0% found this document useful (0 votes)
57 views

Temperature Humidity Controller Manual

Uploaded by

Nur Cholis
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
57 views

Temperature Humidity Controller Manual

Uploaded by

Nur Cholis
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 23

259

Temperature & Humidity Controller

Installation and operation instruction V1.2

ACREL CO.,LTD
Declaration

No part of this publication may be reproduced, stored in a retrieval system, or

transmitted in any form by any means, electronic, mechanical photocopying,

recording,or otherwise without prior permission of AcreL . All rights reserved.

This company reserve power of revision of product specification described in

this manual, without notice. Before ordering, please consult local agent for the

latest specification of product.


Contents

Foreword

1 General.................................................................................................................................................. 1
2 Operational principle.............................................................................................................................1
WHD Series Intelligent Temperature & Humidity Controller

1 Type explanation.................................................................................................................................... 2
2 Technical data........................................................................................................................................ 3
3 Product specification and functions...................................................................................................... 3
4 Wiring.....................................................................................................................................................5
5 Product operation manual.......................................................................................................................7

6 Communication manua.........................................................................................................................13
Sensor

1 General................................................................................................................................................. 20

2 Operational principle............................................................................................................................ 20
Foreword: Temperature & Humidity Controller Brief introduction

1 General

The controller for temperature and humidity is suitable for adjustment and control of temperature and humidity

in equipments of high voltage switchgear, terminal box, ring network panel, box transformer substation etc. It can

effectively protect relevant equipment from faults resulting from excessive low or high temperature, creepage or

flashover etc.from humidity or condensation.

These products meet the requirements of GB/T 15309-1994.

2 Operational principle

The controller for temperature and humidity mainly consists of three parts of transmitter, controller, heater(or
fan etc.), its operational principle is shown as following:

The message of temperature and humidity in the box is detected by the sensor and analyzed by the controller:
When environmental temperature, humidity is up to the presetting value or exceed the presetting value, the controller

is giving related signal to contects of relay, then the heater(or fan) is energized and working to heat of dehumidifying;

after environmental temperature,humidity is well below the presetting value,the heater(or fan) is deednergized and

stop working. In addition to its basic functions, the specific product with different type possess secondary functions

such as alarming output for wire-breaking,communication,forced heating etc.

1
WHD Series Intelligent Temperature & Humidity Controller
1 Type explanation

WHD - -

Adding function:C-RS485 port;M-transmitting output;


J-alarming output;blank-nothing

Control function selection:11-one channel temperature,humidity


22-two channels temperature,humidity
33-three channels temperature,humidity
outline

outline code panel frame


48 square 48*48
72 square 75*75
46 rectangular 120*60
20R Guide rail type DIN35mm

Product series code:intelligent temperature & humidity controller


Note:

1.Number 0f temperature, humidity(or temperature) sensor to be connected with WHD48,WHD72,WHD20R,

WHD46 is up to 1,2, 3 respectively;

2.Every sensor match with two control output contacts(passive), connected with heater and fan respectively,the

heater is used for rising temperature or removing moisture,the fan is used for decreasing temperature;

3.uxiliary function of WHD46:RS485 communication,alarming output function and transmitting function. Only

one can be selected.

Auxiliary function of WHD48:RS485 communication.

Auxiliary function of WHD72:Alarming output function,RS485 communication and transmitting function.The

latter two can only be selected.

Auxiliary function of WHD2OR:RS485 communication and alarming output function.Both can be selected at

the same time.

"- C"for communication,"-J"for alarming,"-M"for transmitting.

4.The connecting wire between sensor and controller must use four-core shielded cable. And its maximum

length must not exceed 20 m.

