0% found this document useful (0 votes)
104 views5 pages

EVP-003-CL2 Vaporizer Piping - Gas Pressure Feed

Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
104 views5 pages

EVP-003-CL2 Vaporizer Piping - Gas Pressure Feed

Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 5

Vaporizer Piping

Gas Pressure Feed Applications

Vaporizers are used for high capacity chemical feed applications when direct gas withdrawal systems are
impractical. This document will provide a generalized overview of vaporizer operation and general design
information for chlorine liquid manifolds. Throughout the document reference will be made to chlorine
(Cl2), but the information also applies to sulfur dioxide (SO 2) and ammonia (NH3). This document should
be used only as a reference and only after proper engineering consideration has been given to all aspects
of the relevant system design. For additional information refer to the Hydro Instruments Chlorine
Handling Manual and the Chlorine Institute, Inc. Pamphlet 6.

Vaporizer Overview
The vaporizer pressure chamber is submerged in a hot water bath at approximately 180°F (82°C). Water
bath temperature can be adjusted depending on feed rate requirements and also can be set lower during
standby usage. As the liquid chlorine flows into the pressure chamber it is vaporized on contact with the
hot walls of the chamber. The resultant gas chlorine is then superheated as it travels out of the vaporizer
before flowing downstream to the process (See Figure 2). The rate at which chlorine passes through the
chamber is dictated by the chemical feed rate of the system. Initially the liquid chlorine level in the
pressure chamber will rise until the heat transfer rate from the pressure chamber walls to the liquid
chlorine is sufficient to balance the chemical feed rate of the system. If the liquid chlorine level rises
above this equilibrium level (or if feed rate demand of the system is reduced) then chlorine gas pressure
inside the chamber will build up and push the liquid chlorine level back until a new equilibrium level is
reached. As the chlorine feed rate is increased, gas pressure will fall causing the liquid level to rise, and
as the liquid chlorine level rises the heat transfer surface area increases between the liquid chlorine and
the pressure chamber walls until an equilibrium level is reached. Therefore, the size of the inner chamber
and its ability to transfer heat to the liquid chlorine determines the feed rate capacity of the vaporizer.

IMPORTANT: Exceeding this feed rate capacity risks the liquid level rising above the height of the
chlorine pressure chamber and flooding liquid chlorine past the vaporizer.

FIGURE 1

Expansion Chamber
Actuated Pressure Reducing Valve

VENT TO SCRUBBER
INTAKE DUCT
Pressure Relief Valve

EMERGENCY SCALE
GAS ALARM
SHUTOFF SYSTEM INDICATOR

NET #1 = 1234 VENT TO SCRUBBER Pressurized Pipe


INTAKE DUCT
(gas)
Cl2 BALL VALVE

Pressurized Pipe
(gas) FILTER

Ton Container

Vaporizer
SCALE

Flexible Connector

Pressurized Pipe
(liquid)

600 Emlen Way, Telford, PA 18969 Telephone: (215) 799-0980 Fax: (215) 799-0984
US Toll Free: (888) 38-HYDRO www.hydroinstruments.com [email protected]

Page 1 of 5 Bulletin EVP-103-CL2 Rev. 11/26/2024


Containers
Connected containers (e.g. ton containers, rail cars and bulk tanks) must be maintained at the same
elevation and temperature in order to prevent unequal feed or contents flowing between containers.
Scales are recommended to monitor over filling and uneven feeding of the containers, as well as monitor
when supply is low.

