Low Voltage

Cables
Operating Voltage
(up to 1.8/3 kV)
Cable Construction
1. Conductor Armouring of Single Core Cable
Copper or Aluminium conductors, 1. Armouring by non-magnetic material
solid stranded or e ible ith round or either Aluminium Tape or Aluminium
sectoral shaped conductors. Wire armouring to reduce the magnetic
losses.
2. Insulation 2. If it is required for single core cable to
An extruded layer of PVC or XLPE is be armoured by steel wire armouring,
applied over the conductor. the magnetic circuit around the single
PVC insulated cables are suitable core cable should be interrupted
for maximum conductor operating by inserting insulated copper wires
temperature of 70ºC or 85ºC and 90ºC between the steel wires.
for XLPE.
3. Assembly
In case of multicore cables’ cores
are assembled together using non
h grosco ic filler if needed to fill
space between cores, wrapped with
suitable binder tape to form a round
cable.
4. Bedding
In case of armoured cables an
extruded layer of PVC or other material
is applied as bedding.
5. Armouring
a. Steel Tape: Double layers of steel
tapes are applied helically with gap.
b. Steel Wire: Galvanized steel wires
are applied helically.
6. Sheath
An extruded layer of PVC is applied as
an outer sheath, or according to the Armouring of Single Core Cable
client special requirements. Figure
Option
Lead Sheath: Upon request a layer of
lead is extruded over the bedding layer.
Low Voltage Cables

450/750 V Indoor wires

Single Core Cables with Stranded


Copper Conductors and PVC Insulated

Description
•Soft annealed stranded Copper conductors insulated with PVC compound rated 70 °C or 90 °C
according to C .
Application
• or indoor fi ed installations in dr locations laid in conduits as ell as in steel su ort brac ets.

Nominal Max. Conductor Resistance Current Rating in Air


Approx.
Cross Approx.
DC at AC at Overall
Product - code Sectional Free In Pipes Weight
20 °C 70 °C Diameter
Area

mm2 m m A A mm Kg/Km
CPD-S001-U04 1.5 RE 12.1 14.6 20 15 2.8 20
CPD-T001-U04 1.5 RM 12.1 14.6 20 15 3 21
CPD-S001-U05 2 RE 9.15 10.9 22 17 3.2 27
CPD-T001-U05 2 RM 9.15 10.9 22 17 3.4 28
CPD-S001-U06 2.5 RE 7.41 8.89 28 22 3.4 31
CPD-T001-U06 2.5 RM 7.41 8.89 28 22 3.6 33
CPD-S001-U07 3 RE 6.1 7.41 31 24 3.6 36
CPD-T001-U07 3 RM 6.1 7.41 31 24 3.8 39
CPD-S001-U08 4 RE 4.61 5.51 37 26 3.9 46
CPD-T001-U08 4 RM 4.61 5.51 37 26 4.1 49
CPD-S001-U09 6 RE 3.08 3.68 46 33 4.4 66
CPD-T001-U09 6 RM 3.08 3.68 46 33 4.7 70
CPD-T001-U10 10 RM 1.83 2.17 66 47 5.8 109
CPD-T001-U11 16 RM 1.15 1.37 87 62 6.8 166
CPD-T001-U12 25 0.727 0.8600 118 81 8.8 278
CPD-T001-U13 35 0.524 0.6300 147 100 9.9 371
CPD-T001-U14 50 0.387 0.4600 197 122 11.8 514
CPD-T001-U15 70 0.268 0.3200 230 151 13.5 711
CPD-T001-U16 95 0.193 0.2300 289 191 15.7 967
CPD-T001-U17 120 0.153 0.1900 337 219 17.4 1240
CPD-T001-U18 150 0.124 0.1500 385 252 19.4 1500
CPD-T001-U19 185 0.0991 0.1200 449 288 21.5 1852
CPD-T001-U20 240 0.0754 0.0920 542 345 24.7 2457
CPD-T001-U30 300 0.0601 0.0750 621 391 27.2 2977
The above data is approximate and subjected to manufacturing tolerance.
re : round, Solid
rm : round, Stranded

58 Power Cables Division


Low Voltage Cables

Single Core Cables with Flexible


Copper Conductors and PVC Insulated

Description
oft annealed Co er fine ires bunched together in subunits or stranded bunched grou s into a main
units hich forms the e ible conductor. nsulated ith soft C C or C Com ound.
•Cables are produced according to IEC 60227 or BS EN 50525-2-31.
Application
or indoor fi ed installations in dr locations here articular e ibilit is re uired. or electrical anels
connection or for electrical apparatus they can be laid in groups around steel sheets.

