Relay ABB
Relay ABB
Contents
Disclaimer
The information in this document is subject to change without notice and should not be construed as a commitment by ABB AB. ABB AB assumes no responsibility
for any errors that may appear in this document.
© Copyright 2012 ABB.
All rights reserved.
Trademarks
ABB and Relion are registered trademarks of ABB Group. All other brand or product names mentioned in this document may be trademarks or registered trademarks
of their respective holders.
2 ABB
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2 Issued: May 2012
Revision: C
Additionally a high impedance differential function Serial data communication is via optical
is available. It can be used as restricted earth connections to ensure immunity against
fault or, as three functions are included, also as disturbances.
differential protection on autotransformers, as
differential protection for a tertiary connected The wide application flexibility makes this product
reactor, as T-differential protection for the an excellent choice for both new installations and
transformer feeder in a mesh-corner or ring the refurbishment of existing installations.
arrangement, as tertiary bus protection and so on.
Six packages have been defined for the following
Tripping from Pressure relief/Buchholz and applications:
temperature devices can be done through the
transformer IED where pulsing, lock-out contact • Transformer back-up protection (A10)
output and so on, is performed. The binary inputs • Voltage control (A25)
are heavily stabilized against disturbance to • Two-winding transformer in single breaker
prevent incorrect operations at for example, dc arrangements (A30)
system capacitive discharges or DC earth faults.
ABB 3
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
• Two-winding transformer in multi breaker has been pre-defined for basic use on the, as
arrangements (B30) standard supplied one binary input module and
• Three-winding transformer in single breaker one binary output module. Add binary I/O as
arrangements (A40) required for your application at ordering. Other
• Three-winding transformer in multi breaker signals need to be applied as required for each
arrangements (B40) application.
Optional functions are not configured but a For details on included basic functions, refer to
maximum configuration with all optional functions chapter "Basic IED functions"
are available as template in the graphical
configuration tool. An alternative for The applications are shown in figures 1, 2, 3and 4
Autotransformers is also available as a for single resp. multi-breaker arrangement.
configuration template. Analog and tripping IO
TRIP BUSBAR
50BF
3I>
51/67
3I>
94/86 CB1
4
TRIP CB1 I->O 4
51N/67N
IN>
4
4
87N
IdN/I>
87T
3Id/I>
87N
IdN/I>
51N/67N
IN>
4
4
51/67
3I>
4
94/86 4
TRIP CB2 50BF
I->O
3I>
25
59 SC/VC
CB2
3U>
2
TRIP BUSBAR
2
27
3U<
2
2
en05000272.vsd
IEC05000272 V1 EN
Figure 1. A typical protection application for a two winding transformer in single breaker arrangements is shown
on the figure. The system earthing principle and connection group will vary which gives different
detailed arrangements for each application.
4 ABB
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
TRIP BUSBAR&CB2
TRIP CB1/3
CB1
50BF
51/67 3I>
3I> S 50BF
94/86
4 3I>
TRIP CB1
I->O 4
51N/67N
94/86 IN>
TRIP CB2 4 CB2
I->O
4
87N
IdN/I>
87T
3Id/I>
87N
IdN/I>
51N/67N
IN>
4
4
51/67
3I>
4
94/86 4
TRIP CB3 50BF
I->O
3I>
25
59 SC/VC
3U> CB3
2
TRIP BUSBAR
2
&CB1/2
27
3U<
2
2
en05000273.vsd
IEC05000273 V1 EN
Figure 2. A typical protection application for a two winding transformer in multi breaker arrangements is shown
on the figure. The system earthing principle and connection group will vary which gives different
detailed arrangements for each application. Breaker failure function is here provided for each breaker.
ABB 5
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
TRIP BUSBAR
50BF
3I>
51/67
94/86 3I>
4 CB1
TRIP CB1
I->O 4
51N/67N
IN>
4
4
87N
IdN/I>
87T
3Id/I>
87N
IdN/I> 50BF
TRIP BUSBAR
&CB1/2 3I>
51N/67N
IN>
4 3I>
4 4
51/67 4
3I>
4 94/86
94/86 4 TRIP
I->O CB3
TRIP CB2 50BF
I->O
3I>
25
SC/
59
VC CB2
3U>
2 59N
TRIP BUSBAR 2 UN>
&CB1/2/3
27 t2 2
2
3U<
2
2
en05000274.vsd
IEC05000274 V1 EN
Figure 3. A typical protection application for a three winding transformer in single breaker arrangements is shown
on the figure. The system earthing principle and connection group will vary which gives different
detailed arrangements for each application.
