Negative Sequence Current Optimizing Control Based on Railway
Static Power Conditioner in V/v Traction Power Supply System. IEEE Trans. Power Electron. 2016, 31, 200–212.
[CrossRef]
10. Li, Q.; Zhang, J.; He, W. Study of a new power supply system for heavy haul electric traction. J. China
Railw. Soc. 1988, 10, 23–31.
11. Zhang, R.; Lin, F.; Yang, Z.; Cao, H.; Liu, Y. A Harmonic Resonance Suppression Strategy for a High-Speed
Railway Traction Power Supply System with a SHE-PWM Four-Quadrant Converter Based on Active-Set
Secondary Optimization. Energies 2017, 10, 1567. [CrossRef]
12. He, X.; Shu, Z.; Peng, X.; Zhou, Q.; Zhou, Y.; Zhou, Q.; Gao, S. Advanced Cophase Traction Power Supply
System Based on Three-Phase to Single-Phase Converter. IEEE Trans. Power Electron. 2014, 29, 5323–5333.
[CrossRef]
13. Han, P.; He, X.; Wang, Yi.; Ren, H.; Peng, X.; Shu, Z. Harmonic Analysis of Single-Phase
Neutral-Point-Clamped Cascaded Inverter in Advanced co-phase traction Power Supply System Based on
the Big Triangular Carrier Equivalence Method. Energies 2017, 11, 1–16.
14. Townsend, C.D.; Baraciarte, R.A.; Yu, Y.; Tormo, D.; Parra, H.Z.; Demetriades, G.D.; Agelidis, V.G. Heuristic
Model Predictive Modulation for High-Power Cascaded Multilevel Converters. IEEE Trans. Ind. Electron.
2016, 63, 5263–5275.
15. Haridas, K.; Khandelwal, S.; Das, A. Three phase to single phase modular multilevel converter using full
bridge cells. In Proceeddings of the 2016 IEEE International Conference on Power Electronics, Drives and
Energy Systems (PEDES), Trivandrum, India, 14–17 December 2016; pp. 1–5.
16. Lin, H.; Shu, Z.; He, X.; Liu, M. N-D SVPWM With DC Voltage Balancing and Vector Smooth Transition
Algorithm for a Cascaded Multilevel Converter. IEEE Trans. Ind. Electron. 2018, 65, 3837–3847. [CrossRef]
17. Plattner, G.; Semlali, H.F.; Kong, N. Analysis of probabilistic load flow using point estimation method to
evaluate the quantiles of electrical networks state variables. CIRED Open Access Proc. J. 2017, 2017, 2087–2091.
[CrossRef]
18. Liu, H.; Tang, C.; Han, J.; Li, T.; Li, J.; Zhang, K. Probabilistic load flow analysis of active distribution
network adopting improved sequence operation methodology. IET Gener. Trans. Distrib. 2017, 11, 2147–2153.
[CrossRef]
485
Energies 2019, 12, 754
19. He, Z.; Hu, H.; Zhang, Y.; Gao, S. Harmonic Resonance Assessment to Traction Power-Supply System
Considering Train Model in China High-Speed Railway. IEEE Trans. Power Deliv. 2014, 29, 1735–1743.
[CrossRef]
20. Hu, H.; Gao, S.; Shao, Y.; Wang, K.; He, Z.; Chen, L. Harmonic Resonance Evaluation for Hub Traction
Substation Consisting of Multiple High-Speed Railways. IEEE Trans. Power Deliv. 2017, 32, 910–920.
[CrossRef]
21. Xu, S.; Miao, S. Calculation of TTC for multi-area power systems based on improved Ward-PV equivalents.
IET Gen. Trans. Distrib. 2017, 11, 987–994. [CrossRef]
22. Hu, S.; Xie, B.; Li, Y.; Gao, X.; Zhang, Z.; Luo, L.; Krause, O.; Cao, Y. A Power Factor-Oriented Railway
Power Flow Controller for Power Quality Improvement in Electrical Railway Power System. IEEE Trans.
Ind. Electron. 2017, 64, 1167–1177. [CrossRef]
23. Madhusoodhanan, S.; Tripathi, A.; Patel, D.; Mainali, K.; Kadavelugu, A.; Hazra, S. Solid-State Transformer
and MV Grid Tie Applications Enabled by 15 kV SiC IGBTs and 10 kV SiC MOSFETs Based Multilevel
Converters. IEEE Trans. Ind. Appl. 2015, 51, 3343–3360. [CrossRef]
24. Wang, C.; Xiao, L.; Zheng, X.; Lv, L.; Xu, Z.; Jiang, X. Analysis, Measurement, and Compensation of the
System Time Delay in a Three-Phase Voltage Source Rectifier. IEEE Trans. Power Electron. 2016, 31, 6031–6043.
[CrossRef]
25. Jie, S.; Stefan, S.; Qu, B.; Zhang, Y.; Chen, K.; Zhang, R. Modulation Schemes for a 30-MVA IGCT Converter
Using NPC H-Bridges. IEEE Trans. Ind. Appl. 2015, 51, 4028–4040.
26. Li, Q.; He, J. Analysis of Traction Power Supply System; Southwest Jiaotong University Press: Chendu,
China, 2012.
27. Olsen, R.G.; Pankaskie, T.A. On the Exact, Carson and Image Theories for Wires at or Above the Earth’s
Interface. IEEE Trans. Power Appar. Sys. 1983, PAS-102, 769–778. [CrossRef]
28. Rao, L.; He, R.; Wang, Y.; Yan, W.; Bai, J.; Ye, D. An efficient improvement of modified Newton-Raphson
algorithm for electrical impedance tomography. IEEE Trans. Magn. 1999, 35, 1562–1565.
© 2019 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access
article distributed under the terms and conditions of the Creative Commons Attribution
(CC BY) license (http://creativecommons.org/licenses/by/4.0/).
486
energies
Article
Small-Scale Modular Multilevel Converter for
Multi-Terminal DC Networks Applications:
System Control Validation
Elie Talon Louokdom 1 , Serge Gavin 2 , Daniel Siemaszko 3 , Frédéric Biya-Motto 1 ,
Bernard Essimbi Zobo 1 , Mario Marchesoni 4 and Mauro Carpita 2, *
1 Laboratory of Electronics, Department of Physics, Faculty of Science, University of Yaoundé I,
P.O. Box 812 Yaoundé, Cameroon; [email protected] (E.T.L.); [email protected] (F.B.-M.);
[email protected] (B.E.Z.)
2 Département des Technologies Industrielles (TIN), Haute école Spécialisée de Suisse Occidentale (HES-SO),
University of Applied Sciences of Western Switzerland, Route de Cheseaux 1, 1401 Yverdon-les-Bains,
Switzerland; [email protected]
3 Power Electronics and Systems Consultancy, Rue de Lyon 27, CH-1201 Geneva, Switzerland;
[email protected]
4 Department of Electrical, Electronic, Telecommunications Engineering and Naval Architecture,
University of Genova, Via all’Opera Pia 11A, 16145 Genova, Italy; [email protected]
* Correspondence: [email protected]; Tel.: +41-(0)24-5576306
Abstract: This paper presents the design and implementation of a digital control system for modular
multilevel converters (MMC) and its use in a 5 kW small-scale prototype. To achieve higher system
control reliability and multi-functionality, the proposed architecture has been built with an effective
split of the control tasks between a master controller and six slave controllers, one for each of the six
arms of the converter. The MMC prototype has been used for testing both converter and system-level
controls in a reduced-scale laboratory set up of a Multi-Terminal DC transmission network (MTDC).
The whole control has been tested to validate the proposed control strategies. The tests performed at
system level allowed exploration of the advantages of using an MMC in a MTDC system.
Keywords: digital controller; digital signal processors (DSP); modular multilevel converters (MMC);
multi-terminal DC network (MTDC)
1. Introduction
Due to the energy challenges the world is facing today, the interest in the integration into the
utility grids of renewable energy sources has significantly increased in recent years. In this context,
high voltage direct current (HVDC) systems are considered one of the best options to achieve high
reliability in future long-distance offshore grids that are needed to interconnect offshore wind farms,
loads and large-scale storage facilities [1].
Among the different power converter topologies proposed in the literature on HVDC applications,
Modular Multilevel Converters (MMC) [2] have emerged in recent years due to their attractive
properties such as low harmonic distortion, scalability and flexibility. The use of MMC for HVDC
systems has been largely studied by the scientific community and some commercials products have
been developed by constructors such as ABB, Siemens and Alstom [3,4].
HVDC systems using MMC installed in the last decade are mostly point-to-point systems [5–7].
However, the needs to strengthen the existing AC transmission grids and to balance the intermittent
power of offshore wind farms over a wider area by interconnecting multiple neighboring HVDC
systems have increased the interest on Multi-terminal HVDC systems (MTDC) [8,9]. The use of MMC
in MTDC systems instead of conventional two-level voltage source converters (VSC) has the already
cited advantages of being redundant and scalable, to reduce or eliminate bulky harmonics filters on the
AC side and to avoid DC link capacitors banks. Despite these advantages, many technical challenges
must be tackled to allow their large-scale use. Among these challenges, the lack of a standardized grid
code for interconnecting adjacent HVDC systems [10], the DC faults protection management [11,12],
the experimental validation of system control strategies to ensure power flow and DC voltage control
can be cited.
Concerning this last issue, MMC-based MTDC system control can be split among a high-level
(or system-level) control and a low-level (or converter-level) control [13–18]. To test and verify these
control levels under realistic conditions, as well as their interactions, it is useful to make use of
small-scale laboratory prototypes, able to handle the various operational modes. Some small-scale
prototypes have been proposed in the scientific literature since the introduction of MMC. For instance,
a prototype of MMC is built in [19], with 44 submodules (SM) per arm, each SM capacitor with
a nominal voltage at 10 V. In [20], a 20 kW back-to-back MMC-based system with 3 SM per arm is
presented, while [21] presents a 25 kW six-level MMC prototype. In [22], a hybrid small-scale prototype
is proposed for Alternate Arm Converter (AAC) and MMC.
Considering all these previous studies, it is obvious that, given the large number of submodules
used to form the whole structure of an MMC [6], the complex command and control schemes require
efficient architectures. This can only be implemented by digital control techniques, making use of
advanced FPGA (Field Programmable Gate Array) or DSP (Digital Signal Processors) for fast calculation
and accurate timing of the switching signals of the multiple power semiconductors. An FPGA-based
control of an MMC has been proposed in [23], making use of a lookup table for the generation of
the output references. This approach is not well suited for closed loop control of both the external
and internal dynamic behavior of the MMC. it is obvious that a single microcontroller will have
difficulties in effectively performing the complex control schemes and the communication with external
peripherals. Most of previous works propose a combination of DSP and FPGA boards to handle the
control and communication. In [24], the combination of both processors (DSP and FPGA) is used as
a central supervision unit. The DSP performs the analog to digital conversion and all the high-level
control tasks, while the FPGA manages the modulation, the capacitor voltage balancing and the
communication with the submodules tasks. This allows the obtaining of the advantage of a central
modulator, which generates all naturally synchronized PWM signals for all switches. However,
the capacitor voltage balancing in an MMC usually uses a sorting algorithm which is in itself a
sequential process, not leading to an efficient use of parallel logical resources.
Distributed controller architecture can meet these challenges. A distributed architecture fits very
well with the scalability of the converter’s structure and the computational load is shared between
several microprocessors. Nevertheless, a distributed architecture of the controller requires an effective
synchronization of all arm controllers to ensure that the gate signals of all submodules are synchronous.
A robust and fast communication link between the master controller and arm controllers must also
be assured.
In this paper, a small-scale MMC prototype with a controller architecture designed with only
DSPs is presented. The master controller uses a dual core processor which combines a C2000
Texas Instruments (TI) MCU for real time control tasks and an Arm Cortex-M3 processor for the
communication purposes. This master controller interacts with six slave controllers, one for each
arm, implemented with another C2000 Texas Instruments MCU. This MMC prototype is used in a
reduced-scale laboratory setup of a MTDC [25] to implement both system-level and converter-level
controls, and to study MMC interactions with other VSC in an existing MTDC system.
Novelty of the paper concerns the experimental verification of the usefulness of the proposed
MMC control structure to ensure power flow and DC voltage control in MTDC systems. Testing on a
reduced-scale mock-up is, in the opinion of the authors, a step further in comparison to the various HIL
(Hardware In a Loop) real-time simulation systems options available on the market. Moreover, it will
488
Energies 2018, 11, 1690
give to the reader a deep description of several implementation details, concerning both hardware and
software choices made.