Nominal Max. Conductor Resistance Current Rating in Air


Maximum Approx.
Cross Approx.
Diameter DC at AC at Overall
Product - code Sectional of Wires Free In Pipes Diameter
Weight
Area 20 °C 70 °C

mm2 mm m m A A mm Kg/Km
CPD-F001-U04 1.5 0.26 13.3 15.9 20 15 3 20
CPD-F001-U06 2.5 0.26 7.98 9.56 28 22 3.7 31
CPD-F001-U08 4 0.31 4.95 5.93 37 26 4.2 44
CPD-F001-U09 6 0.31 3.3 3.95 46 33 4.7 62
CPD-F001-U10 10 0.41 1.91 2.29 66 47 6.2 108
CPD-F001-U11 16 0.41 1.21 1.45 87 62 7.2 162
CPD-F001-U12 25 0.41 0.78 0.9400 118 81 9.5 276
CPD-F001-U13 35 0.41 0.554 0.6630 147 100 11.0 375
CPD-F001-U14 50 0.41 0.386 0.4620 179 122 12.6 542
CPD-F001-U15 70 0.51 0.272 0.3260 230 151 14.6 733
CPD-F001-U16 95 0.51 0.206 0.2470 289 191 16.8 957
CPD-F001-U17 120 0.51 0.161 0.1930 337 219 18.9 1243
CPD-F001-U18 150 0.51 0.129 0.1550 385 252 21.2 1548
CPD-F001-U19 185 0.51 0.106 0.1270 449 288 23.4 1895
CPD-F001-U20 240 0.51 0.0801 0.0960 542 345 26.7 2400
The above data is approximate and subjected to manufacturing tolerance.

Power Cables Division 59


Low Voltage Cables

0.6/1 (1.2) KV Single Core Unarmoured Cables

Single Core Cables, with Stranded


Circular Copper Conductors,
PVC Insulated and PVC Sheathed

Description
•Soft annealed stranded Copper conductor. Insulated with PVC compound rated 70 °C and sheathed
with PVC Compound layer.
•Cables are produced according to IEC 60502.
Application
•For outdoor and indoor installations in damp and wet locations. They are normally used for power
distribution in urban networks, industrial plants, as well as in thermopower and hydropower stations.

1 Core - Cu/PVC/PVC

Maximum Conductor Resistance Current Rating


Nominal Laid in ground Laid in free air (Shaded)
Approx.
Cross Approx.
Product DC at AC at Flat Flat Trefoil Overall
sectional Flat Trefoil Duct
Seperated Touched Touched Weight
Code 20 °C 70 °C Diameter
area

mm2 m m A A A A A A mm Kg/Km
CP1-T101-U08 4 4.61 5.51 53 53 38 50 37 35 7.1 87
CP1-T101-U09 6 3.08 3.68 65 66 47 65 48 46 7.6 113
CP1-T101-U10 10 1.83 2.17 88 89 62 89 9 62 8.3 154
CP1-T101-U11 16 1.15 1.37 113 113 77 108 85 79 9.3 216
CP1-T101-U12 25 0.727 0.8701 143 144 101 143 112 109 10.6 320
CP1-T101-U13 35 0.524 0.6273 171 173 123 176 138 134 11.7 410
CP1-T101-U14 50 0.387 0.4635 203 205 148 214 170 165 13.4 545
CP1-T101-U15 70 0.268 0.3214 248 252 183 271 215 209 15 745
CP1-T101-U16 95 0.193 0.232 296 301 224 332 267 259 17.1 1020
CP1-T101-U17 120 0.153 0.1845 337 342 255 386 310 301 18.5 1260
CP1-T101-U18 150 0.124 0.1501 378 383 292 442 357 347 20.5 1550
CP1-T101-U19 185 0.0991 0.1207 426 433 333 510 415 402 22.8 1925
CP1-T101-U20 240 0.0754 0.0931 494 501 393 608 496 481 25.8 2500
CP1-T101-U30 300 0.0601 0.0755 556 565 450 704 575 558 28.8 3110
CP1-T101-U40 400 0.047 0.0608 629 639 516 819 669 648 32 3975
CP1-T101-U50 500 0.0366 0.0495 709 721 594 957 777 753 36 5080
CP1-T101-U60 630 0.0283 0.041 792 807 672 1113 893 864 39.7 6385
CP1-T101-U70 800 0.0221 0.035 874 891 753 1284 1014 982 44.2 8260
CP1-T101-U80 1000 0.0176 0.0308 956 975 845 1478 1154 1116 51.7 10345
The above data is approximate and subjected to manufacturing tolerance.

