Slab DDM EFM
Slab DDM EFM
Nasr Abboushi
The direct-design method also could have been called “the direct-analysis method,” because
this method essentially prescribes values for moments in various parts of the slab panel
without the need for a structural analysis. The reader should be aware that this design
method was introduced in an era when most engineering calculations were made with a
slide rule and computer software was not available to do the repetitive calculations required
to analyze a continuous-floor slab system. Thus, for continuous slab panels with relatively
uniform lengths and subjected to distributed loading, a series of moment coefficients were
developed that would lead to safe flexural designs of two-way floor systems.
The direct-design method is easier to use than the equivalent-frame method, but can be
applied only to fairly regular multipanel slabs. The limitations, given in ACI Code Section
13.6.1, include the following:
1. There must be a minimum of three continuous spans in each direction. Thus, a
ninepanel structure ( ) is the smallest that can be considered. If there are fewer
than three panels, the interior negative moments from the direct-design method
tend to be too small.
2. Rectangular panels must have a long-span/short-span ratio that is not greater than .
One-way action predominates as the span ratio reaches and exceeds .
3. Successive span lengths in each direction shall not differ by more than one third of
the longer span. This limit is imposed so that certain standard reinforcement cutoff
details can be used.
4. Columns may be offset from the basic rectangular grid of the building by up to 0.1
times the span parallel to the offset. In a building laid out in this way, the actual
column locations are used in determining the spans of the slab to be used in
calculating the design moments.
5. All loads must be due to gravity only and uniformly distributed over an entire panel.
The direct-design method cannot be used for unbraced, laterally loaded frames,
foundation mats, or prestressed slabs.
6. The service (unfactored) live load shall not exceed two times the service dead load.
Strip or checkerboard loadings with large ratios of live load to dead load may lead to
moments larger than those assumed in this method of analysis.
7. For a panel with beams between supports on all sides, the relative stiffness of the
beams in the two perpendicular directions given by ( ) ( ) shall not be less
than or greater than . The term was defined in the prior section, and and
are the spans in the two directions.
Limitations and do not allow use of the direct-design method for slab panels that
transmit load as one-way slabs.
294
Reinforced Concrete II Dr. Nasr Abboushi
295
Reinforced Concrete II Dr. Nasr Abboushi
296
Reinforced Concrete II Dr. Nasr Abboushi
297
Reinforced Concrete II Dr. Nasr Abboushi
9.9.5 Lateral Distribution of Moments (between Column Strips and Middle Strips)
Having distributed the moment to the positive and negative-moment sections as just
described, the designer still must distribute these design moments across the width of the
critical sections. For design purposes, it is convenient to consider the moments constant
within the bounds of a middle strip or column strip unless there is a beam present on the
column line. In the latter case, because of its greater stiffness, the beam will tend to take a
larger share of the column-strip moment than the adjacent slab. The distribution of total
negative or positive moment between slab middle strips, slab column strips, and beams
depends upon the ratio , the relative stiffness of the beam and the slab, and the degree
of torsional restraint provided by the edge beam.
A convenient parameter defining the relative stiffness of the beam and slab spanning in
either direction is
in which and are the moduli of elasticity of the beam and slab concrete (usually the
same) and and are the moments of inertia of the effective beam and the slab.
Subscripted parameters and are used to identify computed for the directions of
, and , respectively.
The flexural stiffnesses of the beam and slab may be based on the gross concrete section,
neglecting reinforcement and possible cracking, and variations due to column capitals and
drop panels may be neglected. For the beam, if present, and for the slab, are
defined as in Section 9.4.
The relative restraint provided by the torsional resistance of the effective transverse edge
beam is reflected by the parameter , defined as
where , as before, is calculated for the slab spanning in direction , and having width
bounded by panel centerlines in the direction. The constant pertains to the torsional
rigidity of the effective transverse beam, which is defined according to ACI Code 13.7.5 as
the largest of the following:
1. A portion of the slab having a width equal to that of the column, bracket, or capital in
the direction in which moments are taken,
2. The portion of the slab specified in 1 plus that part of any transverse beam above and
below the slab,
3. The transverse beam defined as in Section 9.4.
The constant is calculated by dividing the section into its component rectangles, each
having smaller dimension and larger dimension , and summing the contributions of all
the parts by means of the equation
∑( )
With these parameters defined, ACI Code 13.6.4 distributes the negative and positive
moments between column strips and middle strips, assigning to the column strips the
percentages of positive and negative moments shown in the next table. Linear interpolations
are to be made between the values shown.
