Lesson 4 Relays
Lesson 4 Relays
Relays
PJM©2019 10/1/2019
Objectives
2
Objectives
3
Basic Concepts in Protection
6439 4
Purpose of Protective Relaying
6439 5
Purpose of Protective Relaying
‒ Will initiate a desirable system event that will aid in maintaining system reliability
(i.e. trip a circuit breaker, throttle back a unit, etc.)
6439 6
Fault Causes
• Lightning
• Wind and ice
• Vandalism
• Contamination
• External forces
‒ Cars, tractors, balloons, airplanes, trees, critters, etc.
• Equipment failures
• System disturbances
‒ Overloads, system swings
6439 7
Fault Types
Ia
Va Ic
Vaa Ic Ic
6439 8
Overlapping Zones of Protection
6438 9
Primary Transf. Differential
B/U Transf. Differential
10
Overlapping Zones of Protection
6438
Overlapping Zones of Protection
6438 11
Relay Scheme Design Characteristics
Sensitivity - Can scheme detect all “events” that it is supposed to?
Selectivity - Will it remove only the “faulted” piece of equipment?
Speed - Can the scheme clear the fault fast enough to maintain or insure
system integrity?
Reliability - Will the scheme be secure and dependable?
Security - No misoperations
Dependability - Operate when it should
Economy - Provide the desired level of protection for the least cost
Simplicity - Attempt to keep designs straightforward
6438 12
Relay Scheme Components
6438 13
Components
6438 14
Instrument Transformers
6438 15
Current Transformers (CTs)
6438 16
Slipover CTs
Slipover CTs
Primary Conductors
6438 17
Potential Transformer (PTs)
6438 18
Capacitance Potential Devices
6438 19
Diagram Of CCVT Construction
• Primary voltage divides across capacitance
stacks C1, C2, C3 and C4
• Voltage across C4 equals approximately 20 kV
C1
C2
C3
C4
6438 20
Illustration of 230kV CCVT Illustration of 500kV CCVT
Notice that the 230kV CCVT
has 2 capacitor stacks,
while the 500kV CCVT needs
3 stacks to divide the higher
primary voltage
Capacitor
Stacks
Transformer
Enclosure
Grounding
Switch
6438 21
Components
Components That Could Impact System Protection
Current Potential
Battery Bank Control Wiring Operating Coils
Transformers Transformers
Communication
Relays Critters Humans
Circuits
6437 22
Effects
• CTs or PTs
‒ Main source of inputs to protection schemes
‒ Failure would render scheme inoperable if no redundant source
• Battery Bank
‒ Substation equipment uses DC to operate
‒ Loss of the DC would prevent devices from operating
• Control Wiring
‒ Damaged control wiring could prevent operation of isolating devices or relays
• Protection and control circuits are individually fused
6437 23
Effects
• Operating Coils
‒ Part of breaker mechanism and would prevent operation if failed
• Communication Circuits
‒ Could result in an over-trip or no trip at all
• Relays
‒ Could result in miss-operation or no operation of the scheme and
the devices it is to operate
• Critters
‒ Mice can chew through control wires that could affect the operation
of a protection scheme
6437 24
Effects
• Humans
‒ Vandalism
• Copper theft could render schemes inoperable
‒ Incorrect settings
• Scheme not operating when it should, or operating when it shouldn’t
‒ Scheme not completely isolated during testing
• Equipment tripping for non-fault condition
‒ Isolation links left open after testing
• Equipment not tripping for a fault condition
6437 25
Relay Devices
26
General Functions:
• Protective
‒ Remove a system disturbance from the power system
• Regulating
‒ Insures system is operated within proper guidelines
• Auxiliary
‒ Other less critical functions (i.e., alarms, reclosing, etc.)
6441 27
Solid State Microprocessor
Electromechanical
6441 28
Universal Numbering System for Protective Relays
IEEE # Device Relay Function IEEE # Device Relay Function
Requires a combination of high current and low
Operates on low or high pressure of a liquid or
voltage to operate. The various zones of the distance
21 Distance Relay 63 Pressure Relay gas (oil or SF6) or on a rate-of change of pressure
scheme (Z1, Z2, etc.) assist with determining the
(sudden pressure)
location of the fault
Checks voltage magnitude, phase angle, and
Synchronizing Directional Operates if current is above a
25 frequency to verify synchronism across a CB before 67
Relay Overcurrent set value and flowing in the designated direction
allowing a close
Undervoltage Operates when voltage falls below a
27 78 Out-of-Step Detects loss of synchronism.
