Catalogue PFD
Catalogue PFD
PFD-P500VM-E
P U H Y- P 2 5 0 Y J M - A ( - B S )
P U H Y- P 5 0 0 Y S J M - A ( - B S )
P QH Y- P 2 5 0 Y H M - A
Time
(example)
Power Thermo ON =
recovery Compressor ON
Initial setting
Indoor unit in operation
INDOOR Within 20 sec + (indoor unit address /2)
UNIT
Indoor unit in operation
1 sec.
Indoor units start one by one every sec.
PFD series provide you with highly reliable computer room cooling system
1 2
CLOSE CONTROL SYSTEM
Absolute Humidity
Absolute Humidity
temperature by reducing
Plus, new PFD series adopt advanced R410A refrigeration and control technology to offer compressor speed.
lower power consumption.
wn Evaporation
l do
Coo Temperature Cool d
own
Humidification
Evaporation
Temperature
Inverter-driven capacity control Reheating
No large capacity
10HP Outdoor Unit 20HP Outdoor Unit Large capacity humidifier
humidifier needed!
needed! Temperature (DB) Temperature (DB)
100% 100%
Common Close Control Air Conditioner PFD Series
Compressor Capacity Control
No.2
Compressor
Inverter Control
Inverter Control
No.1 This system will also help to minimize maintenance costs by removing the need for a large capacity humidifier.
Compressor No.1
Inverter Control Compressor
Inverter Control
34% 20%
Load Load
Large Small Large Small
3 4
Easy Installation/Maintenance Unit Combination
PFD-P250VM-E PFD-P500VM-E
1
1000mm or more
Indoor unit
800mm or more
Indoor unit
PFD-P250VM-E PUHY-P250YJM-A PFD-P500VM-E PUHY-P250YJM-A x 2 PFD-P500VM-E PUHY-P500YSJM-A
When connecting PFD-P500VM-E unit and water cooled outdoor unit, only 2 refrigerant circuit connection is
Piping length available and single refrigerant connection is not available.
With long pipe-runs of up to 165m, top-bottom differentials of 50m (40m if the outdoor unit is
installed below indoor unit, 15m if the outdoor temperature is under 10˚C), flexible design is
available with both air and water cooled outdoor unit.
60
Lossnay
Indoor Indoor Indoor Indoor
Measurement unit unit unit unit
1m
location
BC controller GL
Heat source unit
Heat
exchanger Auxiliary heat
source
Low noise mode can reduce sound level by sensing ambient temperature condition.
Pump
(This function is available in setting at site.)
Thermal
storage tank
* The water circuit
is closed.
PFD series are made in Japan under a stringent Water cooled PFD series offers reliability and
quality control system of Mitsubishi Electric. energy-saving that computer rooms require.
7 8
Remote Controller
Embedded MA remote controller and display lamps on the PFD unit enables easy control
New Design New Functions
and operation.
Backlight Color liquid crystal display Controllable units/groups
Backlight makes it easy to see and control units. Controls up to 50 units/groups (including indoor units,
A B C E F One can identify whether a unit is ON or OFF from a LOSSNAY, DIDO/AI/PI controller)
distance. Up to 150 units can be controlled via expansion
No.1 No.2
Control in the night with no lights is possible. controller;PAC-YG50ECA (AG-150A software needs to be
Power Operating Check Failure Failure
upgraded)
A Power display lamp Touch panel
*With PFD-P250VM-E, there is B Operation display lamp
only one failure display. 9 inch wide, high-resolution Monitoring functions
C Check display lamp
D Normal / Local switch Touch panel enables operation of units by touching with Temperature/Humidity (using AI controller with WEB
E No.1 Failure display lamp index finger. browser) *1
Local
F No.2 Failure display lamp When object unit is touched, orange box appears around General equipment such as lights on LCD (using DIDO
TEST RUN
* When Local operation is available the unit icon indicating the unit selected. controller)
D TEMP. ON/OFF
FILTER
With a new colored touch panel, and continuation of all the conventional G-50A functions,
System structure
AG-150A visualizes its functions from basic control to advanced operations and bringing an
ultimate controller to reality. M-NET
Switching Hub
LAN
(100BASE-TX) M-NET
Remote
Monitoring PC AG -150A PUHY-P250YJM-A
Remote monitoring
Expansion Controller PAC-YG50ECA via a Web browser
9 10
Indoor Unit Indoor Unit
Specification Specification
1950
Air outlet
Air outlet
1380 780 1980 780
11 12
Outdoor Unit Heat Source Unit
PUHY-P250, P500Y(S)JM-A (-BS) PQHY-P250YHM-A
(connected with PFD series.) (connected with PFD series.)
Specification Specification
550
920
Discharge air 760 920 30 920
Top view 880
Discharge air Outdoor unit 1 Outdoor unit 2
240
Intake Intake
Intake air air
air
1650
1710
1650
1410
1710
1160
Intake Intake
Intake air
air air
760 550
Left view
Left side view Front view Front view Right side view Rear view
(Mounting pitch)
724(721 727)
(550)
760
(880)
80 760 80
(Mounting pitch)
Bottom view
13 14
PFD-P250VM-E
PFD-P500VM-E
P U H Y- P 2 5 0 Y J M - A ( - B S )
P U H Y- P 5 0 0 Y S J M - A ( - B S )
P QH Y- P 2 5 0 Y H M - A