www.fine-tek.

com

Display Scaling Meter /


Temperature Controller
DISPLAY SCALING METER INTRODUCTION

FEATURES
Adapts microprocessor control circuit, modular
design, advanced digital calibration, and switching
power supply technology.

Modulized design is a concept to adapt different


analog input signals by means of changing different
signal board (such as temperature, pressure,
alternating voltage, electric current.). Also, optional
output board could add the analog output signal
(isolated). By using advanced digital calibration
capability, its analog input/output could be accurate to
+/- 1 bit.

PB SERIES---BARGRAPH DISPLAY
It is easy to tell the measuring, operator can tell
measuring range easily by eyesight even in the
remote site.

Provides not only 4 digits numerical display with


bargraph analog output indicator but also 6 relay
setting points. It makes users to tell Process setting
position without difficulties by bargraph indicator. In
general, it is an easy applied and understand model
to customers.

PB-1470 are horizontal mounting design, all functions


are same as vertical models.

PM SERIES---DIGITAL DISPLAY
PM-1430 are single channel models with 5-digit or 4
digit LED display respectively.

1
NON-LINEAR TANK VOLUME CONVERSION FEATURE

NON-LINEAR TANK VOLUME


CONVERSION FEATURE
PM/PB Series support volume adjustment function for
non-linear tanks. By means of a 20-point look-up
table, panel meter calculate tank volume according to
the material level measured.
Bundled with this package, a software is provided,
user simply select tank type shown as below, and
enter necessary dimension, tank volume and 20
control points will be calculated and reported.

TANK TYPE:
Length
Width
Length
Height 1
Height
Diameter
Height 2

Width

Length Width
Diameter
Diameter

Height 1 Height 1
Height
Height 2
Height 2

Diameter
Length Length

Height 1

Diameter Diameter

Height 2

Length

Width
Length
Height 2
Height 1
Height

2
SPECIFICATIONS

Microprocessor Bargraph Microprocessor Digit


Display Panel Meter Display Panel Meter

Appearance

Dimension DIN 3/16 DIN 1/8


(mm) 48 (W) x144 (H) x121.5 (D) 96 (W) x48 (H) x128.5 (D)

Model PB-1471 PM-1430

Display4-Digit,
4 Digits 7-Segment LED
Display
7 Segment LED
101 LED Bargraph Display
4 Relay Setpoints
Totally 6 Set Points
Max. - LED
Display
range -1999 ~ +9999 -1999 ~ +9999

Refer to Input Signal Refer to Input Signal


Input
Selection in Order
Standard

signal Selection in Order


Information (Page 6) Information (Page 8)

Up to 4 Relays Up to 2 Relays
(as standard),SPST (as standard), SPST
Relay (N.O. or N.C. (N.O. or N.C. Jumper
contact
Jumper Selectable), Selectable), 3A@250VAC
3A@250VAC/5A@30VDC /5A@30VDC

Power 85~265VAC or 85~265VAC or


supply 18~36VDC
18~36VDC

Expand Up to
Relay Expand to 6 Relay 4 Relays Max.
Optional

Analog 0/4~20mA or
output 0/4~20mA or 0~10VDC
0~10VDC

Communi-
cation port RS485 MODBUS RS485 MODBUS

Non-Linear 20-Point Linearization 20-Point Linearization


Function for Non-Linear Tanks for Non-Linear Tanks

3
PB-1471 Microprocessor Bargraph Display Panel Meter

FEATURES:
4 Digits LED Numeric Display
101-segment LED Bargraph display
Wide Range of User Definable Scaling Ratio
Modulized input signal boards available for
different applications
Optional Output Boards with Isolated Analog Output
& Relay Output
85V~265VAC or 18~36VDC Switching Power Supply
Support volume adjustment function for non-linear tanks
(optional)

TERMINAL ARRANGEMENTS:

(Option)
Isolated
EXC 24V 1 19 +24V
GND 2 20 GND
Volt Input Signal 3 21 Analog O/P+
Current Input Signal 4 22 Analog GND
Signal GND 5 23
6 24
SPECIFICATIONS 7
8
Dimension (mm) 48 (W) x144 (H) x121.5 (D) DIN 3/16
+
Model PB-1471 9 25 {RS485
SP4
10 26 -
85 ~ 265V AC or 18~36V DC 11 27
Power SUPply Switching Power Supply SP3
12 28
Power supply for sensor DC24V, 50mA SP2
13 29
Option
14 30
4 Digits, 0.36" 7-Segment red LED 15 31
Display SP1
16 32
101 LED Bargraph Display AUX. 17 33
Display POWER SP6
18 34
6 LED set-point indicator 35
SP5
Display Range: -1999 ~ +9999 36
Over Range Display: "1" or "-1"

