Module 7
Module 7
MODULE-7
DESIGN OF TWO-WAY SLABS WITHOUT BEAMS
(FLAT PLATES AND FLAT SLABS)
➢ Background
➢ Example
➢ Introduction
➢ Example
➢ References
Flat plate floor slab, carried directly by columns without Flat slab floor, without beams but with slab thickness increased at the
beams or girders. columns and with flared column tops to provide for local concentration
of forces.
➢ Slab panels are analyzed having 12” of width in longer and shorter directions.
➢ Can be used for two-way slab system with and without beams or walls.
➢ Moments in the frames are distributed in the longitudinal and transverse direction.
➢ It becomes relatively more challenging when analyzing slabs that are supported through
beams or walls. Therefore, it is primarily useful for slabs without beams.
➢ Although the provisions for DDM present in ACI 318-14 Section 8.10 have been eliminated
from the latest version (ACI 318-19), it can still be used as per ACI R6.2.4.1.
➢ Limitations
N-S frame
E-W frame
E-W frame
Exterior
Interior Interior
N-S frame
Wu = 1.2 DL +1.6LL
Wu = 1.2*o.125 + 1.6 *0.144
Wu = 0.38 ksf
l1 = 25’
20 14
l2 = + 0.5 = 10.58′
2 12
ln = 25 – 14/12 = 23.83’
20 14
CS = 4
+ 0.5 12
= 5.58′
𝑙2−𝐶𝑆
Middle strip = MS = = 5′
2
𝑾𝒖 𝒍𝟐𝒍𝒏𝟐 𝟎.𝟑𝟖𝟏 ∗𝟏𝟎 ∗𝟐𝟑.𝟖𝟑 𝟐
𝑴𝒐 = = = 𝟐𝟕𝟎. 𝟒𝟒′ 𝒌𝒊𝒑𝒔
𝟖 𝟖
2.614𝑀𝑢 2.614𝑥1
➢ 𝑎 = 𝑑 − 𝑑2 − = 8.5 − 8.52 − = 0.0042"
𝑓 ′𝑏 3𝑥12
𝑐
𝑀𝑢 1
➢ 𝐴𝑠 = 𝑎 = 0.0042 = 0.0022 𝑖𝑛2
∅𝑓𝑦(𝑑− 2 ) 0.9𝑥60(8.5− )
2
Smax = 2hf
➢ In two-way slabs with beam supports, bars in shorter direction are placed closer to the surface
due to greater moments in the shorter direction.
➢ However, for flat plates, long-direction bars in middle and column strips are placed nearer the
surface due to larger moments in the longer direction.
➢ ACI 8.7.4.2.1 requires that all bottom bars within the column strip in each direction be
continuous or spliced with length equal to 1.0 ld , (For development length see ACI 25.4.2.3 or
Nelson 13th Ed, page 172 chapter 5 or mechanical or welded splices).
Continuity of Bars
➢ ACI 8.7.4.2.2 requires that at least two of the column strip bottom bars in each direction must
pass within the column core and must be anchored at exterior supports.
➢ Standard Bar Cut off Points (Practical Recommendation) for column and middle strips both are shown
below.
➢ ACI 8.7.3.1.2 mandates reinforcement at exterior corners on the top and bottom of the slab, extending
one-fifth the longer span of the corner panel in both directions as shown in the figure.
➢ The positive and negative reinforcement should be of size and spacing equivalent to that required for
maximum positive moments (per foot of width) in the panel.