Elsewedy Cables
Elsewedy Cables
Cables
Operating Voltage
(up to 1.8/3 kV)
Cable Construction
1. Conductor Armouring of Single Core Cable
Copper or Aluminium conductors, 1. Armouring by non-magnetic material
solid stranded or e ible ith round or either Aluminium Tape or Aluminium
sectoral shaped conductors. Wire armouring to reduce the magnetic
losses.
2. Insulation 2. If it is required for single core cable to
An extruded layer of PVC or XLPE is be armoured by steel wire armouring,
applied over the conductor. the magnetic circuit around the single
PVC insulated cables are suitable core cable should be interrupted
for maximum conductor operating by inserting insulated copper wires
temperature of 70ºC or 85ºC and 90ºC between the steel wires.
for XLPE.
3. Assembly
In case of multicore cables’ cores
are assembled together using non
h grosco ic filler if needed to fill
space between cores, wrapped with
suitable binder tape to form a round
cable.
4. Bedding
In case of armoured cables an
extruded layer of PVC or other material
is applied as bedding.
5. Armouring
a. Steel Tape: Double layers of steel
tapes are applied helically with gap.
b. Steel Wire: Galvanized steel wires
are applied helically.
6. Sheath
An extruded layer of PVC is applied as
an outer sheath, or according to the Armouring of Single Core Cable
client special requirements. Figure
Option
Lead Sheath: Upon request a layer of
lead is extruded over the bedding layer.
Low Voltage Cables
Description
•Soft annealed stranded Copper conductors insulated with PVC compound rated 70 °C or 90 °C
according to C .
Application
• or indoor fi ed installations in dr locations laid in conduits as ell as in steel su ort brac ets.
mm2 m m A A mm Kg/Km
CPD-S001-U04 1.5 RE 12.1 14.6 20 15 2.8 20
CPD-T001-U04 1.5 RM 12.1 14.6 20 15 3 21
CPD-S001-U05 2 RE 9.15 10.9 22 17 3.2 27
CPD-T001-U05 2 RM 9.15 10.9 22 17 3.4 28
CPD-S001-U06 2.5 RE 7.41 8.89 28 22 3.4 31
CPD-T001-U06 2.5 RM 7.41 8.89 28 22 3.6 33
CPD-S001-U07 3 RE 6.1 7.41 31 24 3.6 36
CPD-T001-U07 3 RM 6.1 7.41 31 24 3.8 39
CPD-S001-U08 4 RE 4.61 5.51 37 26 3.9 46
CPD-T001-U08 4 RM 4.61 5.51 37 26 4.1 49
CPD-S001-U09 6 RE 3.08 3.68 46 33 4.4 66
CPD-T001-U09 6 RM 3.08 3.68 46 33 4.7 70
CPD-T001-U10 10 RM 1.83 2.17 66 47 5.8 109
CPD-T001-U11 16 RM 1.15 1.37 87 62 6.8 166
CPD-T001-U12 25 0.727 0.8600 118 81 8.8 278
CPD-T001-U13 35 0.524 0.6300 147 100 9.9 371
CPD-T001-U14 50 0.387 0.4600 197 122 11.8 514
CPD-T001-U15 70 0.268 0.3200 230 151 13.5 711
CPD-T001-U16 95 0.193 0.2300 289 191 15.7 967
CPD-T001-U17 120 0.153 0.1900 337 219 17.4 1240
CPD-T001-U18 150 0.124 0.1500 385 252 19.4 1500
CPD-T001-U19 185 0.0991 0.1200 449 288 21.5 1852
CPD-T001-U20 240 0.0754 0.0920 542 345 24.7 2457
CPD-T001-U30 300 0.0601 0.0750 621 391 27.2 2977
The above data is approximate and subjected to manufacturing tolerance.
re : round, Solid
rm : round, Stranded
Description
oft annealed Co er fine ires bunched together in subunits or stranded bunched grou s into a main
units hich forms the e ible conductor. nsulated ith soft C C or C Com ound.
•Cables are produced according to IEC 60227 or BS EN 50525-2-31.