2
2 Technical data

Technical parameter Value


Temperature -40.0℃~99.9℃
Measuring range
Humidity 0%RH~99%RH
Temperature ±1℃
Precision
Humidity ±5%RH
Transmitting output DC 4~20mA or DC 0~20mA

Heating for
-40.0℃~40.0℃
Temperature rising
Set range of Blowing for
controlling temperature 0.0℃~99.9℃
parameter decreasing
Humidity control 20%RH~90%RH

output contact capacity 5A/AC250V

Start/stop gap 5

Communication port RS485,MODBUS(RTU) treaty


Voltage AC/DC 85-265V
Auxiliary power Basic power consumption(≤0.8w)+
Consumption
relay power consumption(each channel≤0.7w)
Insulation resistance ≥100MΩ
power with shell,touchable metal parts/
power-frequency withstand voltage power with other terminal group 2kV/1min(AC,RMS)

average work time without stoppage ≥50000 hours

Temperature -20℃~+60℃
Working condition
Humidity ≤95%RH,without condensation and corrosive gas
(controller)
Altitude ≤2500m

Start/stop gap: In the control process,for the execution part (heater or fan) , the difference between starting

temperature( humidity) and stopping temperature (humidity).

3 Product specification and functions

WHD48 Type with auxiliary function:signal communication"-C"


Type Function Sensor Mounting mode Outline,size
(Pcs)
One channel temperature,
WHD48-11 humidity control WH-3(1) Embedded
WHD48-22 Two channel temperature, WH-3(1) Catout:45x45
humidity control WH-3T(1)

3
WHD46 Type with auxiliary function:fault alarm"-J",signal communication"-C",transmission"-M"
Type Function Sensor Mounting mode Outline,size
(Pcs)
One channel temperature,
WHD46-11 humidity control WH-3(1) Embedded
Catout:116x56
Two channels temperature,
WHD46-22 humidity control WH-3(2)

Three channels temperature,


WHD46-33 humidity control WH-3(3)

WHD72 Type with auxiliary function:fault alarm"-J",signal communication"-C",transmission"-M"


Type Function Sensor Mounting mode Outline,size
(Pcs)
WHD72-11 One channel temperature, WH-3(1) Embedded
humidity control
Catout:67x67
WHD72-22 Two channels temperature, WH-3(2)
humidity control
WHD72-33 Three channels temperature, WH-3(2)
humidity control
WH-3T(1)

WHD20R with auxiliary function:fault alarm"-J" ,signal communication"-C",both are optional


Type Function Sensor Mounting mode Outline,size
(Pcs)
WHD20R-11 One channel temperature, WH-3(1) guide rail
humidity control type:DIN35mm
WHD20R-22 Two channels temperature, WH-3(2)
humidity control
WHD20R-33 Three channels temperature, WH-3(2)
humidity control
WH-3T(1)

4
V+ CLK Data V- FUSE

通讯“-C”
3 4 5 6 2 1 A B

4 Wiring mode
30 31
18 17Type:
WHD48 16 15 30 31
WH-3T
加热控制 风扇控制
V+ CLK Data V-
(无源接点) (无源接点)
Heating control Fan control
(passive contact)(passive contact) WH-3 Auxiliary power
V+ CLK Data V- FUSE

Communication〝-C〞
3 4 5 6 2 1 A B

30 31
18 17 16 15 30 31

Heating control Fan control


(passive contact)(passive contact)

WHD72 Type

WH-3T communication"-C"
V+ CLK Data V- A B

WH-3 WH-3
Auxiliary power
Alarm contact 30 31
FUSE V+ CLK Data V- V+ CLK Data V-
transmission"-M"
1 3 4 5 6 7 10 1+ 2+ COM
2 41 42 8 9

30 31 32
15 16 17 18 19 20 21 22 NC 30 31 32 Alarm"-J"

Fan control Fan control Heating control Heating control


(passive contact)(passive contact)(passive contact) (passive contact)
41 42

5
WHD20R Type:

Heating control Heating control Fan control Fan control Alarm contact Auxiliary power
(passive contact) (passive contact) (passive contact)(passive contact)
FUSE
communication"-C"
A B
19 20 21 22 15 16 17 18 41 42 1 2
31
30
Alarm"-J"
30 31 32 NC 6 5 4 3 10 9 8 7

RS485 Contact V+ CLK Data V- V+ CLK Data V-


WH-3
41 42
WH-3

V+ CLK Data V-
WH-3T

WHD46 Type:

FUSE
1

Auxiliary power
2
32

RS485、Transmitting、
15
30

Alarm Contact
Heating control
(passive contact)
31

16

communication"-C"
A B
FUSE
17

1
V+

Heating control
辅助电源
(passive contact)
30 31
CLK Data

18

Auxiliary power
4
WH-3

Transmitting"-M"
2

COM 1+ 2+
19
5

Heating control
(passive contact) 30 31 32
20

32
V-

Alarm"-J"
21
V+

加热控制I
7

通讯、变送、报警接点 Fan control


15

(无源接点)
30
CLK Data

(passive contact)
WH-3

RS485、Transmitting、
22
8

Alarm Contact 32 30Heating control


(passive contact)
23
9

31

16

Fan control 通讯“-C”


(passive contact)
10

A B
24
V-

加热控制II
17
11

25
V+

V+ 26 CLK

(无源接点)
Fan control
Heating control
30 31
CLK Data

12

(passive contact)
WH-3

(passive contact)
18
4
WH-3
13

变送“-M”
加热控制III COM 1+ 2+
Data
14
V-

19
5

(无源接点)
Heating control
(passive contact) 30 31 32
20
V-

风扇控制I 报警“-J”
21
V+

7
An example of wiring for the communication part is shown below:

Correct wiring method:the communication cable shield is connected to the ground.

1# 2# 32#
. . .

485A

485B

485A

485B

485A

485B
R
computer
Host

485A

485B

Two-core shielded wire,


shielded to the ground

It is recommended to add a matching resistor between A and B of the end meter,and the resistance range is 120

Ω-10KΩ。

5 Product operation manual

5.1 Display introduction


5.1.1 Front diagram

7
5.1.2 Legend explanation

No. Name Status Explanation

temperature Area Display current-measured temperature value,range:-40.0℃~


1 XX.X℃
Temp.area 99.9℃ Display menu and data for keystroke programming

2 Channels X Display current-measured channels,rang:1~3

3 Humidity area XX% Display current-measured humidity value,range:20%~90%

Indicator Working state of 1,2,3,channels,heating (HEAT),


4 Working status
lightering Blowing (FAN),fault of heating (BREAK)

5 SET Pressing Selecting operational function,set up programming

Pressing Look over data or change data


6 Left directional key Keep Keep Pressing the key about 3 seconds,
Pressing all channels are in heating

Pressing Look over data or change data


7 Right directional key Keep Keep Pressing the key about 3 seconds,
Pressing all channels are in blowing

8 ENTER key Pressing Confirm function or go to next menu

5.2 System powered

After wiring correctly according to the instraction,power on and enter into the measuring condition

5.3 Working status

5.3.1 Measurement

Under measuring condition , Area 1,2, 3 display currently: measuring channel and temperature value,humidity

value , temperature value,humidity value circling measurement and display of three sensor's channels.

5.3.2 Control

When environmental temperature value or humidity value satisfy the presetting working condition , starting the

heater or fan, while corresponding indicator lights (Area4) , when the heater is failure, working without as per the

normal working condition, the corresponding indicator for heating-fault lights to give alarming.

5.3.3 Control test

Under the normal working condition, hold pressing the left directional key about 3 seconds,all the allowed

channels are in heating; hold pressing the right directional key over 3 seconds,all the allowed channels are in

blowing .
8
5.3.4 Alarm

When the heater is failure,working without as per the normal working condition, the corresponding indicator for

heating-fault lights to give alarming.when the temperature exceeds the set value,the data of corresponding channel

flashes. Reset when the meter itself fails.

5.4 System setting mode

5.4.1 Entry/exit system setting mode

Under the normal working condition,hold pressing the SET key about 3 seconds,entry in system setting mode,

stroke ENTER and input the pass words , the deliver default value as 0000, if pass words is correct (display YES ) ,

enter into the main menu automatically.

After enter into the main menu , Area 1 display "CH1", stroke ENTER, enter into the working parameter setting

of channel 1, press the left/right key to switch to other menu with same level, this level menu has "CH2", "CH3",

"COMM ","DISP","CTRL","VErn",setting up working parameter of channel 2, channel 3,communication, display

mode, look over software version respectively.

