HBTR-451

Bubble Tight Isolation Damper

Application
The HBTR-451 is an isolation damper designed for isolation
and decontamination applications. The damper has bubble tight
leakage performance per AMCA 500-D up to 30 in. wg (7.5 kPa).
The damper frame is flanged for easy mounting and the blade
seal is mechanically fastened to the blade.

Ratings
Velocity
6500 fpm (33 m/s)
Pressure
30 in. wg (7.5 kPa) - differential pressure
Leakage
Bubble tight per AMCA 500-D *Actual Inside Dimension

Temperature*
-40 to 250°F (-40 to 121°C)

Construction Size Limitations


Standard Optional WxH Minimum Size Maximum Size
Frame Depth (C) See chart on page 2 Inches 6 48
Frame Material Painted steel 304SS, 316SS mm 152 1219
Frame Type Flanged Channel
Frame
Thickness
See chart on page 2 Options:
Flange Width (D) see chart on page 2 • Mounting holes in flanges
• Actuators
Blade Material Painted steel 304SS, 316SS
• Limit switches
Blade Seals Silicone rubber, field removable • Special construction
Blade Thickness see chart on page 2 • Temperatures greater than 250°F (121°C), consult factory.
Blade Type Reinforced butterfly, field replaceable
Blade Stop Pin stop
Axle Diameter see chart on page 2
Axle Bearings Relubricable ball, outboard mounting
Axle Material Plated steel 303SS, 316SS
Axle Seals Double gland stuffing box
Industrial Epoxy,
Paint Finishes Hi Pro Polyester Mill finish
(304SS or 316SS)
On centerline,
Mounting Holes None
Straddle centerline

HBTR-451 September 2024


Dimensions

Diameter (D) Frame Frame Flange Axle Blade


Inches (mm) Depth J & Width F Diameter Thickness
Flange
Inches Inches Inches gauge Flange
Above Through gauge Width (F)
(mm) (mm) (mm) (mm) (mm)
5.906 12 6 12 1.5 0.75 12
(150) (305) (152) (2.7) (38) (19) (2.7)
12 18 8 10 1.5 .75 10
(305) (457) (203) (3.5) (38) (19) (3.5) Diameter (D)
18 24 8 10 1.5 1 10
(457) (610) (203) (3.5) (38) (25) (3.5)
24 27 8 .188 2 1 10
(610) (686) (203) (4.8) (51) (25) (3.5) Frame
Depth (J)
27 35 8 .188 2 1.25 10
(686) (889) (203) (4.8) (51) (32) (3.5)
35 39 8 .188 2 1.25 10
(889) (991) (203) (4.8) (51) (32) (3.5)
39 42 8 .188 2 1.5 10
(991) (1067) (203) (4.8) (51) (38) (3.5)
42 48 8 .25 2 1.5 .188
(1067) (1219) (203) (6) (51) (38) (4.8)

Mounting Holes
Standard - Does not include mounting holes
Optional - Bolt holes in both flanges
Greenheck recommended bolt hole pattern is shown in the table below. Customer must specify bolt holes that are parallel to the axle
centerline (P) or that straddle the axle centerline (S) as shown in the diagrams below. Greenheck can also provide bolt hole sizes and
patterns other than those shown below.

Greenheck Recommended Bolt Hole Pattern


(Bolt Holes Parallel to Axle Centerline)
Diameter Inches Mounting
(mm) Bolt
Hole Circle Degrees
Number
Diameter Diameter Between
of Holes
Above Through in. (mm) Holes
L
N
6 8 3
⁄8
4 * 90
(152) (203) (9.5)
8.001 18 7
⁄16
8 * 45
(203) (457) (11)
18.001 24 7
⁄16
12 * 30
(457) (610) (11)
24.001 36 7
⁄16
16 * 221⁄2
(610) (914) (11)
36.001 48 7
⁄16
24 * 15
(914) (1219) (11)
* Bolt Circle Diameter = Damper Diameter + Flange Height + 1⁄4 in. (6mm)

On Centerline Straddle Centerline

HBTR-451 September 2024


Performance Data
Pressure Drop Data
This pressure drop data was conducted in accordance with AMCA 500-D using Test Figure 5.3. All data has been corrected to
represent standard air at a density of 0.075 lb/ft3 (1.2 kg/m3).
Actual pressure drop found in any HVAC system is a combination of many factors. This pressure drop information along with an
analysis of other system influences should be used to estimate actual pressure losses for a damper installed in a given HVAC system.

AMCA Test Figure 5.3


Figure 5.3 illustrates a fully ducted damper. This configuration
has low pressure drop because entrance and exit losses are
minimized by straight duct runs upstream and downstream of the
damper.

4D 6D

36 in. (914mm) Diameter 36 x 36 in. square duct

Leakage
Every HBTR-451 is leakage tested at 30 in. wg (7.5 KPa) in accordance with AMCA 500-D before it leaves the factory. Greenheck
does not ship a HBTR-451 unless it meets the requirements of the standard.

Axle Seal Detail Bearing Detail


The double gland axle seal is mounted externally for easy access The ball bearings are mounted outboard for easy access. The
and provides bubble tight performance. bearing comes with a grease fitting, allowing for easy lubrication
(axle seals included but not shown in bearing detail).

HBTR-451 September 2024r


HBTR-451
Document Links Bubble Tight Isolation Damper

INSTALLATION TRI-FOLD SUPPLEMENT


INFORMATION

CATALOG SELECTION GUIDE PRODUCT INFO

DAMPER SELECTION SPECIFICATIONS WARRANTY


GUIDE

Copyright ® 2024 Greenheck Fan Corporation


HBTR-451, R16, September 2024
Greenheck Fan Corporation reserves the right to make
product changes without notice