Product Specification of NDM2-400

Product Name:Molded Case Circuit Breaker


Product Model:NDM2-400
1. Applicable Scope and Purpose
NDM2 series of molded case products apply to infrequent switching of circuits with the AC 50Hz (or
60Hz), the rated working voltage of 690V and rated working current of 800A as well as infrequent motor
starting. With the overload, short circuit and undervoltage protection functions, the circuit breaker can protect
lines and power equipment from damage.

2. Picture of the Product

3. Specification and Model Description


ND M 2- 400 M /3 3 00 400A
Rated current of the circuit breaker (Note1)
Application code (Note 2)
Accessory code (Table 1)
Release code (Note 3)
Number of poles: 3
Operation mode (Note 4)
Rated limit short-circuit breaking capacity level
(Note 5)
Rated current of frame: 400A
Design code
Molded case circuit breaker (MCCB)
“Nader” brand low-voltage apparatus
Note 1: The rated current is: 225A, 250A, 315A, 350A, 400A.
Note 2: Application code: No code is available for the circuit breaker for distribution; the protection motor type is
represented as 2.
Note 3: Release code

Page 1 of 8
0: Tripper (none)
2: Instantaneous tripper only
3: Complex tripper
Note 4 Operation mode:
No code is available for the direct handle-operated mode
P: Motor-operated
Z: Rotation handle
Note 5: Rated limit short-circuit breaking capacity level:
C: Basic type
L: Standard type
M: Relatively high breaking type
H: High breaking type

Page 2 of 8
Table 1: Comparison Table of Accessory Code:

Page 3 of 8
4. Main Technical Parameters
(1). Electrical characteristics
▲ Rated insulation voltage Ui: 1000V
▲ Rated working voltage Ue: AC 400V or AC 690V (only for Type M)
▲ Rated current of frame Inm: 400A
▲ Rated limit short-circuit breaking current Icu:
Type C: 35KA
Type L: 50KA
Type M: 65KA (AC 400V)
15KA (AC 690V)
Type H: 100KA
▲ Rated operating short-circuit breaking current Ics:
Type C: 26KA
Type L: 38KA
Type M: 49KA (AC 400V)
11KA (AC 690V)
Type H: 75KA
▲ Rated working current of the auxiliary contact: 0.4A
▲ The conventional thermal current of the auxiliary contact: 3A
(2). Operating performance
▲ With electricity: 7,500 times
▲ Without electricity: 10,000 times
(3). Connection capacity:
Rated current A 225 250 315, 350 400
Wire 95 120 185 240
cross-section area
mm2
4) Tightening torque value of terminal/mounting screw

Thread Torque value


Rated current of frame
diameter (N·m)

M10 20
NDM2-400
M6 6

5 High-altitude derating factor


Altitude (km) Rated operating Maximum Rated power frequency
current operating voltage withstand voltage
2 In Ue U
2.5 In Ue U
3 0.980In 0.87Ue 0.909U
3.5 0.972In 0.846Ue 0.858U
4 0.963In 0.813Ue 0.820U
4.5 0.951In 0.781Ue 0.784U
5 0.938In 0.743Ue 0.752U

Page 4 of 8
5. Normal Working Environment
Normal Working Environment
▲ Altitude: ≤2000m.
▲ Ambient temperature: -35℃~+70℃.
▲ Pollution level: 3.
▲ The product can withstand the effects of wet air, salt mist and oil mist.
▲ The maximum gradient is 22.5°.
▲ The product can be disposed in places that are free from explosive media, media corrosive to metal,
insulation damaging gas, and conductive dust.
The product should be installed free from snow and rain.

6. Tripping Characteristics
Action time

Rated current

Page 5 of 8
7. Outline and Installation Dimensions

Connection
busbar
(optional)

Under-voltage release

Hole Dimensions of Front-plate Connection Mounting Plate

3P
4P

Note: The limit deviation not indicated with the tolerance dimensions is as per GB/T 1804-m.

Page 6 of 8
Mounting distance (mm)
1) Insulation distance mounted in the metal cabinet (unit: mm), as shown below:

Mounting A (inlet wire end to the


C (outlet
distance cabinet face) B (distance
wire end to
With a 0 from side to
Without a 0 the cabinet
Specification arcing cabinet)
arcing cover face)
cover
NDM2-400 25 120 35 35

2) Minimum center distance between rowed circuit breakers:


Width of circuit breaker
Center distance (mm)
Specification (mm)
3P 4P 3P 4P
NDM2-400 150 198 190 238

Note: Check the connected busbar or cable during rowing or stacki ng of the circuit breaker to
ensure that the air insulation distance won't be reduced.
3) Minimum center distance between stacked circuit breakers
H (distance of circuit breaker from bottom)
Specification
With a 0 arcing cover Without a 0 arcing cover
NDM2-400 155 155
Note: 1. Bare cable connection
2. Cable insulating connection
3. Connection without insulation
4. Check whether the 0 arcing cover or phase partition is
assembled properly before products are energized.

Page 7 of 8
8. Installation Mode
Installation mode: To be installed horizontally or vertically.

9. Packaging and Storage


Minimum packaging quantity: 1 piece/box. The packaged products should be stored in a warehouse with
the ambient temperature of -40℃~75℃ and the corresponding relative humidity below 80% without acidic,
alkali or other corrosive gas in the surrounding air. Under the conditions above, the storage period shall be no
more than 36 months since the manufacturing date.

10. List of Accessories and Installation


SN Name Specification Quantity/Set
Cross small pan-head
1 M6X70 4 (3P)/6 (4P)
screws
2. Plain washer 6 8(3P)/12 (4P)
3 Spring washer 6 4 (3P)/6 (4P)
4 Hexagon nut M6 4 (3P)/6 (4P)
5 Phase partition —— 4 (3P)/6 (4P)
6 Plug —— 6 (3P)/8 (4P)

11. Precautions
▲ Various characteristics and accessories of the circuit breaker are set in the factory, which shall not be
adjusted randomly;
▲ The circuit breaker handle can be located in three positions, indicating three states: on, off and free
tripping. When the handle is in the free tripping position, pull the handle in the off direction when the
circuit breaker is connected and on.

Page 8 of 8