The paper is organized as follows: Section 2 presents the topology of MMC and a brief review of its
control and MTDC control strategies. Section 3 describes the controller structure, the task partitioning
as well as the communication protocols. The actual implementation and the experimental validation
of the proposed architecture are presented in Section 4. A discussion on how this architecture may
be practically extended to be used in MMC systems utilizing more submodules is done in Section 5.
Finally, conclusion is given in Section 6.
2.1. Structure
Figure 1 presents the typical structure of an MMC converter [1]. It consists of six arms, working
as voltage sources. Each arm is made of N power submodules. A submodule consists of a storage
capacitor and a half or full bridge converter. The bridge is used to insert or bypass the capacitor. The
three-phase AC voltages and the total arm voltage are respectively composed of 2N + 1 and N + 1
levels per signal cycle, corresponding to different insertions or removal of capacitors. This minimizes
voltage harmonic distortions and consequently allows reduction/elimination of the filter on the AC
side. Furthermore, a large and bulky capacitor on the DC side is no longer necessary. The modularity
of the converter allows the use of power semiconductors with reduced voltage to achieve high AC and
DC voltages.
489
Energies 2018, 11, 1690
,'4B5() 8'4B*5,'
,*5,' 95()B287
$%& '4
3,
,$50
'4
$%&
) ,$50
,32/
9&,5&
9$50B5()
95()B83
,&,5&
3,
95()B/2:
,&,5&B5() 9&$3
9727B$50
93+$6(B727
90($1 3
) 9727
90($1
3, 95() 3:0
93+$6(B',))
3
(a) (b)
Figure 2. (a) MMC control strategy diagram. IARM are the six arm currents of the MMC, IGRID are
the three line currents of the utility grid computed using the block F(IARM ) from the arm’s currents.
ICIRC are the three-circulating currents in each phase of the MMC computed by the block F(IARM ).
ICIRC_REF is the circulating current reference in each phase. IDQ_REF are the AC line current references
in the dq frame. UDQ_GRID are the three AC grid voltages in the dq frame. VREF_OUT are the three AC
grid voltage references given by PI controllers. VTOT_ARM are the six total arms’ voltages. VPHASE_TOT
is the total voltage of each phase of the MMC. VPHASE_DIF is the voltage difference between the upper
and lower arms of the same phase. VDIF_REF is the voltage difference reference between the upper and
lower arms of the same phase. UDC_LOW and UDC_UP are the half of DC grid voltage. VMEAN is the
mean voltage of each phase. VARM_REF are the six arms’ voltage references given by the controller. P is
a proportional controller; (b) Submodules capacitors voltage balancing strategy: VMEAN is the mean
voltage of each arm. VCAP is the capacitor voltage of each submodule. VREF is the voltage reference
of each submodule capacitor. IPOL gives the sign of the arm current. PWM is the block generating
gates signals.
490
Energies 2018, 11, 1690
These include voltage margin control, voltage droop control, dead-band voltage droop control and
non-dead band voltage control [33].
The voltage margin control method is an extension of the point-to-point HVDC transmission
systems control. One of the terminals (also called master terminal or “slack-bus”) controls the DC
voltage and the other terminals (slaves terminals) can arbitrarily (or based on available resources)
inject or draw power. Controlling the MTDC network voltage at a single terminal has the drawbacks
that the master converter is the only one to participate in the regulation of the DC voltage. It is,
therefore, necessary that the AC network associated with the master converter can absorb or provide
all the power variations necessary for the balance of the MTDC system, in particular in case of a
fault. Moreover, the single terminal used as balanced terminal must be sized to cope with all power
variations situations. This result is a weakness of the entire system since if the master converter is lost,
the MTDC system will be no longer regulated and collapses [8].
In the voltage droop control method, the DC voltage variation is used as a common signal by
all converters that adjust their power based on this DC voltage. Thus, the task of controlling the DC
voltage is shared among all the converters. To stabilize the MTDC system, a dead zone can be added
to the droop control setting, also called dead-band voltage droop control. This allows discrimination
between normal and disturbed operation of the MTDC system. However, the control activity of the
converters within the band (normal operation) is fully lost. This has the disadvantage that some of
the droop control parameters are set to zero and infinity, which does not give any degree of freedom
for optimization [34]. In the non-dead band voltage droop control, the dead zone is replaced by a
real power-voltage characteristic slightly inclined. Therefore, different droop constants can be used,
depending on the deviation between DC voltage set-point and measure. Several control characteristics
of a non-dead band voltage control scheme are shown in Figure 3: a reference voltage and power are
set for each converter, and the balancing of the system occurs by increasing the DC voltage in case of
excess of power, while decreasing it otherwise. The slopes of the different sections of the characteristic
are chosen according to the connected loads or sources (e.g., wind generators cannot usually provide
large amounts of additional power). This method is effective to ensure stable operation of the DC
network, also in case of a failure of one or even several converters.
P
Pmax
Pref1
Pref2
Pref3
Pref4
Pmin
491
Energies 2018, 11, 1690
distributed architecture presented in [35], a dedicated synchronization signal has been used here for
an effective synchronization of all arm controllers. More details about the synchronization method are
given in Section 3.3.4.
Remote VPN
control Modem router
PC
WAN
UTP cable
,&
Master board
EXV - Measurement of AC voltages
- Measurement of DC voltage
- Measurement of arm currents
- Control of output currents
- Control of stored energy in the arms
2SWLFDO - Communication with user
ILEHUV
Total arm capacitors
voltages
References Slaves PWM
voltages carriers
Synchronisation
signal
Slave 1 board Slave 2 board Slave 6 board
- Computing total arm - Computing total arm - Computing total arm
voltage voltage voltage
- Modulator PS-PWM - Modulator PS-PWM - Modulator PS-PWM
- Capacitor voltages - Capacitor voltages - Capacitor voltages
balancing balancing balancing
Submodule Gates
Capacitor signal
voltage
submodule 1
submodule 1
submodule 1
submodule 5
submodule 5
submodule 5
MMC
MMC
MMC
MMC
MMC
MMC
All control and communication tasks are distributed between the “master” controller and the
arms “slave” controllers. The master controller manages the real and reactive power flow, and the
communications tasks with the external world. The master controller communicates to the six
slave controllers the voltage references, the arm current signs, the synchronization signal of the arm
controllers and other commands such as start driving submodules. Each slave controller periodically
sends back to the master the total arm voltage and performs the balancing of its arm capacitor voltages
using the arm current sign received from master.
492
Energies 2018, 11, 1690
and AC output connectors (middle points of H-bridge arms). Two PWM input signals are available to
control the two IGBT legs. A 3.2 mF capacitor is connected between the DC bus for local power storage.
In this paper, two IGBTs only (half-bridge operation) are mounted in the power module, requiring
just one PWM input. The nominal ratings of the module are 10 A and 200 V, with some 1 kV isolation
voltage. The low power supply for the sub-module is provided by a medium-frequency current-fed
system, consisting of an isolated power supply and a cable passing through thirty small torus from the
secondary of each torus, one for each sub-module [36]. An inverter fed a nominal current of 5 A in the
cable at 45 kHz. Figure 5 presents the sub-module schematic and its hardware implementation. Table 1
give some specifications of the main power submodules devices.
Current fed
cable
Power submodule
AC
DC
DC +
Drivers
commands
IGBT
IGBT
Faults
AC
IGBT
VCO DC -
Capacitor
voltage
AC
CPLD
Optical fibers
493
Energies 2018, 11, 1690
Start
Start
Turn off No
Connect the MMC to the AC
grid using pre-charge command
resistances received ?
Yes
Regulate the output current at
Each 0A and disconnect AC grid
Leave all
capacitor voltage 1R
switches
reached
open
8 JULG 1 "
No
Is AC grid disconnected?
Yes
Bypass the preload resistances Yes
and active output current
Disable current control and
control
disconnect DC grid
Each
capacitor No No
Is DC grid disconnected?
voltage reached
Vdc/N?
Yes
Yes
Connect DC and place the Is all capacitors No
system into normal operation are discharged ?
Yes
End of pre-charge
End
(a) (b)
Figure 6. Flowchart of the pre-charge and turn off strategy. (a) Pre-charge; (b) Turn off.
494
Energies 2018, 11, 1690
references and arm current sign, which are key information for the control, are updated and sent
to slaves every sampling cycle. After three switching periods, the master has received the six arm
voltages. This reception delay, caused by the low speed of I2C, is not so critical for the control since
the capacitor voltage balancing is performed by the arm controllers. This delay has been taken into
account in the controller design.
ADC conversion
ADC conversion
ADC conversion
Tx 1
Tx 2
Tx 3
Tx 4
Tx 5
Tx 6
Tx 1
Tx 2
Tx 3
Tx 4
Tx 5
Tx 6
Tx 1
Tx 2
Tx 3
Tx 4
Tx 5
Tx 6
Rx 1
Rx 2
Rx 6
1st cycle 2nd cycle 6th cycle time
Six cycles of data transfers
(a)
Start Slave adress Write Arm current sign + Reference Ack Repeat
cmd Ack commands + ref. voltage Ack voltage start
1 bit 7 bits 1 bit 1 bit 8 bits 1 bit 8 bits 1 bit 1 bit
Figure 7. Master to slaves communication protocols. (a) Master controller data transfer with slaves per
ADC cycle of conversion. Tx i = transmit to slave i; Rx i = receipt from slave i; (b) data protocol used
when sending messages to each slave; (c) data protocol used to receive message from each slave.
495
Energies 2018, 11, 1690
4. Experimental Validation
The proposed architecture has been implemented on a 5 kW reduced-scale MMC demonstrator.
Figure 8 shows the whole MMC demonstrator. The main system parameters are shown in Table 2.
Tests have been carried out with MMC working as inverter on a three-phase passive load with a DC
link of 800 V and in a reduced-scale laboratory setup of a MTDC transmission network [25,37].
The experimental validation of the control architecture and the overall functionality of the MMC
includes several aspects. The communication between the master board and an UI, the data flow
between the master and slave boards together with the synchronization of the generated PWM signals,
and the operation of the modules driven by the slave boards have been tested.
The current and voltage waveforms as seen from the AC side, the MMC output current and
energy stored control and the power flow control in a MTDC network have been tested too.
496
Energies 2018, 11, 1690
3: 0 $UP 3: 0 $UP
ȝV
6'$VLJQDORIWKH,&
6\QFKURQL]DWLRQ VLJQDO
Figure 9. Signals on the converter: PWM 1 signals of two arms controllers (duty cycle 25%), Serial data
(SDA) line of the I2C (blue trace) and arms’ synchronization signal (green trace).
497
Energies 2018, 11, 1690
Figure 10. Evolution over time of a submodule capacitor voltage during pre-charge.
(a)
(b)
Figure 11. Capacitor balancing test on the MMC, (a) With the balancing algorithm disabled; (b) With
the balancing algorithm enabled.
498
Energies 2018, 11, 1690
$
PV LR $ LR % LR &
9
PV 9$
Figure 12. Output current control: output currents and output voltage of the phase A.
(a)
(b)
499
Energies 2018, 11, 1690
(c)
Figure 13. Energy control tests results, (a) DC voltage, upper and lower arms total voltages without an
energy control; (b) DC voltage, upper and lower arms total voltages with an energy control and step
change in the DC voltage; (c) DC voltage, upper and lower arms total voltages with an energy control
and step change of total arm voltages.
Hence the DC voltage is not decoupled from capacitor voltages. If a short time brake occurs in the
DC bus, this will directly affect the capacitor voltages. In Figure 13b,c, the energy control is enabled.
In Figure 13b, the total arm voltages are controlled at 800 V and the DC voltage steps successively from
800 V to 850 V, from 850 V to 750 V and from 750 V to 800 V. After a short transient phase, the total arm
voltages remain at their reference value. In Figure 13c, the DC voltage is held at 800 V and the total
arm voltages are set to step successively from 800 V to 850 V, from 850 V to 750 V and from 750 V to
800 V. The energy control allows a decoupling between capacitor voltages and the DC bus voltage.
The dynamics of the total arm voltage control loop has been intentionally reduced to avoid overvoltage
on the capacitors.
500
Energies 2018, 11, 1690
MMC
GAMMA DELTA
(a)
(b)
Figure 14. MTDC mockup, (a) MTDC mockup on laboratory; (b) Single line diagram of the
laboratory setup.
