RPD - ELCO
RPD - ELCO
RPD
500 ... 80000 kW
2 stage progressive/modulating mechanical or electronic
RANGE OVERVIEW
AVAILABLE CONFIGURATIONS
DIMENSIONS (mm)
D1
D2
A1 G* B8 R*
H2
D4
H3
T3
T2
H1
H4
LK
T1 LP W T
Y
Z
P3
P4
X
D3 D3
D2
D2
Model A1 B8 D1 D2 D3 D4 D7 H1 H2 H3 H4 P1 P2 P3 P4 T T1 T2 T3 V W X Y Z LK LP
Gas train for EK EVO 6/7 and NEXTRON N6/N7 (EN676 configuration)
DUNGS
SIEMENS
GT-s451-1“1/2 Threaded design 3750525 s1”1/2-Rp1”1/2 795 375 405 100 285 105 145 65 320 135
GT-s452-2“ Basic version 3750526 s2”-Rp2” 805 405 435 105 285 105 145 100 325 140
GT-s453-65 3750527 s65-DN65 795 355 385 120 305 125 125 110 365 135
GT-s454-80 Flanged design 3750528 s80-dN80 815 375 405 135 315 125 125 110 375 135
GT-s455-100 Basic version 3750529 s100-DN100 855 375 405 145 335 145 145 125 385 135
GT-s456-125 3750530 s125-DN125 905 375 405 180 350 160 160 140 400 135
(2)
: in PED configuration
Gas trains are fully mounted, electrical connected and tested (electrical, hydraulic, leakage)
i Additional components (filter and other options) in order to comply to the local regulation and codes of practise must be ordered separately
FILTERS
Gas filter with flange PN 16, with non-ferrous metal, DN40 L = 160 mm 3757196
max. working pressure 2 bar DN50 L = 160 mm 3757197
DN65 L = 290 mm 3757198
DN80 L = 310 mm 3757201
DN100 L = 350 mm 3757195
L DN125 L = 480 mm 3757209
DN150 L = 480 mm 3757210
Gas train for EK EVO 8/9 and NEXTRON N8/N9 (EN676 configuration)
DUNGS
SIEMENS
GT-s457-2“ Threaded design 3750537 s2”-Rp2” 805 598 623 105 285 105 145 100 325 135
GT-s458-65 3750538 s65-DN65 795 598 623 120 305 125 125 110 365 135
GT-s459-80 Flanged design 3750539 s80-dN80 815 598 623 135 315 125 125 110 375 135
GT-s460-100 Basic version 3750540 s100-DN100 855 598 623 145 335 145 145 125 385 135
GT-s461-125 3750541 s125-DN125 905 598 623 180 350 160 160 140 400 135
(2)
: in PED configuration
Gas trains are fully mounted, electrical connected and tested (electrical, hydraulic, leakage)
i Additional components (filter and other options) in order to comply to the local regulation and codes of practise must be ordered separately
FILTERS
Gas filter with flange PN 16, with non-ferrous metal, DN40 L = 160 mm 3757196
max. working pressure 2 bar DN50 L = 160 mm 3757197
DN65 L = 290 mm 3757198
DN80 L = 310 mm 3757201
DN100 L = 350 mm 3757195
L DN125 L = 480 mm 3757209
DN150 L = 480 mm 3757210
DUNGS
Other configurations:
i available on request
SIEMENS
Other configurations:
i available on request
Gas trains are fully mounted, electrical connected and tested (electrical, hydraulic, leakage)
i Additional components (filter and other options) in order to comply to the local regulation and codes of practise must be ordered separately
FILTERS
Gas filter with flange PN 16, with non-ferrous metal, DN80 L = 310 mm 3757201
max. working pressure 2 bar DN100 L = 350 mm 3757195
DN125 L = 480 mm 3757209
DN150 L = 480 mm 3757210
DUNGS
SIEMENS
K
Other configurations:
i available on request
Gas trains are fully mounted, electrical connected and tested (electrical, hydraulic, leakage)
i Additional components (filter and other options) in order to comply to the local regulation and codes of practise must be ordered separately
FILTERS
Gas filter with flange PN 16, with non-ferrous metal, DN80 L = 310 mm 3757201
max. working pressure 2 bar DN100 L = 350 mm 3757195
DN125 L = 480 mm 3757209
DN150 L = 480 mm 3757210
7
7 6
6 1. main gas pipe
2. ball valve*
3. anti-vibration coupling*
5. minimum gas pressure switch
6. safety gas valve
7. main gas valve
8. leakage control device*
9. gas filter* (governor included in the valve)
1 5 10. actuator SKP 15
1 22 33 9
9 5 8
8 11
11 10
10
11. actuator SKP 75
Gas trains are fully mounted, electrical connected and tested (electrical, hydraulic, leakage)
i Additional components (filter and other options) in order to comply to the local regulation and codes of practise must be ordered separately
FILTERS
2“ on request
DN65 - 2“1/2 on request
DN80 - 3“ on request
DN100 - 4“ on request
DN125 - 5“ on request
BT3
The device is composed of a control box for safety and for programming the parameters of mono- and dual fuel burners with intermittent or conti-
nuous operation through a step by step servomotor up to 10 Nm.
