Heat Dissipation Calculations for AHF Module
Heat Dissipation Calculations for AHF Module
The following formula is used to determine the air volume required to dissipate the heat produced due to power loss:
V = C * (Pa-Pn)
Δt
V = Air volume in m³ per hour
C= Coefficient related to altitude
Pa= The actual power loss
Pn= Heat loss dissipated naturally, in Watt
Δt= Difference between inside and outside temperature in ˚ C
1
1.0384 1
2
0.9184 0
A 3
0.9712 0
4
0.8512 0
5
0.904 0
6
0.784 0
7
0.686 0
Pn= K x A x Δt
Pn K A Δt
5.5 1.0384 10
Pn= 57.112
volume of air required to dissipate the heat produced inside the enclosur due to power loss: V
V V = C * (Pa-Pn)
Δt
C Pa Pn Δt
3.5 3557 57.112 10
V = 1224.9608 m³ per hour 153.1201
Provided 188 m³ Fan 8 Number, considering 0.9 efficiency, , air flow will be 1353.6 m³ per hour