Range: Refer to Ordering information


Accuracy: 0.1%FS or A1 digit
Temperature coefficient: 200ppm/℃ EXTERIOR/CUTOUT DIMENSIONS
Input signal
ADC Resolution: 4-1/2 digit
Sampling Rate: ( Unit:mm)
4 samples/second/channel
6 (max.)
4 relay (up to 6 relay) 48 45 +0.6 10 (min.)
-0
Relay contact 3A/250V AC or 5A/30V DC
(N.C. / N.O. Jumper selectable)

Analog output 4~20mA, 0~20mA, 2~10V and 0~10V (optional)


144 137.8 138+1
-0
Power comsumption Less then 9VA
Communication port RS485 (optional) Modbus Protocol
Operating condition 0~50℃(20 to 90% RH non-condensed)
Storage condition 0~70℃(20 to 90% RH non-condensed) 9 111 22 10
(min.)

4
PM-1430 Microprocessor Digit Display Panel Meter

FEATURES:
4 Digits LED Numeric Display
Wide Range of User Definable Scaling Ratio
Modulized input signal boards available for
different applications
Optional Output Boards with Isolated Analog Output
& Relay Output
85V~265VAC or 18~36VDC Switching Power Supply
Support volume adjustment function for non-linear tanks
(optional)
IP54 Class front panel

TERMINAL ARRANGEMENTS:

RS485 SP4 SP3


Analog Iso
Out GND + - (NC/NO) (COM) (NC/NO) (COM)
SPECIFICATIONS 11 12 13 14 15 16 17 18 19 20

Dimension (mm) 96 (W) x48 (H) x128.5 (D) DIN 1/8 (Option)

Model PM-1430
85 ~ 265V AC or 18~36V DC
Power supply Switching Power Supply 1 2 3 4 5 6 7 8 9 10
Power supply for sensor DC24V, 50mA
EXC GND SIG (NC/NO) (COM) (NC/NO) (COM)
4 Digits, 0.56" 7-Segment red LED
+24V (IN-) (IN+) AUX.
Display SP2 SP1 POWER
4 LED set-point indicator
Display
Display Range: -1999 ~ +9999
Over Range Display: "1" or "-1"

Range: Refer to Ordering information


Accuracy: 0.1%FS or A1 digit
Temperature coefficient: 200ppm/℃
Input signal
ADC Resolution: 4-1/2 digit
Sampling Rate: EXTERIOR/CUTOUT DIMENSIONS
4 samples/second/channel
( Unit:mm)
96
2 or 4 relay
Relay contact 3A/250V AC or 5A/30V DC
48 22
(N.C. / N.O. Jumper selectable) (min)

Analog output 4~20mA, 0~20mA, 2~10V and 0~10V (optional)


10 118.5
Power comsumption Less then 7VA 45+0.6
-0

Communication port RS485 (optional) Modbus Protocol 44.8

92 +0.8 10 (min)
Operating condition 0~50℃(20 to 90% RH non-condensed) -0

Storage condition 0~70℃(20 to 90% RH non-condensed)

5
MODEL NUMBER / ORDER CODE COMPARISON TABLE
ORDER INFORMATION

Model Number Order Code


PB-1471 PBX11400-B6

11 12 13 16 17 18 19

PBX1 1 4 0 0 - B 6 999 0 0 9999


11 Power Supply
A: 85~265Vac (Next page)
B: 18~36Vdc

12 13 Single channel input


A1: 4~20mA DC with Exc 24V
A2: 0~20mA DC with Exc 24V
A3: 0~200mA DC with Exc 24V
A4: 0~5V DC with Exc 24V
A5: 0~10V DC with Exc 24V
A6: 0-20V DC with Exc 24V
A7: 0-200V DC with Exc 24V
B1: 0~2mA AC RMS
B2: 0~20mA AC RMS
B3: 0~200mA AC RMS
B4: 0~1A AC RMS
B5: 0~5A AC RMS
C1: 0~100mV AC RMS
C2: 0~200mV AC RMS
C3: 0~2V AC RMS
C4: 0~20V AC RMS
C5: 0~200V AC RMS
C6: 0~600V AC RMS
D1: 0~±2 mA DC with Exc 24V
D2: 0~±20 mA DC with Exc 24V
D3: 0~±200 mA DC with Exc 24V
D4: 0~±1Amp DC
D5: 0~±5Amp DC
E1: 0~±20mV DC with Exc 24V
E2: 0~±50mV DC with Exc 24V
E3: 0~±100mV DC with Exc 24V
E4: 0~±200mV DC with Exc 24V

