Gac21 (MS21) e
Gac21 (MS21) e
MANAGEMENT
SYSTEM
FOR MARINE USE
Model GAC21
INSTRUCTION MANUAL
MS 21用 (英)
2001.06
GENERATING PLANT MANAGEMENT SYSTEM
GAC21
CAUTION
: A caution notice with this symbol indicates that neglecting the suggested
procedure or practice could result in moderate or slight personal injury
and/or property damage.
INSTRUCTION MANUAL
PART 1
1-1
1. Introduction -----------------------------------------------------------------------
2. Application and Performance ------------------------------------------------ 1-5
1-5
2.1 Applications --------------------------------------------------------------------
1-5
2.1.1 Type of Prime Mover and Generator Combinations -------------- 1-5
2.1.2 Voltage and Frequency Ratings for Generators ------------------- 1-5
1-6
2.1.3 Maximum Number of Generators that can be Controlled -------- 1-6
2.1.4 Generator Bus System --------------------------------------------------- 1-6
2.1.5 Air Circuit Breaker Closing Operation for Generators ------------ 1-6
1-6
2.1.6 Type of Prime Mover Generators -------------------------------------- 1-6
2.2 Performance ------------------------------------------------------------------- 1-6
2.2.1 Applicable Standards ----------------------------------------------------- 1-6
1-7
2.2.2 Environmental Conditions -----------------------------------------------
1-7
2.2.3 Control Power Supply ---------------------------------------------------- 1-7
2.2.4 Input of Measured Voltage/Frequency and Electric Power ------ 1-10
1-10
2.2.5 Structure and Installation Location of GAC21 Controller ------------------
1-10
2.2.6 External Dimensions and Mass ---------------------------------------- 1-11
3. System Structure ---------------------------------------------------------------- 1-25
1-26
3.1 Structure of GAC21 Controller --------------------------------------------
3.1.1 Type and Use ---------------------------------------------------------------
3.1.2 External Dimensions and Mass ----------------------------------------
3.1.3 Specification of Modules -------------------------------------------------
3.2 LED Display Setting Device -----------------------------------------------
3.3 Electric Power/Voltage/Frequency Transducer -----------------------
1. Introduction
The GAC21 Generating Plant Management System (hereafter referred to as“ GAC21 System” is
designed as a highly reliable total system that is very easy to use.
It features our system design based on affluent experiences as a dedicated manufacturer, and makes the
full use of our generator control technology and multiplex transmission technology that have successfully
been applied for a large number of our products for marine vessels.
The GAC21 System is a function-dispersed type system that operates mainly using its programmable
controller.
It consists of two control units, the GAC21 Automatic Generator Controller and the Type EAS-101
Digital Synchronizer, for a maximum of 5 generating plants.
Figs.1-1 and 1-2 shows the appearance of GAC21 Controller and its Setting device.
Coupler lock
Setting device
24V DC source
SX bus Address Number Base board
(254) (1) (2) (3) (4) (5) (6) (7) (8) (9)
6:Now ⇔ New
Change over Slide switch
7:I/O Module Connector (40P)
(254) (1) (2) (3) (4) (5) (6) (7) (8) (9)
Power CPU TM Ana- Ana- Digital Digital Digital Digital Digital Digital
Supply Module Interface logue logue I/O I/O I/O I/O Input I/O
Module Module Input Input Module Module Module Module Module Module
Module Module (G1) (G2) (G3) (Common) (Common) (Setting
Device)
(NP1S (NP1PH (NP1L (NP1AX04 (NP1AX04 (NP1W (NP1W (NP1W (NP1W (NP1X (NP1W
-42) -16) -TMB) -MR) -MR) 3206T) 3206T) 3206T) 1606T) 1606-W) 3206T)
24V DC source
Setting device
TM Bus Switchboard relay module (ESM-1102)
Digital synchronizer (EAS-101)
Voltage, Electric power, Frequency Transducer Input
Various alarm and indication output to shipboard monitor
Three-phase three-wire (3φ 3W) type or three-phase four-wire (3φ 4W) type
・For controlling more than 6 generators or using the dispersion control for generators,
contact us.
2.2 Performance
2.2.1 Applicable Standards
Conforms to the various shipping classification regulations.
3. System Structure
Fig.1-5 shows the configuration of the GAC21 System.
This system roughly consists of the following 3 components.
Base board
(254) (1) (2) (3) (4) (5) (6) (7) (8) (9)
DIGITAL I/O Module
(Setting device)
DIGITAL Input Module (Common)
DIGITAL I/O Module (Common)
DIGITAL I/O Module (G1, G2, G3)
ANALOG Input Module (Transducer)
TM interface Module (TM Bus)
CPU Module (CPU)
POWER SUPPLY Module (24V DC Source)
SX Bus
No. Module Name Type Used Qty.
Address No.
+24V DC
-
LG
FG
NC
NC
Type NP1S-42
PWR Green Turns on when the output voltage is within the rated range
Turns off when out of the range.
ALM Red Turns on when the output voltage is within the rated voltage.
Specifications
ITEM Specification
Type NP1PH-16
Key switch
The CPU operation is selected by the key switch.
RUN When RUN is selected from STOP or TERM, the CPU module starts to run.
Monitoring and program reading are possible by the program loader.
(Data can be read and written), according to the usual state of RUN position.
STOP When STOP is selected from RUN or TERM, the CPU module stops.