Relay set value
Initiates an automatic closing of
Operates when the temperature (usually a winding)
49 Thermal Relay 79 Reclosing Relay a circuit breaker following a
rises above a set level
trip condition
Instantaneous Operates with no time delay when current rises above Operates if frequency goes above or below a
50 81 Frequency Relay
Overcurrent a set level set limit
6441 29
Typical Performance Parameters:
Overcurrent
‒ Required input: Current from CTs
‒ Instantaneous: No intentional time delay
‒ Time delayed: Inverse time/current curve
‒ Can protect for both Phase and Ground faults
• The physical connection determines what current (phase or ground) the relay
will respond to
6441 30
Inverse Curve Characteristic
6441 31
Typical Performance Parameters:
Over/Under Voltage:
‒ Required input: Voltage from PTs
‒ Instantaneous or time delayed
‒ Generally used for automatic sectionalizing
control (i.e. auto transfer schemes, etc.)
6441 32
Typical Performance Parameters:
6441 33
Typical Performance Parameters:
Directional Capability
‒ Required Inputs: Current and Voltage
‒ How is it achieved?
• Directional relays require polarizing quantities
Voltages and/or currents
These are converted into proportional magnetic forces acting on an induction cup that spins
either clockwise or counter-clockwise towards a trip or non-trip position
• As a rule of thumb:
Voltage restrains the induction cup from spinning in the trip direction
Current tends to spin the cup such that its electrical contact operates and trips
• The rule of thumb makes sense: a power system fault decreases voltage and increases
current…less voltage means less restraint and more current means greater torque
toward the trip direction
6441 34
Typical Performance Parameters
Directional Distance Relaying
‒ Requires Current and Voltage inputs
‒ Operates on the V/I = Z (impedance) principle
‒ Constant reach regardless of system
‒ Less susceptible to misoperating on load current (when compared to simple phase
overcurrent relays)
‒ Can provide three Zones of Protection:
• Zone 1 - Instantaneous Operation:
‒ Set for approximately 90% of line
• Beyond that relay would not be able to distinguish between internal or external fault
• Zone 2 - Fixed Time Delay Operation
‒ Set to see entire line + margin
• Zone 3 - Fixed Time Delay Operation (Generally not used for forward faults anymore)
‒ Set greater than Zone 2
6441 35
Directional Distance Relay
6441 37
Transient Load Limits
operating conditions
‒ Operators must be aware of any lines
that are restricted not due
to their thermal capability, but by the
relays themselves
6441 38
Typical Performance Parameters:
Differential
• Required input: Current from CTs
• Relay generally operates very fast (1 cycle)
• Normal protection for Generators, Transformers and Bus sections
• CTs supplying the relay should be matched so that currents into the
“zone of protection” are equal to those currents that leave
• The difference/mismatch in current is observed in the relays operate coil
6441 39
Differential Relay
Current Flow
Protected
Equipment
CT #1 CT #2
6441 40
Differential Relay
Current Flow Current Flow
Protected
Equipment
CT #1 CT #2
6441 41
Typical Performance Parameters:
6441 42
Lockout Relays
• Part of generator, transformer, bus and other switchyard equipment
protection schemes
‒ Relay itself doesn’t protect anything;
• Has multiple contacts that operate multiple devices
• If they failed to trip for a fault, the switchyard GCB would stay closed and the
equipment would remain energized
• Electrical coil that trips the lockout relay is monitored
Amber light above handle
6441 43
Lockout Relays
• The amber lamp is normally lit to indicate three important things about the
Lockout Relay:
1) There is DC control power available to the lockout relay
2) The lockout relay operating coil is electrically intact
3) The lockout relay is reset and ready to trip
6441 44
Illustrations of a Lockout Relay
RESET TRIPPED
6441 45
Line Protection
46
Transmission Line Protection
6456 47
Transmission Line Protection
• Because these lines carry large amounts of energy and are extremely
important to the operation of a power system, it is necessary to use the
most advanced relaying methods to insure their integrity
• The goal is to achieve selective, fast, and simultaneous fault clearing at all
terminals with instantaneous relays that cover 100% of the transmission line
and are immune to faults on adjacent lines or on remote substation buses
6456 48
Transmission Line Protection
6456 49
Transmission Line Protection
6456 50
Transmission Line Protection
System Stability:
6456 51
Transmission Line Protection
Relay Coordination:
6456 52
Relay Coordination – Normal Line Configuration
6456 53
