TECHNICAL DATASHEET P 252 GX
P 252 GX
GALAXY “GX” MAIN DATA
Continuous power (PRP) 250.00 kVA
Continuous power (PRP) 200.00 kW
Emergency power (E.P.) 275.00 kVA
Emergency power (E.P.) 220.00 kW
VAC - HZ - cos(fi) 400 - 50 - 0.8
Sound pressure 7 m. 70.0 dBA
DIMENSIONS AND WEIGHT
Width 1350 mm
For illustrative purposes only
Length 4270 mm
ENGINE Height 2370 mm
Description PERKINS Weight 3060 kg
Engine model 1206A-E70TTAG3
Cylinders 6 ALTERNATOR
RPM speed 1500 Description STAMFORD
Cubic capacity 7.01 l Alternator model UCDI274K
Air intake Turbocharged P.R.P. Power 250.0 kVA
Standard voltage 12 Vdc E.P. Power 275.0 kVA
Optional voltage Vdc Connection Series star
Sae 2-11½ Phases 3FN
BMEP 2582 kPa Winding 311
Cooling Water Terminal Number 12 nr.
Flywheel P.R.P. Power net 217.2 kW IP Protection 23
Flywheel E.P. Power net 239.6 kW Electronic regulator AS440
Fuel Cons. at 100% (E.P.) 64.5 l/h Precision 1.0 ±%
Fuel Cons. at 100% (P.R.P) 56.9 l/h
BASEFRAME
Fuel Cons. at 75% (P.R.P.) 41.5 l/h
Model GV121
Fuel Cons. at 50% (P.R.P.) 28.1 l/h
Standard tank 500 l
Fuel Cons. at 25% (P.R.P.) 15.4 l/h
Optional tank 0 l
Electronic regulator Standard
Oversized tank* 0 l
Precision class G2
Oil quantity 16.0 l CANOPY & SILENCER
Engine Antifreeze capacity 13.7 l Canopy model GV121/00/1
Radiator type TR Silencer model MSR/a 100
Heat from radiator 181.4 kW Silencer outlet diameter 114.0 mm
Standard reference conditions temperature 25°C, altitude 100m asl, relative humidity 30%,
Heat from exhaust 281.6 kW atmospheric pressure 100 kPa (1 bar), power factor 0.8 lag, balanced load - non
distortional. Fuel consumption is nominal and refers to specific weight 0,850kg/l. Sound
Heat from radiation 0.0 kW power values refer to free field conditions: the installation site may influence the values.
Dimensions, weights and other specifications contained in the technical data sheet and
Exhaust temperature 516 °C related attachments are nominal, subject to tolerances and refer to the model with standard
equipment; any optional and additional equipment/accessories can modify weight,
Portata Raffreddamento 265.2 m³/min dimensions, performance. P.R.P. Prime Power-Continuous power at variable load:
The power that a genset can supply in continuous service at a variable load for an unlimited
Combustion air flow 15.7 m³/min number of hours per year while respecting the maintenance intervals established in the
environmental conditions stated by the Manufacturer. according to ISO8528-1. The average
Exhaust gas flow 33.7 m³/min power supplied over time and any applicable overload must be less than the percentages
stated by the Manufacturer. E.P. - Emergency power: This is the maximum power that a
TA Luft N generating set can deliver for a limited number of hours per year while complying with the
maintenance frequency stipulated under the environmental conditions set by the
TA Luft/2 N Manufacturer. The number of hours per year is determined by the engine manufacturer. The
average power output over time must be lower than the percentages set by the engine
EPA N manufacturer. Overloading is not allowed.
Stage N
The data contained in this document is nominal and refers to the standard equipped model and is not binding. Visa S.p.A. reserves the
right to revise the information without notice per our policy of continuous product development and improvement.
VISA S.p.A. s.u. - ITALY- CERTIFIED ISO 9001-2015, 14001-2015, 3834 and EN 1090 - www.visa.it
Visa S.p.A. s.u. is subject to management and coordination of IPG S.p.A., via dei Mercanti 12 - Milano Company registration Office n. 12616930967
Powered by TCPDF (www.tcpdf.org)