Monitoring and program reading are possible with the program loader.
(Data can be read and written)
・Key switch
This adjustment is usually set to“ RUN” position before shipment.
Used for usually“ RUN” position.
・CPU No. Selection key switch
Used for usually setting“ 0” position.
Do not change during operation for generator running, otherwise, system stop
might be causes.
Specifications
ITEM Specification
Type NP1L-TMB
ITEM Specification
SX interface
ITEM Specification
Signal name
1 NC
NC 2 3 NC
V1 4 5 COM
11 6 7 SLD
V2 COM
12 8 SLD
V3 10 9
11 COM
13 12 SLD
V4 14 13
COM
14 16 15
SLD
SLD 18 17
20 19
Terminal No.
Specifications
ITEM Specification
Type NP1AX04-MR
Gain/Offset channel “
Rotary switch: 0” position setting
selection key switch
Used for this position
Gain/Offset setting key “
Slide switch: center” position setting
Switch
Used for this position
・ 1
2
B19
B18
A19
A18
1
2
3 B17 A17 3
4 B16 A16 4
5 B15 A15 5
6 B14 A14 6
7 B13 A13 7
8 B12 A12 8
9 B11 A11 9
10 B10 A10 10
11 B9 A9 11
12 B8 A8 12
13 B7 A7 13
14 B6 A6 14
0.15 1.15
・ 15 B5 A5 15 L
・
NC B4 A4 NC
NC B3 A3 NC
NC B2 A2 PO
+ ・
CO B1 A1 MO
Fig.1-10 Digital I/O Module Front view and Connector Pin arrangement
Specification
ITEM Specification
Type NP1W3206T
Signal name
0
1 1 ・
・ 2 3
2
・
3
5
4 5
4 ・
7
6 7 ・
・ 9 6
CO ・
8 11 +
L 8 10 13 9
10 12 L
15 11
・ L
12 14 17 16 L
・
・ 14
PO
16
18
19 15 L
・
L MO
・
20 L
・
・ +
・
NC
Terminal No.
Fig.1-11 Digital I/O Module Front view and Connector Pin arrangement
Specification
ITEM Specification
Type NP1W1606T
Signal name
・
1
2
1
0
2 ・
3
4
3
5
4 ・
5 +
6 7 ・
・ 7 6
8 CO
8 10 9
・ ・ 10 12 11
9
11
12 14 13
14 16 15
13
15
・
+ C1 18 17
19
・
20
NC
NC ・
Terminal No.
Note: 1. Common terminals CO and C1 (Terminal No. 9 and 18) are electrically
separated and isolated from each other.
2. NC indicate a terminal not connected to an internal circuit.
Do not use NC terminals as repeating terminals.
Fig.1-12 Digital Input Module Front view and Connector Pin arrangement
Specification
ITEM Specification
Type NP1X1606-W
Specification
ITEM Specification
Type NP1BS-13
ITEM Specification
Type HT-001
For details of displaying and changing the setting values, refer to Part 3 “ Setting Value Display Function” .
Notes
*1:If the input is in the reverse flow, the output is maintained at 4 mA.
*2:If the auxiliary power source is active and if the input is less than 55 Hz or zero, the output
is maintained at 4 mA.
For details of adjusting the transducers, refer to Part 4“ Inspection・Maintenance and Self-Diagnostic
Function” .
End
INSTRUCTION MANUAL
PART 2
1. Introduction -----------------------------------------------------------------------------------------
2-1
1.1 Functional Elements of GAC21 System Device -------------------------------------- 2-2
1.2 Control Mode Selection ---------------------------------------------------------------------- 2-3
2. Remote Manual Control Functions ---------------------------------------------------------- 2-5
2-5
2.1 Diesel Engine Start/Stop Control and Abnormal Trip ------------------------------- 2-6
2.2 Generator Air circuit breaker Close/Open Control ------------------------------------ 2-6
3. GAC-UMS Control Functions ----------------------------------------------------------------- 2-6
3.1 Generator Monitoring ------------------------------------------------------------------------- 2-6
2-7
3.1.1 Generator Voltage Monitoring ----------------------------------------------------------- 2-8
3.1.2 Detection of Trouble or Delay in Generator System Control ------------------- 2-9
3.1.3 Detection of Generators Available for Automatic Start-Stop Control --------- 2-9
2-9
3.2 Bus Monitoring --------------------------------------------------------------------------------- 2-10
3.2.1 Bus Voltage Monitoring ------------------------------------------------------------------- 2-10
3.2.2 Bus Frequency Monitoring --------------------------------------------------------------- 2-10
2-10
3.2.3 Two-stage Bus Monitoring ---------------------------------------------------------------- 2-13
3.3 Automatic Generator Start Control ---------------------------------------------------------- 2-15
3.3.1 Stand-by Generator Selection ----------------------------------------------------------- 2-15
2-18
3.3.2 Stand-by Generator Start Control Scheme ------------------------------------------
2-18
3.3.3 Causes of Automatic Stand-by Start and Control After Automatic Start ----- 2-15 2-19
3.4 Automatic Generator Stop ------------------------------------------------------------------ 2-19
2-20
3.4.1 Automatic Stop Sequence Selection --------------------------------------------------
2-20
3.5 Automatic Load Sharing Control ---------------------------------------------------------- 2-21
3.5.1 Types of Load Sharing Control ---------------------------------------------------------- 2-21
2-22
3.5.2 Automatic Frequency Control -----------------------------------------------------------
2-23
3.5.3 Generator Engine Governor Control --------------------------------------------------- 2-23
3.6 Automatic Synchronous closing Control Function ----------------------------------- 2-25
3.6.1 SYNCHRO DETECT Function ---------------------------------------------------------- 2-27
2-28
3.6.2 SPEED MATCHER Function ------------------------------------------------------------ 2-29
3.7 Generator Low-Load Detection Function ----------------------------------------------- 2-29
3.8 Warning Indicator Lamp Signal Output ------------------------------------------------- 2-30
4. GAC-PMS Control Functions ------------------------------------------------------------------ 2-31
4.1 Number of Diesel Generators on Line Control (GAC-PMS-G) --------------------
4.2 Optimum Load Sharing Control (GAC-PMS-TG/SG) --------------------------------
4.3 Large Motor Start Blocking Control (GAC-PMS-M) ----------------------------------
4.3.1 Detection of Start Enable Signal --------------------------------------------------------
4.3.2 Detection of Number of Generators to be Put on Line ---------------------------
5. Communication Function with Monitor System ------------------------------------------
6. Standard Operation Setting Values and Setting Ranges for Each Function -------
7. Monitoring and Control Functions When GAC21 System is in Failure ------------
1. Introduction
The automatic generator control function, one of the main functions of the GAC21 Generating Plant
Management System (hereafter referred to as “GAC21 System”), works with various input signals for
generators, which are sent by digital multiplex transmission or as individual signals.