Relay Coordination – Long Line / Short Line
6456 54
Transmission Line Protection
6456 55
Pilot Schemes
• 3 major components
‒ Protective relays set to look:
• Beyond, or over-reach, the remote terminal of the protected line
• Short of, or under-reach the remote terminal of the protected line
‒ A communications channel between the local and remote terminals:
• Telephone line operating at audio tone frequencies (usually between
1000 and 3000 HZ)
• Fiber optic link
• Powerline carrier
• Microwave
‒ Transmitting and receiving equipment at all terminals capable of either:
• Shifting between a continuous pilot signal (GUARD) and a permissive
signal (TRIP)
• Sending/receiving a blocking signal
6456 56
Logic Gates Overview
A 0 0 0 A Output
B Output
0 1 0
1 0 0 A Output
1 1 1 0 1
OR Gate
Needs 1 input to get an output A B Output 1 0
A 0 0 0
B Output
0 1 1
1 0 1
1 1 1
6456 57
Directional Comparison Blocking Scheme
DCB
6446 58
Directional Comparison Blocking
• Under non-fault conditions, no signal is sent between the terminals of the line
6446 59
Directional Comparison Blocking
• To Initiate Trip:
‒ Over-reaching Relay must operate
‒ Absence of Blocking Signal from remote end
• In digital logic:
Over-reaching Relay
6446 60
Wave Trap and CCVT
Illustration of 500kV Wave Trap & CCVT
• The carrier signal couples to the transmission line
through the CCVT Wave
Trap
• The signal enters and exits the base of the CCVT,
then connects to a nearby impedance-matching
tuning box and then to the transmitter/receiver
equipment located inside the substation control
house
• The carrier signal traffic is bi-directional: the local
terminal both transmits a signal to the remote
terminal and receives a signal from it, all through
CCVT
the same path shown in the illustration
• The wave trap blocks the carrier signal from exiting
the transmission line through any path other than
through the CCVT
6446 61
Directional Comparison Blocking
6446 62
Directional Comparison Blocking
• Disadvantages of a Blocking Carrier Scheme
‒ Proper carrier channel tuning is essential to maintain signal levels
• Improperly tuned carrier channels make the scheme overtrip
‒ Switching coordination is necessary to block carrier schemes out of service at all
terminals as simultaneously as possible to prevent overtripping
‒ Blocking only one terminal of a carrier scheme has the same effect as
deteriorated signal strength by preventing transmission of a carrier signal
‒ No form of a “guard” signal is continuously present to monitor the carrier
channel’s integrity and ensure its viability during an actual fault
• An external checkback scheme that automatically exchanges carrier signals between
line terminals at periodic intervals is the only non-fault of ensuring that the carrier
communications channel is operational
6446 63
Directional Comparison Blocking – Internal Fault
Carrier Start Carrier Trip
B O
O B
Carrier Trip Carrier Start
O O
6445 64
Directional Comparison Blocking – External Fault
Carrier Block Carrier Trip
B O
O B
Carrier Trip Carrier Block
O RX
TX B
6445 65
Directional Comparison Blocking
6445 66
DCB Bismarck Sim
6445 67
Direct Under-reaching Transfer Trip Scheme
DUTT
6447 68
Direct Under-Reaching Transfer Trip
6447 69
Direct Under-reaching Transfer Trip
• To Initiate Trip:
‒ Under-reaching Relay must operate
OR
‒ Receive a TRIP signal from the remote end
• In Digital Logic:
Under-reaching Relay
6447 70
Direct Under-reaching Transfer Trip
6447 71
Direct Under-reaching Transfer Trip
6447 72
Direct Under-reaching Transfer Trip
Under-reaching Relay
U
U
Under-reaching Relay
RX RX
U TX TX U
6448 73
Direct Under-reaching Transfer Trip
Under-reaching Relay
U
U
Under-reaching Relay
RX
U TX
6448 74
Direct Under-Reaching Transfer Trip
6448 75
DUTT Bismarck Sim
6448 76
Permissive Under-Reaching Transfer Trip
(PUTT)
77
Permissive Under-Reaching Transfer Trip
• Direct tripping relays set to under reach remote end
• Fault detector relays set to overreach remote end
• Under non-fault conditions, continuous GUARD signal is sent to remote end
‒ Tests communication path
‒ Loss of GUARD will generate an alarm
6454 78
Permissive Under-Reaching Transfer Trip
• To Initiate Trip:
‒ Under-reaching Relay must operate
OR
‒ Over-reaching relay must operate AND receive a TRIP signal from the remote end
• In digital logic:
Over-Reaching Relay
Under-Reaching Relay
OR Trip
6454 79
Permissive Under-Reaching Transfer Trip
6454 80
Permissive Under-Reaching Transfer Trip
6454 81
Permissive Under-Reaching Transfer Trip
Over-reaching Relay
O
Under-reaching Relay
U
U
Under-reaching Relay
O
Over-reaching Relay
U TX TX U
O RX RX O
6455 82
Permissive Under-Reaching Transfer Trip
Over-reaching Relay
O
Under-reaching Relay
U
U
Under-reaching Relay
