PPT_ BEE Unit 4
PPT_ BEE Unit 4
https://www.studymedia.in/fe/notes
Single Phase Transformer
Unit IV(A)
Assistant Prof B.S Bobdey
Reasons:-
ϕ=ϕm sinωt
Φ - Flux
Φm - maximum value of flux
N1 - Number of primary turns
N2 - Number of secondary turns
F - Frequency of the supply voltage
E1 - R.m.s value of the primary induced e.m.f
E2 - R.m.s. value of theOther
secondary induced
Subjects: e.m.f
https://www.studymedia.in/fe/notes
Contd...
From faraday’s law of electromagnetic induction
Average e.m.f per turns =
dϕ = change in flux
dt = time required for change in flux
The flux increases from zero value to maximum value ϕm in 1/4f of the time period
That is in 1/4f seconds
The change of flux that takes place in 1/4f seconds = ϕm-0 = ϕm webers
In an ideal transformer
V1I1 = V2I2
V1 and V2 are the Vt of primary and secondary by using KVA rating we can calculate I1
and I2.
Iron or Core losses, Pi = Hysteresis loss + Eddy current loss = Constant losses(Pi)
The hysteresis loss can be minimized by using steel of high silicon content
Whereas eddy current loss can be reduced by using core of thin laminations.
Other Subjects: https://www.studymedia.in/fe/notes
Copper losses (Pcu)
These losses occur in both the primary and secondary windings due to their ohmic
resistance. These can be determined by short-circuit test. The copper loss depends on the
magnitude of the current flowing through the windings.
We know that copper loss in a transformer depends on current and iron loss depends on
voltage.
Therefore, the total loss in a transformer depends on the volt-ampere product only and not
on the phase angle between voltage and current i.e., it is independent of load power factor.
For this reason, the rating of a transformer is in kVA and not kW.
Other Subjects: https://www.studymedia.in/fe/notes
EQUIVALENT RESISTANCE
1) It would now be shown that the resistances of the two windings can be transferred to
any one of the two winding.
2) The advantage of concentrating both the resistances in one winding is that it makes
calculations very simple and easy because one has then to work in one winding only.
3) Transfer to any one side either primary or secondary without affecting the
performance of the transformer
The load is varied from no load to full load in desired steps. All the time, keep
primary voltage V1 constant at its rated value with help of variac and tabulated the
reading.
● The size of the auto transformer ● The leakage flux between the primary and
● The saving in cost of the material secondary windings is small hence the
● An auto transformer has higher efficiency impedance is low.
● Auto transformer has better voltage ● it is not possible to earth neutral of one side
regulation only
● It is more difficult to maintain the
electromagnetic balance of the winding
when voltage adjustment tappings are
provided
➢ Balance load: In this type the load in all phase are equal in magnitude. It
means that the load will have the same power factor equal currents in them.
➢ Unbalance load: In this type the load in all phase have unequal power
Other Subjects: https://www.studymedia.in/fe/notes
factor and currents.
Important Definition
➢Phase Voltage : It is defined as the voltage across either phase winding or
load terminal. It is denoted by Vph. Phase voltage VRN, VYN and VBN are
measured between R-N, Y-N, B-N for star connection and between R-Y, Y-B,
B-R in delta connection.
➢ Balance load: In this type the load in all phase are equal in magnitude. It
means that the load will have the same power factor equal currents in them.
➢ Unbalance load: In this type the load in all phase have unequal power
Other Subjects: https://www.studymedia.in/fe/notes
factor and currents.
Important Definition
➢Phase Voltage : It is defined as the voltage across either phase winding or
load terminal. It is denoted by Vph. Phase voltage VRN, VYN and VBN are
measured between R-N, Y-N, B-N for star connection and between R-Y, Y-B,
B-R in delta connection.