This is a summary of the proposal for reducing the variety of Power transformers used in India. Such
standardization will reduce costly special test charges (like short circuit withstand test charges in a
high-power laboratory) by freezing transformer designs for a few years till there are technological
improvements to be incorporated, Utilities will be benefitted by the simplified procurement process,
reduced procurement time, inspection charges, shorter delivery time, interchangeability of different
makes and less inventories. Data provided may be useful for planning engineers as reference
1. Ratings and energy losses for distribution Transformers (up to 2.5 MVA 33 KV) are standardized ir
India vide IS:1180-2014 "Outdoor Type Oil Immersed Distribution Transformers up to and including
2500 kVA 33 kV-Specifications’. Transformers above 2.5 MVA are considered here for proposing the
ratings and efficiency levels. Of course, 100 % requirement of Power Transformers cannot be covered
in such an exercise, but even if 80-90 % of requirements can be brought under this rationalization, it
will be highly beneficial to users and manufacturers. The list does not cover special transformers like
Generator Transformers for hydro-electric projects, industrial transformers (Furnace and Rectifier),
transformers for renewable energy projects and static compensators (STATCOM, SVC), traction
transformers and mining transformers.
2. Preferred Losses for transformers are arrived at on the following assumptions/requirements
2.1. The MVA ratings are all of three phase units except where 3x ABC is shown. Such transformers
are of three phase banks, formed from three single-phase transformers of rating ABC MVA. Preferred
MIVA ratings are generally from R 5 series ie multiples of fifth root of 10 ie. 1-1.6-2.5-4-6.3-10 series
instead of R10 series (multiples of tenth root of 10- 1,1,25,1.6,2,2.5,3.15,4,5,6.38,10) used so far.
2.2 The losses (Wi= No-load Loss; We = Load Loss; Waux = Auxiliary or cooler loss) indicated are
the maximum limits except for stray losses. Stray losses may vary plus or minus from the indicated
values, but maximum I2R and maximum load loss limits shall not be exceeded and are treated as
guaranteed figures. Loss capitalization is not applied during the tendering stages and no advantage is
given for lower measured losses during testing. 2.3 Maximum current density is limited to 2.5
A/mm2 at all taps in all active windings except stabilizing tertiary (unloaded) windings where
maximum current density is to be limited to 4.5 A/mm2. Maximum flux density limit at rated voltage
and frequency is 1,7 T for Generator Transformers and 1.65 T for all other transformers. High
permeability (Hi B) or domain refined CRGO is considered for the no-load losses.
2.4 Continuously transposed cable (CTC) is to be used for any winding current path above 400 A for
transformer ratings of 10 MVA and above. Conductor strand thickness of CTC shall not be less than
Imm
25. Taps and Arrangement
All two winding transformers - +- 5 % (de-energised tap changer) or +5 % to -15 % (on-load Tap-
changer) with body taps or separate tap winding on HV winding neutral end for HV variation. Winding
arrangement - Core -Tertiary - LV-HV -Regulating
Generator Transformers - +- 5 % (de-energised tap-changer) or fixed ratio, without taps. Taps on HV
neutral for HV variation. Body taps or LV-HV-Regulating winding arrangement.Auto- transformers up to and including 420 kV:
At present in the country there are 220 kV class auto-transformers of different tapping arrangement
a) Taps on HV (series winding) for HV variation by +- 10% with two options- constant ohmic or
constant percentage impedance.
b) Taps on MV line end for MV variation by +-10 % with two options- constant ohmic or constant
percentage impedance.
As standard, HV (series winding) taps for HV variation with constant percentage impedance is
selected.
