The facilities include electrical equipment including all distribution, control and
other related systems, such as lighting, grounding.
The design, performance, testing and inspection for equipment covered by this
project will comply with relevant recommendations, established by the
International Electro technical Commission (IEC).
Continuity of service, taking into accounts the internal failures and external
failures.
The main power distribution plant will be from two electric generators 5.5 KV.
1.3.1 5, 5 KV Distribution
The 400V switchboard is configured three sections of bus bars (A, B and E), each
with an incoming circuit breaker, and with interconnecting bus-ties. The bus bars
E shall be used for essential loads. The incoming from transformers TRA-002A/B
is NC and the incomer from Emergency Diesel Generator is NO.
In the normal operating, one bus ties is NC .and the other is NO (depending the
choice of operating mode)
In case of break down of one transformer, the other will supply all the three bus
bars (The two bus ties are NC)
In case of loss of normal power (from the two transformers), the two bus ties will
open and the Emergency Diesel Generator will supply the “E” bus bar only
(emergency bus bar).
Two diesel generator 4 MVA will be installed in this project. The main
characteristics of generators are:
Type: Compact, open for indoor
Power: 4 MVA (regime continues)
Overload: 10% for one hour twelve
Frequency: 50 Hz
Speed: 1500t/mn (auto regulated)
Voltage: 5,5KV vacuum
Mode: Three phase
Cos φ: 0,8
Excitation: self-excited
Equipped with control panel
1.4.2 5, 5 KV Switchgear
Two three phase transformers hermitical solid type, naturally cooled ONAN, for
indoor installation will be installed in this project. The conditions of service will
be compliant CEI354,
The oil used should be compliant HN27-S-02, NF C27 - 101 and IEC 296.
The transformers will be equipped with the following accessories:
- A control switch off ± 2x2, 5%
- DGPT2
- Display of the level of dielectric,
- Thermometer,
- Plug-HT terminals,
- Cover BT
- Acquisition of land
- Nameplates,
- Any other useful adjunct filling, emptying, etc.....
Fréquence: 50 Hz.
Temp. Ambiante maximale: 50°C
Couplage: Dyn11.
In the event of loss of normal power, the EDG shall start automatically to provide
power supplies to consumers designated as Essential Loads.
The EDG shall be capable of starting from a black start condition and shall be
provided with routine facilities to simulate and test auto-start.
During such test, the generators shall run at load, synchronized with the normal
main supply.
When the normal supply is restored, a temporary parallel through EDG and the
normal main supply will be foreseen.
Automatic transfer schemes shall be provided at the 30kV, 5.5kV and 0.4kV
switchgear in order to switch loads to an alternative feeder in case of failure, or
(only for 0.4kV switchgear) to switch on Emergency Diesel Generator.
Frequency: 50 Hz
Cos φ : 0,8
Excitation: self-excited
Supply and installation of arrays of solar energy units rated 12 volts and with
sufficient capacity c/w all necessary batteries, inverters, accessories, container,
fencing, in order to meet the required power supply for:
Chemical dosing pumps at Alkabir Field Satellite
C.P system for the 10” trunk line
C.P system for the ten (10) 4” flow lines
The solar Energy Unit rated 12 V and with a battery cc: type stationary, sealed
lead acid and maintenance free.
A minimum capacity of 200 Ah batteries.
The charge regulator must ensure the protection of equipment and protect the
battery against deep discharge. The charge regulator must be equipped with
warning lights operating status of batteries will be installed on a stand at the
bottom of the envelope outside the box.