6
ORDER INFORMATION

11 12 13 16 17 18 19

PBX1 1 4 0 0 - B 6 999 0 0 9999

16 Relay contact
A: None
C: 2 Relay
E: 4 Relay
G: 6 Relay

17 Non-Linear function
A: None
B: Non - linear bucket conversion

18 Analog output
A: None
B: 0~10V output
C: 0/4~20mA output

19 Communi-cation port
A: None
B: RS-485

7
MODEL NUMBER / ORDER CODE COMPARISON TABLE
ORDER INFORMATION

Model Number Order Code


PM-1430 PMX11400-E2

11 12 13 16 17 18 19

PMX 1 1 4 0 0 - E 2 999 0 0 9999

11 Power Supply
A: 85~265Vac
B: 18~36Vdc
(Next page)
12 13 Single channel input
A1: 4~20mA DC with Exc 24V
A2: 0~20mA DC with Exc 24V
A3: 0~200mA DC with Exc 24V
A4: 0~5V DC with Exc 24V
A5: 0~10V DC with Exc 24V
A6: 0-20V DC with Exc 24V
A7: 0-200V DC with Exc 24V
B1: 0~2mA AC RMS
B2: 0~20mA AC RMS
B3: 0~200mA AC RMS
B4: 0~1A AC RMS
B5: 0~5A AC RMS
C1: 0~100mV AC RMS
C2: 0~200mV AC RMS
C3: 0~2V AC RMS
C4: 0~20V AC RMS
C5: 0~200V AC RMS
C6: 0~600V AC RMS
D1: 0~±2 mA DC with Exc 24V
D2: 0~±20 mA DC with Exc 24V
D3: 0~±200 mA DC with Exc 24V
D4: 0~±1Amp DC
D5: 0~±5Amp DC
E1: 0~±20mV DC with Exc 24V
E2: 0~±50mV DC with Exc 24V
E3: 0~±100mV DC with Exc 24V
E4: 0~±200mV DC with Exc 24V

8
ORDER INFORMATION

11 12 13 16 17 18 19

PMX 1 1 4 0 0 - E 2 999 0 0 9999

16 Relay contact
A: None
C: 2 Relay
E: 4 Relay

17 Non-Linear function
A: None
B: Non - linear bucket conversion

18 Analog output
A: None
B: 0~ 10V output
C: 0/4~20mA output

19 Communication port
A: None
B: RS-485

9
FlneTek
PB DC SIGNAL INPUT MODULE

This section will elaborate how to adapt to different input signals in the PB series panel meter, by using
the correct jumper and using iSEL command. Panel meter series can accommodate 6 types of
conventional input signals, 20mA, 200mA, 5V, 10V, 20V, 200V, please refer below for setup.

Single Channel Signal Input Module:


(For PB-1471)
01: 4~20mA DC with Excitation +24V
EXC 24V
PIN 1
PIN 2
+ - Common PIN 3
PIN 4
200mA
20mA
200V

10V
20V

5V

CH1 Input PIN 5


PIN 6
PIN 7
PIN 8 PMB-0641

02: 0~20mA DC with Excitation +24V


EXC 24V PIN 1
Common PIN 2
PIN 3
CH1 Input PIN 4
200mA

DC mA
20mA
200V

10V
20V

5V

Common PIN 5
PIN 6
PIN 7
PIN 8 PMB-0640

03: 0~200mA DC with Excitation +24V


EXC 24V PIN 1
Common PIN 2
PIN 3
CH1 Input PIN 4
200mA

DC mA
20mA
200V

10V
20V

5V

Common PIN 5
PIN 6
PIN 7
PIN 8 PMB-0640

04:A5V DC with Excitation +24V


EXC 24V PIN 1
Common PIN 2
CH1 Vinput PIN 3
DC V PIN 4
200mA
20mA
200V

10V
20V

5V

Common PIN 5
PIN 6
PIN 7
PIN 8 PMB-0640

05:A10V DC with Excitation +24V


EXC 24V PIN 1
Common PIN 2
CH1 Vinput PIN 3
DC V PIN 4
200mA
20mA
200V

10V
20V

5V

Common PIN 5
PIN 6
PIN 7
PIN 8 PMB-0640

06:A20V DC with Excitation +24V


EXC 24V PIN 1
Common PIN 2
CH1 Vinput PIN 3
DC V PIN 4
200mA
20mA
200V

10V
20V

5V

Common PIN 5
PIN 6
PIN 7
PIN 8
PMB-0640

07: A200V DC with Excitation +24V


EXC 24V PIN 1
Common PIN 2
CH1 Vinput PIN 3
DC V PIN 4
200mA
20mA
200V

10V
20V

5V

Common PIN 5
PIN 6
PIN 7
PIN 8 PMB-0640

10
FlneTek
PB AC SIGNAL INPUT MODULE

This section will elaborate how to adapt to different input signals in the PB series panel meter, by using the
correct jumper and using iSEL command. Panel meter series can accommodate 6 types of conventional
input signals, 20mA, 200mA, 5V, 10V, 20V, 200V, please refer below for setup.