Pressurized Piping
Pressurized piping should be 1” schedule 80 seamless carbon steel. Fittings must be 3000 pound forged
steel, A-105.
Note: Threaded joints must be sealed with Teflon tape or other approved sealant.
Chlorine Liquid Manifold
The liquid manifold can be placed above or below the liquid cylinder valve (e.g. the bottom valve) on the
ton container. However, to prevent liquid traps it is recommended it be placed above. If placed above the
ton container then the pipe should be pitched back toward the ton containers at approximately 2° to 3°.
Flexible connectors are used to connect the manifold piping to the ton containers. Auxiliary valves (e.g.
isolation valves) should be used on all flexible connectors at the ton container.
Pressure Equalization Manifold
The use of a pressure equalization manifold is recommended when utilizing more than one ton container
in order to equalize the pressure within the ton containers. This will help to prevent overfilling of the ton
containers when liquid chlorine is pushed back into them. The pressure equalization manifold must be
placed above the liquid manifold. Pipe size should be 1” schedule 80 seamless carbon steel and fittings
must be 3000 pound forged steel, A-105. If adding a secondary gas discharge line, the pipe size should
be sized appropriately for the flow rate and it must be tilted back toward the containers and installed with
liquid traps and heaters to allow use during times of vaporizer maintenance.
Gas Feed Line (optional)
This piping arrangement can be used for gas feed during times of vaporizer maintenance or as a means
to evacuate the gas piping line.
The gas feed line piping should pitch back (approximately 2° to 3°) toward the ton containers and the gas
outlet of the vaporizer must be higher than the containers. The valves in the optional gas evacuation pipe
line must remain closed during normal operation.

Liquid Reserve Containers


Liquid reserve containers are optional.
Liquid reserve containers can be useful in changeover style systems so that full chemical feed capacity
can be maintained while in the process of changing from a depleted chemical supply to a full one.

600 Emlen Way, Telford, PA 18969 Telephone: (215) 799-0980 Fax: (215) 799-0984
US Toll Free: (888) 38-HYDRO www.hydroinstruments.com [email protected]

Page 2 of 5 Bulletin EVP-103-CL2 Rev. 11/26/2024


Expansion Chambers
Expansion chambers must be installed on liquid lines between any two points where liquid could become
entrained (i.e. between valves that could be closed on both ends).
The expansion chamber must be sized so that its volume is at least 20% of the overall pipe volume that it
is protecting.
Expansion chambers must be located on the highest point of the pipeline section.
The expansion chamber includes:
• A 1” FPT union type (or flange type) holder with rupture disc.
• A suitable diaphragm protected pressure switch for disc rupture indication.
• Either a DOT –or– ASME certified expansion tank.

Pressure Relief Valve


The pressure relief valve assembly must be installed directly at the gas outlet connection of the vaporizer
and must be before any type of obstructions (filters, ball valves, etc.).
Piping to the pressure relief valve is 1” NPT and the vent outlet is 1.5” NPT (1.5” vent piping must be
schedule 80 seamless carbon steel material).
Outlet vent piping must be directed to a safe, unoccupied area outside and should slope downward to
prevent moisture buildup in the line. Alternatively, the piping could be directed to a chlorine scrubber
intake. An insect screen should be installed at the vent piping outlet.
The pressure relief valve has a relief pressure of 560 psig (38.6 bar).

Actuated Pressure Reducing Valve


The electronic pressure reducing valve (PRV) is wired to the vaporizer and will be used to stop chlorine
feed in the event that any relevant alarm condition exists.
Two PRVs in a duty standby arrangement can be connected to one vaporizer to allow operation during
maintenance of one of the PRV’s.
The PRV should be installed using Ammonia type unions at the inlet and outlet with a bypass line to allow
for quick installation and maintenance. This bypass line must include a manual chlorine ball valve and
must run horizontally around the PRV.
NOTE: Do not run the PRV bypass line below the PRV because this could be a trap for liquid chlorine.
The PRV’s vent line connection is ¼” FPT, but it is recommended that the vent line be at least ½” size.
This vent line should be ½” schedule 80 seamless carbon steel material. This vent line must be directed
to a safe, unoccupied location, outside of the building or directed to a scrubber intake. The PRV vent
piping must slope downward toward the outlet at approximately 2° to 3° to allow any condensation to
naturally drain away from the PRV. An insect screen should be installed at the vent outlet.
The PRV will tend to get cool due to the pressure drop through it, making it susceptible to condensation.
An optional heater is available to mount on the PRV in order to avoid this condensation.