Application
or indoor fi ed installations in dr locations here articular e ibilit is re uired. or electrical anels
connection or for electrical apparatus they can be laid in groups around steel sheets.
mm2 mm m m A A mm Kg/Km
CPD-F001-U04 1.5 0.26 13.3 15.9 20 15 3 20
CPD-F001-U06 2.5 0.26 7.98 9.56 28 22 3.7 31
CPD-F001-U08 4 0.31 4.95 5.93 37 26 4.2 44
CPD-F001-U09 6 0.31 3.3 3.95 46 33 4.7 62
CPD-F001-U10 10 0.41 1.91 2.29 66 47 6.2 108
CPD-F001-U11 16 0.41 1.21 1.45 87 62 7.2 162
CPD-F001-U12 25 0.41 0.78 0.9400 118 81 9.5 276
CPD-F001-U13 35 0.41 0.554 0.6630 147 100 11.0 375
CPD-F001-U14 50 0.41 0.386 0.4620 179 122 12.6 542
CPD-F001-U15 70 0.51 0.272 0.3260 230 151 14.6 733
CPD-F001-U16 95 0.51 0.206 0.2470 289 191 16.8 957
CPD-F001-U17 120 0.51 0.161 0.1930 337 219 18.9 1243
CPD-F001-U18 150 0.51 0.129 0.1550 385 252 21.2 1548
CPD-F001-U19 185 0.51 0.106 0.1270 449 288 23.4 1895
CPD-F001-U20 240 0.51 0.0801 0.0960 542 345 26.7 2400
The above data is approximate and subjected to manufacturing tolerance.
Description
•Soft annealed stranded Copper conductor. Insulated with PVC compound rated 70 °C and sheathed
with PVC Compound layer.
•Cables are produced according to IEC 60502.
Application
•For outdoor and indoor installations in damp and wet locations. They are normally used for power
distribution in urban networks, industrial plants, as well as in thermopower and hydropower stations.
1 Core - Cu/PVC/PVC
mm2 m m A A A A A A mm Kg/Km
CP1-T101-U08 4 4.61 5.51 53 53 38 50 37 35 7.1 87
CP1-T101-U09 6 3.08 3.68 65 66 47 65 48 46 7.6 113
CP1-T101-U10 10 1.83 2.17 88 89 62 89 9 62 8.3 154
CP1-T101-U11 16 1.15 1.37 113 113 77 108 85 79 9.3 216
CP1-T101-U12 25 0.727 0.8701 143 144 101 143 112 109 10.6 320
CP1-T101-U13 35 0.524 0.6273 171 173 123 176 138 134 11.7 410
CP1-T101-U14 50 0.387 0.4635 203 205 148 214 170 165 13.4 545
CP1-T101-U15 70 0.268 0.3214 248 252 183 271 215 209 15 745
CP1-T101-U16 95 0.193 0.232 296 301 224 332 267 259 17.1 1020
CP1-T101-U17 120 0.153 0.1845 337 342 255 386 310 301 18.5 1260
CP1-T101-U18 150 0.124 0.1501 378 383 292 442 357 347 20.5 1550
CP1-T101-U19 185 0.0991 0.1207 426 433 333 510 415 402 22.8 1925
CP1-T101-U20 240 0.0754 0.0931 494 501 393 608 496 481 25.8 2500
CP1-T101-U30 300 0.0601 0.0755 556 565 450 704 575 558 28.8 3110
CP1-T101-U40 400 0.047 0.0608 629 639 516 819 669 648 32 3975
CP1-T101-U50 500 0.0366 0.0495 709 721 594 957 777 753 36 5080
CP1-T101-U60 630 0.0283 0.041 792 807 672 1113 893 864 39.7 6385
CP1-T101-U70 800 0.0221 0.035 874 891 753 1284 1014 982 44.2 8260
CP1-T101-U80 1000 0.0176 0.0308 956 975 845 1478 1154 1116 51.7 10345
The above data is approximate and subjected to manufacturing tolerance.
Description
•Multicore cables of stranded Copper conductors are insulated with XLPE compound, assembled
together and covered with an overall jacket of PVC compound.
•Cables are produced according to IEC 60502.
Application
•For outdoor and indoor installations in damp and wet locations. They are normally used for power
distribution in urban networks, in industrial plants, as well as in Thermopower and Hydropower Stations.
Cont'd
Description
•Multicore cables of stranded Copper conductors are insulated with PVC compound rated 70°C,
assembled together, covered with overall jacket of PVC compound.
•Cables are produced according to IEC 60502.
Application
•For outdoor and indoor installations in damp and wet locations.
Cont'd