It outputs the necessary control and status signals to the outside of the GAC21 System by the digital
multiplex transmission or as individual signals.
The automatic generator control function has been developed based on our rich experiences and abundant
records acquired over many years, and includes a variety of control function that meet the customers’
requirements.
The above control functions are roughly classified into the following 3 groups:
Notes:
1) The setting values/setting ranges marked with an asterisk (*) in the text may be changed or
displayed on the Setting device.
For the standard setting values for each function, see Table 2-2“ Setting values and setting
ranges for standard operation” .
2) For the setting value changing procedure, refer to Part 3 “ Setting Value Display Function”
of this instruction manual.
3) If you require any control function other than those of the“ standard specification” included in
this volume, contact TERASAKI.
Note 1:
(*1) Available to close the ACB synchronously by the“ AUTO SYNCHRO” push-button switch (ASS) for
semi- automatic control. (This function os optionally available)
(*2) Automatic frequency control is perform by the GAC21 Controller, during single operation and
parallel operation.
(*3) The“ AUTO” is mean setting position G1, G2, G3 …… .
Note 5:
It is expected for the GAC21 system that the control“ MODE SELECT” switches (COS-A) is also used
when turbo and/or shaft generators are to be controlled.
Note 6:
For control operation procedure when GAC21 system fails, see section 7.“ Monitoring and Control
Functions in Case of GAC21 System” .
・Manual control:
Synchronous closing operation proceeds in manual control mode, if a GAC21 system becomes
inoperative due to a trouble of GAC21 Controller, at that time, performed manual synchronous
closing operation by the SYNCHROSCOPE and“ SYNCHROSCOPE” switch (SYS).
・Semi-automatic control
If required, separate the“ AUTO SYNCHRO” push-button switch (ASS) will be provided for each
generator. The use of this switch allows for activating the synchronous closing function of the
EAS-101 Device, one of the components for the GAC21 System, to perform the automatic
synchronous closing of ACBs.
Interlock between the generator ACB and shore power connection circuit breaker is provided by
hard-wiring logic with the GAC21 Controller being bypassed.
・Reset hysteresis: 20% of rated voltage (Reset point 20% below operate point).
・Auto synchro failure detect timing (AUTO SYNCHRO FAIL TIME):* 0 to 240 seconds.
Note:
The ACB NON-CLOSURE signal may be an OR-operated single group alarm output to
cover one of the following signal combinations;
・ VOLTAGE NON-ESTABLISHED, ACB NON-CLOSURE and AUTOMATIC
SYNCHRONIZING FAILURE.(standerd)
・ VOLTAGE NON-ESTABLISHED and ACB NON-CLOSURE (optional available).
・ All the output signals independently (optional available)
Note:
The“ SYNCHRO & POWER CONTROL” switch (COS-P) and“ CONTROL
POSITION”
select switch (COS-M) is not necessarily required for the GAC21 system standard, and is
available as a request.
(2) Detection of“ Ready for Automatic Stop” Conditions
In general, a generator can be automatically stopped (remove from the line) when all of the
following conditions are satisfied:
Ⅰ ) The generator is on line with its ACB closed.
Ⅱ ) The associated control switches are set to the specified positions (See Ⅶ) of (1) above).
Ⅲ ) The generator is in the parallel operation.
The stopping order of generators ready for automatic stop is determined by the“ Automatic Stop
Sequence Selection” function mentioned in 3.4.1 below.