60 Power Cables Division


Low Voltage Cables

0.6/1 (1.2) KV Multi Core Unarmoured Cables


Multicore Cables, with Stranded, Copper
Conductors, XLPE Insulated and PVC
Sheathed

Description
•Multicore cables of stranded Copper conductors are insulated with XLPE compound, assembled
together and covered with an overall jacket of PVC compound.
•Cables are produced according to IEC 60502.
Application
•For outdoor and indoor installations in damp and wet locations. They are normally used for power
distribution in urban networks, in industrial plants, as well as in Thermopower and Hydropower Stations.

Nominal Maximum Conductor Resistance Current Rating


Approx. Approx.
Cross
Product Laid in Laid in Laid in free Overall Overall
sectional DC at 20 °C AC at 90 °C air
Code ground duct Diameter Diameter
area (Shaded)
mm2 m m A A A mm Kg/Km
2 core cables - Cu/XLPE/PVC
CX1-T102-U04 1.5 RM 12.1 14.6 41 31 28 9.1 115
CX1-T102-U06 2.5 RM 7.41 8.87 50 39 38 10 148
CX1-T102-U08 4 RM 4.61 5.54 68 49 52 11 194
CX1-T102-U09 6 RM 3.08 3.69 86 64 67 12.2 255
CX1-T102-U10 10 RM 1.83 2.19 112 85 89 13.4 345
CX1-T102-U11 16 RM 1.15 1.39 144 102 118 15.4 500
CX1-T102-U12 25 RM 0.727 0.9272 188 133 154 18.9 675
CX1-T102-U13 35 RM 0.524 0.6685 227 162 189 21.1 880
CX1-T102-U14 50 SM 0.387 0.4938 276 193 230 20.9 1045
CX1-T102-U15 70 SM 0.268 0.3423 337 236 286 22.9 1460
CX1-T102-U16 95 SM 0.193 0.2469 405 288 357 26.6 2000
CX1-T102-U17 120 SM 0.153 0.1961 463 336 419 30.1 2485
CX1-T102-U18 150 SM 0.124 0.1593 519 378 478 32.9 3070
CX1-T102-U19 185 SM 0.0991 0.1279 590 438 560 37.5 3815
CX1-T102-U20 240 SM 0.0754 0.0982 682 513 663 41.6 4955
CX1-T102-U30 300 SM 0.0601 0.0792 767 582 757 45 6150
CX1-T102-U40 400 SM 0.047 0.0632 872 673 884 50.7 7895
3 core cables - Cu/XLPE/PVC
CX1-T103-U04 1.5 RM 12.1 14.6 31 25 23 9.5 130
CX1-T103-U06 2.5 RM 7.41 8.87 42 33 34 10.6 175
CX1-T103-U08 4 RM 4.61 5.54 54 39 44 11.6 233
CX1-T103-U09 6 RM 3.08 3.69 68 49 53 12.9 310
CX1-T103-U10 10 RM 1.83 2.19 89 65 72 14.2 430
CX1-T103-U11 16 RM 1.15 1.39 116 82 95 16.4 625
CX1-T103-U12 25 RM 0.727 0.9273 153 110 126 20.1 895
CX1-T103-U13 35 RM 0.524 0.6686 184 132 156 22.5 1180
CX1-T103-U14 50 SM 0.387 0.494 220 157 186 22.6 1490
CX1-T103-U15 70 SM 0.268 0.3425 270 195 236 26.1 2135
CX1-T103-U16 95 SM 0.193 0.2471 324 236 290 29.4 2895
CX1-T103-U17 120 SM 0.153 0.1964 368 272 337 32.8 3605
CX1-T103-U18 150 SM 0.124 0.1597 410 307 383 35.9 4435
CX1-T103-U19 185 SM 0.0991 0.1284 464 351 441 39.9 5555
CX1-T103-U20 240 SM 0.0754 0.0988 537 414 524 45 7250
CX1-T103-U30 300 SM 0.0601 0.0799 605 471 602 49.9 9050
CX1-T103-U40 400 SM 0.047 0.0641 688 547 701 57.3 11675
CX1-T103-U50 500 SM 0.0366 0.0518 776 625 806 63.8 14945
The above data is approximate and subjected to manufacturing tolerance.
rm: Round, Stranded
sm: Sector, Stranded

