GENERAL ELECTRICAL NOTES GENERAL SITE PLAN NOTES LEGEND NOTE: INTERPRET IN CONTEXT

1. CODE COMPLIANCE: ALL WORK SHALL CONFORM TO AND BE PERFORMED IN ACCORDANCE WITH CODES, STANDARDS, AND ORDINANCES AS SET A. TRENCHING AND BACKFILLING FOR ALL CONDUIT SYSTEMS SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR. ALL LIGHT FIXTURES POWER/COMM. CONDUIT/WIRE
FORTH BY THE AUTHORITIES HAVING JURISDICTION AND THEIR LATEST ADOPTED EDITIONS (IN EFFECT AT TIME OF BUILDING PERMIT APPLICATION) CONDUITS SHALL HAVE MINIMUM COVER REQUIREMENTS AS SPECIFIED IN CEC 300-5. MORE STRINGENT DEPTH REQUIREMENTS MAY

P.O. Box 1167 - 3562 Empleo St.


THOMA ELECTRIC, INC.
CEILING SURFACEMOUNT SINGLE RECEPT. NEW
BE IMPOSED BY UTILITY COMPANY AND / OR THIS SPECIFICATION. JOINT TRENCHING MAY BE UTILIZED WHERE PRACTICABLE AND

San Luis Obispo, CA 93406


OF THE FOLLOWING PUBLICATIONS:

Phone: (805) 543-3850

[email protected]
WALL SURFACEMOUNT DUPLEX RECEPT. UNDERGROUND

Fax: (805) 543-3829


WERE PERMITTED BY THIS SPECIFICATION.
PENDANT MOUNT DUPLEX- HALF SWITCHED NEW POWER HOMERUN
A. CALIFORNIA CODE OF REGULATIONS TITLE 24; INCLUDES 2016 CALIFORNIA ELECTRICAL CODE, 2016 CALIFORNIA FIRE CODE, 2016 CALIFORNIA
(3 HOTS & NEUT SHOWN)
BUILDING CODE, ETC. WITH LOCAL AMENDMENTS AS APPLICABLE. B. LOCATIONS OF EXISTING UNDERGROUND (UG) UTILITY SYSTEMS SHALL BE DETERMINED BY CALLING UNDERGROUND SERVICE ALERT RECESSED DOWNLIGHT DOUBLE DUPLEX
(USA). WHEN PLANNING UNDERGROUND WORK, AND BEFORE YOU DIG, CONTACT UNDERGROUND SERVICE ALERT (USA) AT LEAST 48 ISOLATED GROUND
RECESSED WALLWASH SPECIAL CONFIGURATION
E EXISTING TO REMAIN
B. AMERICANS WITH DISABILITIES ACT (ADA). HOURS PRIOR TO EXCAVATION (WEEKENDS EXCLUDED) FOR THE LOCATION OF UNDERGROUND GAS AND ELECTRIC LINES OR RECESSED FIXTURE FLOORMOUNT 208V, 1Ø RECEPT
EQUIPMENT. SURFACE FIXTURE DUPLEX- FLOOR OUTLET
(E) POWER HOMERUN
2. SAFETY: THE ELECTRICAL CONTRACTOR IS RESPONSIBLE TO MAINTAIN ALL EQUIPMENT IN A SAFE AND RESPONSIBLE MANNER. KEEP DEAD FRONT STRIP FIXTURE GFI GROUND FAULT CIRCUIT INTERRUPT
WIRE LINE- CONTINUES
EQUIPMENT IN PLACE WHILE EQUIPMENT IS ENERGIZED. CONDUCT ALL CONSTRUCTION OPERATIONS IN A SAFE MANNER FOR EMPLOYEES AS WELL C. MAINTAIN REQUIRED CLEARANCES FROM ALL SANITARY SEWER, WATER AND STORM DRAIN PIPING. REFER TO CIVIL PLANS FOR EXACT CONDUIT STUB (W/MARKER)
TRACK LIGHT * MOUNTED ABOVE COUNTER
AS OTHER WORKPERSONS OR ANYONE VISITING THE JOB SITE. PROVIDE BARRIERS, FLAGS, TAPE, ETC. AS REQUIRED FOR SAFETY. THE LOCATIONS AND DEPTHS OF PIPING. VERTICAL CONDUIT RUN
DIRECTIONAL FLOOD J JUNCTION BOX
CONTRACTOR SHALL HOLD ALL PARTIES HARMLESS OF NEGLIGENT SAFETY PRACTICES, WHICH MAY CAUSE INJURY TO OTHERS ON OR NEAR THE JOB CONDUIT SEAL
EMERGENCY FIXTURE TELEPHONE OUTLET
SITE. FLEXIBLE CONNECTION
POLE LIGHT DATA OUTLET
LV
LOW VOLTAGE
3. FIRE RATED ASSEMBLIES SHALL MAINTAIN RATINGS AS SPECIFIED IN THE CALIFORNIA BUILDING CODE CHAPTER 7. CONTRACTOR SHALL PROVIDE POLE LIGHT- DECORATIVE PHONE/DATA COMBO OUTLET
SURFACEMOUNT RACEWAY
AND INSTALL PHYSICAL ENCLOSURE AROUND FIXTURES, PANELS, ETC. AS REQUIRED. ALL ASSEMBLIES TO BE PENETRATED SHALL BE INSTALLED UPLIGHT- FLUSH IN GRADE * MOUNTED ABOVE COUNTER
FESSIONA
WITH APPLICABLE THROUGH-PENETRATION FIRESTOP SYSTEM AS DETERMINED BY UL CLASSIFICATION. BEFORE CONSTRUCTION, VERIFY AND BOLLARD TV TELEVISION OUTLET
INDICATES LINE CONTINUES PRO L
CORD W/PLUG ED A M A. T H
COMPLY WITH REQUIREMENTS OF LOCAL AUTHORITY HAVING JURISDICTION.