(a)
(b)
Figure 15. MTDC results with a variation of power transmitted in the onshore AC grid, (a) Power
variations in the experimental set-up with controlled MMC and two inverters implemented with non-dead
band voltage control; (b) DC voltage variation and two arms of the MMC voltages during power flow.
501
Energies 2018, 11, 1690
(a)
(b)
Figure 16. MTDC results when the stored energy in the MMC varies, (a) DC voltage variation and two
arms of the MMC voltages; (b) Power variations in the experimental set-up with controlled MMC and
two inverters implemented with non-dead band voltage control.
A third test was run to test the MTDC system with all VSC implementing the non-dead band
droop control. Figure 17 presents the DC link voltage and power variation over the three converters
when slight power variations are provoked. It can be seen on Figure 17 that the DC bus is well
controlled, and the transients are well absorbed by the three converters when the entire system is
facing power variations. This third scenario also highlights the contribution of each converter to the
stability of the DC bus.
Those results confirm the correct behavior of the MMC in a MTDC system and against
power variation.
Figure 17. MTDC results when all VSC implement Non-dead band droop control.
502
Energies 2018, 11, 1690
implemented in a small-scale prototype to test the control strategies developed. One critical point of
this control structure is its scalability in case of a higher number of modules. Due to its decentralized
architecture, in principle it is suitable for a higher number of SM in each arm, because all the operations
assigned to the master controller and the communication between the master and the slave controllers
do not depend on the number of SM to control. The local management of each arm is performed by an
independent controller sending the reference set-points to all PWM modulators. However, the DSP
used has twelve independent PWM outputs, so a maximum number of 12 modules can be controlled,
without acting on the slave hardware.
For more modules, the slave controller could be combined, or even replaced by a low-cost FPGA
that would produce as many PWM outputs as required. In case of combination of the slave DSP and
an FPGA, the capacitor balancing and sorting algorithms which are sequential operations remain the
task of the DSP. These aspects are under development and will not be discussed further in this paper.
The proposed hardware structure will be used for a lower demanding application in terms of
voltage rating, i.e., a medium-voltage application such as a MV-Statcom or MV-SOP (Soft Open Point).
In this case, the number of modules to be managed is about 20–24, which is feasible with the proposed
multi-DSP approach.
Another critical point is the robustness of the I2C bus. It appeared a few times during tests in
a highly EM perturbed environment that the I2C bus was perturbed when the bus was not shielded
enough. However, all the EMC problems in the prototype have been solved with suitable shielding and
accurate state-machine and communication tuning to avoid critical situations, such as the switching of
the main contactors.
6. Conclusions
This paper presents the design and the implementation of a small-scale modular multilevel
converter. The proposed MMC prototype has been used to test both converter and system-level
controls in a reduced-scale MMC-based MTDC network. Several MMC control levels have been tested
and the results obtained validated the control strategies implemented and the controller architecture
designed. The tests performed at system level have enabled exploration of the advantages of using
an MMC-based MTDC system, which include the capability of the MMC to store and restore the
energy in the system, its scalability which allows the extension of the DC link voltage as desired,
and improvement to the AC side voltage harmonics contents.
Author Contributions: Conceptualization, E.T.L., S.G., D.S. and M.C.; Formal analysis, all authors; Funding
acquisition, M.C.; Software, E.T.L., S.G. and D.S.; Supervision, M.C.; Validation, all authors; Writing—original
draft, E.T.L.; Writing—review & editing, E.T.L. and M.C.
Funding: The authors acknowledge EOS-Holding (CH) for the funding of the research presented in this paper.
This research is part of the activities of the Swiss Centre for Competence in Energy Research on the Future
Swiss Electrical Infrastructure (SCCER-FURIES), which is financially supported by the Swiss Innovation Agency
(Innosuisse-SCCER program).
Acknowledgments: The authors would like to thank P. Favre-Perrod, D. Leu, H. Parisod (HES-SO), J. Braun
(CERN) for their contributions and useful suggestions.
Conflicts of Interest: The authors declare no conflict of interest.
References
1. Siemaszko, D.; Carpita, M.; Favre-Perrod, P. Conception of a modular multilevel converter in a
multi-terminal DC/AC transmission network. In Proceedings of the Power Electronics and Applications
(EPE’15 ECCE-Europe), Geneva, Switzerland, 8–10 September 2015. [CrossRef]
2. Lesnicar, A.; Marquardt, R. An innovative modular multilevel converter topology suitable for a wide
power range. In Proceedings of the IEEE Bologna Power Tech Conference, Bologna, Italy, 23–26 June 2003.
[CrossRef]
503
Energies 2018, 11, 1690
3. Sharifabadi, K.; Harnefors, L.; Nee, H.P.; Norrga, S.; Teodorescu, R. Design, Control, and Application of Modular
Multilevel Converters for HVDC Transmission Systems; Wiley-IEEE Press: Hoboken, NJ, USA, 2016.
4. Perez, M.A.; Bernet, S.; Rodriguez, J.; Kouro, S.; Lizana, R. Circuit topologies, modelling, control schemes
and applications of modular multilevel converters. IEEE Trans. Power Electron. 2015, 30, 4–17. [CrossRef]
5. Dorn, J.; Gambach, H.; Strauss, J.; Westerweller, T.; Alligan, J. Transbay cable-A breakthrough of VSC
multilevel converters in HVDC transmission. In Proceedings of the CIGRE San Francisco Colloquium,
San Francisco, CA, USA, 7–9 March 2012.
6. Francos, P.L.; Verdugo, S.; Alvarez, H.F.; Guyomarch, S.; Loncle, J. INELFE—Europe’s first integrated onshore
HVDC interconnection. In Proceedings of the IEEE Power and Energy Society General Meeting, San Diego,
CA, USA, 22–26 July 2012.
7. Hussennether, V.; Rittiger, J.; Barth, A.; Worthington, D.; Rapetti, D.G.M.; Huhnerbein, B.; Siebert, M. Project
borwin2 and helwin1-large scale multilevel voltage sources converter technology for bundling of offshore
windpower. In Proceedings of the CIGRE, Paris, France, 26–31 August 2012.
8. Zhang, L.; Zou, Y.; Yu, J.; Qin, J.; Vittal, V.; Karady, G.; Shi, D.; Wang, Z. Modeling, control, and protection of
modular multilevel converter-based multi-terminal HVDC systems: A review. CSEE J. Power Energy Syst.
2017, 3, 340–352. [CrossRef]
9. Ronanki, D.; Williamson, S. Modular Multilevel Converters for transportation electrification: Challenges
and opportunities. IEEE Trans. Transport. Electrification 2018, 4, 399–407. [CrossRef]
10. Van Hertem, D.; Ghandhari, M. Multi-terminal VSC HVDC for the European supergrid: Obstacles.
Renew. Sustain. Energy Rev. 2010, 14, 3156–3163. [CrossRef]
11. Bucher, M.K.; Franck, C.M. Fault current interruption in multiterminal HVDC networks. IEEE Trans.
Power Deliv. 2015, 31, 87–95. [CrossRef]
12. Li, R.; Xu, L.; Yao, L.; Williams, B.W. Active control of DC fault currents in DC solid-state transformers during
ride-through operation of multi-terminal HVDC systems. IEEE Trans. Energy Convers. 2016, 31, 1336–1346.
[CrossRef]
13. Egea-Alvarez, A.; Bianchi, F.; Junyent-Ferre, A.; Gross, G.; Gomis-Bellmunt, O. Voltage control of
multiterminal VSC-HVDC transmission systems for offshore wind power plants: Design and implementation
in a scaled platform. IEEE Trans. Ind. Electron. 2013, 60, 2381–2391. [CrossRef]
14. Aragüés-Peñalba, M.; Egea-Àlvarez, A.; Galceran Arellano, S.; Gomis-Bellmunt, O. Droop control for loss
minimization in HVDC multi-terminal transmission systems for large offshore wind farms. Electr. Power
Syst. Res. 2014, 112, 48–55. [CrossRef]
15. Debnath, S.; Qin, J.; Bahrani, B.; Saeedifard, M.; Barbosa, P. Operation, control, and applications of the
modular multilevel converter: A review. IEEE Trans. Power Electron. 2015, 30, 37–53. [CrossRef]
16. Belhaouane, M.; Freytes, J.; Ayari, M.; Colas, F.; Gruson, F.; Braiek, N.; Guillaud, X. Optimal control design
for Modular Multilevel Converters operating on multi-terminal DC Grid. In Proceedings of the 2016 Power
Systems Computation Conference (PSCC), Genova, Italy, 20–24 June 2016; pp. 1–7. [CrossRef]
17. Ji, H.; Chen, A.; Liu, Q.; Zhang, C. A new circulating current suppressing control strategy for modular
multilevel converters. In Proceedings of the 36th Chinese Control Conference (CCC), Dalian, China,
26–28 July 2017; pp. 9151–9156. [CrossRef]
18. Zama, A.; Benchaib, A.; Bacha, S.; Frey, D.; Silvant, S. High dynamics control for MMC based on exact
discrete-time model with experimental validation. IEEE Trans. Power Deliv. 2018, 33, 477–488. [CrossRef]
19. Zhou, Y.; Jiang, D.; Hu, P.; Guo, J.; Liang, Y.; Lin, Z. A prototype of modular multilevel converters. IEEE Trans.
Power Electron. 2014, 29, 3267–3278. [CrossRef]
20. Binbin, L.; Dandan, X.; Dianguo, X.; Rongfeng, Y. Prototype design and experimental verification of modular
multilevel converter based back-to-back system. In Proceedings of the International Symposium on Industrial
Electronics, Istanbul, Turkey, 1–4 June 2014; pp. 626–630.
21. Moranchel, M.; Sanchez, F.M.; Bueno, E.J.; Rodriguez, F.J.; Sanz, I. Six-level modular multilevel converter
prototype with centralized hardware platform controller. In Proceedings of the IECON 2015, Yokohama,
Japan, 9–12 November 2015; pp. 863–868.
22. Jasim, O.F.; Moreno, F.J.; Trainer, D.R.; Feldman, R.; Farr, E.M.; Claree, J.C. Hybrid experimental setup for
alternate arm converter and modular multilevel converter. In Proceedings of the 13th IET international
conference on AC and DC Power Transmission, Manchester, UK, 14–16 February 2017; pp. 1–6.
504
Energies 2018, 11, 1690
23. Islam, M.R.; Guo, Y.; Zhu, J. FPGA-based control of modular multilevel converters: Modeling and
experimental evaluation. In Proceedings of the International Conference on Electrical & Electronic
Engineering (ICEEE), Rajshahi, Bangladesh, 4–6 November 2015; pp. 89–92.
24. Lago, J.; Sousa, G.J.M.; Heldwein, M.L. Digital control/modulation platform for a modular multilevel
converter system. In Proceedings of the COBEP, Gramado, Brazil, 27–31 October 2013; pp. 271–277.
25. Luginbühl, M.; Pidancier, T.; Favre-Perrod, P. Transmission d’énergie par réseaux à courant continu
multiterminaux. Bull. AES/Electrosuisse 2014, 12, 70–74.
26. Hagiwara, M.; Akagi, H. Control and experiment of pulse width modulated modular multilevel converters.
IEEE Trans. Power Electron. 2009, 24, 1737–1746. [CrossRef]
27. Siemaszko, D. Fast sorting method for balancing capacitor voltages in modular multilevel converters.
IEEE Trans. Power Electron. 2015, 30, 463–470. [CrossRef]
28. Ängquist, L.; Antonopoulos, A.; Siemaszko, D.; Ilves, K.; Vasiladiotis, M.; Nee, H.P. Open-loop control of
modular multilevel converters using estimation of stored energy. IEEE Trans. Ind. Appl. 2011, 47, 2516–2524.
[CrossRef]
29. Edpuganti, A.; Rathore, A.K. Optimal pulsewidth modulation of medium-voltage modular multilevel
converter. IEEE Trans. Ind. Appl. 2016, 52, 3435–3442. [CrossRef]
30. Franquelo, L.G.; Rodriguez, J.; Leon, J.I.; Kouro, S.; Portillo, R.; Prats, M.M. The age of multilevel converters
arrives. IEEE Trans. Ind. Electron. Mag. 2008, 2, 28–39. [CrossRef]
31. Delarue, P.; Gruson, F.; Guillaud, X. Energetic macroscopic representation and inversion based control of a
modular multilevel converter. In Proceedings of the 15th European Conference on Power Electronics and
Applications (EPE’13 ECCE Europe), Lille, France, 3–5 September 2013; pp. 1–10.