An interior panel of a flat-plate floor in an apartment building shown below. The slab
thickness is . The slab supports a design live load of and a superimposed
dead load of for partitions. The columns and slab have the same strength of
concrete. The story height is . Compute the column-strip and middle-strip moments
in the short direction of the panel.
Solution:
The column strip extends the smaller of or on each side of the column
centerline (ACI Code Section 13.2.1). Thus, the column strip extends on each
side of column centerline. The total width of the column strip is . Each half-middle strip
extends from the edge of the column strip to the centerline of the panel. The total width of
two half-middle strips is .
299
Reinforced Concrete II Dr. Nasr Abboushi
(b) Compute .
(c) Divide into negative and positive moments. From ACI Code Section 13.6.3.2,
Negative moment
Positive moment
This process is illustrated in the figure (a) below, and the resulting distribution of total
moments is shown in figure (b).
300
Reinforced Concrete II Dr. Nasr Abboushi
(d) Divide the moments between the column and middle strips.
Negative moments: From Table (page 299) for ( because there
are no beams between columns and in this panel),
These calculations are illustrated in figure (a) below. The resulting distributions of moments
in the column strip and middle strip are summarized in figure (c).
301
Reinforced Concrete II Dr. Nasr Abboushi
In the next figure, the moments in each strip have been divided by the width of that strip.
3. Compute the moments in the long span of the slab. Although it was not asked for in
this example, in a slab design, it now would be necessary to repeat steps 2(a) to 2(d)
for the long span.
4. Design the middle and the column strips for these moments and find the
reinforcement area for each strip.
The ACI Code presents two general methods for calculating the longitudinal distribution of
moments in two-way slab systems. These are the direct-design method (presented in the
previous section) and equivalent-frame methods, which are presented in this section.
Equivalent-frame methods are intended for use in analyzing moments in any practical slab–
column frame. Their scope is thus wider than the direct-design method, which is subject to
the limitations presented in Section 9.9.1 (ACI Code Section 13.6.1). In the direct-design
method, the statical moment, is calculated for each slab span. This moment is then divided
between positive- and negative-moment regions using arbitrary moment coefficients, which
are adjusted to reflect pattern loadings. For equivalent-frame methods, a stiffness analyses
of a slab–column frame is used to determine the longitudinal distribution of bending
moments, including possible pattern loadings. The transverse distribution of moments to
column and middle strips, as defined in the prior section, is the same for both methods.
The design requirements can be explained as follows.
1. Description of the equivalent frame: An equivalent frame is a two-dimensional
building frame obtained by cutting the three-dimensional building along lines
midway between columns (see the figure below). The resulting equivalent frames are
considered separately in the longitudinal and transverse directions of the building.
302
Reinforced Concrete II Dr. Nasr Abboushi
For vertical loads, each floor is analyzed separately, with the far ends of the upper
and lower columns assumed to be fixed. The slab-beam may be assumed to be fixed
at any support two panels away from the support considered, because the vertical
loads contribute very little to the moment at that support. For lateral loads, the
equivalent frame consists of all the floors and extends for the full height of the
building, because the forces at each floor are a function of the lateral forces on all
floors above the considered level. Analysis of frames can also be made using
computer programs.
2. Load assumptions: When the ratio of the service live load to the service dead load is
less than or equal to , the structural analysis of the frame can be made with the
factored dead and live loads acting on all spans instead of a pattern loading. When
the ratio of the service live load to the service dead load is greater than , pattern
loading must be used, considering the following conditions:
303
Reinforced Concrete II Dr. Nasr Abboushi
a. Only of the full-factored live load may be used for the pattern loading
analysis.
b. The maximum negative bending moment in the slab at the support is
obtained by loading only the two adjacent spans.
c. The maximum positive moment near a midspan is obtained by loading only
alternate spans.
d. The design moments must not be less than those occurring with a full-
factored live load on all panels (ACI Code, Section 13.7.6).
e. The critical negative moments are considered to be acting at the face of a
rectangular column or at the face of the equivalent square column having
the same area for nonrectangular sections.