600 Emlen Way, Telford, PA 18969 Telephone: (215) 799-0980 Fax: (215) 799-0984
US Toll Free: (888) 38-HYDRO www.hydroinstruments.com [email protected]

Page 3 of 5 Bulletin EVP-103-CL2 Rev. 11/26/2024


Vaporizer Pressure Chamber
1” Ammonia type unions are to be installed on the ASME certified vaporizer pressure chamber liquid inlet
and gas outlet. Liquid inlet and gas outlet are identified on the pressure chamber and must be installed
appropriately. Inaccurate installation of the liquid and gas lines into the vaporizer will result in serious
malfunction of the unit and potential damage to other equipment.
Piping in and out of the vaporizer must be installed in a way that will allow relatively easy disconnection
from the piping and allow for vertical removal of the vaporizer pressure chamber for inspection and
maintenance. Hydro Instruments recommends at least 12ft. (3.65m) of clearance space above the
vaporizer and the use of a 4,000+ lbs. (1,800 kg) capacity lifting crane.
The chlorine feed rate is proportional to the heat transfer rate from the hot water to the chlorine liquid.
Heat transfer rate is proportional to…

Therefore, the chamber size determines maximum capacity and the water temperature is the only variable
the vaporizer can adjust under operating conditions.
As illustrated in Figure 2 below, the superheat is an indication of how high the liquid level is in the
chamber. If the superheat falls to zero then this means that liquid has reached the top of the pressure
chamber and will flood past the vaporizer. The Hydro Instruments Vaporizer monitors the superheat and
has a superheat alarm feature that will stop liquid chlorine flow by cutting power to the actuated pressure
reducing valve in the gas outlet line should the superheat fall below the alarm set point. This is critically
important because if liquid chlorine passes through the vaporizer it could enter equipment downstream of
the vaporizer or reach the process, which could cause a chlorine release or downstream process
malfunction.

FIGURE 2

T2

Superheat = T2 – T1

T1

Normal Liquid level


too high

600 Emlen Way, Telford, PA 18969 Telephone: (215) 799-0980 Fax: (215) 799-0984
US Toll Free: (888) 38-HYDRO www.hydroinstruments.com [email protected]

Page 4 of 5 Bulletin EVP-103-CL2 Rev. 11/26/2024


E1

A. Ton container scale with trunnion J. Pressure relief assembly


B. Chlorine ton container J1. Pressure relief valve
N
C. Isolation valve assembly J2. Pressure switch E3 E2
D. Flexible connector J3. Burst disc J
E. Expansion chamber assembly J4. Manifold union
M

Page 5 of 5
E1. Expansion chamber 662 m3 volume K. Chlorine gas filter E
E2. Testing tee with plug L. Manifold union J2 VENT TO SCRUBBER
J1 INTAKE DUCT H
0
10
80 0
14

40 0
18

E3. Pressure switch M. Diaphragm protected pressure gauge 0


20

E4. Burst disc N. Pressure reducing valve (electronically actuated) E5 J4 J3


E5. Manifold union O. Drip leg & heater E4 H
F. Header valve P. Gas alarm controller
VENT TO SCRUBBER
G. 1" schedule 80 seamless carbon steel pipe P1. Chlorine gas sensor INTAKE DUCT
L L
H. Chlorine ball valve Q. Automatic changeover controller
H1. Chlorine ball valve with lock Q1. Actuated chlorine ball valve
I. Evaporator Q2. Diaphragm protected pressure gauge w/ I1
I1. Manifold union (liquid inlet) adjustable switch I2
I2. Manifold union (gas outlet) K

F F F
L H1

N
PLUG
P Q
D D D

M
B
VENT TO SCRUBBER
O INTAKE DUCT 0
10
H
G 80 0
14

40 0
18

0
20

E1
H
C
P1 VENT TO SCRUBBER
INTAKE DUCT L L
E3 E2

I1
I2

US Toll Free: (888) 38-HYDRO


E A
Q2 Q1 K
D D D
FIGURE 3

F F F
100
E5 80 140

40 180
200

E4

600 Emlen Way, Telford, PA 18969


I

F F F
L H1

PLUG

D D D N

B
O M

VENT TO SCRUBBER
INTAKE DUCT 0
10
H
80 0
14
E1 40 0
18

0
20

C
G

www.hydroinstruments.com
P1 H

VENT TO SCRUBBER
E3 E2 INTAKE DUCT L L

Telephone: (215) 799-0980


E A
Q1 I1
Q2
I2
D D D
F F F K
E5 80
100
140

40 180
200

E4

Fax: (215) 799-0984


[email protected]

Bulletin EVP-103-CL2 Rev. 11/26/2024

You might also like