Data sheet 6AG1221-1BH32-2XB0
SIPLUS S7-1200 SM 1221 16DI based on 6ES7221-1BH32-0XB0 with conformal
coating, -40…+70 °C, start up -25 °C, digital input 16 DI, 24 V DC, sink/source
General information
Product type designation SM 1221, DI 16x24 V DC
Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
Input current
from backplane bus 5 V DC, max. 130 mA
Digital inputs
● from load voltage L+ (without load), max. 4 mA; per channel
output voltage / header
supply voltage of the transmitters / header
● product function / supply voltage for transmitters Yes
Power loss
Power loss, typ. 2.5 W
Digital inputs
Number of digital inputs 16
● in groups of 4
Input characteristic curve in accordance with IEC 61131, type 1 Yes
Number of simultaneously controllable inputs
all mounting positions
— up to 40 °C, max. 16
horizontal installation
— up to 40 °C, max. 16
— up to 50 °C, max. 16
vertical installation
— up to 40 °C, max. 16
Input voltage
● Rated value (DC) 24 V
● for signal "0" 5 V DC at 1 mA
● for signal "1" 15 V DC at 2.5 mA
Input current
● for signal "0", max. (permissible quiescent current) 1 mA
● for signal "1", min. 2.5 mA
● for signal "1", typ. 4 mA
Input delay (for rated value of input voltage)
for standard inputs
— parameterizable Yes; 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in
groups of four
6AG12211BH322XB0 Subject to change without notice
6/20/2023
Page 1/3 © Copyright Siemens
for interrupt inputs
— parameterizable Yes
Cable length
● shielded, max. 500 m
● unshielded, max. 300 m
Interrupts/diagnostics/status information
Diagnostics function Yes
Alarms
● Diagnostic alarm Yes
Diagnoses
● Monitoring the supply voltage Yes
Diagnostics indication LED
● for status of the inputs Yes
● for maintenance Yes
Potential separation
Potential separation digital inputs
● between the channels, in groups of 4
Degree and class of protection
IP degree of protection IP20
Ambient conditions
Free fall
● Fall height, max. 0.3 m; five times, in product package
Ambient temperature during operation
● min. -40 °C; = Tmin (incl. condensation/frost); start-up @ -25 °C
● max. 70 °C; = Tmax; Tmax > +60 °C number of simultaneously activated inputs 8 (no
adjacent points) for horizontal mounting position
● At cold restart, min. -25 °C
Ambient temperature during storage/transportation
● min. -40 °C
● max. 70 °C
Altitude during operation relating to sea level
● Installation altitude above sea level, max. 5 000 m
● Ambient air temperature-barometric pressure-altitude Tmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax
- 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K)
at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
Relative humidity
● With condensation, tested in accordance with IEC 60068- 100 %; RH incl. condensation/frost (no commissioning under condensation
2-38, max. conditions)
Resistance
Coolants and lubricants
— Resistant to commercially available coolants and Yes
lubricants
Use in stationary industrial systems
— to biologically active substances according to EN Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna);
60721-3-3 Class 3B3 on request
— to chemically active substances according to EN Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity
60721-3-3 degree 3); *
— to mechanically active substances according to EN Yes; Class 3S4 incl. sand, dust, *
60721-3-3
Use on ships/at sea
— to biologically active substances according to EN Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on
60721-3-6 request
— to chemically active substances according to EN Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity
60721-3-6 degree 3); *
— to mechanically active substances according to EN Yes; Class 6S3 incl. sand, dust; *
60721-3-6
Usage in industrial process technology
— Against chemically active substances acc. to EN Yes; Class 3 (excluding trichlorethylene)
60654-4
— Environmental conditions for process, measuring Yes; Level GX group A/B (excluding trichlorethylene; harmful gas
and control systems acc. to ANSI/ISA-71.04 concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level
LC3 (salt spray) and level LB3 (oil)
Remark
— Note regarding classification of environmental * The supplied plug covers must remain in place over the unused interfaces
conditions acc. to EN 60721, EN 60654-4 and during operation!
6AG12211BH322XB0 Subject to change without notice
6/20/2023
Page 2/3 © Copyright Siemens
ANSI/ISA-71.04
Conformal coating
● Coatings for printed circuit board assemblies acc. to EN Yes; Class 2 for high reliability
61086
● Protection against fouling acc. to EN 60664-3 Yes; Type 1 protection
● Military testing according to MIL-I-46058C, Amendment 7 Yes; Discoloration of coating possible during service life
● Qualification and Performance of Electrical Insulating Yes; Conformal coating, Class A
Compound for Printed Board Assemblies according to IPC-
CC-830A
connection method
required front connector Yes
Mechanics/material
Enclosure material (front)
● Plastic Yes
Dimensions
Width 45 mm
Height 100 mm
Depth 75 mm
Weights
Weight, approx. 210 g