5.4.2 Setting channel parameters

The parameter setting process of CH1, CH2,CH3 is one and the same. Taking CH1 as example , to explain

clearly: After setting entry system, menu and data display in Area 1 , after setting entry channel, Area 2 display

channel sequence number. Display before entry in.CH1:

Example Explanation
1 CH1 Single click ENTER,enter into parameter setting of channel 1
2 Blank

Single click ENTER the display as follows:

Example Explanation
1 ON Allow channel 1,selecting left/right key for "on"/"off",click ENTER for confirm
2 1 Current setting is the first channel

Selecting "on",Single click ENTER the display as follows:

Example Explanation
Single click ENTER for entry, setting humidity value for starting process
1 H.dry
of heating and removing moisture
2 1 Current setting is the first channel
Single click ENTER the display as follows:
Example Explanation
Single click left/right key for revising , hold pressing for increasing/decreasing of
1 85
quickly, click ENTER for confirm
2 1 Current setting is the first channel

9
Single click ENTER the display as follows:
Example Explanation
Single click ENTER for entry, setting temperature value for starting process
1 HEAt
of heating and temperature rising
2 1 Current setting is the first channel
Single click ENTER the display as follows:
Example Explanation
Single click left/right key for revising , hold pressing for increasing/decreasing of
1 5.0
quickly, click ENTER for confirm
2 1 Current setting is the first channel
Single click ENTER the display as follows:
Example Explanation
1 ALM.H Single click ENTER , setting ifopen heating-fault alarm
2 1 Current setting is the first channel
Single click ENTER the display as follows:
Example Explanation
1 OFF selecting left/right key for "on"/"off",click ENTER for confirm
2 1 Current setting is the first channel
Single click ENTER the display as follows:
Example Explanation
Single click ENTER , setting temperature value to start
1 FAn.C
blowing-reducing temperature
2 1 Current setting is the first channel
Single click ENTER the display as follows:
Example Explanation
Single click left/right key for revising , hold pressing for increasing/decreasing of
1 40.0
quickly, click ENTER for confirm
2 1 Current setting is the first channel
Single click ENTER the display as follows:
Example Explanation
1 HYS.X Single click ENTER for entry, setting hysteresis value of this channel
2 1 Current setting is the first channel
Single click ENTER the display as follows:
Example Explanation
1 5 Single click left/right key for revising , click ENTER for confirm
2 1 Current setting is the first channel

Single click the Enter, return the main menu, use left/right key to select other main menu and setup the optional

item. The communication "COMM"may set up Local address ( 1~247) and Communication baud rate value (1200,

2400,4800,9600,19200) . The display mode"dISP" is used to set three channels: interval in circling measurement

10
display; closed circling or interval for 2s,4s,6s,8s. AI random position of main menu ,single click SET to select

storage or not and exit system setting, then return back normal working mode.

5.4.3 Set up system password

Press SET and ENTER simultaneously about three seconds, display: "CodE", Single click ENTER for entry,

type current system password. Single click ENTER to confirm the typed password, the correct password display

"yES",and switch to "n.Cod" automatically, single click entry to type new password, press ENTER to select storage

or not, then to exit..

At random setting position, if within 1 minutes, no effective key is pressed, the system return to measuring status

automatically the setting is not stored.

5.4.4 User’s Programming flow diagram

11
Character Explanation Character Explanation
Prog Access programming CoMM Communication
CodE Password Addr Address
xxxx Figure and others bAud Baud rate
CH1/CH2/CH3 Access channels 1/2/3 diSP Display setting
H.dry Heating to remove moisture d.Cyc Circling display
Length of communication
HEAt Heating to rise temperature CdLy
frequency interval
ALM.H Heater alarm for broken wire VErn Version No. of software
Fan.C Blow to reduce temperature n.Cod Typing password
Hysteresis value of heating to
Hys.H SAVE Storage
remove moisture
Hysteresis value of heating to rise
Hys.d ruPt Sensor failure
temperature
Hysteresis value of blow to reduce
Hys.U SEL relevant output select
temperature
tr.1/tr.2 Deliver access programming tr.Lo programming low
tr.Hi programming high
CTRL Forced heating/blowing time setting x.xH Time , 0.0H: Keep on

12
6 Communication manual

6.1 Communication

This chapter mainly explains how to use software to operate this series meter by communication interface. You
are required to obtain the knowledge of MODBUS protocol and have general comprehension of the meter's function

and application after reading through out other content of this manual.