Single Channel Signal Input Module: (For PB-1471)

A1: 2mA AC Scaled RMS B1: 100mV AC Scaled RMS


PIN 1 PIN 1
PIN 2 PIN 2
PIN 3 Vin ( v ) PIN 3
Iin ( v ) PIN 4 AC mV PIN 4
AC mA
Iin (w) PIN 5 Vin (w) PIN 5
200mA
20mA
2mA

PIN 6 PIN 6

J3
PIN 7 PIN 7
PIN 8 PMB-0672 PIN 8 PMB-0675

A2: 20mA AC Scaled RMS B2: 200mV AC Scaled RMS


PIN 1 PIN 1
PIN 2 PIN 2
PIN 3 Vin ( v ) PIN 3
Iin ( v ) PIN 4 AC mV PIN 4
AC mA
Iin (w) PIN 5 Vin (w) PIN 5
200mA
20mA
2mA

PIN 6 PIN 6
PIN 7 PIN 7
PMB-0672 PMB-0671

2V

200mV
PIN 8 PIN 8

A3: 200mA AC Scaled RMS B3: 2V AC Scaled RMS


PIN 1 PIN 1
PIN 2 PIN 2
PIN 3 Vin ( v ) PIN 3
Iin ( v ) PIN 4 AC V PIN 4
AC mA
Iin (w) PIN 5 Vin (w) PIN 5
200mA
20mA
2mA

PIN 6 PIN 6
PIN 7 PIN 7
PMB-0672 PMB-0671
2V

PIN 8 PIN 8 200mV

A4: 1Amp AC Scaled RMS B4: 20V AC Scaled RMS


PIN 1
PIN 2
Vin ( v ) PIN 3
AC V PIN 4
PIN 1 20V

PIN 2
Vin (w) PIN 5 200V
600V
PIN 6
PIN 3
Secondary PIN 7
PIN 4 PMB-0670
1A PIN 8
PIN 5
Current PIN 6
J3

PIN 7
AC current

PIN 8 PMB-0674
B5: 200V ACScaled RMS
Primary

PIN 1
PIN 2
CH1 Vin ( v ) PIN 3
AC V PIN 4 20V

A5: 5 Amp AC Scaled RMS CH2 Vin (w) PIN 5


200V
600V

PIN 6
PIN 7
PIN 8 PMB-0670

PIN 1
PIN 2
B6: 600V AC Scaled RMS
PIN 3
Secondary
PIN 4 PIN 1
5A PIN 5 PIN 2
Current PIN 6 CH1 Vin ( v )
J3

PIN 3
PIN 7 AC V PIN 4 20V
AC current

PMB-0673
CH2 Vin (w)
200V
PIN 8 PIN 5 600V
Primary

PIN 6
PIN 7
PIN 8 PMB-0670

11
FlneTek
PB DC SIGNAL INPUT MODULE

This section will elaborate how to adapt to different input signals in the PB series panel meter, by using the
correct jumper and using iSEL command. Panel meter series can accommodate 6 types of conventional
input signals, 20mA, 200mA, 5V, 10V, 20V, 200V, please refer below for setup.

Single Channel Signal Input Module:


(For PB-1471)
C1: 2mA DC with Excitation +24V D1: 20 mV DC with Excitation +24V
EXC 24V PIN 1 EXC 24V PIN 1
Common PIN 2 Common PIN 2
PIN 3 Input PIN 3
Input PIN 4 DC mV PIN 4
DC mA

100mV
200mV
20mV
50mV
Common PIN 5 Common PIN 5
200mA
20mA
2mA

PIN 6 PIN 6
PIN 7 PIN 7
PIN 8 PMB-0681 PIN 8 PMB-0680

C2: 20mA DC with Excitation +24V D2: 50 mV DC with Excitation +24V


EXC 24V PIN 1 EXC 24V PIN 1
Common PIN 2 Common PIN 2
PIN 3 Input PIN 3
Input PIN 4 DC mV PIN 4

100mV
200mV
DC mA

20mV
50mV
Common PIN 5 Common PIN 5
200mA
20mA
2mA

PIN 6 PIN 6
PIN 7 PIN 7
PIN 8 PMB-0681 PIN 8 PMB-0680

C3: 200mA DC with Excitation +24V D3: 100 mV DC with Excitation +24V
EXC 24V PIN 1 EXC 24V PIN 1
Common PIN 2 Common PIN 2
PIN 3 Input PIN 3
Input PIN 4 DC mV PIN 4

