Nader-NDM2-400-MCCB
Nader-NDM2-400-MCCB
Page 1 of 8
0: Tripper (none)
2: Instantaneous tripper only
3: Complex tripper
Note 4 Operation mode:
No code is available for the direct handle-operated mode
P: Motor-operated
Z: Rotation handle
Note 5: Rated limit short-circuit breaking capacity level:
C: Basic type
L: Standard type
M: Relatively high breaking type
H: High breaking type
Page 2 of 8
Table 1: Comparison Table of Accessory Code:
Page 3 of 8
4. Main Technical Parameters
(1). Electrical characteristics
▲ Rated insulation voltage Ui: 1000V
▲ Rated working voltage Ue: AC 400V or AC 690V (only for Type M)
▲ Rated current of frame Inm: 400A
▲ Rated limit short-circuit breaking current Icu:
Type C: 35KA
Type L: 50KA
Type M: 65KA (AC 400V)
15KA (AC 690V)
Type H: 100KA
▲ Rated operating short-circuit breaking current Ics:
Type C: 26KA
Type L: 38KA
Type M: 49KA (AC 400V)
11KA (AC 690V)
Type H: 75KA
▲ Rated working current of the auxiliary contact: 0.4A
▲ The conventional thermal current of the auxiliary contact: 3A
(2). Operating performance
▲ With electricity: 7,500 times
▲ Without electricity: 10,000 times
(3). Connection capacity:
Rated current A 225 250 315, 350 400
Wire 95 120 185 240
cross-section area
mm2
4) Tightening torque value of terminal/mounting screw
M10 20
NDM2-400
M6 6
Page 4 of 8
5. Normal Working Environment
Normal Working Environment
▲ Altitude: ≤2000m.
▲ Ambient temperature: -35℃~+70℃.
▲ Pollution level: 3.
▲ The product can withstand the effects of wet air, salt mist and oil mist.
▲ The maximum gradient is 22.5°.
▲ The product can be disposed in places that are free from explosive media, media corrosive to metal,
insulation damaging gas, and conductive dust.
The product should be installed free from snow and rain.
6. Tripping Characteristics
Action time
Rated current
Page 5 of 8
7. Outline and Installation Dimensions
Connection
busbar
(optional)
Under-voltage release
3P
4P
Note: The limit deviation not indicated with the tolerance dimensions is as per GB/T 1804-m.
Page 6 of 8
Mounting distance (mm)
1) Insulation distance mounted in the metal cabinet (unit: mm), as shown below:
Note: Check the connected busbar or cable during rowing or stacki ng of the circuit breaker to
ensure that the air insulation distance won't be reduced.
3) Minimum center distance between stacked circuit breakers
H (distance of circuit breaker from bottom)
Specification
With a 0 arcing cover Without a 0 arcing cover
NDM2-400 155 155
Note: 1. Bare cable connection
2. Cable insulating connection
3. Connection without insulation
4. Check whether the 0 arcing cover or phase partition is
assembled properly before products are energized.
Page 7 of 8
8. Installation Mode
Installation mode: To be installed horizontally or vertically.
11. Precautions
▲ Various characteristics and accessories of the circuit breaker are set in the factory, which shall not be
adjusted randomly;
▲ The circuit breaker handle can be located in three positions, indicating three states: on, off and free
tripping. When the handle is in the free tripping position, pull the handle in the off direction when the
circuit breaker is connected and on.
Page 8 of 8