32. Siemaszko, D.; Talon Louokdom, E.; Parisod, H.; Braun, J.; Gavin, S.; Eggenschwiler, L.; Favre-Perrod, P.;
Carpita, M. Implementation and experimental set-up of a Modular Multilevel Converter in a Multi Terminal
DC/AC transmission network. In Proceedings of the 18th European Conference on Power Electronics and
Applications (EPE’16 ECCE Europe), Karlsruhe, Germany, 5–9 September 2016; pp. 1–12.
33. Luginbühl, M.; Lalou, M.J. Contrôle coordonné des convertisseurs de réseaux MTDC. Bull. AES/Electrosuisse
2013, 12, 36–39.
34. Vrana, T.K.; Zeni, L.; Fosso, O.B. Active power control with undead-band voltage & frequency droop
for HVDC converters in large meshed DC grids. In Proceedings of the EWEA Conference, Copenhagen,
Denmark, 16–19 April 2012.
35. Talon, E.L.; Gavin, S.; Siemaszko, D.; Biya-Motto, F.; Essimbi, B.Z.; Carpita, M. Design and implementation
of a multi-dsp based digital control system architecture for modular multilevel converters. In Proceedings of
the IEEE-PEMC, Varna, Bulgaria, 25–30 September 2016; pp. 1182–1187.
36. Wen, H.; Xiao, W.; Lu, Z. Current-fed high-frequency AC distributed power system for medium–high-voltage
gate driving applications. IEEE Trans. Ind. Electron. 2013, 60, 3736–3751. [CrossRef]
37. Talon Louokdom, E.; Siemaszko, D.; Gavin, S.; Leu, D.; Favre-Perrod, P.; Carpita, M. Use of Modular
Multilevel Converter in multi-terminal DC transmission network: Reduced scale set-up and experimental
results. In Proceedings of the 19th European Conference on Power Electronics and Applications
(EPE’17 ECCE Europe), Warsaw, Poland, 11–14 September 2017; pp. P.1–P.9.
© 2018 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access
article distributed under the terms and conditions of the Creative Commons Attribution
(CC BY) license (http://creativecommons.org/licenses/by/4.0/).
505
energies
Article
Theoretical and Experimental Investigation of the
Voltage Ripple across Flying Capacitors in the
Interleaved Buck Converter with Extended
Duty Cycle
Peter Zajec * and Mitja Nemec
Faculty of Electrical Engineering, Department of Mechatronics, University of Ljubljana, Trzaska 25,
1000 Ljubljana, Slovenia; [email protected]
* Correspondence: [email protected]; Tel.: +386-1-4768-479
Abstract: The interleaved buck converter with an extended duty cycle is analyzed in terms of
unexplored parasitic switching states that diminish the switch utilization and its safety due to
high-magnitude charging and discharging currents. The analysis explains the origin of the states and
their effects and demonstrates their correlation with the existing voltage ripple on flying capacitors.
The article further demonstrates that the voltage ripple can no longer be arbitrarily chosen as parasitic
states emerge whenever the ripple exceeds an identified critical value being equal to the twofold
voltage drop on the diode. A simple design criterion for flying capacitance is proposed. For a limited
set of battery-powered DC–DC converters, a solution permitting the use of smaller capacitance
by adding an extra switch is proposed. The derived findings are verified using experimental and
simulation results.
1. Introduction
DC–DC converters, capable to operate at a high voltage conversion ratio between the input Vin and
output voltages Vout , are gaining noticeable consideration in different applications [1,2], ranging from
point-of-load converters to converters in several hybrid vehicle configurations. In these applications,
power switches are commonly poorly utilized. Switch utilization is, in general, defined as the ratio
between the output power consumed on a load and the product of the maximum voltage and current
on the switch, thus being proportional to the duty cycle [3,4]. In the past, low switch utilization was
successfully addressed in inductor-tapped solutions; with the only drawback of the increased blocking
voltage [5–8]. In recent years, the voltage rating of the switch is commonly reduced by applying
multi-level DC–DC converters, such as the one with a flying capacitor [9–14]. In this case, the switch
utilization is increased at the price of increased control complexity. On the other hand, the switches
with lower voltage ratings exhibit lower conduction and switching losses, consequently increasing the
overall efficiency.
Traditionally, switch utilization can be enhanced by sharing the total power among converters
operating in parallel. Such a converter is designated as a multi-phase converter [15–20].
Additional benefits can be further gained by interleaving as the current ripple through the output
smoothing capacitor is decreased. In order not to exceed the current rating of the individual
switch, the complexity of control becomes problematic not only due to the increased number of
current transducers but mostly as the current has to be evenly shared both in the steady state and
during transients.
The advantages of both concepts, i.e. multi-level and multi-phase, have been successfully
combined in the interleaved multi-phase Buck converter with an extended duty cycle proposed
in [19,20]. There, two different topologies are presented. Both feature almost the same benefits,
differing in the number of switches per phase. In a topology with two metal oxide semiconductor field
effect transistors (MOSFET) per output phase (analyzed in this paper—Figure 1), all MOSFETs (T1 –T4 )
are subjected to the same current (Iload /n, where n denotes the number of phases) and voltage (Vin /2)
stress. Most importantly, the current sharing among phases takes place spontaneously. Accordingly,
only the load current needs to be measured, thus make the analyzed topology an ideal example for
high-current applications.
Regardless of the topology, flying capacitors are exposed to large current and thermal stress,
which leads to a more rapid ageing of the component [21]. Its consequences are reduced capacitance
and increased equivalent series resistance (ESR). Accordingly, when selecting capacitors, a wider design
margin is needed in order to mitigate the capacitor’s degradation and to guarantee error-free operation.
Commonly, when analyzing DC–DC converters, bulky capacitors are implied, assuming the
voltage ripple on the capacitor is small enough compared to its average voltage. This is certain for
output smoothing capacitor, which has the direct impact on the output voltage quality and on the
electromagnetic interference (EMI). On the other hand, in practice, a larger voltage ripple is usually
allowed across flying capacitors in order to decrease the required volume in high-density designs.
No serious impacts on the basic operation of the converter owed to a higher voltage ripple on flying
capacitors have been reported [9–14].
This paper offers an in-depth analysis of interleaved buck topology. The paper also derives
a condition referring to the minimum capacitance that separates error-free operation from the
appearance of the parasitic switching states, and discuss the effects if the condition is not met.
The origin of the parasitic switching states is analyzed in detail as not yet reported in references
dealing with this topology [19,20]. Furthermore, a simple solution that prevents the appearance of
parasitic states and their effects is proposed and commented.
iin
T1 vDS,1 vDS,4 T4
iC1 iC2
vC1 vC2
T2 vDS,2 C1 C2 vDS,3 T3
Vin
iL2 L2
iL1 Iload
Cin
L1
Figure 1. The interleaved two-phase buck converter with an extended duty cycle.
Accordingly, the converter enters four active switching intervals (identified by the conduction
of a particular switch) that take part in a predefined sequence—either clockwise (CW sequence:
T4 -T3 -T2 -T1 ) or counter-clockwise (CCW sequence: T1 -T2 -T3 -T4 ). Between two consecutive active
switching intervals, the freewheeling interval (FW) occurs. In that interval, inductors’ currents flow
507
Energies 2018, 11, 1017 3 of 13
through D11 and D22 . All active switching intervals have the same duty cycle (dsw ) which never
exceeds 0.25. In the same paper, it is further demonstrated that, assuming the circuit symmetry,
the average voltage across the flying capacitor (C1 , C2 ) equals Vin /2, and the load current is equally
shared among inductors. As a result, in steady-state operation, the output voltage is proportional to
Vin ·dsw /2. To sum up, all results and conclusions provided in [19,20] apply only to highly idealized
cases due to the assumed bulkiness of C1 and C2 .
vC1
Interval IV
Interval I
Vin
iC2 iC1
I L1 I L2 2
Interval III
Interval II
FW FW FW t
dswTsw
Tsw 1 / fsw
Figure 2. Simulation results showing voltages and currents that flow through flying capacitors (details
regarding the simulation models built in LTspiceXVII can be found in Section 3).
T1 vD_body T4 T1 vD_body T4
VA VB VA VB
vC1 vC2 vC1 vC2
Vin Vin
T2 C1 C2 T3 T2 C1 C2 T3
L2 L2
L1 L1
D22 D22
D11 vD22 D11 vD22
Cout Cout
(a) (b)
T1 T4 T1 T4
VA VB VA VB
vC1 vC2 vC1 vC2
Vin Vin
C1 C2 T3 C1 C2 T3
vD_body T2 vD_body T2
L2 L2
L1 L1
D22 D22
D11 vD22 vD22
Cout D11
Cout
(c) (d)
Figure 3. Equivalent circuits with indicated current paths (in red) when ΔvC (see text) is below a critical
value in: (a) Interval I; (b) Interval II; (c) Interval III; (d) Interval IV.
508
Energies 2018, 11, 1017 4 of 13
In Interval I, the capacitor C1 is charged by the inductor current i L2 . In Interval II, when T2 is
switched ON, C1 is discharged by current i L1 .
Assuming a lossless capacitor vC1 remains unchanged during the FW interval, as well as in
consecutive intervals when vC2 at first decays in Interval III (due to i L2 ) and then in Interval IV rises
back (due to i L1 ). In the steady-state, the voltage increase and decrease on the individual flying
capacitor are in equilibrium:
Assuming symmetrical circuit the voltage ripples, expressed as a peak–peak value, are equal
(ΔvC1 = ΔvC2 = ΔvC ) on both flying capacitors.
In Interval II (Figure 3b), the diode D22 is forward-biased. Therefore, the potential in node A is
equal to the sum:
VA,I I = −v D22 + vC1 . (2)
Figure 2 demonstrates that at the end of Interval I, the capacitor voltages vC1 and vC2 tend to
reach their maximum values (V in /2 + ΔvC /2) and remain unchanged until the start of Interval II.
Consequently, at the start of Interval II, VB reaches its maximum as well:
Providing that VB,I I max is lower than Vin +v D_body , the body diode in MOSFET ( T4 ) remains
reverse-biased. Thus, if an equal voltage drop across the body diode and the freewheeling diode
is assumed, the voltage sum across flying capacitors (Vin + ΔvC ) should be kept below Vin +2v D .
The latest can be rephrased into the condition:
ΔvC ≤ 2v D , (5)
However, as voltages on both flying capacitors have already reached their minimum
(V in − ΔvC /2), VA,IV drops to:
Vin − ΔvC1
VA,IVmin = −v D22 + . (8)
2
By assuming equal voltage drops across the body diode and the freewheeling diode, the same
condition already stated in Equation (5) determines whether the body diode in MOSFET ( T2 ) remains
biased in reverse or it turns into conduction.
509
Energies 2018, 11, 1017 5 of 13
T1 vD_body T4 T1 T4
VA VB VA VB
L2 L2
L1 L1
D22 D22
vD22 D11 vD22
D11 Cout
Cout
(a) (b)
Figure 4. Equivalent circuits showing extra current paths (in blue) that occur when ΔvC exceeds the
critical value: (a) in Interval II*; (b) in Interval IV*.
The extra current path emerges at the beginning of Interval II and exists only for a limited time,
being denoted as Interval II*. Figure 5 shows this phenomenon in detail. During this interval, a surplus
charge, which has accumulated on flying capacitors, is abruptly discharged back to the voltage source.
'vC 2 vD 'vC t 2 vD
vC2
i(t)
v(t)
vC1
Interval II*
Interval IV
Interval I
iC2 iC1
I L1 I L2
Interval III
Interval II
FW FW FW t
Interval IV*
Figure 5. Simulation results showing flying capacitor currents and voltages with zoomed voltage
waveforms in parasitic Interval II*.
This overcharging does not jeopardize the validity of the derived Equations (2–8) as these define
electric potentials in nodes A and B only in Interval II and Interval IV. In fact, at the end of Interval I,
the flying capacitors could be charged to a higher voltage as shown in the zoomed part in Figure 5,
depending on the parameters involved in Equation (1), thus forcing the voltage ripple over the critical
510
Energies 2018, 11, 1017 6 of 13
value. If this is the case, the capacitors discharge until their ripples drop below 2v D . If the ripples
remain inside the boundaries, the error-free operation depicted in Figure 2 takes place.