100mV
200mV
DC mA

20mV
50mV
Common PIN 5 Common PIN 5
200mA
20mA
2mA

PIN 6 PIN 6
PIN 7 PIN 7
PIN 8 PMB-0681 PIN 8 PMB-0680

C4: 1A DC D4: 200 mV DC with Excitation +24V


EXC 24V PIN 1
Common PIN 2
Input PIN 3
DC mV PIN 4
100mV
200mV
20mV
50mV

PIN 1 Common PIN 5


PIN 2 PIN 6
PIN 3
Secondary PIN 7
PIN 4 PIN 8 PMB-0680
1A PIN 5
Current PIN 6
J3

PIN 7
AC current

PIN 8 PMB-0683
Primary

Fully User Scalable

C5: 5A DC

PIN 1
PIN 2
PIN 3
Secondary
PIN 4
5A PIN 5
Current PIN 6
J3

PIN 7
AC current

PIN 8 PMB-0682
Primary

Fully User Scalable

12
FlneTek
PM DC SIGNAL INPUT MODULE

This section will elaborate how to adapt to different input signals in the PM series panel meter, by using the
correct jumper and using iSEL command. Panel meter series can accommodate 6 types of conventional
input signals, 20mA, 200mA, 5V, 10V, 20V, 200V, please refer below for setup.

Single Channel Signal Input Module:


(For PM-1430)
01:4~20mA DC with Excitation +24V

EXC +24V PIN 1 PMB-0030


I Ch1 V

Common PIN 2
DC mA
200mA
20mA
200V
20V
10V
5V

Input PIN 3

PIN 4

02: 20mA DC with Excitation +24V

EXC +24V PIN 1 PMB-0030


I Ch1 V

Common PIN 2
DC mA
200mA
20mA
200V
20V
10V
5V

Input PIN 3

PIN 4

03: 200mA DC with Excitation +24V

EXC +24V PIN 1 PMB-0030


I Ch1 V

Common PIN 2
DC mA
200mA
20mA
200V
20V
10V
5V

Input PIN 3

PIN 4

04: 5V DC with Excitation +24V

EXC +24V PIN 1 PMB-0030

Common PIN 2
DC V
200mA
20mA
200V
20V
10V
5V

Input PIN 3

PIN 4

05: 10V DC with Excitation +24V

EXC +24V PIN 1 PMB-0030


I Ch1 V

Common PIN 2
DC V
200mA
20mA
200V
20V
10V
5V

Input PIN 3

PIN 4

06: 20V DC with Excitation +24V

EXC +24V PIN 1 PMB-0030


I Ch1 V

Common PIN 2
DC V
200mA
20mA
200V
20V
10V
5V

Input PIN 3

PIN 4

07: 200V DC with Excitation +24V

EXC +24V PIN 1 PMB-0030


I Ch1 V

Common PIN 2
DC V
200mA
20mA
200V
20V
10V
5V

Input PIN 3

PIN 4

13
FlneTek
PM AC SIGNAL INPUT MODULE

This section will elaborate how to adapt to different input signals in the PM series panel meter, by using the
correct jumper and using iSEL command. Panel meter series can accommodate 6 types of conventional
input signals, 20mA, 200mA, 5V, 10V, 20V, 200V, please refer below for setup.

Single Channel Signal Input Module:


(For PM-1430)

