VAV IP CONTROLLER

The VAV IP is a freely programmable controller designed for


pressure-independent control of any single duct Variable
Air Volume (VAV), Constant Air Volume (CAV) and Supply/
Exhaust terminal units. These controllers are ideally suited for
critical environment applications such as Laboratory Airflow
Tracking, Critical Patient Rooms, Operating Rooms, and
other applications requiring precise control of airflows.

This controller is supported by Alerton’s VisualLogic®


programming tool and the Compass 2.2.0 and above version
supervisor. The VAV IP controller has an integral damper actuator,
field replaceable airflow sensor, up to seven flexible universal
inputs/outputs (UIO), five solid state relay outputs, and a Microset
bus. The controller supports BACnet/IPv4 and BACnet/IPv6.

The integrated Bluetooth® Low Energy (BLE) capability enables


easy pairing with mobile apps such as BMS Startup app.
FEATURES AND BENEFITS

COMMUNICATION • Up to seven Universal Inputs/ • 3 Schedules and 1 Zone (Optimum


Outputs (UIO) configurable as Start for internal point only).
• Supports BACnet® IP communication analog voltage/current output
which enables faster download, or as a analog/binary input. • 25 Alarms (Event Enrollment Objects).
thereby reducing commissioning
time, and increased data bandwidth • Up to five 24 VAC solid state relay outputs • 5 Notification Class Objects.
for increased data sharing. with 1.5 A continuous and 3.5 A in-rush
• Supports BMS Startup - Device
for 100 milliseconds per SSR output.
• Built-in 2-port Ethernet switch Pairing mobile app for device
supports 10/100 Mpbs. • All UI can be used for pulse pairing, device numbering and easy
input. Maximum frequency 100 deployment using BACnet® “Who
• Supports full duplex IPv4/IPv6 Hz, Minimum duty cycle (50 % / Am I” and “You are” messages.
addressing, DHCP, SLAAC, and 50 %) 5 ms ON / 5 ms OFF.
Link Local addressing modes. FREELY PROGRAMMABLE
• Integrated 44 in-lbs (5 Nm) modulating
• Supports Rapid Spanning Tree • Supports Alerton’s BD9 DDC file
actuator with 90 seconds runtime
Protocol (RSTP) and Network format using Alerton’s VisualLogic®.
at 60 Hz (108 seconds at 50 Hz)
Time Protocol (NTPv4). with analog position feedback. • Extensive library of VAV
• Features a non-isolated RS-485 applications is available, including
• Field replaceable differential
interface for Modbus communication ASHRAE Guideline 36.
pressure sensor (± 500 Pa;
(future firmware upgrade required). accuracy +/- 3% of full range). • All control logic is programmed using
CHARACTERISTICS • The airflow sensor is factory
Alerton’s easy-to-learn graphical
programming language, VisualLogic®.
• Compact design for small enclosures and calibrated at multiple velocity points.
easy to install on round and square ducts. Minimum, maximum and reheat • Using BD9 DDC the VAV IP controller
airflows can be entered using a can execute more complex
• Color-coded, removable terminal blocks Microset wall unit or compatible calculations to meet the needs of
to simplify wiring and replacement. operator workstation software. increasingly demanding sequences
• Real-time clock with super capacitor of operations for building systems.
SUPPORTS
circuit providing up to 24 hours
of date/time retention. • 50 trendlogs at 60 seconds
interval minimum. (This includes
• 20 VDC at 75 mA auxiliary 10 COV trendlogs).
supply for field devices.
SYSTEM OVERVIEW
COMPASS 2.2.0 OR ABOVE VERSION

BACNET® IP

VAV IP CONTROLLER
WITH INTEGRATED
#1...#N ACTUATOR

BACNET® IP

MODBUS RTU (FUTURE FIRMWARE RELEASE)

DALI LUMINAIRE(S) 21°C VAV CO2 I/O kWh


1
BLIND&LIGHT
I/O MODULE MODBUS FIELD DEVICES LIKE
WALL MODULE FOR HVAC, LIGHT & BLIND,
DALI LIGHT & BLIND I/OS ETC.

BLE PUSH
BUTTON MICROSET BUS
SWITCH
DALI INPUT MODULE
PUSH BUTTON MICROSET 4

ORDERING NUMBERS
CONTROLLER MODEL POWER SUPPLY UIO SOLID STATE RELAY INTEGRATED ACTUATOR COMMUNICATION BLUETOOTH

VAVi-7u5-IP 24 VAC 7 5 Yes IP No


VAVi-0-IP 24 VAC 0 0 Yes IP No
VAVi-7u5-IP-BLE 24 VAC 7 5 Yes IP Yes

REPLACEMENT PARTS
PART NUMBER TYPE DESCRIPTION
SDPPF500PA Air flow sensor Replacement air flow sensor for use if the original sensor is damaged, or becomes inoperable. (Sold in pack of 2)

CONTROLLER PART NUMBERS DESCRIPTION


VAV i - 7u 5 - IP - BLE

VAV Bluetooth

Integrated Actuator
Communication Protocol
Universal Inputs/Outputs

Digital Outputs (SSR)


PRODUCT SPECIFICATIONS
HARDWARE ELECTRICAL
PARAMETER SPECIFICATION PARAMETER SPECIFICATION
CPU Crossover processor NXP I.MRT, Cortex M7 20-30 VAC; Class 2
VOLTAGE RANGE
transformer
MEMORY CAPACITY 512 MB QSPI Flash, 128 MB SDRAM
POWER
2 X RJ-45 Ethernet ports with a protection that allows loop CONSUMPTION Nominal 9.3 VA (actuator
BACnet® IP topology to continue the communication with other controllers FOR VAVI-7u5-IP, at nominal load and IP
even if one node fails, when used with an RSTP supporting device. VAVI-7u5-IP-BLE- communication active)
24-Hours backup after power failure. AND VAVI-0-IP
The controller includes a supercapacitor to power the built-in FREQUENCY
real time clock for 24-Hours. In case of power failure, the super 50 to 60 Hz
REAL TIME CLOCK RANGE
capacitor retains the time set in controller for 24-Hours. After
24-Hours, the time will reset to default factory time until user AUXILIARY
20 VDC @ 75 mA
perform BACnet Time Sync. OUTPUT
SMALL LEDS Transmission or Reception of communication Signal (green) INTERNAL
Half-wave rectified
POWER SUPPLY
LARGE LEDS Controller status (green, yellow and red).