The BT300 combines the benefits of an electronic fuel-air ratio control system with up to three motorised actuating devices and an optional modules
like an analogue output for speed control of the combustion air fan with an electronic burner control unit.
The BT300 is available in three designs with the following specific functions:
• BT320 for single fuel burner and intermittent operation, with an output 0...10 V, 0/4...20 mA and the management of two servomotors;
• BT330 for single fuel burner and continuous operation, using suitable flame detectors, with an output 0...10 V, 0/4...20 mA and the management
of three servomotors;
• BT340 for dual fuel burner and continuous operation, using suitable flame detectors, with an output 0...10 V, 0/4...20 mA and the management of
three servomotors.
COMMUNICATION MODULE
BT300 module for electronic burners mounted in the switch cabinet of the burner ModBus/BT3 3754081
(Note: one LCM module is required)
ProfiBus/BT3 3750142
Ethernet/BT3 on request
LCM MODULE
Module required for O2 control, Variatron and communication buses connections 3752286
Note: only one LCM module is necessary for these 3 options; the module is already included on dual fuel burners
REMOTE SOFTWARE
Kit to connect a PC laptop to the BT300 for its parametrization LSA100 + USB/CAN + CD-Rom 3751130
Electronic control Etamatic with 4 DPS-adjusting outputs for servodrives up to 50 mA of direct current with:
• incorporated tightness control of the valves;
• incorporated regulator of power;
• incorporated counter of working hours with pulse transducer;
• incorporated relay of flame;
• incorporated program of O2 regulation, including the system Lamtec with connecting bus.
Electronic control Etamatic S with a steady adjusting output for the regulation of the number of revolutions of the fan supplying the air of nurning
and 4 DPS-adjusting outputs for the servodrives up to 50 mA of direct current with:
• incorporated tightness control of the valves;
• incorporated regulator of power;
• incorporated counter of working hours with pulse transducer;
• incorporated relay of flame;
• incorporated program of O2 regulation, including the system Lamtec with connecting bus.
For the control of the number of revolutions it is required additionally:
• Static frequency converter;
• Switch Namur.
Software for remote PC connection for Lamtec ETAMATIC OEM with all its accessories for the connection (available languages: English, German and French) 3753366
Customer interface (DISPLAY) for ETAMATIC OEM 3751683
Hand held programming unit for ETAMATIC OEM (languages: German and English) - Alternative to software 3753366 when PC is not available 1718850339
Hand held programming unit for ETAMATIC OEM (language: Russian) - Alternative to software 3753366 when PC is not available 3754519
Note: either customer interface or operation and display unit has to be included
The control unit has to be installed close to the probe (max 20 m of cable)
The probe needs a calibration but no reference gas is necessary.
The display shows the O2 content.
Maximum distance between the control unit and the burner control panel is 500 m.
The control unit has to be installed close to the probe (max 20 m of cable).
The probe needs a calibration but no reference gas is necessary.
The display shows the O2 content.
Maximum distance between the control unit and the burner control panel is 500 m.
Note: this system is not suitable for GL-EUF and L-EUF burners