A1: 2mA AC Scaled RMS B1: 100mV AC Scaled RMS

PIN 1 PMB-0056 PIN 1


PMB-0059

Iin ( v ) PIN 2 Vin ( v ) PIN 2

AC mA PIN 3 AC mV PIN 3
200mA
20mA
2mA

J3
Iin (w) PIN 4 Vin (w) PIN 4

A2: 20mA AC Scaled RMS B2: 200mV AC Scaled RMS

PIN 1 PMB-0056 PIN 1 PMB-0055

Iin ( v ) PIN 2 Vin ( v ) PIN 2

AC mA PIN 3 AC mV PIN 3
200mA
20mA
2mA

Iin (w) PIN 4 Vin (w) PIN 4

2V

200mV
A3: 200mA AC Scaled RMS B3: 2V AC Scaled RMS

PIN 1 PMB-0056 PIN 1 PMB-0055

Iin ( v ) PIN 2 Vin ( v ) PIN 2

AC mA PIN 3 AC V PIN 3
200mA
20mA
2mA

Iin (w) PIN 4 Vin (w) PIN 4


2V

200mV

A4: 1Amp AC Scaled RMS B4: 20V AC Scaled RMS

PIN 1 PMB-0054

PIN 1 PMB-0058
Vin ( v ) PIN 2
20V

PIN 2 200V
AC V PIN 3 600V

1A Secondary PIN 3
Vin (w) PIN 4
J3

Current PIN 4
AC current
Primary

B5: 200V ACScaled RMS

PIN 1 PMB-0054

Vin ( v ) PIN 2
20V

A5: 5 Amp AC Scaled RMS AC V PIN 3


200V
600V

Vin (w) PIN 4

PIN 1 PMB-0057

PIN 2
B6: 600V AC Scaled RMS
Secondary PIN 3
5A
J3

PIN 4 PIN 1 PMB-0054


Current
AC current

Vin ( v ) PIN 2
Primary

20V
200V
AC V PIN 3 600V

Vin (w) PIN 4

14
FlneTek
PM DC SIGNAL INPUT MODULE

This section will elaborate how to adapt to different input signals in the PM series panel meter, by using the
correct jumper and using iSEL command. Panel meter series can accommodate 6 types of conventional input
signals, 20mA, 200mA, 5V, 10V, 20V, 200V, please refer below for setup.

Single Channel Signal Input Module:


(For PM-1430)

C1: 2mA DC with Excitation +24V D1: 20 mV DC with Excitation +24V

PIN 1
PMB-0051 PMB-0050
EXC 24V EXC 24V PIN 1

Common PIN 2 Common PIN 2

100mV
200mV
20mV
50mV
DC mA DC mV
Input PIN 3 Input PIN 3
200mA
20mA
2mA

PIN 4 PIN 4

C2: 20mA DC with Excitation +24V D2: 50 mV DC with Excitation +24V

EXC 24V PIN 1 PMB-0051 PIN 1


PMB-0050
EXC 24V
Common PIN 2 Common PIN 2

100mV
200mV
DC mA

20mV
50mV
DC mV
Input PIN 3 Input PIN 3
200mA
20mA
2mA

PIN 4 PIN 4

C3: 200mA DC with Excitation +24V D3: 100 mV DC with Excitation +24V

EXC 24V PIN 1 PMB-0051 EXC 24V PIN 1 PMB-0050

Common PIN 2 Common PIN 2

100mV
200mV
DC mA

20mV
50mV
DC mV
Input PIN 3 Input PIN 3
200mA
20mA
2mA

PIN 4 PIN 4

C4: 1A DC D4: 200 mV DC with Excitation +24V

EXC 24V PIN 1 PMB-0050


PIN 1 PMB-0053
Common PIN 2
100mV
200mV
20mV
50mV

PIN 2
DC mV
Input PIN 3
Secondary PIN 3
1A PIN 4
J3

CT
PIN 4
DC current
Primary

Fully User Scalable

C5: 5A DC

PIN 1 PMB-0052

PIN 2

Secondary PIN 3
5A
J3

CT
PIN 4
DC current
Primary

Fully User Scalable

15
FlneTek
TEMPERATURE CONTROLLER INTRODUCTION

PRODUCT INTRODUCTION
The 76 series programmable temperature controller
is FineTek's high-end controller. Equipped with a
14 bit analog/ digital converter core processor and
with FUZZY and improved PID calculation
microprocessor, the controller is capable of fast and
accurate performance with reliable results. Double
row of 4 digit displays indicates Present Value and
Set Value (except PT7610), enables user friendly PT-7610
readings and coupled with 3 buttons operation, it (48x24)
makes operating the controller very convenient.

High Sampling Rate, High Accuracy


Sampling rate of 4 times per second (equivalent to
0.25sec per sampling) enables the controller to
achieve high accuracy readings and accurate
operations.

PID + FUZZY Control


Addition of FUZZY technology to PID control
enables the controller to use the shortest time
required as well as the smallest transients in order
to achieve stability at the set value required by the PT-7620
user. (48x48)

Auto-tuning
Artificial intelligence technology enables the
controller to calculate the most efficient parameters
Lock Protection for Control Parameters
to suit each and every application, thereby
Provides 3 levels of lock protection available should
increasing the efficiency of the process to the
the user choose to lock the parameters in case of
maximum.
parameters change by accident.

Heating / Cooling Bi-directional Control


Enables the user to select between both heating
Temp. and cooling processes, reduces inconveniences of
PID
single direction control methodology and reduces
inventory.
SV
Universal Input
Support the input signal of industry measurement,
program setting through software, facility in
installation and operation.

Switching Power Supply


Time Accepts 100 ~ 240VAC, 50/60Hz power supply, able
Auto Tuning to prevent controller from being affected by
interferences due to ripples in power supply.

RS485 (Modbus) Communication:


Both RTU and ASCII communication modes for
Sensor Break Alarm: selection
If the temperature sensor malfunctions / breaks, an
alarm figure will be displayed on the panel to notify
users.