COMMUNICATION INTEGRATED MODULATING OPERATIONAL ENVIRONMENT


PARAMETER SPECIFICATION ACTUATOR PARAMETER SPECIFICATION
PROTOCOL BACnet/IPv4, BACnet/IPv6,
PARAMETER SPECIFICATION STORAGE -40 °F to 150 °F (-40 °C to 66 °C)
SUPPORTED BACnet/Ethernet
44 in-lbs (5 Nm) with OPERATION 32 °F to 122 °F (0 °C to 50 °C)
ETHERNET TORQUE
CONNECTION 10/100 Mbps analog position feedback. HUMIDITY 5% to 95% RH., non condensing
SPEED 108 seconds at 50 Hz;
RUN TIME PROTECTION IP20, NEMA 1
INTERNET 90 seconds at 60 Hz
PROTOCOL IPv4 and IPv6 POLLUTION
Round 8-16 mm (5/16 – 5/8”); 2
VERSION MOUNTING LEVEL
Square 6-13 mm (15/64 –
SHAFT
IP ADDRESS- 33/64”)
Supports Static, DHCP, SLAAC
ING MODES SHAFT LENGTH ≥ 1 5/8 in (41 mm) AIR-FLOW SENSOR
Rapid Spanning Tree Protocol PARAMETER SPECIFICATION
NETWORKING
(RSTP) and Network Time
PROTOCOL
Protocol (NTP4) RANGE ± 2 in. w.c. (± 500 Pa)
2 wire, polarity sensitive bus ZERO-POINT
0.0004 in.w.c. (0.1 Pa)
for Microtouch, Microset-BT, ACCURACY
MICROSET BUS
Microset II and Microset 4 wall
modules REPEATABILITY 0.5% of reading
1/8-inch x 3/8-inch long
SOLID STATE RELAY CONNECTION
barbfitting
SPECIFICATION RESOLUTION 16 bit input
SSR does switch supply voltage, works with AC and DC, however in case of DC no support for
synchronous motor.
STANDARDS AND COMPLIANCE
• 1.5 A constant; 3.5 A inrush for 0.1 sec per SSR output
• Optional bridge provides shared power to all SSRs from 24 VAC powering controller. SPECIFICATION

Note: SSR will not close the contact unless voltage is present, they cannot be used as dry contact. BACnet® BTL®-Listed; IP VAV model as
BACnet® Advanced Application Controller
UIO (CONFIGURABLE AS ANALOG OUTPUT OR UNIVERSAL INPUT) (B-AAC); (BTL certification is in progress).
FCC Part 15, Class A
PARAMETER SPECIFICATION
IC – ICES-003 Issue 6
16-bit universal analog outputs support Voltage Mode: 0-10 VDC @ 10 mA maximum
(1k ohm minimum); Current Mode: 4-20 mA @ 550 ohms Maximum; or Binary Mode: UL916, Energy Management Equipment
AO
11 VDC @ 20 mA maximum relay coil current (for controlling low-coil current 11 VDC
relays and solid-state relays). RoHS
EN 55022. Class A
16-bit universal inputs accept 10 k thermistor (type II and III), dry contact, 1k platinum
RTD, 0-20 mA, 0-10 V, or dry-contact pulse. Pulse input maximum frequency of 100 Hz. EN 61000-3-2, 61000
UI Pulse input minimum duty cycle 5ms ON / 5ms OFF.
NOTE: Some 4-20 mA input sensors may need an external resistor to function properly. CE
Please refer to the sensor’s documentation.
Common terminal shared by 2 UIO, protected against 24 VAC mis-wiring and short circuit.

Important Note: This device is UL listed and limited to 100 VA maximum. Binary
output loads are restricted by this maximum VA rating. If all 5 SSR binary outputs are
connected and fully loaded (@24 VA each) the total VA of the device will exceed the UL
listed and limited maximum rating. DO NOT EXCEED 100 VA MAXIMUM RATING!
INTERFACE
Service Button
Integrated Actuator

Declutch Button

RS485 Modbus RTU 24 VAC power

5 solid state
7 Universal Relays (SSR)
Inputs/Outputs
Microset
Auxiliary Power for Bus
Field Devices 20VDC
Bluetooth connectivity Field-replaceable
status Airflow sensor
Antenna BACnet®
IP ethernet Modbus
RJ45-1 / RJ45-2

Field-replaceable
Airflow sensor

DIMENSIONS
6”
(154 mm)
2 1/2”
(66 mm)

7 1/4”
(187 mm)
7”
(175 mm)
5 3/4” 7 3/4”
(147 mm) (197 mm)
4 3/4”
(124 mm)

2”
(52 mm)
3 1/2” (90 mm)
3 1/2” (92 mm)

PARAMETER SPECIFICATION
DIMENSION (LXWXH) 7 X 6 X 3 1/2 inches (175 X 154 X 92 mm)
WEIGHT 1.5 kg
MOUNTING Fixation with bracket and shaft