The content of this chapter includes: brief introduction of MODBUS protocol, detailed explanation of

communicate application format,application details of the meter and parameter address table.

6.1.1 Communication

WHD Series Intelligent Temperature & Humidity Controller. MODBUS protocol defines detailedly checkout

code, data sequence and so on which are necessary content of specific data change. MODBUS protocol uses half

duplex connection mode in one communication wire. That means signals of a separate wire transfer along contrary

direction. Firstly,signal of host computer seeks address to a exclusive terminal unit,then terminal unit sends out

responding signal that is transmitted to the host computer with contrary direction.

MODBUS protocol only allows communication between mainframe(PC, PLC etc.) and terminal unit, it doesn't

permit data change between separate terminal equipment. Each terminal unit will not occupy communication wire

while initializing, it only responses to rogatory signal itself.

6.1.2 Searching-responding period

图1 master-slave searching-responding period form

13
Searching

Function code of searching information tells the selected slave unit should carry out which kinds of function.
Data segment includes any addition information that the slave unit will operate the function. For example, function

code 03 required reading keep register from slave unit and returning their content. Data segment should contain the

information that will be sent to slave unit: read from which register and the number of Register.Error detecting region

supplies slave unit with a method that can validate if the information content is correct.

Responding

If the slave unit brings a normal response,function code of the response information is the response of function
code in searing information.Data segment includes collecting data of slave unit: such as register value or state. If

error occurs, function code will be amended to indicate the response information is wrong, meanwhile, data segment

contains the code which describes this error. Error detecting region allows main unit affirm if the information is

usable.

6.1.3 Transmit mode

Transmit mode is a series of data configuration in a data frames and finity rule used for data transmission.
Transmit mode that is compatible with MODBUS protocol-RTU mode is defined as follows.

Bit of each byte:

• 1 start bit

• 8 data bits, the minimal efficient bit delivering first

• No parity check bit

• 1 stop bit

Error checking: CRC(circle redundancy check)

6.1.4 Protocol

When data frame reaches terminal unit, it enters searching addressed unit from a simple "port" .The unit takes
out the "envelop" (data head) and reads data, then carries out mission required by data if there is no error.After that,

the unit adds the produced data to "envelop" and returns data frame to sender. Response data returned includes:

Address of terminal slave unit, Function carried out, Data produced and a Check. There is no successful response if

any error occurs, or return to a false frame.

Data frame format


Address Function Data Check
8-bits 8-bits N x 8-bits 16-bits

14
Address region

Address region which is the beginning of frame consists of a byte( 8 bits binary code). The decimalist is 0-255,

and the system uses 1-247. The bits indicate address of terminal unit appointed by users which acquire data from the

connected host computer. Address of each terminal unit must be exclusive, and the address searched terminal will

bring address search. When terminal returns a response, slave address data of response tells host computer with which

terminal is communicating.

Function region

Function region code tells the address searched terminal which function to carry out. Function codes used in

meter are as follows.

Code Meaning Action


03 or 04 Read data register Acquire one or several current binary value of register
16 Preset multi-register Set binary value to series of multi-register

Date region

Data region includes the data which terminal needed to carries out specific function or which is sampled when
terminal responses searching. The content of data maybe numerical value, reference address or setup value. For
example, the function domain code tells the terminal to read a register, while the data field needs to indicate which
register to start from and how many data to read. The embedded address and data vary according to the type and the
contents of the slave.