16
FlneTek
SPECIFICATIONS

CONTROL FUNCTION SIGNAL INPUT


ON/OFF, PID+Auto Tuning, Signal Input Range Accuracy
Control Method
PID+Auto Tuning+Fuzzy K Type -200~1370BC A0.3% A1digit
Fraction Value 0~9999 K Type -128.0~500.0BC A0.3% A1digit
J Type -200~1200BC A0.3% A1digit
Integral time 0~9999

Thermocouple
J Type -128.0~500.0BC A0.3% A1digit
Differential time 0~9999
T Type -200~400BC A0.3% A1digit
Alarm / Output T Type -128.0~400.0BC A0.3% A1digit
Hysteresis setting 0~9999 E Type -200~800BC A0.3% A1digit
Sampling Interval 0.25s R Type 0~1760BC A0.3% A1digit
Output S Type 0~1760BC A0.3% A1digit
Control Cycle 0.1~999.9s B Type 0~1820BC A0.3% A1digit
N Type -200~1300BC A0.3% A1digit
PT Type -200~850BC A0.2% A1digit
PT Type -199.9~850.0BC A0.2% A1digit
RTD
ALARM FUNCTION
JPT Type -200~500BC A0.2% A1digit
Absolute Value Alarm, JPT Type -199.9~500.0BC A0.2% A1digit
Alarm Types 0~50mV -1999~9999 A0.3% A1digit
Discrepancy Alarm,Area Alarm
Direct Voltage

Set Value 0~99s 0~1V -1999~9999 A0.3% A1digit


0~5V -1999~9999 A0.3% A1digit
SPST- ON, 3A-250VAC
Alarm Output 1~5V -1999~9999 A0.3% A1digit
(Resistance Load)
0~10V -1999~9999 A0.3% A1digit
Alarm Activation /
Action Method De-Activation delay 2~10V -1999~9999 A0.3% A1digit
Current

0~20mA -1999~9999 A0.3% A1digit


Direct

Signal Output Relay Output


4~20mA -1999~9999 A0.3% A1digit
≒ Accuracy A8BC for R and S in 0~500BC range
≒ For 0~600BC range, it does not guarantee accuracy on B type.
MAIN CONTROL OUTPUT

Specifications Model
7610 7620
Module
SPST-ON SPST-ON
Relay 3A/250Vac 3A/250Vac
Pulse Output (SSR) 0/12Vdc (NPN), Max.20 mA
Analog 4~20 mA
(Re-transmission) 0~10Vdc Min.600W

2nd CONTROL OUTPUT

Specifications Model
7610 7620
Module
SPST-ON
Relay
3A/250Vac
Pulse Output (SSR) 0/12Vdc (NPN), Max.20 mA
Analog 4~20 mA
(Re-transmission) 0~10Vdc Min.600W

17
FlneTek
STANDARD SPECIFICATIONS COMMUNICATIONS
Power Supply 100~240Vac, 50/60Hz
Communication
Power Consumption 7VA Interface RS-485
Input Resistance > 1M W Communication
Input Compensation -1999~9999 Modbus RTU or ASCII
Protocol
Digital Filter 1~50 Times
8 bits, Bit check: odd/even/none.
International Standard CE Data Format Stop Bit: 1 or 2bits
Settings Range -1999~9999
Communication 600, 1200, 2400, 4800, 9600,
Speed 19200 bps
DISPLAY Address 1~255
4 digit of 7 segment display, Accuracy A0.3%A1 digit
Digit Size Model
7610 7620 OTHER FUNCTIONS
Display
PV (red) 0.31" 0.36" Temperature
SV (green) 0.28" Sensor Break Error display on panel
Detection
LED Indicators Parameters Lock 3 tier protection
Digit Size Model
Adjustable: Input signal, alarm
7610 7620
Display 1st Tier setpoint, set values, control type
(All parameters)
Control Output X1 X2
Alarm Output X1 X1 Adjustable: alarm setpoint, set
2nd Tier values, control type (Auto-tuning)
Celsius Display X1 X1
Fahrenheit Display X1 3rd Tier Fully lock

BREAKOUT PROTECTION
Memory Retention EEPROM

OPERATING & STORAGE ENVIRONMENT


Operation Temperature 0~50BC
Operation Humidity 20~85%RH
Storage Temperature -20B~60BC

STRUCTURE

Installation Panel Mounted using 2 locking clips


Casing
Plastic
Material
Dimensions Refer to page 19
Colour Black
Protection 7610 7620
Rating IP-54 IP-65

18
FlneTek
DIMENSION / PANEL CUTOUT & WIRING DIAGRAM

DIMENSION / PANEL CUTOUT & WIRING DIAGRAM


PT-7610:48mm(W) x 24mm(H) x 98.5mm(D)

G mA F

NO B b A
48 8 90.5 RTD
ALM
TC/V F G
24 21.6
7 8 9 10 11 12

58 min.
1 2 3 4 5 6
G F
RS-485 NO 100~240V AC
OUT
46 min.