The generator specified as being in the single running order will not stop automatically. (System standard)
Voltage settings
・BUS VOLT HIGH :* 100 to 125% of rated voltage
・BUS VOLT LOW :* 75 to 100% of rated voltage
・Time delay (BUS VOLT HIGH TIME and BUS VOLT LOW TIME):* 0 to 30 seconds
Frequency settings
・BUS FREQ HIGH :* 100.0 to 120.0% of rated frequency
・BUS FREQ LOW :* 80.0 to 100.0% of rated frequency
・Time delay (BUS FREQ HIGH TIME and BUS FREQ LOW TIME):* 0 to 30 seconds
(1) One Mode Select Switch for Each Generator (Standard arrangement)
MANU AUTO MANU AUTO MANU AUTO MANU AUTO MANU AUTO
G1 G2 G3 G4 G5
When mode select switches (one/generator) as illustrated above are provided on the main
switchboard or engine control console the stand-by generator select function checks each generator
for“ ready for automatic start” conditions and selects the generator ready for automatic start as 1st
stand-by, 2nd stand-by and so on, in the order they become ready for automatic start.
Since setting the mode select switch from“ MANU” to“ AUTO” position is one of the“
ready for
automatic start” conditions, the order of stand-by generators is usually determined from the
temporal order of setting their select switches from“ MANU” to“ AUTO” position.
SELECTION EXAMPLE
The select switches for G1 and G3 and G5 are set to“ AUTO” position as illustrated above.
G2 are on line. G1 became ready for automatic start first, G3 second, and G5 third.
G1 G2 G3
MANU G4
G5
Fig.2-2 Example of STANDBY SELECT switch
When a“ STANDBY SELECT” switch as illustrated above is provided on the main switchboard or
generator control console.
The stand-by generator mode select function checks this switch position and each generator for
“ ready for automatic start” conditions and selects the generators ready for automatic start as 1st
stand-by, 2nd stand-by, 3rd stand-by and so on enable in ascending order of generator Nos.
(Illustrated above is clockwise direction on the select switch) starting from the position to which the
select switch is set.
SELECTION EXAMPLE
The select switch is set to“ G2” position as illustrated above. Generators G1 are on line, and
generators G2, G3 and G5 are ready for automatic start.
With the stand-by generator list as inⅠ ) above, if G3 is put out of the“ ready for automatic
start” conditions, then G3 will be removed from the stand-by generator 1st and the order of the
other stand-by generators lower in order than G3 will be moved up as follows:
Stand-by : 1st → 2nd
| |
Generator : G2 G5
Ⅲ ) With the stand-by generator list as in Ⅰ ) above, if G3 becomes ready for automatic start, then
G3 will newly be included in the stand-by generator list with its order as determined from the
select switch position.
The new stand-by generator list will be as follows:
A failure of this stand-by too will be similarly followed and covered by the next lower order stand-by.
This sequence would be continued as long as there is a follower stand-by.
The stand-by start control will be terminated when there is no follower stand-by.
3.3.3 Causes of Automatic Stand-by Start and Control After Automatic Start
The generator that is the 1st stand-by on the stand-by generator list is automatically started by the
automatic start command signal, which is generated on one of different causes.
In the case of follower start scheme, depending on the type of cause the 2nd stand-by on the list may
also be started simultaneously.
In the case of simultaneous start scheme, the order of stand-bys on the stand-by generator list may not
agree with the actual order of stand-bys after voltage establishment.
Operation control of the started stand-by generator after its voltage establishment differs depending on
the type of cause of automatic stand-by start, such as whether it is paralleled to the generator(s) on line
or it replaces the latter.
The following describes the automatic start. This control is performed by the GAC21 Controller
functions.
(4) Generator on Line Automatically Replaced by Stand-by (s) without Blackout Period
In this control scheme, one or more stand-by generators are started on the automatic start command
signal, synchronized to the bus and put on line. Then predetermined generator on line is automatically
removed after load shift control.
The control scheme is in two types, depending on the number of stand-by generators to be put on line.
(1) One Mode Select Switch for Each Generator (Standard arrangement)
MANU AUTO MANU AUTO MANU AUTO MANU AUTO MANU AUTO
G1 G2 G3 G4 G5
When mode select switches (one/generator) as illustrated above are provided on the main switchboard
or engine control console, the stopping sequence select function checks each generator on line for
“ ready for automatic stop” conditions and selects the generators ready for automatic stop as 1st
stopping, 2nd stopping, 3rd stopping and so on, in the reverse sequence of their becoming ready for
automatic stop.
SELECTION EXAMPLE
The mode select switches for G2, G3 and G5 are set to“ AUTO” position as illustrated above, G2, G3
and G5 were put on line in this order, and all of them are ready for automatic stop.
The generator specified as being in the last stopping order will not stop automatically.
Ⅰ ) Stopping Orders
The stopping generator list in this example will be as follows:
At this time, if the ACB of G1 in place of G3 is closed automatically and synchronously, the
order of stopping generators is as follows (See alsoⅡ ) above):
(2) Single Standby Select Switch to Cover All Generators (arrangement available on request)
G1 G2 G3
MANU G4
G5
When a“ STANDBY SELECT” switch as illustrated above is provided on the main switchboard or
generator control console.
The stop sequence select function checks this switch position and each generator on line for ready for
automatic stop” conditions and selects the generators ready for automatic stop as 1st stopping, 2nd
stopping, 3rd stopping and so on enable in descending order of generator Nos. (Illustrated above is
counter-clockwise direction on the select switch) starting from the position to which the switch is set.
SELECTION EXAMPLE
The stand-by select switch is set to“ G2” position as illustrated above. Generators G1, G2 and G5
are on line and all ready for automatic stop. In this case, the stopping generator list will be as
follows:
The generator specified as being the last stopping order will not stop automatically.