The shape of the discharging current, which flows simultaneously through both flying
capacitors, follows:
V −αt R 1 R 2
i(t) = e · sin(ωr t); α = ; ωr2 = −( ) , (9)
ωr L p 2L p LpC 2L p
where V stands for the voltage difference seen in the zoomed section in Figure 5. The shape is defined
by R-L-C parameters found in the depicted path (Figure 4a, blue line) where small resistances (R) and
inductances L p , both contributed by parasitic components of circuit and flying capacitors (C), have
a dominant impact on the magnitude and period of the signal. Its period could be as short as the
conduction interval of power switches, whereas its magnitude can easily reach or even surpass the
inductor current.
Figure 4b indicates a similar parasitic switching state which could occur when T4 turns ON if
in that instant the sum of voltages across C1 and C2 is too low to maintain the body diode of T2
reverse-biased. In that case, the capacitors are abruptly charged from the power source through the
forward-biased body diode of MOSFET T2 . As D22 is forward biased by the freewheeling current forced
by L2 , the surge current (blue line) can be considered to flow in opposite direction thus decreasing the
current through D22 .
It is apparent that such an operation is not desirable as conduction losses may increase
considerably, but also since semiconductors and flying capacitors could be overstressed by the current.
In addition, if the front side of the converter includes an overcurrent protection, its level should be
high enough to prevent an unintentional tripping. Therefore, to prevent the occurrence of these states
and their impacts, the capacitance should be set higher than the critical one:
Iload Vout
Ccrit = · . (10)
2v D · f sw Vin
Equation (10) is derived from Equation (1) by taking into account that the load current is equally
shared among inductors and the voltage ratio Vout /Vin is proportional to dsw /2. It is important to
point out that the form of Equation (10) is not significantly different from equations that can be derived
for an arbitrary converter with flying capacitors [9,11,13,14]. The critical capacitance in this particular
converter is inherently limited by topology itself, as the ripple must not exceed the twofold voltage
drop on the diodes (2v D ). This finding is the essential contribution to the original papers [19,20] in
order to preserve an error-free operation.
511
Energies 2018, 11, 1017 7 of 13
(a)
(b)
Figure 6. Pictures of the experimental setup: (a) an unpopulated printed circuit board (PCB) with
a marked (yellow) section consisting of six MOSFETs and flying capacitors; (b) converter at the
test bench.
The converter is deployed on a two-layer PCB. The topology is the same as in Figure 1 but
the D11 and D22 were replaced with MOSFETs in order to increase the flexibility of converter thus
enabling additional research. For measurements, these MOSFETs were permanently OFF to emulate
the freewheeling diodes D11 and D22 . In order to reduce EMI to the lowest possible level, flying
capacitors are placed in a close proximity of switching nodes with a high dv/dt, thus keeping the
current loops that are subjected to pulses with a high di/dt short as well. In order to enable the current
measurement through flying capacitors, the PCB was not equipped with multilayer ceramic capacitors
(MLCC). Instead, they are placed on dedicated holders which are connected to the rest of the circuit by
solid wires where a current probe (A6302 from Tektronix, Beaverton, OR, USA) can be clamped on.
To simplify the tests, each MLCC holder was populated with three 15 μF/50 V capacitors. According
to the known current that flows through parallel capacitors, their capacitance was estimated at 30 μF at
an average capacitor voltage (15 V). For tests requiring a critical or higher capacitance, the difference
was realized by fastening a temporary capacitor of an adequate capacitance.
The first test was carried out in order to verify the steady-state waveforms of the converter and its
numerical model built in LTspiceXVII. Due to the additional inductance introduced by the aforesaid
capacitor placement, tests have been performed at a reduced current capability ( Iload, max∗ = 20 A) in
order to reduce overvoltage on MOSFETs. In accordance with Equation (10), the critical capacitance
amounts to 44 μF. Figure 7a,b depict iC1 (blue) and iC2 (red) at different load currents and with
a capacitance greater than Ccrit specified in Equation (10). The shape and magnitude of both currents
closely match simulation traces seen in the top part of Figure 7c,d, but there is slight asymmetry of
magnitudes between currents due to mismatch of inductance and capacitor values.
512
Energies 2018, 11, 1017 8 of 13
(a) (b)
(c) (d)
Current spikes, which appear in experimental traces whenever an individual MOSFET turns ON,
are caused by the reverse recovery charge Qrr of the freewheeling diodes. Owing to the increased
inductance, the trailing edges of these spikes are additionally prolonged. In addition, a capacitive
coupling due to the close proximity between switching nodes with a high dv/dt and the current probe
rendered the shape of current measurements, too. When voltages—especially those referenced against
one of the switching node—are measured with passive voltage probes, the quality of captured traces
on oscilloscope (Tektronix–DPO 4034B) usually worsen substantially. As a result, voltages shown
on oscilloscope window were not measured simultaneously with current traces. Instead, they were
measured separately and then recalled from internal memories.
In addition, voltage ripples in the middle part of Figure 7c,d exhibit their dependency on the
load current (traces at the bottom of the same figures) as identified in the analysis. As it can be
noticed, the experimental voltage ripples (at the bottom part of the Figure 7a,b) match the simulated
ones quite faithfully, both in the magnitude and the shape. The average value of the flying capacitor
voltages differs from Vin /2, being theoretically derived with neglected voltage drops on MOSFETs and
freewheeling diodes.
513
Energies 2018, 11, 1017 9 of 13
The effectiveness of the proposed analytical developments given by Equations (2)–(10) is further
confirmed in Figure 8, where an experimental verification was carried out considering the violation
of the critical value of flying capacitance. Compared to the simulation results in Figure 8a, it can be
noticed that the experimental currents in Figure 8b exhibit a longer duration of parasitic intervals.
Referring to Equation (9), this deviation can be explained as simulation did not include any additional
parasitic inductances which were present in the circuit (PCB traces, transistor terminals, equivalent
series inductance of capacitors, capacitor holder).
(b)
(a)
(c)
Figure 8. Simulation and experimental results obtained at an average inductor current 10 A and at
C1 = C2 = 35 μF: (a) simulated results: the upper part, flying capacitors’ currents: the middle part,
voltages on the flying capacitors: the lower part, inductors’ currents; (b) measured results: flying
capacitors’ currents (blue: iC1 ; red: iC2 ); (c) voltages on the flying capacitors (blue: vC1 ; black: vC2 ).
4. Discussion
All in all, the benefit of knowing the critical capacitance can be of higher importance in the
converter with n larger than 2, particularly if the converter works at higher operational temperatures.
There, the selection and placement of flying capacitors in a confined volume are strengthened in
order to satisfy thermal and EMI specifications. Commonly, MLCCs of type X8R, X7R or X5R are
implemented [22,23]. Nowadays, they can be produced with high-temperature grades (150 ◦ C) and
with a high rated capacitance (22 μF/100 V) in a relatively small package of size 2220. On the other
hand, MLCC faces a considerable voltage dependency. As a result, its rated capacitance could be met
only at a reduced voltage. For high volumetric parts, the decrease of C with voltage can be greater
than 50% of its rated value [23]. Furthermore, a current derating has to be taken into account in order
to reduce the dissipating power inside of the flying capacitors. All this increases the chance that in
space-confined designs the flying capacitance has to be chosen close to its critical value, thus increasing
514
Energies 2018, 11, 1017 10 of 13
the probability to violate Equation (10). Taking into account the ageing effects of MLCC as well [24–26],
the aforesaid becomes even more likely. Furthermore, the situation becomes even worse if diodes
D11 and D22 are replaced with a synchronous MOSFET, in order to boost the efficiency even further.
In this case, the peak–peak voltage ripple across C1 and C2 falls under the voltage drop of a single
body diode, basically halving the voltage ripple given in Equation (5).
As an additional remark, it was found out that, if the sequence changes from CCW to CW, parasitic
switching states occur at the beginning of Interval I and Interval III. Since the body diodes of T1 and T3
are biased in the forward direction, the flying capacitors are again exposed to charging and discharging
currents. All together, tests show that despite high expectations, the applicability of the converter
could be significantly limited due to Equation (10).
Nevertheless, simulation results additionally exhibit that in the case of battery-powered
converters—equipped with a MOSFET for battery reversal protection—the parasitic switching states
vanish completely. Figure 9a,b show results obtained when extra MOSFETs were added in series with
the top positioned MOSFETs T1 and T4 , forming a back-to-back switch.
(a) (b)
Figure 9. Comparison of results obtained at an average inductor current 10 A, with inserted extra
switches and with C1 = C2 = 5 μF: (a) simulation results: the upper part, flying capacitors’ currents:
the middle part, voltages on flying capacitors: the lower part, inductors’ currents: (b) measured results:
the upper part, flying capacitors’ currents (blue: iC1 ; red: iC2 ): the lower part, voltages on flying
capacitors (bottom black: vC1 ; top black: vC2 ).
The extra MOSFETs are switched simultaneously with T1 and T4 . As a result, no discharging
current could flow back to the voltage supply irrespective of the CW or CCW sequence. In this case,
the flying capacitor is not required to fulfil Equation (5). Thus, a larger voltage ripple may be accepted.
In fact, traces on the left and right side in Figure 9 correspond to a flying capacitance of just 5 μF. Traces
iC1 and iC2 are similar to those in Figure 7d obtained with a much larger capacitance (60 μF). Although
the voltage ripples in Figure 9a,b are more than five times larger than the ones in Figure 7d, the load
current is ideally shared among both inductors. In Figure 10, current sharing is proved even in the
case when the resistance of one inductor has been intentionally increased to fivefold.
As it can be noticed in Figures 9 and 10, not only the ripple voltages increase, the average
voltage across flying capacitors tends to increase as well. In this particular case, the converter remains
functional at the price of an uneven voltage stress of the individual MOSFET (T1 –T4 ). Furthermore,
as extra MOSFETs are switched simultaneously with T1 and T4 and at the zero-current condition,
the total losses of the switches remain more or less unaffected. The control itself remains simple and
straightforward. The additional MOSFETs are placed at the bottom side of PCB in order to be efficiently
cooled and to keep the parasitic inductance as low as possible.
515
Energies 2018, 11, 1017 11 of 13
Figure 10. Simulation results obtained at an average inductor current 10 A, with inserted extra
switches, with C1 = C2 = 5 μF and with unsymmetrical inductors’ resistances R L2 = 5R L1 : the
upper part, flying capacitors’ currents: the middle part, voltages on flying capacitors: the lower part,
inductors’ currents.
5. Conclusions
The voltage ripple in the interleaved buck converter with an extended duty cycle has been
analyzed in this paper, as the converter has been recognized as an ideal candidate for high-current
DC–DC applications from many points of view. Specifically, in contrast to other converters being
referenced, it provides an equal current and voltage stress on all MOSFETs. And most importantly,
it requires less current transducers as the current sharing in output inductors takes place automatically.
The analysis presented in this paper focuses on unexplored switching states which occur under
specific conditions in the two-phase interleaved converter. As their occurrence has a significant
negative impact on the converter operation, a critical capacitance was derived in order to avoid them.
This has been verified with a simulation model and confirmed by the measurements performed on the
prototype converter. Furthermore, a simple mitigation solution based on the additional switch per
converter’s phase is proposed and verified. The solution is justified for battery-powered converters
enabling to install a smaller flying capacitance as required by Equation (10).
Author Contributions: Both authors contributed to all of the aspects of the manuscript. To emphasize a particular
specific contribution, Peter Zajec wrote the paper, designed and performed the experiments. Mitja Nemec wrote
the code for the DSP and analyzed the simulation and experimental results.
Conflicts of Interest: The authors declare no conflict of interest.
References
1. Forouzesh, M.; Siwakoti, Y.P.; Gorji, S.A.; Blaabjerg, F.; Lehman, B. Step-Up DC-DC Converters:
A Comprehensive Review of Voltage-Boosting Techniques, Topologies, and Applications. IEEE Trans.
Power Electron. 2017, 32, 9143–9178. [CrossRef]
2. Du, S.; Wu, B. A Transformerless Bipolar Modular Multilevel DC-DC Converter With Wide Voltage Ratios.
IEEE Trans. Power Electron. 2017, 32, 8312–8321. [CrossRef]
3. Erickson, R.W.; Maksimovic, D. Fundamentals of Power Electronics; Springer Science & Business Media: Berlin,
Germany, 2007; ISBN 978-0-306-48048-5.
4. Schwingal, N.; Bernet, S. Power Semiconductor Loss Comparison of Low-Voltage, High-Power Two-Level
and Three-Level Voltage Source Converters. In Proceedings of the PCIM Europe 2015, International
Exhibition and Conference for Power Electronics, Intelligent Motion, Renewable Energy and Energy
Management, Nuremberg, Germany, 19–20 May 2015; pp. 1–9.