EN A
ER
TANDEM-WIRED LAMPS SAFETY DISCONNECT L I

REGI ST

GI N
WI L

OM
UNDERCABINET LIGHT J DROP CORD RECEPT

EER
4. MOUNTING HEIGHTS SHALL BE AS FOLLOWS UNLESS OTHERWISE NOTED: WALL SURFACEMOUNT LINEAR TYPE ABOVE-CLGMOUNT J-BOX
J C
NO. 10757
PENDANT LINEAR FIXTURE TV TV OUTLET-FLOORMOUNT
+15" AFF: RECEPTACLES & DATA OUTLETS. (MEASURED BOTTOM OF OUTLET BOX) FIRE ALARM L

L
AT E C T R I C A N

ST

IA
RECESSED WALLMOUNT TELEPHONE FLOOR OUTLET
+46" AFF: OUTLET ABOVE COUNTER (MEASURED TOP OF OUTLET BOX) EO R
+48" AFF: LIGHT SWITCHES. (MEASURED TOP OF OUTLET BOX) WALLPACK DATA FLOOR OUTLET FIRE ALARM CONTROL PANEL F C A L I FO
EXIT LIGHT- WALL PHONE/DATA COMBO FLOOR OUTLET RPS REMOTE POWER SUPPLY
+48" AFF: FIRE ALARM MANUAL PULL STATIONS, T-STATS. (MEASURED TOP OF OUTLET BOX) EXPIRES: 06/30/21
THE LOWER OF +80" AFF TO BOTTOM OF LENS, OR 6" BELOW CEILING: FIRE ALARM VISUALS. EXIT LIGHT- CEILING IDF INTERMEDIATE DISTRIBUTION FRAME H HORN- AUDIBLE DEVICE
THOMA #19-8075
(ARROW INDICATES DIRECTION) MDF MAIN DISTRIBUTION FRAME V VISUAL- VISUAL DEVICE
A
ELECTRICAL SWITCHES: CONTROLS AND SWITCHES INTENDED TO BE USED BY THE OCCUPANT OF THE ROOM OR AREA TO CONTROL LIGHT AND LETTER ADJACENT INDICATES AP ACCESS POINT AV AUDIBLE/VISUAL
RECEPTACLE OUTLETS, APPLIANCES OR COOLING, HEATING AND VENTILATING EQUIPMENT, SHALL BE LOCATED NO MORE THAN 48 INCHES FIXTURE TYPE SV SPEAKER/VISUAL
MEASURED FROM THE TOP OF THE OUTLET BOX NOR LESS THAN 15 INCHES MEASURED FROM THE BOTTOM OF THE OUTLET BOX TO THE LEVEL OF F FLOW SWITCH
THE FINISH FLOOR OR WORKING PLATFORM. [CBC 11B-308.1.1] MISCELLANEOUS T TAMPER SWITCH
P MANUAL PULL STATION
ELECTRICAL RECEPTACLE OUTLETS: ELECTRICAL RECEPTACLE OUTLETS ON BRANCH CIRCUITS OF 30 AMPERES OR LESS AND COMMUNICATION MOTOR
SWITCHES SD SMOKE DETECTOR