Cont'd

Power Cables Division 85


Low Voltage Cables

0.6/1 (1.2) KV Multi Core Unarmoured Cables

Multicore Cables, with Stranded, Copper


Conductors, XLPE Insulated and PVC
Sheathed

Nominal Maximum Conductor Resistance Current Rating


Approx. Approx.
Cross
Product Laid in Laid in Laid in free Overall Overall
sectional DC at 20 °C AC at 90 °C air
Code ground duct Diameter Diameter
area (Shaded)
mm2 m m A A A mm Kg/Km
4 core cables - Cu/XLPE/PVC
CX1-T104-U04 1.5 RM 12.1 14.6 32 26 24 10.3 155
CX1-T104-U06 2.5 RM 7.41 8.87 43 33 35 11.4 210
CX1-T104-U08 4 RM 4.61 5.54 55 40 45 12.6 280
CX1-T104-U09 6 RM 3.08 3.69 70 50 55 14 385
CX1-T104-U10 10 RM 1.83 2.19 92 67 75 15.5 535
CX1-T104-U11 16 RM 1.15 1.39 118 84 98 17.9 790
CX1-T104-U12 25 RM 0.727 0.9273 155 112 131 22.1 1170
CX1-T104-U13 35 RM 0.524 0.6686 186 136 161 24.8 1545
CX1-T104-U14 50 SM 0.387 0.494 225 162 197 26.3 1970
CX1-T104-U15 70 SM 0.268 0.3425 276 204 249 30.4 2825
CX1-T104-U16 95 SM 0.193 0.2471 330 243 303 33.1 3825
CX1-T104-U17 120 SM 0.153 0.1964 374 282 352 37.2 4785
CX1-T104-U18 150 SM 0.124 0.1597 421 321 405 41.7 5875
CX1-T104-U19 185 SM 0.0991 0.1284 475 369 467 46.7 7395
CX1-T104-U20 240 SM 0.0754 0.0988 551 431 554 52.5 9620
CX1-T104-U30 300 SM 0.0601 0.0799 621 493 636 58.1 11995
CX1-T104-U40 400 SM 0.047 0.0641 706 571 741 66.7 15480
CX1-T104-U50 500 SM 0.0366 0.0518 797 653 851 74.2 19815
4 core cables with reduced neutral - Cu/XLPE/PVC
CX1-T105-U12 25 RM / 16 RM 0.727 / 1.15 0.9273 / 1.4666 154 111 129 21.2 1075
CX1-T105-U13 35 RM / 16 RM 0.524 / 1.15 0.6686 / 1.4666 185 133 157 23.2 1365
CX1-T105-U14 50 SM / 25 RM 0.387 / 0.727 0.494 / 0.9273 226 163 198 26.1 1755
CX1-T105-U15 70 SM / 35 RM 0.268 / 0.524 0.3425 / 0.6686 277 204 250 30.2 2495
CX1-T105-U16 95 SM / 50 SM 0.193 / 0.387 0.2471 / 0.494 329 243 301 32.6 3380
CX1-T105-U17 120 SM / 70 SM 0.153 / 0.268 0.1964 / 0.3425 372 278 347 35.5 4290
CX1-T105-U18 150 SM / 70 SM 0.124 / 0.268 0.1597 / 0.3425 418 315 397 39.3 5115
CX1-T105-U19 185 SM / 95 SM 0.0991 / 0.193 0.1284 / 0.2471 472 363 458 44.2 6505
CX1-T105-U20 240 SM / 120 SM 0.0754 / 0.153 0.0988 / 0.1964 546 424 543 49.7 8415
CX1-T105-U30 300 SM / 150 SM 0.0601 / 0.124 0.0799 / 0.1597 615 485 624 55 10480
CX1-T105-U40 400 SM / 185 SM 0.047 / 0.0991 0.0641 / 0.1284 700 560 727 62.7 13460
CX1-T105-U50 500 SM / 240 SM 0.0366 / 0.0754 0.0518 / 0.0988 789 643 834 70.1 17300
The above data is approximate and subjected to manufacturing tolerance.
rm: Round, Stranded
sm: Sector, Stranded

