Project: ETAP Page: 1

Location: 19.0.1C Date: 11-19-2024

Contract: SN:

Engineer: Revision: Base


Study Case: LF
Filename: LOAD Config.: Normal

LOAD FLOW REPORT

Bus Voltage Generation Load Load Flow XFMR


ID kV % Mag. Ang. MW Mvar MW Mvar ID MW Mvar Amp %PF %Tap

* Bus1 11.000 100.000 0.0 486.790 346.980 99.997 50.006 Bus3 131.246 103.475 8772.1 78.5

Bus5 89.426 67.413 5877.9 79.9

Bus4 166.121 126.087 10946.1 79.7

Bus3 11.000 86.742 -13.1 0.000 0.000 150.480 75.252 Bus1 -131.246 -61.576 8772.1 90.5

Bus5 -19.234 -13.676 1428.0 81.5

Bus4 11.000 88.956 -10.8 0.000 0.000 158.259 79.142 Bus5 7.861 3.451 506.6 91.6

Bus1 -166.121 -82.593 10946.1 89.5

Bus5 11.000 88.347 -11.7 0.000 0.000 78.053 31.216 Bus1 -89.426 -42.330 5877.9 90.4

Bus4 -7.861 -3.302 506.6 92.2

Bus3 19.234 14.416 1428.0 80.0


* Indicates a voltage regulated bus ( voltage controlled or swing type machine connected to it)
# Indicates a bus with a load mismatch of more than 0.1 MVA