Note:
The“ SYNCHRO & POWER CONTROL” switch (COS-P) does not come standard with the
system. When the“ SYNCHRO & POWER CONTROL” switch is added and is set to the“
AUTO”
position. the automatic load sharing function will be alive, irrespective of control mode selector
switch (COS-A) setting to“ AUTO” or“ MAMU” positions.
value. See section 4.2“ Optimum Load Sharing Control (GAC-PMS-TG/SG)” for full information.
Note:
The“ SYNCHRO & POWER CONTROL” switch (COS-P) is provided, the automatic frequency
control does function if this switch is set to“ AUTO” or“ MANU” position take priority,
irrespective
of control mode selector switch (COS-A) setting to“ AUTO” or“ MANU” positions.
3.5.3 Generator Engine Governor Control
Actual kW load on each generator on line is monitored and compared with the target kW load share
mentioned in section 3.5.1 to compute:
・Power Deviation=Target kW Share-Actual kW Load.
The bus frequency is also monitored to compute:
・Frequency Deviation=Rated Frequency-Actual Bus Frequency.
According to whether these deviations are positive or negative in value, one of two governor control
signals is selected as follows:
・Positive Deviation … Governor Raise (UP) signal;
According to the magnitude of the above deviations and based on the GOV CHARACT[sec/Hz]
setting:
The pulse duty ratio of these governor control signals is determined.
The governor control signal has been detected is output from the GAC21 controller to the generator
that is now operating at the frequency of once every 5 seconds and the maximum governor drive time
of 2.4 seconds (8 seconds/Hz).
The governor control signal is output based on the resultant value of power deviation and frequency
deviation.
This function is used to place a generator on a live bus served by other generator or generators for
parallel operation with the latter.
This function compares the frequency of a started generator that has built up the voltage with the bus
frequency, and brings the generator frequency closer to the bus frequency through governor control.
When the differences in voltage and frequency between the generator and bus fall within their
predetermined limits.
If the frequency difference or voltage difference becomes smaller than the predetermined value, the
EAS-101 Device outputs the ACB closing signal to the outside via the GAC21 Controller, so that the
ACB is closed when the bus voltage phase matches with the generator voltage phase.
Specifications
・Acceptable frequency difference limit :* 0.1 to
0.5 Hz
・Acceptable voltage difference limit 8 Hz :* 2 to
10% of bus voltage
・Governor characteristic setting range :* 2.0 to
・Maximum
16.0 (sec/Hz)permissible frequency difference for operation :
・Circuit breaker closing time :
* 0 to 500 ms
The following describes
・Automatic functionalfail
synchronizing elements
time of this function. :* 0
to 240 sec
3.6.1 SYNCHRO DETECT function
This function compares the generator voltage signal with the bus voltage signal, both inputted from
the external potential transformers, to check if the following conditions are satisfied:
Difference between the bus and generator frequencies is within the acceptable frequency
difference limit (normally set to 0.3Hz).
If these conditions are satisfied, then the EAS-101 Device function outputs an ACB close command
signal to the external generator ACB control circuit a certain length of time (ACB closing time,
normally set to 75 ms) prior to the instant when the generator voltage becomes exactly in phase with
the bus voltage.
These governor control signals are pulsed signals interval of maximum 5 seconds and governor driving
time 2.4 seconds (8sec/Hz) constant pulse repetition period, and the pulse duty ratio is varied
according to the magnitude of frequency difference and based on the GOV CHARACT (governor
characteristic) setting.
The governor control signals are outputted from EAS-101 Device through the GAC21 Controller to
the generator engine governor motor.
Alarm signal
*1
Group alarm signal
An alarm
Note:
1. When the power source of 24V DC is turned ON, the output signal and control are stopped for
2 seconds.
2. For the group warning signal *1, if a new error occurs during the output of the error signal,
the system is restored to the normal state (for 2 seconds) and then the error signal is output
again.
N
Σ
n=1
PLn
K1 = ─ ─ ─ ─ ─ 100〔%〕
N
───× Σ PRn
n=1
100
P11 P12 P13
K1
N
Σ
n=1
PLn
K2 = ─ ─ ─ ─ ─ 100〔%〕
N
───× Σ Pn-PR
n=1
PTG-R
TG TG
PTG-O
PTG-H
DG DG
PDG-L
PTG-L
LOAD ZONE
A B C D E F
The total kW load PL, is known as the sum of kW loads on generators on line.
The following describes the operation under GAC-PMS-TG for each PL zone specified in Fig.2-7.
Note:
(1) The setpoint of PTG-H is expressed in percentage with respect to the TG conventional
output PTG-O (kW).
(2) In this example of optimum load sharing control, the last diesel generator remaining on line
is intentionally not removed.
It is also possible to design the control scheme to remove this diesel generator according to
the criteria mentioned in Paragraph (2) of Subsection 4.1 of this Part.
Specifications
・Setting for required starting power :* 0 to 2000kW.
・Number of motors under control : 16 motors maximum.
・Setting for required starting confirmation time :* 0 to 60 seconds
[standard setting time : 15 seconds]
(From closing operation of the stand-by generator ACB to output of
the motor start enable signal).
MCCB TH
MC
Main power source M
MC
MC
To GAC21 system
For each large motor under this control, the required starting power PMn in kW is set. normally, each
PMn value is compared with the total surplus power PS (kW) as computed from the loading
conditions of the generators on line, to give the start enable signal to the starter circuit (See the
above diagram) of each large motor under this control.