3. Slab-beam moment of inertia: The ACI Code specifies that the variation in moment
of inertia along the longitudinal axes of the columns and slab beams must be taken
into account in the analysis of frames. The critical region is located between the
centerline of the column and the face of the column, bracket, or capital. This region
may be considered as a thickened section of the floor slab. To account for the large
depth of the column and its reduced effective width in contact with the slab beam,
the ACI Code, Section 13.7.3.3, specifies that the moment of inertia of the slab beam
between the center of the column and the face of the support is to be assumed equal
to that of the slab beam at the face of the column divided by the quantity
— , where is the column width in the transverse direction and is the
width of the slab beam. The area of the gross section can be used to calculate the
moment of inertia of the slab beam.
4. Column moment of inertia: The ACI Code, Section 13.7.4, states that the moment of
inertia of the column is to be assumed infinite from the top of the slab to the bottom
of the column capital or slab beams.
304
Reinforced Concrete II Dr. Nasr Abboushi
∑ ∑
where ∑ is the sum of the stiffness of the upper and lower columns at their ends,
∑
( )
∑( )
Stirrups:
ACI Code Section 11.11.3 allows the use of single-leg, multiple-leg and closed stirrups,
provided there are longitudinal bars in all corners of the stirrups.
Stirrups are allowed in slabs with effective depths, , that exceed the larger of or
16 times the stirrup diameter. The precision required to bend and place either the closed
stirrups or the multiple-leg stirrups makes these types of shear reinforcement labor-
intensive and expensive. As a result, shear reinforcement consisting of stirrups or bent
reinforcement is not used widely.
305
Reinforced Concrete II Dr. Nasr Abboushi
placement of the shear studs and to anchor the lower ends of the studs, they generally are
shop-welded to flat steel bars at the desired spacing. The vertical rods are referred to as
headed shear reinforcement or headed shear studs. The assembly of studs plus the bar is
called a stud rail.
ACI Section 11.11.5 — Headed shear stud reinforcement, placed perpendicular to the plane
of a slab or footing, shall be permitted in slabs and footings in accordance with 11.11.5.1
through 11.11.5.4. The overall height of the shear stud assembly shall not be less than the
thickness of the member less the sum of:
(1) the concrete cover on the top flexural reinforcement;
(2) the concrete cover on the base rail; and
(3) one-half the bar diameter of the tension flexural reinforcement.
Where flexural tension reinforcement is at the bottom of the section, as in a footing, the
overall height of the shear stud assembly shall not be less than the thickness of the member
less the sum of:
(1) the concrete cover on the bottom flexural reinforcement;
(2) the concrete cover on the head of the stud; and
(3) one-half the bar diameter of the bottom flexural reinforcement.
11.11.5.1 — For the critical section defined in 11.11.1.2, shall be computed using
Eq. (11-2) ( ), with and not exceeding √ and √ ,
respectively. shall be calculated using Eq. (11-15) ( ) with equal to the cross-
sectional area of all the shear reinforcement on one peripheral line that is approximately
parallel to the perimeter of the column section, where is the spacing of the peripheral
lines of headed shear stud reinforcement. shall not be less than √ .
11.11.5.2 — The spacing between the column face and the first peripheral line of
shear reinforcement shall not exceed . The spacing between peripheral lines of shear
reinforcement, measured in a direction perpendicular to any face of the column, shall be
constant. For prestressed slabs or footings satisfying 11.11.2.2, this spacing shall not exceed
; for all other slabs and footings, the spacing shall be based on the value of the shear
stress due to factored shear force and unbalanced moment at the critical section defined in
11.11.1.2, and shall not exceed:
(a) where maximum shear stresses due to factored loads are less than or
equal to √ ;
(b) where maximum shear stresses due to factored loads are greater than
√ .
11.11.5.3 — The spacing between adjacent shear reinforcement elements, measured
on the perimeter of the first peripheral line of shear reinforcement, shall not exceed .
11.11.5.4 — Shear stress due to factored shear force and moment shall not exceed
√ at the critical section located outside the outermost peripheral line of shear
reinforcement.
307
Reinforced Concrete II Dr. Nasr Abboushi
Example (Checking One-Way and Two-Way Shear at an Interior Column in a Flat Plate):
The figure below shows an interior column in a large uniform flat-plate slab. The slab is
thick. An average effective depth, , as shown, normally is used in shear strength
calculations for two-way slabs. Both one-way and two-way punching shear usually is checked
near columns where top reinforcement is used in both principal directions to resist negative-
bending moments. ACI Code Section 7.7.2(c) states that the minimum clear cover for slab
reinforcement is . Thus, assuming
bars are used as flexural reinforcement, the
average value for determining shear strength
of the slab is
Solution:
1. Determine the factored uniform load.
2. Check the one-way shear. One-way shear is critical at a distance from the face of
the column. Thus, the critical sections for one-way shear are A–A and B–B.
