PX3005-DIFF

Pressure Transmitter with Display,


Rangeable Wet/Wet Differential

Product Details
The Omega differential PX3005-DIFF is a compact,
rangeable, pressure transmitter ideal for monitoring
pressures in process automation, hydraulic systems,
compressors, pumps, and in tank level applications where
consistent, reliable pressure measurement is essential.
The PX3005-DIFF utilizes a unique encapsulation
construction of a MEMs piezoresistive pressure sensor
coupled to an advanced microprocessing to provide
superior accuracy and performance.

The unique construction enables high line pressure


operations and superior protection from pressure
overloads. The rugged 316 stainless-steel enclosure is
IP67 rated making it suitable for wash down environments.
A 5-digit backlit LCD allows for a full precision
representation of process variable. Available in ranges
from 1 to 1,500 psi, the intelligent transmitter module
allows for configuration of the 4 to 20 mA signal, display of
input or output, and choice of 19 measurement units. The
output signal can be adjusted to re-arrange the transmitter
or “tare” unwanted fluid head preloads. Rangeability is
capable of adjusting zero and span are from -100 to 100%
FS URL (Upper Range Limit) with a minimum span of 30%
URL. This means a 15 psi transducer can have the zero
set between -15 to FS 15 psi. For example, zero could be
set for -15 psi and maximum 15 psi so the output would be
Pressure Pressure
4 mA at -15 psi, midpoint 12 mA would be 0 psi and 20 Product Number Range Type
mA would be 15 psi.
PX3005-25WDWBI -25 to 25 inH2O Differential
Features PX3005-160WDWBI -160 to 160 inH2O Differential
• 0.075% Accuracy PX3005-1KWDWBI -1,000 to 1,000 Differential
• Linear or Square Root Output inH2O
• Adjustable Pulsation Dampening PX3005-150DWBI -70 to 150 psi Differential
• LCD Displays Either Process Variable, mA, or % PX3005-400DWBI -70 to 400 psi Differential
• Nineteen User Selectable Engineering Units
PX3005-1.5KDWBI -70 to 1,500 psi Differential
• IP67 316 SS Enclosure

1
Specifications
Turndown = nominal range of the device / set span of device
EXAMPLE: a PX3005-1KWDWBI with set span of 500"H2O TD = 1000"H2O/500"H2O = 2
Accuracy (NLHR, 20°C ±5°C): Power Consumption:
±0.075TD% SPAN 500mW(20.8mA output @ 24VDC)
(Square root output accuracy is 1.5 times linear output accuracy) Operating Temperature:
Long Term Stability: -20 to 70°C (-4 to 160°F)
±0.2% URL/60 months Storage Temperature:
Ambient Temperature Effects -20 to 80°C (-4 to 176°F): -40 to 85°C (-40 to 185°F)
±(0.1 +0.1TD)% SPAN Media Temperature:
Static Pressure Effects: -40 to 120°C (-40 to 250°F)
Effect on zero ±0.15TD % SPAN/10MPa (1450 psi); Effect Environmental Rating:
IP67
Power Supply Effects: Media:
± 0.005TD% SPAN/V (Zero and Span) Fluids and gasses compatible with 316 SS
Mounting Position Effects: Process Connection/Material:
¼" -18NPT F/316 SS
Install error less than 400Pa (1.60” H2O) can be
Electrical Connection:
corrected by PV = 0 reset 4 pin male M12
Vibration Effects: Isolating Diaphragm:
GB/T 1827.3/IEC61298-3 tests, 20g (5 to 2000 HZ, max 316L SS
<±3 mm), <0.1% URL Sensor Fill Fluid:
Supply Voltage: Silicone Oil
10.5 to 55VDC Sensor Seal:
Output Signal: O-ring, FKM
4 to 20mA Two wire, linear or square root output selectable Housing Material:
Sensor Response Time: 316 SS
200 mS Weight:
Damping Time: Net Weight: about 3kg (without mounting bracket and
Selectable, 0 to 100 S process connection adaptor)
Load Resistance Ω:
<(U-10.5)/0.021
Transmission Distance:
< 1000m

Range Limit Table


Static Pressure Hi Side Over Lo Side Over
Nominal Value Minimum Span UPPER (URL) LOWER (LRL)
Limit Range Limit Range Limit
Mbar "H2O Mbar "H2O Mbar "H2O Mbar "H2O Bar Psi Bar Psi Bar Psi
60 25 0.02 0.8 60 25 -60 -25 250 3600 250 3600 160 2300
400 160 0.04 1.6 400 160 -400 -160 400 5750 250 3600 160 2300
2500 1000 0.25 10 2500 1000 -2500 -1000 400 5750 250 3600 160 2300
Bar Psi Bar Psi Bar Psi Bar Psi Bar Psi Bar Psi Bar Psi
10 150 0.1 1.5 10 150 -5 -70 400 5750 250 3600 160 2300
30 400 0.3 4 30 400 -5 -70 400 5750 250 3600 160 2300
100 1500 1 15 100 1500 -5 -70 400 5750 250 3600 160 2300