516
Energies 2018, 11, 1017 12 of 13
5. Park, J.H.; Cho, B.H. Nonisolation Soft-Switching Buck Converter With Tapped-Inductor for Wide-Input
Extreme Step-Down Applications. IEEE Trans. Circuits Syst. Regul. Pap. 2007, 54, 1809–1818. [CrossRef]
6. Yao, K.; Ye, M.; Xu, M.; Lee, F.C. Tapped-Inductor Buck Converter for High-Step-Down DC-DC Conversion.
IEEE Trans. Power Electron. 2005, 20, 775–780. [CrossRef]
7. Park, J.H.; Cho, B.H. The Zero Voltage Switching (ZVS) Critical Conduction Mode (CRM) Buck Converter
With Tapped-Inductor. IEEE Trans. Power Electron. 2005, 20, 762–774. [CrossRef]
8. Williams, B.W. Unified Synthesis of Tapped-Inductor DC-to-DC Converters. IEEE Trans. Power Electron. 2014,
29, 5370–5383. [CrossRef]
9. Zhang, F.; Du, L.; Peng, F.Z.; Qian, Z. A new design method for high efficiency DC-DC converters with
flying capacitor technology. In Proceedings of the Twenty-First Annual IEEE Applied Power Electronics
Conference and Exposition, APEC ’06, Dallas, TX, USA, 19–23 March 2006.
10. Lei, Y.; Liu, W.C.; Pilawa-Podgurski, R.C.N. An analytical method to evaluate flying capacitor multilevel
converters and hybrid switched-capacitor converters for large voltage conversion ratios. In Proceedings of
the 2015 IEEE 16th Workshop on Control and Modeling for Power Electronics (COMPEL), Vancouver, BC,
Canada, 12–15 July 2015; pp. 1–7.
11. Shenoy, P.S.; Lazaro, O.; Amaro, M.; Ramani, R.; Wiktor, W.; Lynch, B.; Khayat, J. Automatic current sharing
mechanism in the series capacitor buck converter. In Proceedings of the 2015 IEEE Energy Conversion
Congress and Exposition (ECCE), Montreal, QC, Canada, 20–24 September 2015; pp. 2003–2009.
12. Zhang, F.; Peng, F.Z.; Qian, Z. Study of the multilevel converters in DC-DC applications. In Proceedings of
the 2004 IEEE 35th Annual Power Electronics Specialists Conference (IEEE Cat. No.04CH37551), Aachen,
Germany, 20–25 June 2004; pp. 1702–1706.
13. Parastar, A.; Gandomkar, A.; Seok, J.K. High-Efficiency Multilevel Flying-Capacitor DC/DC Converter for
Distributed Renewable Energy Systems. IEEE Trans. Ind. Electron. 2015, 62, 7620–7630. [CrossRef]
14. Jin, K.; Yang, M.; Ruan, X.; Xu, M. Three-Level Bidirectional Converter for Fuel-Cell/Battery Hybrid Power
System. IEEE Trans. Ind. Electron. 2010, 57, 1976–1986. [CrossRef]
15. Chuang, C.F.; Pan, C.T.; Cheng, H.C. A Novel Transformer-less Interleaved Four-Phase Step-Down DC
Converter With Low Switch Voltage Stress and Automatic Uniform Current-Sharing Characteristics.
IEEE Trans. Power Electron. 2016, 31, 406–417. [CrossRef]
16. Pattnaik, S.; Panda, A.K.; Mahapatra, K.K. An Improved Multiphase converter for New Generation
Microprocessr. In Proceedings of the Industrial and Information Systems, 2008, ICIIS 2008. IEEE Region 10
and the Third international Conference on, Kharagpur, India, 8–10 December 2008; pp. 1–5.
17. Harada, K.; Nishijima, K.; Nakano, T.; Nabeshima, T.; Sato, T. Analysis of Double Step-Down Two-Phase
Buck Converter for VRM. In Zuk. Durch Informationstechnik Schnell-Mobil-Intell. Informationstechnik Für
Menschen-50 Jahre ITG Vorträge Jubil. Am 26 27 April 2004 Johann-Wolfgang-Goethe-Univ. Frankf. Am Main Mit
CD-ROM; VDE Verlag: Berlin/Offenbach, Germany, 2004; p. 497.
18. Gleissner, M.; Bakran, M.M. Design and Control of Fault-Tolerant Nonisolated Multiphase Multilevel DC-DC
Converters for Automotive Power Systems. IEEE Trans. Ind. Appl. 2016, 52, 1785–1795. [CrossRef]
19. Jang, Y.; Jovanovic, M.M.; Panov, Y. Multiphase buck converters with extended duty cycle. In Proceedings of
the IEEE Applied Power Electronics Conference (APEC’06), Dallas, TX, USA, 19–23 March 2006; pp. 38–44.
20. Jang, Y.; Jovanović, M. Non-isolated Power Conversion System Having Multiple Switching Power Converters.
U.S. Patent 7,230,405, 12 June 2007.
21. Rating and Derating for Low-Voltage Multilayer Ceramic Capacitors (MLCCs). Available online: https:
//nepp.nasa.gov/files/25843/2013-Teverovsky-pres-MLCCsBME-n263.pdf (accessed on 19 March 2018).
22. Stewart, J.; Neely, J.; Delhotal, J.; Flicker, J. DC link bus design for high frequency, high temperature
converters. In Proceedings of the 2017 IEEE Applied Power Electronics Conference and Exposition (APEC),
Tampa, FL, USA, 26–30 March 2017; pp. 52–55.
23. Choi, D.H.; Randall, C.; Furman, E.; Ma, B.; Balachandran, U.B.; Zhang, S.; Lanagan, M. Energy and power
densities of capacitors and dielectrics. In Proceedings of the 2015 IEEE International Workshop on Integrated
Power Packaging (IWIPP), Chicago, IL, USA, 3–6 May 2015; pp. 52–55.
24. Biba, D.R.; Musuroi, S.; Svoboda, M. A new approach to lifetime and loading stress level estimation
for Multilayer Ceramic Capacitors in Electronic Control Units. In Proceedings of the 2017 International
Conference on Optimization of Electrical and Electronic Equipment (OPTIM) 2017 Intl Aegean Conference
on Electrical Machines and Power Electronics (ACEMP), Brasov, Romania, 25–27 May 2017; pp. 37–42.
517
Energies 2018, 11, 1017 13 of 13
25. Jiang, W.; Hu, Y.; Bao, S.; Lijie, S.; Yuwei, Z.; Cui, Y.; Qiang, L. Analysis on the causes of decline of MLCC
insulation resistance. In Proceedings of the 2015 16th International Conference on Electronic Packaging
Technology (ICEPT), Changsha, China, 11–14 August 2015; pp. 1255–1257.
26. Scarpulla, J.; Ayvazian, T.; Buell, W.; Campbell, M.; Dubitsky, A.; Lin, R.; Martin, W.; Moss, S.; Nuccio, S.;
Yarbrough, A.; et al. Thin MLCC (multi-layer ceramic capacitor) reliability evaluation using an accelerated
ramp voltage test. In Proceedings of the IEEE Accelerated Stress Testing Reliability Conference (ASTR),
Pensacola Beach, FL, USA, 28–30 September 2016; pp. 1–12.
© 2018 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access
article distributed under the terms and conditions of the Creative Commons Attribution
(CC BY) license (http://creativecommons.org/licenses/by/4.0/).
518
energies
Article
Voltage Balance Control Analysis of Three-Level
Boost DC-DC Converters: Theoretical Analysis and
DSP-Based Real Time Implementation
Driss Oulad-Abbou 1,2, *, Said Doubabi 1 and Ahmed Rachid 2
1 Laboratory of Electric Systems and Telecommunications, Cadi-Ayyad University, BP 549,
Av Abdelkarim Elkhattabi, Gueliz, 4000 Marrakesh, Morocco; [email protected]
2 Laboratory of Innovative Technologies, University of Picardie Jules Verne, 80025 Amiens, France;
[email protected]
* Correspondence: [email protected]; Tel.: +212-651-260-941
Abstract: In this paper, a step-by-step description to get a unique three-level boost DC–DC converter
(TLBDC) (DC—direct current) small signal model is first presented and validated through simulations
and experiments. This model allows for overcoming the usage of two sub-models as in the
conventional modeling approach. Based on this model, voltage balance (VB) controllers are designed
and VB control analysis is presented. Two VB controllers, namely Proportional Integral (PI) and
Fuzzy, were analyzed when the VB control was applied on both TLBDC switches or only one.
According to the obtained simulation and experimental results, the proposed model gives an accurate
approximation in dynamic, small perturbations around an operating point and steady state modes.
Moreover, it has been shown that VB is achieved in a reduced time when VB control is applied on
both the TLBDC’s switches. Furthermore, the Fuzzy controller performs better than PI controller for
VB control.
Keywords: three-level boost DC-DC converter; small signal modeling; voltage balance control
1. Introduction
In recent decades, modeling and control of DC–DC (DC—direct current) converters have gained
much attention. This is due to their increased uses in various applications, such as voltage regulation [1–4],
renewable energy interfacing [5–7], electric vehicle charging [8–10], etc. The conventional boost and
buck converters are the basic topologies that are shown in Figure 1a,b, respectively. Due to their
simplicity and high efficiency, they are the most used DC–DC converters. However, because of high
voltage stress on their switching components, these conventional converters are not recommended for
medium- and high-voltage ratings that require more powerful switching devices, which increase the
cost, the volume, and the system complexity.
(a) (b)
Figure 1. Conventional two-level schemes: (a) a boost converter, and (b) a buck converter.
Multilevel DC–DC converters are a suitable solution to overcome the aforementioned limitations.
This is due to their ability to operate at high power ratings with higher efficiencies compared to
conventional two-level topologies. They also provide other advantages such as low distortion of
the output voltage and lower switching losses [2–4,11–14]. The three-level DC-DC boost converter
(TLBDC) depicted in Figure 2a, has been widely discussed [14–19]. The converter fundamentals and
design considerations were presented in Reference [19], where it has been shown, for instance, that
the converter inductance and capacitors can be significantly reduced when compared to the two-level
boost DC–DC converter.
Based on the state-space modeling approach, several TLBDC models were presented [17,18,20–22],
where two sub-models were used: the first one used for a duty ratio (DR) less than 50%, and the
second one is used for a DR greater than 50%. Hence, a selection parameter is required to distinguish
between these two sub-models. Using a state space averaged modeling (SSAM) approach and a small
signal model (SSM), introduced in Reference [23] and discussed in detail in Reference [3], the transfer
functions around a corresponding operating point could be extracted. A discrete-time approach
is another way for TLBDC modeling [11,24]. However, it requires long and complex calculations
when compared to the previous SSAM method. In Reference [25], a DSP-based implementation of a
self-tuning Fuzzy controller for TLBDC has been presented. The converter was modeled using SSAM
and three cases based on the DR values were presented: for a DR less than 50%, for a DR higher than
50%, and for any DR. The main objective was the output voltage controller synthesis. However, neither
the modeling procedure has been described in detail, nor the simulation and practical model validation
were carried out. Moreover, comparison between the single model and the conventional modeling
approach was not addressed.
The proper operation of TLBDC needs the balance of the output capacitors’ voltages.
Different voltage balance (VB) control methods were presented [15,21,26–34]. In References [21,29],
and referring to Figure 2, the VB control was achieved by delaying forward or backward SW2 switch
control signals of the TLBDC. Another method using an existing energy storage system to ensure
the VB was presented in Reference [26]. In References [30–34], the VB control was performed by a
PI controller. The controller output was added to the DR of the switch SW1 and subtracted from the
DR of switch SW2. A sensor-less VB control method was also proposed in Reference [15] using a PI
controller whose output was added to the DR of switch SW2. Finally, in Reference [25], the output
capacitors’ voltages were sensed, and a PI-controller was used for VB control. The controller output
was added to the SW2 switch DR.
Through this literature review, it is clear that the main VB control methods consist in the following:
add a small perturbation to one (or both) converter’s switch(es) DR(s), or adjust the delay between the
switches control signals. However, the method to choose the TLBDC switch(es) on which VB control
should be applied was not addressed.