O
Over-reaching Relay
U TX
O RX O
6455 83
Permissive Under-Reaching Transfer Trip
6455 84
PUTT Bismarck Sim
6455 85
Permissive Over-Reaching Transfer Trip
(POTT)
86
Permissive Over-Reaching Transfer Trip
• The nature of a POTT relay scheme requires two things to
happen before tripping is allowed:
‒ The protective relays must sense a fault, and
‒ The protective relays must receive a valid TRIP signal from the
remote terminal
6452 87
Permissive Over-Reaching Transfer Trip
• A GUARD tone or other pilot signal is continuously sent between
terminals for two purposes:
‒ To monitor integrity of the communications channel
‒ To enhance security of the POTT scheme:
• The GUARD signal must be present and recognized by the local receiver prior to
receipt of a TRIP signal from the remote transmitter in order to permit a local trip
output;
• In an audio tone POTT scheme the local receiver will not produce a trip output unless
the shift from GUARD to TRIP is accomplished within several hundred
milliseconds…this is GUARD-BEFORE-TRIP logic
6452 88
Permissive Over-Reaching Transfer Trip
• To Initiate Trip:
‒ Over-reaching Relay must operate
AND
‒ Receive a trip signal from the remote end
• In digital logic:
Over-Reaching Relay
AND Trip
Trip Signal from
Remote End
6452 89
Permissive Over-Reaching Transfer Trip
6452 90
Permissive Over-Reaching Transfer Trip
6452 91
Permissive Over-Reaching Transfer Trip
Over-reaching Relay
O
O
Over-reaching Relay
O TX TX O
RX RX
6453 92
Permissive Over-Reaching Transfer Trip
Over-reaching Relay
O
O
Over-reaching Relay
O TX
RX
6453 93
Permissive Over-Reaching Transfer Trip
6453 94
POTT Bismarck Sim
6453 95
Phase Comparison Blocking Scheme
96
Phase Comparison Blocking
6450 97
Phase Comparison Blocking
‒ The BLOCKING CARRIER signal pulse trains received at each terminal are
in-phase with the TRIP signal pulse trains generated at each terminal…
each time the TRIP signal goes to full value, the CARRIER signal does
likewise and BLOCKs tripping of either terminal
6450 98
Phase Comparison Blocking
Local Terminal Fault Current Remote Terminal
External Fault
6450 99
Phase Comparison Blocking
6450 100
Phase Comparison Blocking
Local Terminal Remote Terminal
Internal Fault
6450 101
AC Pilot Wire
102
AC Pilot Wire
6451 103
Pilot Wire Scheme
6451 104
Line Differential Scheme
105
Line Differential Relaying
• Relays operate on a current differential basis
• Requires the use of optical fiber to transit digital information
• The digital information contains the current magnitudes and other
diagnostic parameters and is transmitted continuously between
connected stations
• Failure of the fiber communication path will automatically block the
scheme and initiate an alarm
6449 106
Line Differential Relaying
FIBER FIBER
LOCAL REMOTE
OPTIC OPTIC
RELAY RELAY
TX/RX TX/RX
LOCAL REMOTE
TERMINAL TERMINAL
Each line differential relay directly measures line current at its own terminal
and, via the fiber optic communications link, instantaneously receives from its
counterpart a measurement of the line current at the remote terminal.
The sum of the local and remote line currents seen by each relay is normally
zero; a non-zero result indicates a line fault and causes both relays to trip.
6449 107
Backup Transmission Line Protection
6570 108
Backup Transmission Line Protection
• In non-pilot applications, line protection
generally consists of the following:
‒ Stepped Distance for Phase Protection
‒ Directional Time and Instantaneous Overcurrent
for Ground Protection
• With microprocessor based relays, additional
functions are available for use.
The more common functions include:
‒ Ground Stepped Distance elements
‒ Negative Sequence Overcurrent elements
6570 109
Other Functions Performed:
6570 110
Breaker Failure Relaying
• Breaker Failure protection clears a fault even if the circuit breaker that’s called
upon to trip fails to operate or fails to interrupt the fault
• Every function that sends a TRIP signal to a transmission line circuit breaker also
initiates its breaker failure scheme
‒ Except manual and SCADA TRIP commands
• If a breaker has not interrupted fault current within 7 to 10 cycles
‒ Breaker failure scheme operates to trip all adjacent circuit breakers, and
‒ Remote line terminals via DTT (if necessary)
• After a breaker failure operation, all tripped breakers generally stay locked open
until the master trip relay is hand reset
‒ Some locations have automatic restoration schemes that allow adjacent
breakers to reclose once the failed circuit breaker has been isolated by its MODs
6434 111
Breaker Failure Relaying
6434 112
Breaker Failure Relaying
DTT
6434 113
Close In Fault Protection
6444 114
Reclosing Practices
6440 115
Reclosing Practices