Error-checking region

Check region allows error between host computer and terminal transmission. Sometimes because of electrical

noise and other disturbance,a set of data may change while transmitting from one unit to another,error- checking can

assure host or terminal not to answer the changed data.It improves the security and efficiency of system.

Error-checking adopts CRC16 method.

6.1.5 Protocol

CRC region occupies 2 bytes, binary value 16 bits. CRC value is accounted by transmit unit,then adds to data

frame. Receiver unit accounts CRC value again while receiving data, then compares with the value of CRC region.If

the two are unlikeness, there is an error.

While CRC operating,Preset 16 bits register 1 beforehand, then operate the 8 bits of each byte in data frame and

current value of register Continuously.Only 8 data bits of each byte participate in creating CRC, which is not

influenced by start bit, stop bit and parity bit. While creating CRC. 8 bits of each byte exclusive OR with the content

15
in register. The result is moved to low bit, "0" is used in high bit. LSB moves out and will be detected, if 1, the

register carries out a exclusive OR operation with a preset fixed value(OA001H), if the lowest bit is 0, do nothing.

Operation above carries repeatedly till 8 bit moving is completed. When the last bit moves,next 8 bits carries

out exclusive OR operation with current value of register. while operating another said 8 bit moving exclusive OR

operation. AII bytes are operated, CRC value is the final value.

Flow to create a CRC:

• Preset a 16 bits register OFFFFH beforehand,which is called CRC register.

• The 8 bits of first byte in data frame carries out exclusive OR operation with the low byte in CRC register and

store the result in CRC register.

• Move CRC register one bit to right, define the highest 0, move out the lowest and check it.

• If the lowest bit is 0, repeat step 3; if is 1, the register carries out a exclusive OR operation with a preset fixed

value (OA001H)

• Repeat the step 3 and 4 till the eighth moving. A whole 8 bits is transacted.

• Repeat step 2 to 5 to deal with next 8 bits till all bytes to be transacted.

• CRC value is the final CRC register value.

In addition, there is a way to account CRC by presetting a table beforehand. The main characteristic is

speediness of account, but the table needs biggish storage space.

6.2 Communication format explanation

Examples as follows is used as tables (hexadecimal)


Data start Data start Number of Number of Cyclic Cyclic
Function address address data read data read redundancy redundancy
Addr
code register high register low register high register low check low check high
byte byte byte byte byte byte
01H 03H 00H 00H 00H 03H 05H CBH

6.2.1 Reading( function code 03 or 04)

Searching data frame

This function allows user acquire system parameter and data of sampled and recorded by unit. It is not limited

for data number of required by host computer but can't beyond the defined address range.

The following example show that from 01 slave computer to read two collected basic data reading, CH1

temperature value and humidity value, address of temperature value is 0003H,address of humidity value is 0004H,

both length is 2 byte.

Addr Function Data start Data start Number of Number of Cyclic Cyclic

16
code address address data read data read redundancy redundancy
register high register low register high register low check low check high
byte byte byte byte byte byte
01H 03H 00H 01H 00H 02H 95H CBH

Response data frame

Response includes slave computer address,function code,byte length of data,data and CRC error-checking.

Following example is response of reading CH1 temperature,humidity value.


Cyclic Cyclic
Function Byte Data1 Data1 Data 2 Data2 redundancy redundancy
Addr
code count high byte low byte high byte low byte check low check high
byte byte
01H 03H 04H 01H 20H 02H 5EH 7AH 9DH

temperature = (0120H )/OAH = 288/10 = 28.8℃

humidity = (025EH)/OAH = 606/10 = 60.6%

The address table for reading parameters is shown as following:

Read/ Command
Address Data Content Data type word Note
Write

Working condition:bit0~bit3 are the


first ways
Working condition:bit 4~bit7 are the
second ways
Working condition:bit8~bit11 are the Unsigned
0 third ways R 03,04 0~4095
int
Bit0 Heater status 0=normal 1=fault
Bit1 Sensor status 0=normal 1=fault
Bit2 Heating status 0=cease 1=heating
Bit3 Blast state 0=cease 1=blast
Temperature value measured in signed
1 R 03,04
channel 1 int
signed
2 Humidity value measured in channel 1 R 03,04
int