6. Standard Operation Setting Values and Setting Ranges for Each Function
The standard operation setting values used for the functions of the GAC21 Controller are shown in the
following table:
Table 2-2 Setting values and setting ranges for standard operation
Table 2-3 Monitoring and control functions in case of GAC21 Controller failure-1
3. ACB closing/opening
Use the“ ACB ONTROL
”
4. Synchronous closing switch (BCS) on
After checking theMSB
the synchro-
scope pointer on the MSB
and ACB closed manually
5. Load sharing/shifting
Use the“ GOVERNOR
MOTOR” control switch
(GCS) on the MSB
Table 2-4 Monitoring and control functions in case of GAC21 Controller failure-2
Module Module Sensor
Control Function and Operation Switches abnormal abnormal abnormal
(For control) (Except
control)
In case of the I/O combined module for the Setting device fail …
The operation of the Setting device becomes impossible.
*8:In case of the power (watt) transducer fault …
The malfunctioning generator stops the automatic control when the generator voltage is
established (80% for 3 seconds).
1. Major system failure The module fault (control-related) is defined here as a major failure.
・Failure in other than the power supply module and the CPU module:
The malfunctioning module stops the output signals and the
control signal output by the software.
The CPU module continues to operate.
・Failure in the power supply module or the CPU module:
The CPU module stops and all the output signals from the GAC21
Controller also stop.
2. . Minor system failure The module fault (not control-related) is defined here as a minor
failure.
・If a fault that is not directly related to the control of the generators
occurs in the TM module (including the TM transmission line) or the
I/O module for the Setting device, the CPU module continues to
operate.
3. Minor system failure The sensor fault (in the power, voltage, and frequency transducers)
(Sensor fault) is defined here as included in the minor failures.
・Voltage transducer:
Any sensor fault is always detectable.
If the ACB is opened…
The control for concerned the generators is canceled.
If the ACB is closed… The current state is maintained.
A bus fault is detectable, but the automatic control is not
performed if a bus fault occurs.
----- continue
End
INSTRUCTION MANUAL
PART 3
3. Standard Setting Values and Addresses for Setting Value -------- 3-2
1. Introduction
As the display function for entering and modifying various parameter values and for displaying the
measured values, the handy type Setting device with an LED display (red) (hereafter referred to as
“Setting device”) is provided for the GAC21 System.
The communication between the GAC21 System and the Setting device is performed via the digital I/O
module for the Setting device, which is included in the GAC21 Controller.
However, this communication is only possible when the control-related modules and the digital I/O
module for the Setting device are normal.
In addition to the parameter values, the voltage and power for generators, and the measured value for the
frequency of the bus can be displayed.
The Setting device is normally removed and put in the accommodation pocket on the rear of the door for
the common section at the lower part of the generator panel.
1:LED Display (Red ) 4 character 5:Add. No. ⇔ Value Change over Slid switch
:SETTING ADDRESS-□ □
□ □
Serial number (01~99)
Group of setting item
(0: Constant setting, 1: Timer setting, 2: Measured value)
Generator number or other
(0:Common, 1:G1, 2:G2, 3:G3 …)
1 0001
1.0 0010
10 0010
10.0 0100
100 0100
100.0 1000
500kW 0500
450V 0450
60.0Hz 0600
ENG IDLING TIME 0~2400 sec 600 0600 1105 2105 3105
VOLT NON EST TIME 0~30 sec 20 0020 1102 2102 3102
ACB NON CLOSE TIME 0~10 sec 3 0003 1103 2103 3103
GEN LIGHT LOAD TIME 0~240 sec 0 0000 1106 2106 3106
CAUTION Search for Various Setting Values for Functions of GAC21 System
The standard setting values may be changed to the optical values depending on the
applicable ship. Some groups of setting values may be added.
To search for setting values, use address numbers for the following items included in “VOL. 3
GENERATOR AUTOMATIC CONTROL DEVICE --- GA” in the completed view of the main
switchboard.
・GENERATOR
・BUS MONITOR
(5) The module for the setting device returns the transmitted changed value to the Setting device,
which is then displayed on the LED.
Establish the changed value by pressing the ENTER key on the Setting device.
After the changed value has been transmitted to the module for the setting device, the setting
range and the changed value are checked.
If the changed value falls in that range, that changed value is accepted.
(6) 3 :
C Key(CANCEL)
If the entered value falls outside the setting range, an error is generated with“ 9999” displayed on the
LED of the Setting device.
To enter another value, press the CANCEL key. The displayed“ 9999” will be cleared.
Enter another changed setting value using numeric keys.
The CANCEL key is used to reset the specified data number (address) or the entered value to be
changed. When this data is reset, the LED on the Setting device simultaneously displays“ 0000” .
4. Check that the shaded part on the top of the module, shown in Fig. 3-2, does not
indicate any illuminated LED error message like “ERR” or “ALM”.
For the “ERR” indication, refer to “Part 4“ Inspection・Maintenance and Self-Diagnostic
Functions.”
Connector cables
(254) (1) (3) (2) (4) (5) (6) (7) (8) (9)
Step ①:Check that two slide switches are in the Add No.
(Setting address) and Now (Current value) positions.
Also check that the LED on the Setting device 0000
Indicates“ 0000” . Add No Value Now
Step ③:Check with the LED display that the entered address is
correct, and then press the ENTER key.
If the entered address is wrong.