6440 116
Reclosing Practices
6440 117
Reclosing Practices
Manual Reclosing
• This includes supervisory (SCADA) control in addition to control handle closures
• Used when switching equipment in or out of service. (SCADA is typically used
instead of control handle in order to confirm its availability
• Should fault occur as soon as a CB energizes a piece of equipment,
no automatic reclosing will take place
6440 118
Reclosing Practices
Manual Reclosing
• Also used for “Try Back” (testing) of a line after a fault
• Company policy should be followed when fault testing is being considered
• The operator should consider the effects that testing may have on the
electrical system (shocking the system again)
• If possible, it is always better to request a patrol of line before trying to
restore it to service
6440 119
Reclosing Practices
6440 120
Protective Relay Alarms via SCADA
6477 121
Risks Involved
• Directional or Phase Comparison Schemes
‒ With low signal levels, there is a good chance that the protected
line could overtrip for a fault
• Permissive Transferred Trip Schemes
‒ With a continuous loss of guard, the scheme will shut itself down
• Little risk of overtripping exists
‒ With a sporadic loss of guard, noise is being introduced into
communication channel
• Fair chance of incorrect tripping exists
‒ Momentary loss of guard and return to normal
• Little risk of overtripping exists
6477 122
Risks Involved
6477 123
Transformer Protection
124
Transformers:
• Because they are critical to the Bulk Power System, high speed
clearing for faults is desirable
6460 125
Transformer Protection
• Typical Problems that can occur:
‒ Inside the Tank
1) Winding Faults to Ground
2) Winding Turn to Turn Shorts
3) Excessive Winding and/or Oil Temperature
4) Overloads (i.e. winding/oil temperature
‒ External to Tank
1) Bushing Lead Failure
2) Bushing Flashover
3) Lightning Arrester Failure
4) “Through Faults”
6460 126
Transformer Protection
• Transformer Protection is typically provided by differential relaying
• Transformers provide unique problems for differential relaying that
must be accounted for:
1) Different voltage levels (i.e. different current magnitudes)
2) Automatic Tap Changers (LTC’s or TCUL’s) associated with transformers
cause further mismatch between high side and
low side currents
3) Energizing a transformer causes magnetizing inrush current
which appears as an internal fault to the differential relay
4) Because of Delta-Wye connections, the transformer introduces a
30 degree phase angle shift that must be accounted for
6460 127
CT Connections for Tapped Transformer
6460 128
CT Connections for Bus Connected Transformer
6460 129
Transformer Protection
• Bottom Line:
‒ The differential relay is the ideal device for transformer protection
in that it takes advantage of the zone type of protection to provide
sensitive high speed clearing of transformer faults
• Since high voltage transformers are critical to the Bulk Power System,
generally primary and back-up differential relays are used for protection
• Beyond using two discrete differential relays, additional devices are used
to protect the transformer
6460 130
Transformer Protection
‒ If an arcing fault occurs inside the transformer tank, gases are generated
which can be detected by a pressure relay
6460 131
Transformer Protection
‒ The gas analyzer relay constantly monitors the gas space above
the transformer oil, and will actuate an alarm if gas levels exceed
a predetermined level
6460 132
Transformer Protection
6460 133
Transformer Protection
6460 134
Illustrations of Analog Gauge Style Winding Temperature
and Liquid Temperature Thermal Devices
6460 135
Illustration of
Microprocessor Based
Thermal Device
Liquid Temperature
is the upper unit
Winding Temperature
is the lower unit
6460 136
Transformer Protection
6460 137
Transformer Protection
‒ Line Relaying may not respond to a fault that could occur between
the Transformer Diff
• CTs and the MOAB
6460 138
CT Connections for Tapped Transformer
Fault
6460 139
Transformer Protection
‒ Low Oil Level - Lack of proper oil level compromises transformer cooling
• This device will alarm and eventually trip the transformer if oil level drops below a certain
threshold
6460 140
Transformer Protection
• Operation of any of the above relay schemes will initiate other
protective functions
• The physical design of the electrical system will define what
additional actions are taken
• Some actions include:
1) Initiate Direct Transfer Trip to remote terminals
2) Initiate breaker failure relaying
3) Block reclosing of CBs that are tripped (until transformer is isolated)
4) Close the high speed ground switch
5) Initiate permissive trip/stop sending blocking signal, etc.
