ghjkl
ghjkl
A)
1
for safety in case of any disruptions, which can affect domestic
installations.
2
❖ Statutory Regulations commercial electrical installation
3
❖ Non-Statutory Regulations commercial electrical installation
4
❖ Comparisons Between Domestic and Commercial Regulations:
1. Safety Emphasis:
• In both domestic and commercial installations, safety is
paramount, but commercial systems often have stricter
requirements due to the higher complexity and risks involved.
2. Fire Safety:
• Fire risk is a larger concern in commercial installations, reflected
in statutory regulations such as the Fire Safety Order 2005,
while domestic installations rely more on Building Regulations
(Part P) to manage fire risks
4. Equipment Maintenance:
• PUWER applies to commercial installations, mandating regular
maintenance and inspections of work equipment, while
domestic regulations focus more on the safety of the installed
electrical system itself.
❖ Alternatives:
5
2. NFPA 70 (NEC):
• The National Electrical Code (NEC) in the USA could serve as an
alternative for international comparisons or for companies
operating under different jurisdictions.
3. CENELEC HD 60364:
• This European equivalent to BS 7671 could be considered for
installations in European contexts.
B)
❖ Fuses
1. Theory of Operation:
• Fuses protect
circuits by breaking the circuit
when current exceeds a certain
limit. The fuse element melts,
cutting off the current flow and thus
preventing damage to the circuit.
Fuses are designed with specific melting points to cater to
varying current ratings.
2. Construction:
• A fuse consists of a metal wire or strip (fuse element) housed
within a protective casing. The material and size of the fuse
element determine its current-carrying capacity and response
time. Fuses are single-use components, requiring replacement
after each operation.
6
3. Application in BS 7671:
• BS 7671 specifies fuse ratings, selection, and installation
requirements, ensuring they suit the current-carrying capacity
of circuits they protect, aligning with regulations on preventing
thermal and electrical hazards.
1. Theory of Operation:
• RCDs detect earth
faults by measuring
the current
difference between
the live and neutral conductors. Any imbalance suggests
current leakage, possibly through a person or faulty insulation,
prompting the RCD to break the circuit.
2. Construction:
• An RCD includes a toroidal transformer, a trip mechanism, and
live and neutral conductors passing through the transformer
core. When leakage occurs, an imbalance in the magnetic field
activates the trip mechanism, disconnecting the circuit.
3. Application in BS 7671:
• BS 7671 mandates the use of RCDs for circuits at high risk of
earth faults, such as sockets accessible to users. RCDs must
have suitable ratings and sensitivity levels to ensure prompt
and effective protection, per regulatory standards.
7
❖ Miniature Circuit Breakers (MCBs)
1. Theory of Operation:
• Miniature circuit breakers
protect circuits from over
currents and short circuits by
interrupting the current flow.
They are resettable devices, meaning they can be manually
reset after tripping, unlike fuses that need replacement.
2. Construction:
• An MCB contains both a thermal and a magnetic mechanism.
The thermal mechanism consists of a bimetallic strip that bends
and trips the circuit breaker under overload conditions. The
magnetic mechanism uses an electromagnet that responds
quickly to large, sudden current surges (e.g., short circuits),
instantly tripping the breaker.
3. Application in BS 7671:
• BS 7671 outlines MCB selection and installation criteria to
match circuit characteristics. It specifies MCB ratings and trip
settings to protect against specific circuit overloads and short
circuits, aligning with safety requirements.
c)
❖ TN-C System
8
1. Description:
• In a TN-C (Terre-Neutral Combined) system, the neutral (N) and
earth (PE) conductors are combined into a single PEN
(Protective Earth-Neutral) conductor throughout the system.
2. Sketch:
• One single PEN conductor runs from the power source to the
load, acting as both the neutral and earth conductor.
3. Use:
• Often used in older systems but less common now due to
potential safety risks associated with the combined conductor.
❖ TT System
1. Description:
• In a TT (Terre-Terre) system, the neutral is grounded at the
transformer, but the customer’s installation uses a separate
local earth electrode for protection. The installation’s earth is
not connected back to the supply earth.
9
2. Sketch:
• The source is grounded separately at the transformer, while the
customer has a separate earth electrode connected to their
installation.
3. Use:
• Common in rural or isolated areas and where utility earth
reliability may be uncertain.
❖ TN-C-S System
1. Description:
• The TN-C-S (Terre-Neutral Combined-Separated) system is a
combination of the TN-C and TN-S systems. It has a combined
PEN conductor from the supply transformer to the building, and
at the building’s entry point, it separates into PE (earth) and N
(neutral) conductors.
2. Sketch:
• A PEN conductor is used up to the main distribution board,
where it splits into separate PE and N conductors.
3. Use:
• Common in modern installations due to enhanced safety.
10
❖ EEBADOS (Earthed Equipotential Bonding and Automatic Disconnection
of Supply)
1. Description:
• EEBADOS is a safety approach involving equipotential bonding
and automatic disconnection of the supply to minimize electric
shock hazards. This system ensures all accessible metal parts
are bonded to a common earth potential and that
disconnection occurs automatically when fault conditions are
detected.
2. Sketch:
• Equipotential bonding conductors connect all exposed metal
parts to the main earth, and disconnection is achieved through
protective devices like RCDs.
3. Use:
• Commonly implemented in installations for enhanced shock
protection
❖ Equipment Classes
1. Class II Equipment:
• Double-insulated equipment that doesn’t rely on a safety earth
connection. The equipment has additional insulation layers or
reinforced insulation to protect against electric shocks.
- Sketch:
• Symbolized by a square within a square on the equipment,
indicating double insulation.
11
- Use:
• Often used for portable or handheld equipment, reducing
reliance on earth safety.
- Sketch:
• Indicated by the Roman numeral “III” on the equipment and
doesn’t require protective earth.
- Use:
• Typically found in devices like toys and medical equipment
where very low voltages ensure user safety.
12
❖ Areas of Increased Risk
13
5. Correct Placement: Ensure that sockets are positioned outside of
Zones 0, 1, and 2, and use pull-cord switches for lighting within
these zones.
2. Lighting:
14
❖ Zoning Requirements
2. Zone 1: The area immediately above and around the shower basin,
up to 2.25 meters from the floor. In this zone, only equipment rated
IPX4 or higher can be installed, and equipment such as electric
showers must be protected by an RCD (Residual Current Device)
with a rating of 30mA or less.
15
3. Zone 2: Extends 0.6 meters horizontally outside Zone 1 and up to
2.25 meters above the floor. Equipment here must also be rated
IPX4 or higher, and any electrical outlets must be shaver sockets or
specifically designed for wet areas.
16