151 West Branch Street; Suite E


SYSTEM RECEPTACLES SHALL BE LOCATED NO MORE THAN 48 INCHES MEASURED FROM THE TOP OF THE RECEPTACLE OUTLET BOX OR T THERMOSTAT
SD D DUCT SMOKE DETECTOR
RECEPTACLE HOUSING NOR LESS THAN 15 INCHES MEASURED FROM THE BOTTOM OF THE RECEPTACLE OUTLET BOX OR RECEPTACLE HOUSING TO

Arroyo Grande, CA 93420


SPST CIRCUIT BREAKER
SD CO SMOKE/CO DETECTOR
THE LEVEL OF THE FINISH FLOOR OR WORKING PLATFORM [CBC 11B-308.1.2] 2 DPST FUSIBLE SWITCH

(805) 574-1550
3-WAY H HEAT DETECTOR
3 GROUND
BEFORE ROUGH-IN, VERIFY ALL MOUNTING HEIGHTS AND EXACT LOCATIONS FOR ALL EQUIPMENT ELECTRICAL CONNECTIONS, STUB-UPS, 4-WAY B BELL
4 Ø PHASE
RECEPTACLES, OUTLETS, ETC. WITH ARCHITECT OR OWNER. PLACE DEVICES LOCATED ABOVE COUNTERS, SHELVING, ETC. AND IN BATHROOMS SO DIMMER END OF LINE RESISTOR
D CLOCK
AS NOT TO CONFLICT WITH EDGES OF WAINSCOTING, COUNTER SPLASH, SHELVING, ETC. ARCHITECTURAL SHEETS SHALL GOVERN. C CHIME
TIMER SWITCH S CLOCK/SPEAKER COMBINATION
T W/THERMAL OVERLOAD
5. WIRING DEVICES SHALL BE WHITE IN COLOR. WIRING DEVICE FACEPLATE SHALL BE STAINLESS STEEL. WALL MOUNTED CLOCK
P W/PILOT LIGHT PUSHBUTTON
6. LABEL PANELS, CABINETS, BACKBOARDS, MAIN DEVICES, SAFETY SWITCHES, CONTACTORS AND OTHER SPECIFICALLY DESIGNATED EQUIPMENT K KEY OPERATED
SOUND
FLUSHMOUNT PANEL
SHOWN ON PLANS. USE ENGRAVED LAMINATED PLASTIC NAMEPLATES ATTACHED BY SCREWS OR RIVETS. FOR FEEDERS, NEATLY AND INDELIBLY DUAL LEVEL SWITCHING S SPEAKER- CLG FLUSHMOUNT
SURFACEMOUNT PANEL
LABEL CONDUIT DESTINATIONS ON BOTH VISIBLE ENDS OF CONDUIT RUNS WHERE CONDUITS TERMINATE AT DESIGNATED ENCLOSURES, ,a SWITCHLEG DESIGNATION FLUSHMOUNT CABINET
S SPEAKER- WALLMOUNT
STRUCTURES OR EQUIPMENT (INCLUDING PULL AND SPLICE BOXES). OS OCCUPANCY SENSOR S WP WEATHERPROOF SPEAKER
SURFACEMOUNT CABINET
M MICROPHONE INPUT
DM DAMPER MOTOR
7. EQUIPMENT ANCHORAGE NOTE A
H HUMIDISTAT AUXILIARY INPUT
ALL MECHANICAL AND ELECTRICAL EQUIPMENT SHALL BE ANCHORED OR BRACED TO MEET THE HORIZONTAL AND VERTICAL FORCES PRESCRIBED IN