PT-9910-S10 PT-9910-S20 PT-9910-S40


22.2 +0.3
-0 PT-9910-S30
Relay Output 0~20mA Output 12VDC Voltage pulse
0~10V Output
45
+0.6 F F
-0
4 4 4
OUT DC 0~20mA 12VDC
3 3 G
3 G

PT-7620:48mm(W) x 48mm(H) x 101mm(D)


48 9 92 PT-9920-S10 PT-9920-S20 PT-9920-S40
PT-9920-S30
Relay Output 0~20mA Output 12VDC Voltage pulse
0~10V Output
48 44.8 F F
4 4 4
OUT1 DC 0~20mA 12VDC
3 3 G 3 G

55 min.
F
RS 18 6 100~240V AC
485
11 G 17 5
RTD F F
G B 10 EXC 16 4
TC/V OUT1
F 24V
mA b 9 G 15 3 G
F
67 min.
F A G 8 OUT2 14 2
ALM
G
13 1

45 +0.6
-0
F F
14 14 14
OUT2 DC4~20mA 12Vdc
45+0.6
13 13 13
-0 G G

19
FlneTek
MODEL NUMBER / ORDER CODE COMPARISON TABLE

Model Number Order Code


PT-7610 SFX10000-F
PT-7620 SFX10000-A

20
FlneTek
ORDER INFORMATION

09 10 11 12 13 14 15 16

PTX1 0 0 0 0 -99999999

09 Model
A: 48x48
F: 48x24

10 Power supply
A: 100~240Vac, 50/60Hz
B: 20~36Vdc

11 Output 1
0: None E: 4-20mA DC analog retransmit
A: Relay control output F: 0-10V DC analog retransmit
B: 4-20mA DC control output G: 2-10V DC analog retransmit
C: 0-10V DC control output H: 0-5V DC analog retransmit
D: Voltage pulse (12Vdc) for SSR drive I: 1-5V DC analog retransmit

12 Output 2
0: None E: 4-20mA DC analog retransmit
A: Relay control F: 0-10V DC analog retransmit
B: 4-20mA DC control output G: 2-10V DC analog retransmit
C: 0-10V DC control output H: 0-5V DC analog retransmit
D: Voltage pulse (12Vdc) for SSR drive I: 1-5V DC analog retransmit

13 Alarm output
0: None
A: 1 Set
B: 2 Set

14 Communication
0: None
A: RS-485

15 Auxiliary power
0: None
A: 24VDC/50mA

16 Terminal protector
0: None
C: Requested

21
FlneTek
Global Network

Germany
China

U.S.
Taiwan U.S.
Singapore
Malaysia

Indonesia

Asia North America Europe


Taiwan California, U.S. Germany
FineTek Co., Ltd. - Taipei Head Quarter Aplus Finetek Sensor Inc. - US Office FineTeK GmbH - Germany Office
No.16, Tzuchiang St., Tucheng Industrial Park 355 S. Lemon Ave, Suite D, Walnut, Frankfurter Str. 62, OG D-65428
New Taipei City 236, Taiwan CA 91789 Ruesselsheim, Germany
TEL: 886-2-2269-6789 TEL: 1 909 598 2488 TEL: +49-(0)6142-17608-0
FAX: 886-2-2268-6682 FAX: 1 909 598 3188 FAX: +49-(0)6142-17608-20
EMAIL: [email protected] EMAIL: [email protected] EMAIL: [email protected]

China Illinois, U.S. Mütec Instruments GmbH - Germany Office


Fine automation Co., Ltd. - Shanghai Factory Aplus Finetek Sensor Inc. Bei den Kämpen 26
No.451 DuHui Rd, MinHang District, Shanghai, TEL: 1 815 632-3132 21220 Seevetal-Ramelsloh, Germany
China 201109 FAX: 1 815 716 8464 TEL: + 49 (0)4185-8083-0
TEL: 86-21-6490-7260 EMAIL: [email protected] FAX: + 49 (0)4185-8083-80
EMAIL: [email protected] EMAIL: [email protected]

Singapore
FineTek Pte Ltd. - Singapore Office
No. 60 Kaki Bukit Place, #07-06 Eunos
Techpark 2 Lobby B, Singapore 415979
TEL: 65-6452-6340
EMAIL: [email protected]

Indonesia
FineTek Co., Ltd. - Indonesia Office
Ruko Golden 8 Blok H No.38
Gading Serpong, Tangerang, Indonesia
TEL: 62 (021)-2923-1688
EMAIL: [email protected]
Distributor:
Malaysia
FineTek Co., Ltd. - Malaysia Office
8-05, Plaza Azalea, Persiaran Bandaraya,
Seksyen 14, 40000 Shah Alam, Selangor, Malaysiac
TEL: 603-5524-7168
EMAIL: [email protected]

08-PMTE-111517

You might also like