Based on these motivations, and unlike Reference [25], where the main goal was the output
voltage controller synthesis, this paper adds further contributions to the state of the art by giving
a step-by-step description of the followed method to get a unique model for a TLBDC working in
continuous conduction mode (CCM), with a non-zero inductor equivalent series resistor. The unique
model allows for avoiding the usage of two sub-models as in the conventional modeling approach, and
facilitates synthesizing a convenient VB controller. This model has been validated using simulation
and experimental tests, and a comparison with the conventional modeling approach is addressed.
On the other hand, a technique is presented to best ensure the VB of the TLBDC. The analysis is carried
out using two different VB methods and controllers, namely PI and Fuzzy controllers. This allows for
figuring out the convenient controller and the adequate way for the VB control of the TLBDC.
The rest of paper is organized as follows. Section 2 describes the TLBDC operation and the
developed small signal model (SSM). The VB control of the TLBDC is analyzed in Section 3, followed
by the conclusion. Each of Sections 2 and 3 gives theoretical developments as well as simulation and
experimental results.
520
Energies 2018, 11, 3073
(a)
(b) (c)
Figure 2. (a) The electrical scheme of the TLBDC under study, (b) TLBDC control signals for a DR less
than 50%, and (c) TLBDC control signals for a DR higher than 50%.
Under CCM, the TLBDC is described by a set of equations and equivalent electrical schemes.
These are summarized in Table 1 and Figure 3, respectively. il , rl , vc1 , vc2 , v I N , and vout are the inductor
current, inductor equivalent series resistor (ESR) (that equals 0.1 Ω in our case), capacitor C1 voltage,
capacitor C2 voltage, and input and output voltages, respectively.
(a) (b)
(c) (d)
Figure 3. TLBDC equivalent electrical schemes for control signals u1 (t)-u2 (t) sequence: (a) 0-0, (b) 1-0,
(c) 0-1 and (d) 1-1.
521
Energies 2018, 11, 3073
Table 1. Differential equations for each control signals sequence of TLBDC working in CCM.
d 1 1 1 r
i = − vc1 − vc2 + v I N − l il , (1)
dt l L L L L
d 1 1 1
0-0 v = i − v − v , (2)
dt c1 C1 l R·C1 c1 R·C1 c2
d 1 1 1
v = i − v − v , (3)
dt c2 C2 l R·C2 c1 R·C2 c2
vout = vc1 + vc2 , (4)
d 1 1 r
i = − vc2 + v I N − l il , (5)
dt l L L L
d 1 1
1-0 v =− v − v , (6)
dt c1 R·C1 c1 R·C1 c2
d 1 1 1
v = i − v − v , (7)
dt c2 C2 l R·C2 c1 R·C2 c2
vout = vc1 + vc2 , (8)
d 1 1 r
i = − vc1 + v I N − l il , (9)
dt l L L L
d 1 1 1
0-1 v = i − v − v , (10)
dt c1 C1 l R·C1 c1 R·C1 c2
d 1 1
v =− v − v , (11)
dt c2 R·C2 c1 R·C2 c2
vout = vc1 + vc2 , (12)
d 1 r
i = v I N − l il , (13)
dt l L L
d 1 1
1-1 v =− v − v , (14)
dt c1 R·C1 c1 R·C1 c2
d 1 1
v =− v − v , (15)
dt c2 R·C2 c1 R·C2 c2
vout = vc1 + vc2 , (16)
Based on the differential Equations (1)–(16), the TLBDC state space equations for the four control
signals sequences are given by Equations (17)–(24), where Equations (17) and (18) correspond to the
state space equations for 0-0 control signals state, Equations (19) and (20) correspond to the state space
equations for 0-1 control signals state, Equations (21) and (22) correspond to the state space equations
for 1-0 control signals state, and Equations (23) and (24) correspond to the state space equations for 0-0
control signals state.
i − rl − L1 − L1 i 1
d l
1L
l
L
v = C1 − R·1C1 − R·1C1 · vc1 + 0 ·v I N , (17)
dt c1 1
vc2 C2 − R·1C2 − R·1C2 vc2 0
il
vout = 0 1 1 · vc1 , (18)
vc2
522
Energies 2018, 11, 3073
i − rl − L1 i 1
d l l L
L 0
v = 0 − R·1C1 · vc1
− R·1C1 + 0 ·v I N , (19)
dt c1 1
vc2 C2 − R·1C2 vc2
− R·1C2 0
il
vout = 0 1 1 · vc1 , (20)
vc2
i − rl − L1 il 1
d l L
L 0
v = 0 − R·1C1 − R·1C1 · vc1 + 0 ·v I N , (21)
dt c1 1
vc2 C2 − R·1C2 − R·C2 vc2
1 0
il
vout = 0 1 1 · vc1 , (22)
vc2
i − rl − L1 i 1
d l l L
0
1L
v = C1 − R·1C1 − R·1C1 · vc1 + 0 ·v I N , (23)
dt c1
vc2 0 − R·1C2 − R·C2 vc2
1 0
il
vout = 0 1 1 · vc1 , (24)
vc2
Using discrete variables u1 (t) and u2 (t), Equations (17)–(24) could be assembled into one equation.
The obtained TLBDC model is given by Equations (25) and (26).
i − rLl − 1−uL1 (t) − 1−uL2 (t) i 1
d l
1− u1 ( t )
l
L
v = − R·1C1 − R·1C1 · vc1 + 0 ·v I N , (25)
dt c1 C1
vc2 1− u2 ( t )
− R·1C2 − R·1C2 vc2 0
C2
il
vout = 0 1 1 · vc1 , (26)
vc2
il
vout = 0 1 1 · vc1 , (28)
vc2
i
l
Let us denote x = vc1 , v I N , vout , u1 , and u2 as the average values of the state vector
vc2
i
l
x = vc1 , v I N , vout , u1 , and u2 , respectively. Using this notation, the obtained SSAM is given
vc2
by Equations (29) and (30):
523
Energies 2018, 11, 3073
⎡ r ⎤
i − l − L1 − L1 0 1 0 1 i 1
l 0 0 l L
d ⎢ 1L L
L
⎥
dt vc1 = ⎣ C1 − R·1C1 − R·1C1 + u ·
1 − C1
1
0 0 + u ·
2 0 0 0 ⎦ . vc1 0 ·v I N ,
+ (29)
1
vc2 C2 − R·1C2 − R·1C2 0 0 0 − C2
1
0 0 vc2 0
il
vout = 0 1 1 · vc1 , (30)
vc2
Each variable can be written as the sum of small alternating current (AC) variations and DC
steady-state quantities as follows:
x = X + x, (31)
u1 = U1 + u1 , (32)
u2 = U2 + u2 , (33)
v I N = VI N + v-
IN, (34)
vout = Vout + v-
out , (35)
Using this decomposition, Equations (31)–(35), Equations (29) and (30) become:
.
x = [.
u1 A 1 + u
.2 A2 ]·
x + B-
vIN + [A0 + U1 A1 + U2 A2 ]·
x + u1 A1 X + u2 A2 X+[ A0 + U1 A1 + U2 A2 ].X + BVI N , (36)
il
vout = 0 1 1 · vc1 , (37)
vc2
− rl − L1 − L1 0 1 0 1
L 0 0
1L 1 L
where: A0 = c1 − R·1C1 − R·1C1 , A1 = − 0 0 , and A2 = 0 0 0 .
1 C1 −1
C2 − R·1C2 − R·1C2 0 0 0 C2 0 0
Neglecting the higher-order terms, steady-state terms are null, and supposing that the supply
voltage is constant, terms written in bold, italic, and bold italic in Equation (36), respectively [3].
The SSM of the TLBDC is given by Equations (38) and (39):
.
x+u
x = [A0 + U1 A1 + U2 A2 ]. .1 A1 X + u
.2 A2 X, (38)
il
out = 0 1 1 . v.
v- , (39)
c1
v. c2
The proposed model is validated through simulation and experimental results. Simulations were
performed on MATLAB software (Matworks, Natick, MA, USA) using the ode23 function, while the
experimental tests were carried out on the experimental setup depicted in Section 3. The TLBDC
parameters used for these tests are listed in Table 2.
The simulated and experimental output voltage curves for the switched model and the SSM
around 30% and 60% DRs are respectively illustrated in Figures 4 and 5, where 4% positive and
negative perturbations were introduced around those DR values.
Based on the results reported in Figure 4, it can be seen that the SSM behavior was in accordance
with the switched one. In addition, the presented experimental results in Figure 5 were closely
matching those obtained from the proposed SSM. By analyzing these results, one can see that the
proposed SSM gave an averaged behavior of the TLBDC for both DR cases.
524
Energies 2018, 11, 3073
(a) (b)
Figure 4. Simulated SSM and switched model output voltage curves in the case of 4% DR perturbation:
(a) around 30%, and (b) around 60% DRs.
(a) (b)
Figure 5. Experimental and SSM output voltages curves with 4% perturbation width: (a) around thirty
percent and (b) around sixty percent DRs.
The results for a DR transition from a value less than 50%, namely 30%, to another one higher
than 50%, namely 60%, are shown in Figure 6. The proposed SSAM and experimental output voltage
curves are shown in Figure 6a, while Figure 6b illustrates the conventional SSAM and experimental
output voltage curves. Finally, Figure 6c presents a comparison between the conventional approach
and the proposed one.
(a) (b)
Figure 6. Cont.
525
Energies 2018, 11, 3073
(c)
Figure 6. Curves for a DR value change from 30% to 60% to 30%: (a) proposed model and experimental
output voltages, (b) experimental and conventional approach output voltages, and (c) proposed and
conventional approach output voltages.
By analyzing the results depicted in Figure 6, the model behavior when the DR was changed from
a value less than 50% to another one higher than 50% is similar to the conventional one. Both SSAM
approaches had identical output voltage curves, but the conventional approach used two different
sub-models for the two duty ratio ranges, 0–50% and 50–100%, which required an additional selection
parameter that allowed for choosing the convenient model [17,18,20–22]. Additionally, unlike the
previous works [17,18,20–22,25], the followed procedure for TLBDC modeling was described in
step-by-step detail.
Applying Laplace transforms with zero initial conditions and using the superposition theorem,
.1 and u
the small-signal duty-cycles u .2 to state vector
x transfer functions are as follows [3,24,35]:
x(s)
= |sI − [A0 + U1 A1 + U2 A2 ]|−1 .A1 X, . (40)
.1 (s)
u
x(s)
= |sI − [A0 + U1 A1 + U2 A2 ]|−1 .A2 X, (41)
.2 (s)
u
-
V - - -
c1 (s) Vc1 (s) Vc2 (s) Vc2 (s)
-
Vc1 (s)
The transfer functions .1 (s) u
, . (s) , u. (s) , u. (s) , and - can be deduced, and the required VB
c2 (s)
u 1 1 2 V
controllers are then designed.
526
Energies 2018, 11, 3073
527
Figure 7. Block diagram of voltage balance control (VBC) schemes.
Energies 2018, 11, 3073
Parameter Value
Switching frequency 12.5 kHz
Inductance, ESR 9 mH, 0.1 Ω
Output capacitors 100 uF
Input voltage 15 Volts
Load 82 Ω
Diode’s forward voltage 0.5 Volts
528
Energies 2018, 11, 3073
VB control was implemented using the dSPACE 1104. After building the TLBDC VBC based on
real-time Simulink-blocks, including the dSPACE 1104 slave-PWM generator and analog to digital
(A/D) converters, the C code was automatically generated, downloaded and executed on the dSPACE
board. The 180◦ phase-shifted control signals were generated using the dSPACE 1104. The logic
signals were provided to an IR2110 gate driver that allowed for controlling the two TLBDC’s MOSFETs
(Metal–Oxide–Semiconductor Field-Effect Transistors). The dSPACE DS1104 ControlDesk monitor
software was used to visualize and save the experimental data. The implemented Matlab/Simulink
models on the dSPACE DS1104 board are shown in Figure 10, where Figure 10a illustrates the
implemented model when the VB was applied on the lower switch of TLBDC, and Figure 10b shows
the implemented model when the VB control was applied on both TLBDC switches. The VB controller,
indicated in Figure 10, was either a Fuzzy or PI controller whose parameters are shown in Figure 7.
(a)
(b)
Figure 10. Matlab/Simulink implemented model on the dSPACE DS1104 board: (a) VB control applied
on the TLBDC lower switch, and (b) VB control applied on either switche of the TLBDC.