86 Power Cables Division


Low Voltage Cables

0.6/1 (1.2) KV Multi Core Unarmoured Cables


Multicore Cables, with Stranded
Copper Conductors PVC Insulated
and PVC Sheathed

Description
•Multicore cables of stranded Copper conductors are insulated with PVC compound rated 70°C,
assembled together, covered with overall jacket of PVC compound.
•Cables are produced according to IEC 60502.
Application
•For outdoor and indoor installations in damp and wet locations.

Nominal Maximum Conductor Resistance Current Rating


Approx. Approx.
Cross
Product Laid in Laid in Laid in free Overall Overall
sectional DC at 20 °C AC at 70 °C air
Code ground duct Diameter Diameter
area (Shaded)
mm2 m m A A A mm Kg/Km
2 core cables - Cu/PVC/PVC
CP1-T102-U04 1.5 RM 12.1 14.6 34 25 21 9.5 127
CP1-T102-U06 2.5 RM 7.41 8.87 43 33 29 10.4 163
CP1-T102-U08 4 RM 4.61 5.54 57 42 41 12.2 233
CP1-T102-U09 6 RM 3.08 3.69 72 53 52 13.4 300
CP1-T102-U10 10 RM 1.83 2.19 93 73 69 14.6 390
CP1-T102-U11 16 RM 1.15 1.39 122 86 92 16.6 550
CP1-T102-U12 25 RM 0.727 0.8701 156 114 121 20.1 730
CP1-T102-U13 35 RM 0.524 0.6273 189 137 149 22.3 940
CP1-T102-U14 50 SM 0.387 0.4634 236 165 186 22.5 1140
CP1-T102-U15 70 SM 0.268 0.3212 287 204 230 24.3 1565
CP1-T102-U16 95 SM 0.193 0.2317 346 249 287 28.6 2145
CP1-T102-U17 120 SM 0.153 0.1841 396 287 336 31.7 2630
CP1-T102-U18 150 SM 0.124 0.1496 443 325 383 34.5 3245
CP1-T102-U19 185 SM 0.0991 0.1201 503 373 446 39.2 4040
CP1-T102-U20 240 SM 0.0754 0.0923 582 439 528 43.8 5245
CP1-T102-U30 300 SM 0.0601 0.0745 653 497 601 47 6475
CP1-T102-U40 400 SM 0.047 0.0595 741 570 699 52.9 8310
3 core cables - Cu/PVC/PVC
CP1-T103-U04 1.5 RM 12.1 14.6 27 21 20 10 150
CP1-T103-U06 2.5 RM 7.41 8.87 35 27 24 11 195
CP1-T103-U08 4 RM 4.61 5.54 46 36 34 12.8 282
CP1-T103-U09 6 RM 3.08 3.69 59 43 43 14.2 370
CP1-T103-U10 10 RM 1.83 2.19 78 57 59 15.5 490
CP1-T103-U11 16 RM 1.15 1.39 98 71 80 17.6 700
CP1-T103-U12 25 RM 0.727 0.8702 130 94 102 21.4 975
CP1-T103-U13 35 RM 0.524 0.6274 156 114 125 23.8 1270
CP1-T103-U14 50 SM 0.387 0.4635 189 136 151 24.2 1620
CP1-T103-U15 70 SM 0.268 0.3214 232 169 191 27.5 2280
CP1-T103-U16 95 SM 0.193 0.2319 278 205 235 31.6 3120
CP1-T103-U17 120 SM 0.153 0.1844 315 234 270 33.6 3820
CP1-T103-U18 150 SM 0.124 0.15 354 266 310 37.5 4685
CP1-T103-U19 185 SM 0.0991 0.1206 399 303 357 41.7 5870
CP1-T103-U20 240 SM 0.0754 0.0928 462 357 423 47.2 7680
CP1-T103-U30 300 SM 0.0601 0.0752 521 406 486 52.5 9600
CP1-T103-U40 400 SM 0.047 0.0603 593 468 567 59.7 12310
CP1-T103-U50 500 SM 0.0366 0.0489 668 534 650 66.4 15690
The above data is approximate and subjected to manufacturing tolerance.
rm: Round, Stranded
sm: Sector, Stranded