M HS HEADSET OUTLET
THE 2016 CBC, SECTIONS 1613A AND 1616A AND ASCE 7-10 SECTIONS 13.3, 13.4 & 13.6. MAGNETIC CONTACTOR
V VOLUME CONTROL
COMBINATION STARTER
THE ATTACHMENT OF THE FOLLOWING ITEMS SHALL BE DESIGNED TO RESIST THE FORCES PRESCRIBED ABOVE, BUT NEED NOT BE DETAILED ON THE V S SPEAKER- CLG FLUSHMOUNT
VANDAL-RESISTANT
PLANS PER 2016 CBC SECTION 1616A.1.18:
S CLOCK/SPEAKER WALLMOUNT
A. FURNITURE(EXCEPT STORAGE CABINETS AS NOTED IN 2016 CBC TABLE 13.5-1) SEMI-FLUSH
B. TEMPORARY OR MOVABLE EQUIPMENT WITH EXCEPTIONS NOTED IN 2016 CBC SECTION 1616A.1.18 ITEM 2.
C. ARCHITECTURAL, MECHANICAL, AND ELECTRICAL COMPONENTS IN SEISMIC DESIGN CATEGORIES D, E, OR F
THAT MEET ALL OF THE CRITERIA LISTED IN 2016 SECTION 1616A.1.18 ITEM 3.
D. EQUIPMENT WEIGHING LESS THAN 20 POUNDS SUPPORTED BY VIBRATION ISOLATORS. CONVENTIONS

REVISIONS
E. EQUIPMENT WEIGHING LESS THAN 20 POUNDS SUSPENDED FROM A ROOF OR FLOOR OR HUNG FROM A
WALL NUMBERED SHEET NOTES: REFERS TO NOTES
X
ON SAME SHEET AS REFERENCE
FOR THOSE ELEMENTS THAT DO NOT REQUIRE DETAILS ON THE APPROVED DRAWINGS, THE INSTALLATION SHALL BE SUBJECT TO THE APPROVAL OF

4
2

3
THE MECHANICAL/ELECTRICAL ENGINEER. DETAIL REFERENCE:
1
-DETAIL DESIGNATION
-
PIPING, DUCTWORK, AND ELECTRICAL DISTRIBUTION SYSTEM BRACING NOTE -SHEET NUMBER REFERENCE

PIPING, DUCTWORK, AND ELECTRICAL DISTRIBUTION SYSTEMS SHALL BE BRACED TO RESIST THE FORCES PRESCRIBED IN ASCE 7-10 SECTION 13.3 AS
3103 FEEDER SCHEDULE DESIGNATION
DEFINED IN ASCE 7-10 SECTION 13.6.8, 13.6.7, AND 13.6.5.5, ITEM 6, RESPECTIVELY. (EXAMPLE: 3103 = 310 AMPERE, 600V,
3 CURRENT CARRYING CONDUCTORS,
THE BRACING AND ATTACHMENTS TO THE STRUCTURE SHALL COMPLY WITH ONE OF THE OSHPD PRE-APPROVALS WITH AN OPM, SUCH AS MASON PREFIXES: 'M' INDICATES MEDIUM VOLTAGE,
INDUSTRIES (OPM 0043-13) AS MODIFIED TO SATISFY ANCHORAGE REQUIREMENTS OF ACI 318, APPENDIX D. 'CO14' INDICATES CONDUIT ONLY,
QUANTITY (1) AND SIZE (4"))