With respect to 400 kV class auto-transformers, there are two voltage ratios- 400/ 220 kV (most
common) and 400/132 kV. In case of 400/132 kV class transformers, OLTC is provided in HV (series)
winding for HV variation by +-10 % with regulating winding positioned between tertiary and common
so as to get constant ohmic impedance at all taps. But an economical solution used in most countries
is to provide OLTC at neutral end of common winding for MV variation. This neutral end application of
OLIC is selected as the standard
400/220 KV class auto-transformers form bulk of the 400 kV transformer population and in these units,
OLTC is provided in HV (series) winding for HV variation by +-10 %. In this application, there are two
variants used in the country. In North and East India, regulating winding is positioned between tertiary
and common winding, resulting in constant ohmic impedance at all taps. But in West and South India,
regulating winding is placed between common and series winding, resulting in constant percentage
impedance at all taps. Since the 400 kV grid in the country is strong and well interconnected, these
tap-changers in 400/220 kV units are found to be ineffective and rarely used. Hence as standard, fixed
ratio 400/220 kV auto-transformers without OLTC is selected as standard and where ever OLTC is
essential, constant percentage impedance arrangement (Try-Common-Reg-Ser) is proposed as
standard
800 kV Auto-Transformers
When the first 3x500 MVA 765/400 kV auto-transformers were procured in 2005, these were double
limb wound, with TRY-Reg-Common-Series winding arrangement and with OLTC on HV neutral end
for HV variation by +-5 %. But transformers procured in later years were single limb wound type with
tertiary and regulating windings on the side core limb. These were with very high tertiary impedances
(HV-Try 195 % and MV-Try with 180 % instead of the earlier 67 % and 49 % respectively) and at
present these high tertiary impedance transformers are the standard. Units from these two types of
banks cannot be interchanged to form three phase banks, due to the difference in tertiary
impedance. In future, at many locations fixed ratio units will be sufficient and where ever, OLTC is
required, single limb Try-Reg-Common-Series winding arrangement is proposed
2.6. Purchaser has the right to check the specific loadings (current density in winding and flux
density in core) at various stages of procurement (tender stage, design review stage, manufacturing
stage) against the values furnished in GTP2.7. Stabilizing delta tertiary winding is not required for transformers with 3 phase 3 limbed core
construction, At present, stabilizing delta tertiary winding is not provided in YNyn connected
transformers up to a rating of 100 MVA. Since rating has no significance with stabilizing tertiary, core
construction is considered as criteria for deciding the necessity of stabilizing delta winding
2.8 ONAN cooling will be used for ratings up to 31.5 MVA. Preferred cooling for ratings of
5OMVA and above is ONAN/ONAF-1/ONAF-2(with 60:80:100 rating). ONAN/ONAF/ODAF or OFAF can
ve alternate to ONAN/ONAF-1/ONAF-2 cooling subject to purchaser's approval. As very low current
densities are used in windings (due to the high energy efficiency specified) there is very little
advantage with forced oil cooling and the preferred cooling is ONAN/ONAF-1/ONAF-2.
29 The Insulation levels for various voltage classes are as below.
Voltage class [AC Power Frequency | Basic impulse Level | Swiching Impulse level | Bushing Insulation Levels
Test Voltage kV kv Kv
@ 2 5 4285
36 70 170 7770
725 740 cy 1551825
123 230 Ea 3051650
145 25 650 3051650
25 35 350 750 ‘05/T0507850
420 570 1300 1050 951142511050
Note +
00 3 1950 1550 ‘aTORTOOrIO50
Note 2
Note 1- Generator Transformers are with one step higher test voltages- 630/1175/1425 kV
Note 2- Generator Transformers are with one step higher test voltages -/1700/2050 kV
MAXIMUM LOSSES FOR STANDARD TRANSFORMERS
412KV Class Transformers
Par
Peak
31 | Rating | % | ype | WE | We | Waux| wey PRLoss | g') | wotsway | eMtciency| level?)
No | (HVA) | impedance 419 | (aw) | te) ww Loss | Index’ | ecspors.
wey | Se
To
+[ a5 [6 | wming| 2 | 2 | o [us] 6 soso | 905s
233 ~ [sao | ea] wae | Sart
3 [0 3 Fo woes | w9sis
«[ 6 | 10 o[m | 0 [se] ss s9 704 | 99.863
264V Clase Transformers
Zz Per
tout | sot (iovol2) as
st Rating | 1% wi | we | wax s Peak 2
No | (HVA) | impedance | "YP® | aw) | caw | wy | MEM! | eee | Gtey | Stay | emiciency | yechoo7e.
0
s{ as |e [mel 2 | | o | us 9569 | ose
o[3 7 a a wse0_| art
za 3 a _[ 48 [0] 88 39510 | 99615
a6 10 oe 99.563 99663
sts] es [= 6 [10 [or 99701 | 99700