The loaded areas causing shear on these sections are cross hatched. Their outer boundaries
are lines of symmetry on which Because the tributary area for section A–A is larger,
this section will be more critical.
(c) Compute at section A–A.
309
Reinforced Concrete II Dr. Nasr Abboushi
√ √
– the slab is OK in one-way shear.
3. Check the two-way punching shear. Punching shear is critical on a rectangular section
located at away from the face of the column. The load on the cross-hatched area
causes shear on the critical perimeter. Once again, the outer boundaries of this area
are lines of symmetry, where is assumed to be zero.
(b) Compute for the critical section. The length of the critical perimeter is
( )√ ( ) ( )
( )√ ( ) ( )
310
Reinforced Concrete II Dr. Nasr Abboushi
( )√ √
So
Because exceeds the slab is OK in two-way shear.
Solution:
The design shear strength of the concrete alone at the critical section from the face of
the column, is the smallest of the following:
( )√ ( ) ( )
( )√ ( ) ( )
where
√ √
This is less than , indicating that shear reinforcement is required. The effective
depth just satisfies the minimum allowed to use stirrup reinforcement, as
described in the beginning of this Section.
In this case, the maximum design strength allowed by the ACI Code is
√ √
satisfactorily above the actual . When shear is resisted by combined action of concrete and
bar reinforcement, the concrete contribution is reduced to
√ √
311
Reinforced Concrete II Dr. Nasr Abboushi
The vertical closed hoop stirrups will be used since must be times the stirrup
diameter ( ) and arranged along four integral beams as shown below.
Thus, the provided is at the first critical section, a distance
from the column face, and the required spacing can be found from:
√ √
from which the minimum perimeter . Using this value of in the other
equations for :
( )√ ( )√
( )√ ( )√
( √ ) ( )
√
( )
√
( √ )
which exceeds the requirement.
Note: the projection distance can be
calculated from the face of the column and assuming that is the column width.
( √ )
312
Reinforced Concrete II Dr. Nasr Abboushi
Four longitudinal bars will be provided inside the corners of each closed hoop stirrup,
as shown, to provide for proper anchorage of the shear reinforcement.
Note that the approach taken here is somewhat conservative because the portion of the slab
load applied inside the perimeter of the critical section does not act on that section and can
thus be subtracted from the factored load of .
Solution:
1. Select the critical section for two-way shear around the column. At this stage in the
calculations, the designer does not know whether shear reinforcement will be
required.
We will assume it is not and will redo the calculations if we are wrong. Assuming
flexural reinforcement, the average effective depth of the slab is
The inner critical shear section for two-way shear in a flat plate extends around the column
at from the face of the column, as shown in the figure below.
The length of one side of the critical shear section around the column is
giving a shear perimeter
2. Compute the shear acting on the critical shear section. The load combinations from
ACI Code Section 9.2 will be used to compute the total factored dead and live loads.
The basic combination for gravity load is
( )√ ( ) ( )
( )√ ( ) ( )
√ √
So
Because less than , shear reinforcement is required at
the critical shear section. Using shear studs as shear reinforcement results in
√ √
This gives
√ √
3. Lay out the punching shear reinforcement. Rows of shear studs welded to bars will
be placed parallel and perpendicular to the main slab reinforcement to cause the
least disruption in the placement of the main slab steel. Using a trial and error
process:
Try eight stud rails, each with seven -diameter studs ( ) with
-diameter heads, and (typical for shear studs).
The spacing to the first set of shear studs, , is to be taken less than or equal to . Thus,
select (see figure). Before proceeding to layout the subsequent rows of shear
studs, the shear strength should be checked at the inner critical section. In Equation
, the area provided by the inner row of shear studs is
314
Reinforced Concrete II Dr. Nasr Abboushi
Try eight stud rails with the first stud located at from the column face.
Subsequent studs are at a spacing of with seven -diameter headed shear
studs per rail.
The outermost studs are at from the face of the column, and the
outer critical section is from the face of the column.
315
Reinforced Concrete II Dr. Nasr Abboushi
The outer critical-shear section is a series of straight line segments passing through points
located outside the outer shear studs, as shown in the figure. The perimeter of this
peripheral line is
( √ )
4. Check the shear stresses on the outer critical section. The factored shear force on the
concrete at the outer critical section is
and
√ √
Because this is larger than , the design is OK.
316