ARROYO GRANDE HIGH SCHOOL


COPIES OF THE MANUAL SHALL BE ON THE JOBSITE PRIOR TO STARTING HANGING AND BRACING OF THE PIPE, DUCTWORK, AND ELECTRICAL
DISTRIBUTION SYSTEMS.

THE STRUCTURAL ENGINEER OF RECORD SHALL VERIFY THE ADEQUACY OF THE STRUCTURE TO SUPPORT THE HANGER AND BRACE LOADS. ABBREVIATIONS

495 VALLEY ROAD, ARROYO GRANDE, CA 93420


FIRE ALARM SYSTEM A AMPERE EL EVENING LIGHT LS LIFE SAFETY BRANCH (R) RELOCATE(D)
AB AMP BREAKER ELEC ELECTRICAL LT LIGHT RECEPT RECEPTACLE

300 WING REMODEL


ABAND ABANDONED EM EMERG BATTERY BACKUP LTG LIGHTING REF REFRIGERATOR
1. PROVIDE ALL WORK AND MATERIAL REQUIRED FOR A COMPLETE AND OPERATING FIRE ALARM SYSTEM. WORK SHALL INCLUDE (BUT NOT BE LIMITED ABV ABOVE EMERGENCY BALLAST LV LOW VOLTAGE REQ'D REQUIRED
TO): AC ALTERNATING CURRENT EMERG EMERGENCY MC MECHANICAL CONTRACTOR RLA RATED LOAD AMPS
AC-# AIR CONDITIONER EOL END OF LINE MCA MINIMUM CKT AMPS RM ROOM
ADJ ADJACENT EQUIP'T EQUIPMENT MCB MAIN CIRCUIT BREAKER RMC RIGID METAL CONDUIT
A. PRODUCT DATA SUBMITTAL FOR APPROVAL. AF AMP FUSE, AMP FRAME ES ENERGY SAVING MCTB MAIN CATV TERMINAL BOARD RMV REMOVE
B. COMPLETE INSTALLATION AND TESTING AFF ABOVE FINISH FLOOR (EXN) (E) IN (N) LOCATION MCTC MAIN CATV TERMINAL CABINET RPLC REPLACE

APN # 006-095-026
C. SYSTEM TRAINING FOR OWNER'S REPRESENTATIVE AFG BOVE FINISH GRADE (EXR) (E) TO BE (R) MDF MAIN DISTRIBUTION FRAME RS RAPID START
AIC AMPERES INTERRUPTING CAPACITY EXT EXTERIOR MECH MECHANICAL SC SIGNAL CABINET
D. WARRANTY Al ALUMINUM F FLUORESCENT MFR MANUFACTURER SCC SHORT CKT CURRENT
AS AMP SWITCH RATING (F) FUTURE MFS MAIN FUSIBLE SWITCH SFM STATE FIRE MARSHAL
EXISTING BUILDINGS ATS AUTOMATIC TIME SWITCH F-# FURNACE MH METAL HALIDE SHT SHEET
ATS AUTOMATIC TRANSFER SWITCH FA FIRE ALARM MLO MAIN LUGS ONLY SL SLIMLINE, SWITCH LEG
AV AUDIBLE/AUDIO VISUAL FACP FIRE ALARM CONTROL PANEL MOCP MAXIMUM OCP SPEC SPECIFICATION
1. ASBESTOS: IF DURING THE COURSE OF WORK THE CONTRACTOR OBSERVES THE EXISTENCE OF ASBESTOS, OR ASBESTOS-BEARING MATERIALS, AWG AMERICAN WIRE GAGE FAT FIRE ALARM TERMINAL MSB MAIN SWITCHBOARD SPST SINGLE POLE SINGLE THROW
THE CONTRACTOR SHALL IMMEDIATELY TERMINATE FURTHER WORK ON THE PROJECT AND NOTIFY THE OWNER OF THE CONDITION. THE OWNER BFG BELOW FINISH GRADE FAU FORCED AIR UNIT MT MOUNT SQ SQUARE
BIL BASIC IMPULSE LEVEL FBO FURNISHED BY OTHERS MT HT MOUNTING HEIGHT STR'G STORAGE
WILL, AFTER CONSULTATION WITH THE OWNER'S REPRESENTATIVE, DETERMINE A FURTHER COURSE OF ACTION. BLDG BUILDING FC-# FAN COIL MTS MANUAL TRANSFER SWITCH SURF SURFACE
Apr 15, 2020 - 8:51am - pat - K:\ENG\2019\19-8075\19-8075_E-001 - E-003_ GENERAL NOTES, LEGENDS, & ABBREVIATIONS.dwg