Cont'd

Power Cables Division 67


Low Voltage Cables

0.6/1 (1.2) KV Multi Core Unarmoured Cables

Multicore Cables, with Stranded


Copper Conductors, PVC Insulated
and PVC Sheathed

Nominal Maximum Conductor Resistance Current Rating


Approx. Approx.
Cross
Product Laid in Laid in Laid in free Overall Overall
sectional DC at 20 °C AC at 70 °C air
Code ground duct Diameter Diameter
area (Shaded)
mm2 m m A A A mm Kg/Km
4 core cables - Cu/PVC/PVC
CP1-T104-U04 1.5 RM 12.1 14.6 28 22 21 10.8 180
CP1-T104-U06 2.5 RM 7.41 8.87 36 28 25 11.9 235
CP1-T104-U08 4 RM 4.61 5.54 46 36 36 14 343
CP1-T104-U09 6 RM 3.08 3.69 60 44 45 15.6 454
CP1-T104-U10 10 RM 1.83 2.19 79 58 61 17 610
CP1-T104-U11 16 RM 1.15 1.39 99 73 83 19.6 880
CP1-T104-U12 25 RM 0.727 0.8702 131 96 105 23.5 1270
CP1-T104-U13 35 RM 0.524 0.6274 158 116 129 26.2 1660
CP1-T104-U14 50 SM 0.387 0.4635 195 141 161 28.3 2140
CP1-T104-U15 70 SM 0.268 0.3214 239 175 203 32.1 3025
CP1-T104-U16 95 SM 0.193 0.2319 285 211 247 35.8 4125
CP1-T104-U17 120 SM 0.153 0.1844 324 243 287 39.4 5095
CP1-T104-U18 150 SM 0.124 0.15 364 277 329 43.9 6245
CP1-T104-U19 185 SM 0.0991 0.1206 411 316 379 48.9 7840
CP1-T104-U20 240 SM 0.0754 0.0928 476 372 450 55.2 10195
CP1-T104-U30 300 SM 0.0601 0.0752 537 425 516 61.3 12720
CP1-T104-U40 400 SM 0.047 0.0603 610 490 601 69.9 16365
CP1-T104-U50 500 SM 0.0366 0.0489 689 561 690 77.4 20815
4 core cables with reduced neutral - Cu/PVC/PVC
CP1-T105-U12 25 RM / 16 RM 0.727 / 1.15 0.8702 / 1.3762 130 95 103 22.6 1170
CP1-T105-U13 35 RM / 16 RM 0.524 / 1.15 0.6274 / 1.3762 157 115 126 24.6 1470
CP1-T105-U14 50 SM / 25 RM 0.387 / 0.727 0.4635 / 0.8702 195 141 161 28.3 1920
CP1-T105-U15 70 SM / 35 RM 0.268 / 0.524 0.3214 / 0.6274 239 175 203 31.9 2680
CP1-T105-U16 95 SM / 50 SM 0.193 / 0.387 0.2319 / 0.4635 282 209 243 34.3 3640
CP1-T105-U17 120 SM / 70 SM 0.153 / 0.268 0.1844 / 0.6214 322 241 282 37.7 4575
CP1-T105-U18 150 SM / 70 SM 0.124 / 0.268 0.15 / 0.6214 361 273 323 41.5 5440
CP1-T105-U19 185 SM / 95 SM 0.0991 / 0.193 0.1206 / 0.2319 407 311 372 46.4 6910
CP1-T105-U20 240 SM / 120 SM 0.0754 / 0.153 0.0928 / 0.1844 472 366 441 52.4 8905
CP1-T105-U30 300 SM / 150 SM 0.0601 / 0.124 0.0752 / 0.15 532 419 507 58.2 11105
CP1-T105-U40 400 SM / 185 SM 0.047 / 0.0991 0.0603 / 0.1206 605 482 590 65.9 14245
CP1-T105-U50 500 SM / 240 SM 0.0366 / 0.0754 0.0489 / 0.0928 682 550 676 73.3 18190
The above data is approximate and subjected to manufacturing tolerance.
rm: Round, Stranded
sm: Sector, Stranded

68 Power Cables Division