Simulation and experimental results are depicted in Figures 11 and 12, respectively. Simulated
output capacitors’ voltages before and after applying the VB control at t = 0.025 s are presented in
Figure 11. Using a PI controller, the VB was approximately achieved in 5 ms and 15 ms when the
VBC was applied on both TLBDC switches, or only one, respectively. While the Fuzzy controller
ensured a VB within 3 ms and 10 ms when the VBC was applied on both switches or on the lower
switch, respectively. The same results could be deduced from experimental results presented in
Figure 12, where the VB control was applied at t = 0.05 s. The VB, using a PI controller, was achieved
in approximately 0.1 s and 0.3 s, when applying the VB control on both switches or one switch,
respectively. While it was approximately achieved, using a Fuzzy controller, within 0.08 s and 0.15 s
when the VB control was applied on both switches or on the lower switch, respectively.
529
Energies 2018, 11, 3073
(a) (b)
(c) (d)
Figure 11. Simulated output capacitors’ voltage curves after applying a balancing control at t = 0.025 s:
(a) on both switches using a PI VB controller, and (b) on the lower switch using a PI VB controller, (c) on
both switches using a Fuzzy VB controller, and (d) on the lower switch using a Fuzzy VB controller.
(a) (b)
(c) (d)
Figure 12. Experimental output capacitors’ voltage curves: (a) on both switches using a PI VB controller,
and (b) on the lower switch using a PI VB controller, (c) on both switches using a Fuzzy VB controller,
and (d) on the lower switch using a Fuzzy VB controller.
530
Energies 2018, 11, 3073
According to the previous results, static and dynamic behaviors of the proposed model are in
agreement with the experiments. The slight observed differences were mainly caused by the simplified
assumptions made in the analysis, the slight errors introduced by measuring instruments, etc.
By analyzing the obtained results from the VB control analysis, one can see that the experimental
results were in good agreement with the simulated ones. The differences observed in the VB controller’s
response times, in simulations and experiments, were mainly due to delays included by the digital to
analogue (D/A) conversions, the processing time for real time implementation, and the needed time
for the voltage average value calculation loop.
The analysis has shown that a VB was ensured in all cases. However, for both controllers,
applying the VB control on either of the TLBDC’s switches allows achieving the VB within a
reduced time compared to applying it on one switch only. This showed that the works presented in
References [29–33], where a VB control was applied on both TLBDC switches, have used an efficient
way to ensure a VB control. In addition, the Fuzzy VB controller showed better performances compared
to the PI controller, in terms of the requested time to ensure a VB for both cases as indicated in Table 3.
Author Contributions: Conceptualization, D.O.-A., S.D. and A.R.; Methodology, D.O.-A., S.D. and A.R.; Software,
D.O.-A., S.D. and A.R.; Validation, D.O.-A., S.D. and A.R.; Writing—Original Draft Preparation, D.O.-A.;
Writing—Review and Editing, D.O.-A., A.R. and S.D.; Supervision, S.D. and A.R.; Funding Acquisition, S.D. and A.R.
Funding: This work is performed in the framework of VERES Project funded by the Research Institute in Solar
Energy and New Energies (IRESEN).
Conflicts of Interest: The authors declare no conflict of interest.
531
Energies 2018, 11, 3073
References
1. Sun, Y.; Ma, L.; Zhao, D.; Ding, S. A Compound Controller Design for a Buck Converter. Energies 2018, 11, 2354.
[CrossRef]
2. Rashid, M.H. Power Electronics Handbook, 3rd ed.; Butterworth-Heinemann: Oxford, UK, 2011.
3. Monmasson, E. Power Electronic Converters-PWM Strategies and Current Control Techniques; ISTE Ltd.:
London, UK, 2011.
4. Gerard, V.P.; Eduard, A. CMOS Integrated Switching Power Converters; Springer: New York, NY, USA, 2009.
5. Reza Tousi, S.M.; Moradi, M.H.; Basir, N.S.; Nemati, M. A function-based maximum power point tracking
method for photovoltaic systems. IEEE Trans. Power Electron. 2016, 31, 2120–2128. [CrossRef]
6. Hossain, M.Z.; Rahim, N.A.; Selvaraj, J. A/L Recent progress and development on power DC-DC converter
topology, control, design and applications: A review. Renew. Sustain. Energy Rev. 2018, 81, 205–230. [CrossRef]
7. Patel, H.; Agarwal, V. Maximum power point tracking scheme for PV systems operating under partially
shaded conditions. IEEE Trans. Ind. Electron. 2008, 55, 1689–1698. [CrossRef]
8. Miao, K.; Ramachandaramurthy, V.K.; Yong, J.Y. Integration of electric vehicles in smart grid: A review on
vehicle to grid technologies and optimization techniques. Renew. Sustain. Energy Rev. 2016, 53, 720–732.
9. Goli, P.; Shireen, W. PV powered smart charging station for PHEVs. Renew. Energy 2014, 66, 280–287.
[CrossRef]
10. Torreglosa, J.P.; Fern, L.M.; García-trivi, P.; Jurado, F. Control and operation of power sources in a
medium-voltage direct- current microgrid for an electric vehicle fast charging station with a photovoltaic
and a battery energy storage system. Energy 2016, 115, 38–48.
11. El Aroudi, A.; Robert, B.; Martinez-Salamero, L. Modelling and analysis of multi-cell converters using
discrete time models. In Proceedings of the IEEE International Symposium on Circuits and Systems,
Island of Kos, Greece, 21–24 May 2006; pp. 2161–2164.
12. Zhang, Y.; Shi, J.; Fu, C.; Zhang, W.; Wang, P.; Li, J.; Sumner, M. An Enhanced Hybrid Switching-Frequency
Modulation Strategy for Fuel Cell Vehicle Three-Level DC-DC Converters with Quasi-Z Source. Energies
2018, 11, 1026. [CrossRef]
13. Hafez, A.A.A. Multi-level cascaded DC/DC converters for PV applications. Alex. Eng. J. 2015, 54, 1135–1146.
[CrossRef]
14. Zajec, P.; Nemec, M. Theoretical and Experimental Investigation of the Voltage Ripple across Flying
Capacitors in the Interleaved Buck Converter with Extended Duty Cycle. Energies 2018, 11, 1017. [CrossRef]
15. Chen, H.C.; Lin, W.J. MPPT and voltage balancing control with sensing only inductor current for
photovoltaic-fed, three-level, boost-type converters. IEEE Trans. Power Electron. 2014, 29, 29–35. [CrossRef]
16. Zhang, Y.; Sun, J.T.; Wang, Y.F. Hybrid boost three-level DC-DC converter with high voltage gain for
photovoltaic generation systems. IEEE Trans. Power Electron. 2013, 28, 3659–3664. [CrossRef]
17. Bougrine, M.D.; Benalia, A.; Benbouzid, M.H. Simple sliding mode applied to the three-level boost converter
for fuel cell applications. In Proceedings of the International Conference on Control, Engineering and
Information Technology, Tlemcen, Algeria, 25–27 May 2015; pp. 1–6.
18. Yaramasu, V.; Wu, B. Predictive control of a three-level boost converter and an NPC inverter for high-power
PMSG-based medium voltage wind energy conversion systems. IEEE Trans. Power Electron. 2014, 29,
5308–5322. [CrossRef]
19. Ruan, X.; Li, B.; Chen, Q.; Tan, S.C.; Tse, C.K. Fundamental considerations of three-level DC-DC converters:
Topologies, analyses, and control. IEEE Trans. Circuits Syst. I Regul. Pap. 2008, 55, 3733–3743. [CrossRef]
20. Ma, H.; Yang, C.; Zhang, Y.Y. Analysis and design for single-phase three-level boost PFC converter with
quasi-static model. In Proceedings of the 37th Annual Conference of the IEEE Industrial Electronics Society,
Melbourne, VIC, Australia, 7–10 November 2011; pp. 4385–4390.
21. Krishna, R.; Soman, D.E.; Kottayil, S.K.; Leijon, M. Pulse delay control for capacitor voltage balancing in a
three-level boost neutral point clamped inverter. IET Power Electron. 2015, 8, 268–277. [CrossRef]
22. Meleshin, V.; Sachkov, S.; Khukhtikov, S. Three-level boost converters. Modes, sub-modes and asymmetrical
regime of operation. In Proceedings of the 16th European Conf. on Power Electronics and Applications,
Lappeenranta, Finland, 26–28 August 2014; pp. 1–10.
532
Energies 2018, 11, 3073
23. Middlebrook, R.D.; Cuk, S. A general unified approach to modelling switching-converter power stages.
In Proceedings of the Power Electronics Specialists Conference, Cleveland, OH, USA, 8–10 June 1976;
pp. 18–34.
24. Khaldi, H.S.; Ammari, A.C. Fractional-order control of three level boost DC/DC converter used in hybrid
energy storage system for electric vehicles. In Proceedings of the 6th International Renewable Energy
Congress, Sousse, Tunisia, 24–26 March 2015; pp. 1–7.
25. Nouri, A.; Salhi, I.; Elwarraki, E.; El Beid, S.; Essounbouli, N. DSP-based implementation of a self-tuning
fuzzy controller for three-level boost converter. Electr. Power Syst. Res. 2017, 146, 286–297. [CrossRef]
26. Rivera, S.; Wu, B. Electric Vehicle Charging Station with an Energy Storage Stage for Split-DC Bus Voltage
Balancing. IEEE Trans. Power Electron. 2016, 32, 2376–2386. [CrossRef]
27. Tan, L.; Zhu, N.; Wu, B. An Integrated Inductor for Eliminating Circulating Current of Parallel Three-Level
DC–DC Converter-Based EV Fast Charger. IEEE Trans. Ind. Electron. 2016, 63, 1362–1371. [CrossRef]
28. Tan, L.; Wu, B.; Yaramasu, V.; Rivera, S.; Guo, X. Effective Voltage Balance Control for Bipolar-DC-Bus-Fed
EV Charging Station With Three-Level DC–DC Fast Charger. IEEE Trans. Ind. Electron. 2016, 63, 4031–4041.
[CrossRef]
29. Vitoi, L.A.; Krishna, R.; Soman, D.E.; Leijon, M.; Kottayil, S.K. Control and implementation of three level
boost converter for load voltage regulation. In Proceedings of the Industrial Electronics Society Conference,
Vienna, Austria, 10–13 November 2013; pp. 561–565.
30. Tan, L.; Wu, B.; Rivera, S.; Yaramasu, V. Comprehensive DC Power Balance Management in High-Power
Three-Level DC–DC Converter for Electric Vehicle Fast Charging. IEEE Trans. Power Electron. 2016, 31,
89–100. [CrossRef]
31. Xia, C.; Gu, X.; Shi, T.; Yan, Y. Neutral-Point Potential Balancing of Three-Level Inverters in Direct-Driven
Wind Energy Conversion System. IEEE Trans. Energy Convers. 2011, 26, 18–29. [CrossRef]
32. Oulad-Abbou, D.; Doubabi, S.; Rachid, A.; García-Triviño, P.; Fernández-Ramírez, L.M.; García-Vázquez, C.A.;
Sarrias-Mena, R. Combined control of MPPT, output voltage regulation and capacitors voltage balance
for three-level DC/DC boostconverter in PV-EV charging stations. In Proceedings of the International
Symposium on Power Electronics, Electrical Drives, Automation and Motion (SPEEDAM), Amalfi, Italy,
20–22 June 2018; pp. 372–376.
33. Costa, L.F.; Mussa, S.A.; Barbi, I. Capacitor voltage balancing control of multilevel DC-DC converter.
In Proceedings of the Brazilian Power Electronics Conference, Gramado, Brazil, 27–31 October 2013;
pp. 332–338.
34. Zhao, Q.; Fang, Y.; Ma, M.; Wang, J.; Xie, Y. Study on a Fuzzy Controller for the Balance of Capacitor Voltages
of Three-Level Boost Dc-Dc Converter. In Proceedings of the International Power Electronics and Application
Conference and Exposition (PEAC), Shanghai, China, 5–8 November 2014; pp. 993–996.
35. Mobarrez, M.; Ghanbari, N. Subhashish Bhattacharya Control Hardware-in-the-Loop Demonstration of a
Building-Scale DC Microgrid Utilizing Distributed Control Algorithm. In Proceedings of the PES General
Meeting 2018, Portland, OR, USA, 5–9 August 2018.
© 2018 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access
article distributed under the terms and conditions of the Creative Commons Attribution
(CC BY) license (http://creativecommons.org/licenses/by/4.0/).
533
MDPI
St. Alban-Anlage 66
4052 Basel
Switzerland
Tel. +41 61 683 77 34
Fax +41 61 302 89 18
www.mdpi.com