C CONDUIT FLA FULL LOAD AMPS MTTB MAIN TELEPHONE TERMINAL BOARD SVC SERVICE
2. ANY DEMOLITION WORK SHOWN WAS PREPARED FOR THE CONVENIENCE OF THE CONTRACTOR. THE ENGINEER DOES NOT REPRESENT THAT ALL -C- CATV CONDUIT FLR FLOOR MTTC MAIN TELEPHONE TERMINAL SW SWITCH
CAB'T CABINET FLUOR FLUORESCENT CABINET T TRANSFORMER, TERMINAL
ITEMS WHICH MAY REQUIRE DEMOLITION HAVE BEEN SHOWN. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO CAREFULLY EXAMINE THE CATV CABLE TELEVISION FS FUSIBLE SWITCH MW MICROWAVE -T- TELEPHONE CONDUIT
SITE AND THE CONTRACT DOCUMENTS AND TO PERFORM ALL DEMOLITION AND RECONSTRUCTION WHICH MAY BE REQUIRED FOR THE PROPER CB CIRCUIT BREAKER, CODE BLUE FVNR FULL VOLTAGE NON-REVERSING N NEUTRAL (GROUNDED CONDUCTOR) (TBR) TO BE REMOVED
EXECUTION AND COMPLETION OF THE WORK. CBC CA. BUILDING CODE G GROUNDING CONDUCTOR (N) NEW TC TIME CLOCK
CEC CA. ELECTRICAL CODE GC GENERAL CONTRACTOR N3R NEMA 3R TEL TELEPHONE
CA. ENERGY COMMISSION GD GARBAGE DISPOSAL NC NORMALLY CLOSED TELCO TELEPHONE COMPANY
3. EXISTING CONDITIONS: INFORMATION SHOWN FOR EXISTING CONDITIONS WAS PRIMARILY GAINED FROM "AS BUILT" DRAWINGS AND/OR LIMITED FIELD CF COMPACT FLUORESCENT GFCI GROUND FAULT CIRCUIT NEC NATIONAL ELECTRICAL CODE TS TIME SWITCH
INVESTIGATION. BEFORE BID, VISIT SITE TO VERIFY EXISTING CONDITIONS AND MAKE ALLOWANCE FOR VARIATIONS FROM THAT SHOWN. CFC CALIFORNIA FIRE CODE INTERRUPTER NEMA NAT'L ELEC MANUFACTURER'S TSO TIME SWITCH OVERRIDE
CLG CEILING GFI GROUND FAULT CIRCUIT ASSOC TSP TWISTED SHIELDED PAIR
CL CENTER LINE INTERRUPTER NIC NOT IN CONTRACT TTB TELEPHONE TERMINAL BOARD
4. WHERE EXISTING BUILDING CONSTRUCTION, MECHANICAL UNITS AND OTHER EQUIPMENT IS SHOWN TO BE REMOVED, DISCONNECT AND REMOVE ALL CKT CIRCUIT GND GROUND NL NIGHT LIGHT TTC TELEPHONE TERMINAL CABINET
ASSOCIATED ELECTRICAL INSTALLATION. CNT'R CONTRACTOR GRS GALVANIZED RIGID STEEL NO NORMALLY OPEN TX TRANSFORMER
C.O. CONDUIT ONLY (W/PULLROPE) GWS GANG WITH SWITCH NPF NORMAL POWER FACTOR TYP TYPICAL
COND CONDUIT, CONDUCTOR H HEIGHT, HIGH NTS NOT TO SCALE TYP SIM TYPICAL SIMILAR