I00I
1001
Press the C key and clear the LED display on the Setting No Value
Add No Value Now New
Step ⑧:Check with the LED that the changed value is correct,
and then press the ENTER key.
If the entered value is wrong, press the C key and
clear the LED display on the Setting device to“ 0000”
0020
1001
Add No
No Value
Value Now New
The“ measured value” is displayed only and can be viewed by performing the steps ① through ⑤
.
Handling and Disposing the Setting Device
CAUTION
After Changing the Setting
1. Check the setting positions of the slide switches:
Add. No. ÅÆValue : Add. No. position
-Even if this order is reversed, the setting device and the I/O module will not be damaged.
End
INSTRUCTION MANUAL
PART 4
Inspection・Maintenance
and
Self-Diagnostic Functions
1. Introduction
The GAC21 Automatic Generator controller (hereafter referred to as“ GAC21 Controller” ) and the
Handy Type Setter with an LED Display (hereafter referred to as“ Setting device” ) are designed to
allow you to perform maintenance and checks at ease.
(1) The GAC21 Controller is located in the common section on the lower front of the generator
panel, allowing you to perform maintenance, checks, and replacement from the front of the
GAC21 Controller.
(2) If each module of a GAC21 Controller should detect any anomaly with its self-diagnostic
function, it would turn ON the “ERR” LED indicator located on its front to notify you that the
anomaly has occurred.
(3) The Setting device has no self-diagnostic function, but allows you to find anomalies, if any,
from the initial information displayed when the Setting device is connected.
For operations and display for changing any setting value, refer to“ Part 3 Setting Value
Display Functions.”
(4) If any anomaly should occur, take action in accordance with “Section 3.2 Action Against the
Detected Anomaly” of this section.
Setting device
24V DC source
SX bus Address Number
(254) (1) (2) (3) (4) (5) (6) (7) (8) (9)
(2) Others
1) Check that the installed state is as follows:
a. Each module is installed firmly.
b. The terminal screws for external wiring are not loosened.
c. The connectors for connection cables are inserted firmly.
2) Check to see whether or not the battery in the CPU module needs to be replaced.
For replacing the batter, see “2.5 (3) Replacing the battery for data backup use in
the CPU Module”.
(The expected service life of the battery is indicated on the battery ---- approx. 5
years after manufacture.)
Do not perform the insulation resistance test and/or the withstand voltage test for the
GAC21 Controller since the module will be broken.
To perform either or both of these tests for the switchboard or Generator control
console with the GAC21 Controller, take the following actions:
(1) Remove the connection cable connected to the power inlet terminal of 24V DC
(power module) of the GAC21 Controller.
(2) Remove the input/output cable and connector connected to each module of the
GAC21 Controller.
Details of maintenance:
・ Disconnection and connection of the wiring connected to the GAC21 Controller
・ Removal/ insertion of connectors from/into each module
・ Replacement of wiring and equipment (including the power transducer, voltage
transducer, frequency transducer, and transformer and current transformer for
equipment) related to the GAC21 System.
(1) If a generator is being controlled for the automatic operation, change the
operation mode to MANU.
Trying to replace any equipment in the AUTO mode will cause the system to
malfunction and will hinder the power plant from the normal operation.
(2) To replace a module of the GAC21 Controller, turn OFF the power source of 24V
DC.
(3) To replace any cable, connector, or transducer, turn OFF the power source of
24V DC.
(4) After replacing any cable, connector, transducer, or module, set the cable
connection terminals and the switches located on the module to the same
positions as on the removed members or module, and firmly insert the
connectors into the correct positions.
(5) Each module is very susceptible to static electricity.
If you handle it when you are static electricity charged, the module may be
damaged.
Before handling the module, discharge your static electricity by touching
appropriate nearby metal.
For the“ Type EAS-101 Digital Synchronizer” , refer to the corresponding instruction
manual.
(1) The transducers convert the power (effective power), voltage, and frequency that are required
for executing the automatic control function for a generator, into the signal level of 4~20 mA DC
that can be sent via the analog multiplex transmission.
(2) Each transducer provides a trimmer (VR) for correcting the output.
Manually adjust the power, voltage, and frequency values to the rated ones while viewing the
readings on the instruments on the switchboard or the control panel for generators, and then
adjust the transducers by the following procedure.
For the positions of the trimmers (VR) for the transducers, see “Fig.4-2 Electric power
transducer, voltage transducer, and frequency transducer.”
Adjustment method:1
Measure the output current of the transducer with precision DC ammeter of low input impedance
(Max.500Ω ) and adjust the output adjuster so that output will equal to;
Adjustment method:2
Set the rated value by the transducer trimmer (VR) as read on the Setting device display function
(Part 3“ Setting Value Display Function, Table 3-3 List of Measuring Value” ).
Step ②:Mounting upper part of the module’s , backside on the base board.
Step ③ :Confirm the coupler lock to hang on the hole which is in the upper part of the
module’s backside.
If the module is loose, push the coupler lock to the direction of the arrow.
To remove a module, pull down the coupler lock toward you and then perform the
reversed steps for installing a module.
SETTING VALUE” .
(4) After replacing the ROM card, set the new ROM card to the“ CHANGED
Knob
WRITE PROTECT
WRITE ENABLE
Step ② :Turn down the battery folder. Insert the ROM card from the position of the
following figure of the CPU module to the backside.
Step ③ :Push the knob the ROM card to the right firmly.
Step ④ :1) Close the battery folder with pushing the battery leads not to be jammed.