6460 141
Transformer Protection
6460 142
Transformer Protection
• If the differential relay responds, a master trip auxiliary relay will trip and
block closing of devices which could re-energize the transformer
• To reclose the locked out devices, this master trip relay must be
hand reset
6460 143
Operator’s Role if Transformer Protection Operates
6460 144
Direct Transfer Trip (DTT) Relaying for
Transformer Protection
6459 145
Clearing Sequence For A Fault On Auburn Transformer 20
Yakima Auburn
230/69 kV SUB 230 kV PLANT and SWITCHYARD
Auburn 230 Yakima
kV CB East 230 kV GCB
230/13.8/4 kV
T20 MOD Transformer 20 To
13.8 kV and 4 kV Lowside
CBs
inside Plant
T20 HSGS
Yakima
Transformer West 230 kV GCB
69kV CB
6459 146
Clearing Sequence For A Fault On Auburn Transformer 20
2) At Auburn, Transformer 20 protection operates to immediately trip the Yakima East and West 230kV circuit breakers and
the 13.8kV and 4kV Transformer 20 lowside circuit breakers. Simultaneously, a DTT TRIP signal is initiated to Yakima, the
T20 HSGS closes and the T20 MOD starts to open
3) At Yakima, the 230kV line and 69kV transformer lowside breakers open immediately upon receipt of the DTT TRIP
signal…all circuit breakers at Yakima are open before the HSGS at Auburn closes fully into the transmission line
Yakima Auburn
230/69 kV SUB 230 kV PLANT and SWITCHYARD
Auburn 230 Yakima
kV CB East 230 kV GCB
230/13.8/4 kV
T20 MOD Transformer 20 To
13.813.8
kV and
kV 4and
kV4Lowside
kV
CBs CBs
Lowside
inside Plant
T20 HSGS
Yakima
Transformer West 230 kV GCB
69kV CB
6459 147
Clearing Sequence For A Fault On Auburn Transformer 20
4) At Auburn, the T20 MOD opens fully to physically isolate the fault and stops the DTT TRIP
signal to Yakima…all circuit breakers at Yakima reclose automatically. The transmission line
breakers at Auburn also reclose automatically after the failed transformer is isolated, but the T20
lowside breakers are designed to stay open
Yakima Auburn
230/69 kV SUB 230 kV PLANT and SWITCHYARD
Auburn 230 Yakima
kV CB East 230 kV GCB
230/13.8/4 kV
T20 MOD Transformer 20 To
13.813.8
kV and
kV 4and
kV4Lowside
kV
CBs CBs
Lowside
inside Plant
T20 HSGS
Yakima
Transformer West 230 kV GCB
69kV CB
6459 148
Clearing Sequence For A Fault On Auburn Transformer 20
If the DTT TRIP signal had failed to reach Yakima, the line relays there would recognize the phase-to-ground
fault created by the T20 HSGS at Auburn and open the 230kV and 69kV circuit breakers
The Yakima circuit breakers at Auburn would be unaffected by a DTT failure because they are tripped locally
by Transformer 20 protection
Yakima Auburn
230/69 kV SUB 230 kV PLANT and SWITCHYARD
Auburn 230 Yakima
kV CB East 230 kV GCB
230/13.8/4 kV
T20 MOD Transformer 20 To
13.813.8
kV and
kV 4and
kV4Lowside
kV
CBs CBs
Lowside
inside Plant
T20 HSGS
Yakima
Transformer West 230 kV GCB
69kV CB
6459 149
Bus Protection
150
Bus Protection
6435 151
Bus Protection
• Generally, the CTs used for Bus Protection are located on the line or
equipment side of the circuit breaker
‒ Consequently, the CB is within the protection zone of the bus differential
and the line or piece of equipment (overlapping zones of protection)
6435 152
Bus Protection
• If a bus differential relay operates, the relay will typically do the following:
1) Energize a Master Trip Auxiliary Relay
2) Trip all sources to that bus section (via the Master Trip)
3) Setup the Reset of the Master Trip Relay if bus testing is to occur
4) Block reclosing of all CBs except that of the automatic testing source
(if so equipped)
5) Initiate Breaker Failure
6) Initiate an Alarm
6435 153
Bus Protection
6435 154
Bus Protection
• If the bus test was unsuccessful, all CBs, including the testing CB,
will be locked out
6435 155
Operator’s Role is Bus Protection - De-Energize a Bus
• If the bus trips and locks out, no testing via SCADA should occur
until the station is inspected by authorized personnel
6435 156
Bus Differential with Automatic Testing
6436 157
Illustration of Automatic Bus Testing
in a Transmission Switchyard
6436 158
Illustration of Automatic Bus Testing
in a Transmission Switchyard
6436 162
Illustration of Automatic Bus Testing
at a Generating Station
G
G
G
1 2 3 4
6436 163
Generator Protection
164
Station Arrangement
6443 165
Station Arrangement – Unit in Service
DC Field
Prime Mover
AC
To Transmission
Grid
Unit CB
Generator Main Power
Transformer
(GSU)
To Transmission
Grid
Station Bus
Station Service
Bus
Station Service
Transformer
Emergency Start Up CB
Start Up
Diesel Generator
Transformer