Temperature value measured in signed


3 R 03,04
channel 2 int
signed
4 Humidity value measured in channel 2 R 03,04
int

Temperature value measured in signed


5 channel 3 R 03,04
int
signed
6 Humidity value measured in channel 3 R 03,04
int

17
Unsigned
7 Meter communication address R/W 03,04 / 16 1~247
int
Unsigned 0~4 show 1200~19200
8 Meter communication baud rate R/W 03,04 / 16
int respectively
Alarm permission and channel
permission
bit0~bit1 are the first ways
bit2~bit3 are the second ways
bit4~bit5 are the third ways Unsigned
9 bit0 fault detection of the first heater:0 R/W 03,04 / 16 0~63
permit 1 prohibit int
Bit1 is the first channel open :0 permit
1 prohibit

Unsigned Cycling time(S),0FFH


10 Meter display mode R/W 03,04 / 16
int indicate non-cycling

Temperature set for blowing in signed


11 R/W 03,04 / 16 0~1000
channel 1 int
signed
12 Humidity set for heating in channel 1 R/W 03,04 / 16 10~999
int

Temperature set for heating in channel signed


13 1 R/W 03,04 / 16 -400~1000
int
Unsigned
14 Hysteresis value in channel 1 R/W 03,04 / 16 1~40(low byte)
int

Temperature set for blowing in signed


15 channel 2 R/W 03,04 / 16 0~1000
int
signed
16 Humidity set for heating in channel 2 R/W 03,04 / 16 10~999
int

Temperature set for heating in channel signed


17 2 R/W 03,04 / 16 -400~1000
int
Unsigned
18 Hysteresis value in channel 2 R/W 03,04 / 16 1~40(low byte)
int

Temperature set for blowing in signed


19 channel 3 R/W 03,04 / 16 0~1000
int
signed
20 Humidity set for heating in channel 3 R/W 03,04 / 16 10~999
int

Temperature set for heating in channel signed


21 3 R/W 03,04 / 16 -400~1000
int
Unsigned
22 Hysteresis value in channel 3 R/W 03,04 / 16 1~40(low byte)
int

18
1~40(The high byte is
Hysteresis of heating and cooling in Unsigned
23 channel 1 R/W 03,04 heating up,the low byte is
int
the cooling of air blast)
1~40(The high byte is
Hysteresis of heating and cooling in Unsigned
24 channel 2 R/W 03,04 heating up,the low byte is
int
the cooling of air blast)
1~40(The high byte is
Hysteresis of heating and cooling in Unsigned
25 channel 3 R/W 03,04 heating up,the low byte is
int
the cooling of air blast)

6.2.2 Preset multi-register (Function code 16)

Searching data frame

The temperature value set for starting the heater in Channel 1 is 5℃ , its register address is 0012H.

Delivered by host computer:


Number
Data start Data start Number Cyclic Cyclic
of data Data Data Data
Function address of data redundancy redundancy
address setting
Addr setting leng high low
code register register registers check low check high
registers th byte byte
high byte high
low byte low byte byte byte
byte
01H 10H 00H 0DH 00H 01H 02H 00H 32H 26H 98H

Response data frame


Data start Data start Number of Cyclic Cyclic
Number of data
Function address address data setting
Addr setting registers redundancy redundancy
code register register registers
high byte check low byte check high byte
high byte low byte low byte
01H 10H 00H 0DH 00H 01H 90H 0AH

19
Sensor

1 General

The sensor of WHD Series Intelligent Temperature & Humidity Controller adopt external connecting mode,
and special housing with advantages of good ventilation, aesthetic appearance, protect inner component effectively,
boost service life,easily mounting and wiring.

2 Type explanation

WHD Series Intelligent purpose temperature & humidity controller sensor:


Type Function Wiring Mounting mode Outline size

Guideway type
One temperature V+,V-,CLK,Data is
WH-3 humidity connected with the
controller’s matched wiring
terminal respectively.
Fixed

20

You might also like