2) Close the battery cover.
(3) Replacing the battery for data backup use on CPU module.
CPU module incorporates the lithium primary battery for data backup use.
(no spare battery is supplied since the battery is consumed even if it is not used).
・Nominal voltage:3.6 V
(2) If the“ BAT” LED indicator on the CPU module turns ON, immediately replace the
battery. After this warning has been issued, the CPU module will remain durable
against a power failure for approximately 1 week at 25 ℃ considering the
Tips:
The battery is used to back up the specific memory area of the CPU memory.
For example, if any set value is changed on the Setting device, the changed value is stored in
the memory area backed up with the battery.
Since this memory area is backed up with both the 24V DC power source and the battery, the
set values are not reset even if the 24V DC power source becomes unavailable.
However, if the 24V DC power source is lost for a long time when the battery runs out, the set
values will be reset to the initial value shown in the drawing for the finished system.
For this reason, the replacement of the battery is not necessary so far as the CPU module is
used without changing the initial values.
If any initial value is changed, replace the battery when necessary.
If you need to turn OFF the 24V DC power source when the battery is dead, check and record
the currently set values using the Setting device.
After the 24V DC power source has been restored, check again the set values using the
Setting device.
If the set values return to the initial values, change the initial values.
3. Self-Diagnostic Function
3.1 Check with the LED indicators
The operating state of each module can be checked with the LED indicators located on the front of
the module.
Table 4-1 shows the states of the LED indicators for the normal operation and the Table 4-5
occurrence of any anomaly.
For the items and states displayed on the module, refer to“ 3.1 Structure of GAC21 Controller” ,
“ 3.1.3 Specification of Modules” and“ States indication LED” of Part 1.
- Source ○ ●
supply
245 CPU ● ○ ● ○ ●
1 TM ○ ● ◎ ◎
2,3 Analogue ○ ●
4,5,6,7 Digital I/O ○ ●
8 Digital input ○ ●
9 Digital I/O ○ Setting
●
device
If an anomaly is found with the LED display on a module, take the following action.
1) Anomaly in the CPU module
Not just a CPU module anomaly, but also an anomaly in the system controlled by the
CPU can be displayed.
Even if the “RUN” LED shown in Table 4-1 is OFF statuses, an anomaly in any other
module can be detected. In this case, an anomaly occurs in another module.
If an anomaly is found in the internal CPU, identify the cause and make the
necessary replacement.
2) Anomaly in any module other than the CPU
If the “ERR” or “ALM” LED indicator on a module turns ON, identify the cause and
make the necessary replacement.
Electric power・Volt ・ Cause of detection: If the output current decreases below 0mA
(electrical discontinuity) with the input signal of 4~20mA, the
Frqequency transducer
SENSOR FAIL signal is output (the upper limit is not detected).
3.4 Troubleshooting
If the GAC21 system failure signal is output during the operation, recover the system in
accordance with the following chart.
If a failure occurs after any module has been replaced, take action according to the troubleshooting
chart on the next page.
Normal
*2)
Is the CPU No. NO Select the same CPU
Replace the CPU module same as that of the No. as that of the
previous module?
previous module
YES *3)
Is the Set the selection key
Selection key switch set to NO
Replace the Analogue switch to the sam e
input module the same position as on position as on the
the previous module?
previous module
YES
Replace the TM
interface module
Note:
*1) The RUN indic ator on the CPU module Identify the cause and take action in accordance
turn OFF or the ERR/ALM indic ator on with the 3.5 ”Indication of SYSTEM FAIL for the
the CPU module may be ON.
GAC21 System” in this PART.
*2) The CPU No. is norm ally set to “0”.
[Note:8]
・All the LED indicators on the other modules turn OFF.
[Note:9]
・On the CPU module, the ONL, ERR, RUN, and ALM LED indicators turn ON.
On the other modules, the ONL and ERR LED indicators turn ON.
(On the Power supply module, the PWR LED indicator is illuminated; and on the
Digital input module, only the ONL LED is illuminated.)
[Note:10]
・If any module other than the CPU and Power supply modules is disconnected, this
anomaly is classified according to the situation as follows:
… If the module is disconnected after the power has been turned ON:
CPU module ----------------- The ONL, RUN, and ALM LEDs turn ON.
Power supply module ----- The PWR LED turns ON.
Other modules -------------- The ONL LED turns ON.
[Note:11]
・The ON/OFF statuses of the LEDs located on the modules other than the CPU
module are classified according to the situation of occurrence as follows:
… If the anomaly occurs after the power has been turned ON:
Power supply module ---- The PWR LED turns ON.
Other modules ------------- The ONL and ERR LEDs turn ON.
(Except for the Digital input module, on which only the ONL LED turns ON.)
[Note:12]
・The BAT LED on the CPU is turns ON, and BAT LOW alarm is detect on monitor side
for abnormal watching.
4. Service Network
For the supply of parts, maintenance, and other services, Contact the following network consisting
of the members of I.S.E.S.
HEAD OFFICE
TERATEC LTD. --- Terasaki Main Service & Spare Center
1-12-12 NISHITANABE. ABENOKU.OSAKA. JAPAN
TELEPHONE:+81-6-6693-6971
FAX :+81-6-6693-1716
E-MAIL : elparts@teratec.co.jp/
Shipeng@teratec.co.jp/
WEB SITE : http://www.teratec.co.jp/
End