6443 166
Station Arrangement – Unit Out of Service
DC Field
Prime Mover
AC
To Transmission
Grid
Unit CB
Generator Main Power
Transformer
(GSU)
To Transmission
Grid
Station Bus
Station Service
Bus
Station Service
Transformer
Emergency Start Up CB
Start Up
Diesel Generator
Transformer
6443 167
Station Arrangement – Station Blackout
DC Field
Prime Mover
AC
To Transmission
Grid
Unit CB
Generator Main Power
Transformer
(GSU)
To Transmission
Grid
Station Bus
Station Service
Bus
Station Service
Transformer
Emergency Start Up CB
Start Up
Diesel Generator
Transformer
6443 168
Generator Unit Tripping
6443 169
Generator Unit Tripping
• The frequency of failures in Rotating Machines is low, however
failures can and do occur
• Beyond actual failures, certain abnormal conditions can cause
generator failure if not corrected quickly
• Some of these harmful conditions are:
‒ Winding Faults
‒ Overheating
‒ Loss of Field
‒ Single Phasing
‒ Overloading
‒ Overspeed
‒ Motoring (turbine)
‒ Overexcitation
6443 170
Generator Unit Tripping
6443 171
Generator Unit Tripping
6443 172
Generator Unit Tripping
• When a unit trips, the function of the plant operator is to stabilize the
prime mover and auxiliary systems to insure a controlled shut down
6443 173
Overall Unit Protection
6443 174
Areas to be Protected and Concerns
6443 175
Ground
Relay Unit Differential
DC Field
AC
To Transmission
Grid
Unit CB
Main Power
Transformer
Generator Differential (GSU)
To Transmission
Station Bus Grid
Transformer Differential Protection Station Bus
Station Service
Bus
Station Service
Transformer
Start Up CB
Start Up
Station Service
Transformer
Bus Differential
Transformer Differential
6443 176
Protective Relay Schemes for the Generator
Generator Differential
‒ Wraps only the Stator Windings of the Generator
6443 177
Generator Differential
6443 178
Protective Relay Schemes for the Generator
Overall Differential
‒ Wraps the Generator, Gen Step-up Transformer and Station Service
Transformer
‒ Sensitive to phase and some ground faults
‒ Backs up the Generator Diff, GSU Diff, Station Service Diff, etc.
‒ Less sensitive than the Generator Diff
‒ Operation of this relay will initiate a unit trip
6443 179
Unit Differential Protection
Unit Differential
DC Field 87
AC
To Transmission
Grid
Generator Unit CB
Neutral to Main Power
Ground Transformer
(GSU)
To Transmission
Grid
Station Bus
Station Service
Bus
Station Service
Transformer
Start Up CB
Start Up
Transformer
6443 180
Protective Relay Schemes for the Generator
Overcurrent Protection
‒ Provide Backup Protection for Gen. Diff Scheme
‒ Protects the generator from system faults that are not cleared within a
predetermined time interval
‒ Coordinated with System Overcurrent schemes
‒ Usually time delayed to minimize tripping for transient surges
or synchronizing
‒ Will initiate a unit trip
6443 181
Other Generator Protection Relays
Generator
To Generator
CT
Step-up
Transformer
CT (GSU)
PT
51G 51 46 32 40 59 81
6443 182
Protective Relay Schemes for the Generator
6443 183
Protective Relay Schemes for the Generator
6443 184
Protective Relay Schemes for the Generator
‒ System Effects
• Loss of reactive support
• Creates a reactive drain
• Can trigger system/area voltage collapse
6443 185
Protective Relay Schemes for the Generator
6443 186
Protective Relay Schemes for the Generator
Overexcitation Protection
‒ Concern is for the Generator Field and main GSU transformer since overexcitation
can cause damaging overheating due to core saturation in a very short time
‒ Volts/Hertz, or Voltage or Current relaying is employed
• Typically “stair-step” operation
• One relay will alarm or automatically reduce field to allowable limits
• One relay will trip unit
6443 187
Protective Relay Schemes for the Generator
Overexcitation Protection
‒ Generator issues:
• Voltage regulator problems
• Operating error during manual operation
• Control failure
• Loss of sensing signal
6443 188
Protective Relay Schemes for the Generator
Overexcitation Protection
‒ System issues:
• Unit load rejection: full load, partial rejection
• Power system islanding during major disturbances
• Ferranti effect
• Reactor out of service
• Capacitors in service
• Faulty LTCs
6443 189
Protective Relay Schemes for the Generator
Underfrequency Protection
‒ If System load exceeds the capability of the machine, the frequency will decay
‒ In PJM, machines are typically set for 57.5 hz with a 5.0 second time delay
‒ If unit tripping occurs, pull out your “Black Start Restoration” guide
because it will be needed!