PROJECT TITLE
5. CLOSELY COORDINATE OUTAGE AND FACILITY DISRUPTION TIME WITH ARCHITECT AND OWNER. MINIMUM 72-HOUR NOTICE IS REQUIRED BEFORE CR CRITICAL BRANCH HACR HEATING, AC & REFRIG OC ON CENTER UC UNDERCABINET, UNDERCOUNTER
ANY CIRCUIT SHUTDOWN OR DISRUPTION OF FACILITY PERSONNEL FUNCTIONING. CSFM CALIFORNIA SFM HID HIGH INTENSITY DISCHARGE OCP OVERCURRENT PROTECTION UG UNDERGROUND
CT CURRENT TRANSFORMER HO HIGH OUTPUT OD OUTSIDE DIAMETER UGPS UNDERGROUND PULL SECTION
Cu COPPER HOA HAND-OFF-AUTO OH OVERHEAD UL UNDERWRITERS LABORATORIES
6. EXISTING ABANDONED CONDUCTORS BEING REMOVED SHALL BE SALVAGED BACK TO THE DISTRICT. CU-# CONDENSING UNIT hp HORSEPOWER OSA OFFICE of the STATE ARCHITECT UON UNLESS OTHERWISE NOTED
D DEPTH HPF HIGH POWER FACTOR OSHPD OFFICE of STATEWIDE HEALTH USA UG SVC ALERT 800-642-2444
DC DIRECT CURRENT HPS HIGH PRESSURE SODIUM PLANNING & DEVELOPMENT V VOLT
DF DRINKING FOUNTAIN IC INTERCOM OVLD OVERLOAD VA VOLT AMPERES
DIA DIAMETER ID IDENTIFICATION P POLE VAC VOLT ALTERNATING CURRENT
DISC DISCONNECT IDF INTERMEDIATE DISTRIBUTION PA PUBLIC ADDRESS VHO VERY HIGH OUTPUT
DIST DISTRIBUTION FRAME PB PULLBOX VOLT VOLTAGE
DPST DOUBLE POLE SINGLE THROW IF INSIDE FROST PC PULL CHAIN VR VANDAL-RESISTANT DRAWN BY: TWS
DW DISHWASHER IG ISOLATED GROUND PC PHOTOCELL W WIDTH, WATT, WIRE
EM EMERGENCY J-BOX JUNCTION BOX PC PLUMBING CONTRACTOR WH-# WATER HEATER April 15, 2020
(E) EXISTING k QUANTITY 1000 ph PHASE WP WEATHERPROOF (NEMA 3R)
EA EACH kVA KILOVOLTAMPS PNL PANEL XFMR TRANSFORMER CHECKED:
EB ELECTRONIC BALLAST kW KILOWATT POC POINT OF CONNECTION +48 INDICATES MOUNTING HEIGHT AFF
EC ELECTRICAL CONTRACTOR LC LIGHTING CONTACTOR -PP- POWER PRIMARY SHEET TITLE:
EC-# EVAPORATIVE COOLER LPS LOW PRESSURE SODIUM -PS- POWER SECONDARY ELECTRICAL
EF-# EXHAUST FAN LRA LOCKED ROTOR AMPS PV PHOTOVOLTAIC
SYMBOLS LEGEND
& GENERAL NOTES

E-001