6443 190
Protective Relay Schemes for the Generator
Underfrequency Protection
• Turbine blades are designed and tuned to operate at rated frequencies
‒ Operating at frequencies different than rated can result in blade resonance and
fatigue damage
‒ Accumulated operation, for the life of the machine, not more than:
• 10 minutes for frequencies between 56 and 58.5 Hz
• 60 minutes for frequencies between 58.5 and 59.5 Hz
6443 191
Protective Relay Schemes for the Generator
6443 192
Protective Relay Schemes for the Generator
6443 193
Protective Relay Schemes for the Generator
6443 194
Remedial Action Schemes (RAS)
195
Disclaimer
• Examples of RAS will be provided for schemes used in the PJM RTO
‒ Each individual scheme on the PJM system is not covered in this presentation
6458 196
Introduction
6458 197
Problem Statement
www.gedigitalenergy.com (2013)
6458 198
Problem Statement
• Unaddressed system
vulnerabilities could result
in:
‒ Multiple contingencies
‒ Equipment damage
‒ Power system collapse
6458 199
Solution: Use Remedial Action Schemes (RAS)
6458 200
Criteria
• Dependability:
‒ Certainty that the scheme operates when required to avoid a collapse
• Security:
‒ Certainty that the scheme does not operate when not required
• Selectivity:
‒ Ability to select the correct and minimum amount of action
• Robustness:
‒ Ability of the scheme to provide dependability, security, and selectivity over the
full range of dynamic and steady state operating conditions
6458 201
NERC Standards
• As the Reliability Coordinator, Transmission Operator and Balancing Authority,
PJM is responsible to monitor the status of all schemes in the RTO
PRC-001.1(ii) R6
IRO-002-4 R5
6458 202
RAS Requirements
Communication Network
Relays
Scheme Logic
IF circuit breaker X trips THEN circuit breakers Y and Z
will____?
6458 203
PJM RAS Review Process
6458 204
PJM RAS Identification
6458 205
RAS Questions for Activation
6458 206
Types of RAS
6457 207
Types of RAS
6457 208
Trip Scheme
• Will initiate breaker operation to mitigate overload
The contingency loss
of this line…….
1 2 3
4 5
6
6457 210
Generation Load Rejection
6457 211
Generation Load Rejection
6457 212
Generation Load Rejection
If breaker 1 trips
open……..
6457 213
PJM RAS Actions
1. PJM will contact the TO to verify EMS results
and direct the RAS to be Enabled
6457 214
PJM TO/GO RAS Actions
6457 215
Relay Testing
Considerations & Concerns
216
Relay Testing
6442 217
Why Can Tripping Occur?
• Wiring errors
6442 218
Considerations and Concerns for S.O.’s:
‒ Would the removal of relay scheme go beyond the setting criteria for
other relay schemes?
6442 219
Protection Practice:
• Protection and Coordination are typically based upon the electrical system
being normal or altered by any single contingency
• A single contingency is the outage of a piece of equipment such as a line,
transformer or relay scheme
• If more than one piece of equipment is outaged at a station, protection or
coordination can be compromised
• The relay engineers should be contacted to insure protection and
coordination will still exist
6442 220
General Considerations for Dispatchers
Following a Relay Operation
6442 221
Know Your Company’s Policy Regarding
Dispatcher Response to a Relay Trip
6442 222
Data Collection and Fault Analysis
• Often knowing what has tripped may lead to a determination of the faulted
piece of equipment or potential relay problem
(See examples)
6442 223
Fault Analysis
Breakers 1 thru 7
trip open
Where is the
likely fault
location?
6442 224
Fault Analysis
6442 225
Appendix
Summary of Line Protection Schemes
6571 226
Summary of Line Protection Schemes
Scheme Will initiate trip when…
Local over-reaching relay operates AND there is an absence of a
Directional Carrier Blocking
BLOCKING signal from the remote end
Local under-reaching relay operates OR TRIP signal is received from
Direct Under-reaching Transfer Trip
the remote end
Permissive Under-reaching Transfer Local under-reaching relay operates OR local over-reaching relay
Trip operates AND a TRIP signal is received from the remote end
Local over-reaching relay operates AND a TRIP signal is received from
Permissive Over-reaching Transfer Trip
the remote end
Both the LOCAL TERMINAL and the REMOTE TERMINAL see fault
Phase Comparison current flowing INTO the line and BLOCKING CARRIER signal is out-of-
phase with the TRIP signal
The current flow induced in the operating coil is less than the current
AC Pilot Wire
induced in the restraint coil
The sum of the local and remote line currents seen by each relay is a
Line Differential
non-zero result
6571 227
Summary of Line Protection Schemes
Carrier Trip
Carrier Start
B T
Carrier Trip Carrier Start
T B
T T
B B
Under-reaching Relay
U
Under-reaching Relay
U
U U
6571 228
Summary of Line ProtectionOver-reaching
Schemes Relay
O
Under-reaching Relay
U
U
Under-reaching Relay
O
Over-reaching Relay
Permissive Under-Reaching Transfer Trip
U U
O O
Over-reaching Relay
O
Over-reaching Relay
O
O O
6571 229
Summary of Line Protection Schemes
Local Terminal Remote Terminal
Phase Comparison Blocking
6571 230
Summary of Line Protection Schemes
AC Pilot Wire
6571 231
Summary of Line Protection Schemes
FIBER FIBER
LOCAL REMOTE
OPTIC OPTIC
RELAY RELAY
TX/RX TX/RX
Line Differential
LOCAL REMOTE
TERMINAL TERMINAL
6571 232
Questions?
PJM Client Management & Services
Telephone: (610) 666-8980
Toll Free Telephone: (866) 400-8980
Website: www.pjm.com
233