6 ABB
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
TRIP BUSBAR&CB2/3/4
CB1
50BF TRIP CB1/3/4/X
51/67
3I>
3I> S 50BF
94/86
4 3I>
TRIP CB1
I->O 4
51N/67N
94/86 IN>
TRIP CB2 4 CB2
I->O
4
87N
IdN/I>
87T
3Id/I>
87N
IdN/I> TRIP BUSBAR 50BF
&CB1/2/3 3I>
51N/67N
IN>
4 3I>
4 4
51/67 4
3I>
4 94/86
94/86 4 TRIP
I->O CB4
TRIP CB3 50BF
I->O
3I>
25
59 SC/VC
3U> CB3
2 59N
TRIP BUSBAR
2 UN>
&CB1/2/4
27 t2 2
2
3U<
2
2
en05000275.vsd
IEC05000275 V1 EN
Figure 4. A typical protection application for a three winding transformer in multi breaker arrangements is shown
on the figure. The system earthing principle and connection group will vary which gives different
detailed arrangements for each application. Breaker failure function is here provided for each breaker.
ABB 7
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
2. Available functions
RET670 (B30)
RET670 (B40)
RET670 (A10)
RET670 (A30)
RET670 (A40)
RET670 (A25)
Differential protection
Impedance protection
8 ABB
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
RET670 (B30)
RET670 (B40)
RET670 (A10)
RET670 (A30)
RET670 (A40)
RET670 (A25)
Current protection
NS4PTOC 46I2 Four step directional negative 2-C42 2-C42 2-C42 3-C43 3-C43 2-C19
phase sequence overcurrent
protection
SDEPSDE 67N Sensitive directional residual 1 1-C16 1-C16 1-C16 1-C16 1-C16
overcurrent and power
protection
Voltage protection
UV2PTUV 27 Two step undervoltage 1-D01 1B, 1- 1B, 1- 1B, 2- 1B, 2- 2-D02
protection D01 D01 D02 D02
OV2PTOV 59 Two step overvoltage 1-D01 1B, 1- 1B, 1- 1B, 2- 1B, 2- 2-D02
protection D01 D01 D02 D02
ROV2PTOV 59N Two step residual 1-D01 1B, 1- 1B, 1- 1B, 2- 1B, 2- 2-D02
overvoltage protection D01 D01 D02 D02
Frequency protection
ABB 9
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
RET670 (B30)
RET670 (B40)
RET670 (A10)
RET670 (A30)
RET670 (A40)
RET670 (A25)
SAPTUF 81 Underfrequency protection 6-E01 6-E01 6-E01 6-E01 6-E01
Multipurpose protection
10 ABB
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
RET670 (B30)
RET670 (B40)
RET670 (A10)
RET670 (A30)
RET670 (A40)
RET670 (A25)
Control
TR1ATCC 90 Automatic voltage control for 1-H11 1-H11 1-H11, 1-H11, 2B, 2-
tap changer, single control 2-H16 2-H16 H16
ABB 11
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
RET670 (B30)
RET670 (B40)
RET670 (A10)
RET670 (A30)
RET670 (A40)
RET670 (A25)
CCSRDIF 87 Current circuit supervision 2 3 3 5 4
Logic
Monitoring
CVMMXN Measurements 6 6 6 6 6 6
12 ABB
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
RET670 (B30)
RET670 (B40)
RET670 (A10)
RET670 (A30)
RET670 (A40)
RET670 (A25)
Metering
ABB 13
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
Designed to communicate
RET670 (B30)
RET670 (B40)
RET670 (A10)
RET670 (A30)
RET670 (A40)
RET670 (A25)
Station communication
Multiple command and transmit 60/10 60/10 60/10 60/10 60/10 60/10
IEC 62439-3 Edition 1 parallel 1-P01 1-P01 1-P01 1-P01 1-P01 1-P01
redundancy protocol
IEC 62439-3 Edition 2 parallel 1-P02 1-P02 1-P02 1-P02 1-P02 1-P02
redundancy protocol
Remote communication
Binary signal transfer receive/transmit 6/36 6/36 6/36 6/36 6/36 6/36
Receive binary status from remote 6/3/3 6/3/3 6/3/3 6/3/3 6/3/3 6/3/3
LDCM
Scheme communication
14 ABB
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
ABB 15
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
xx05000053.vsd
two-winding power
IEC05000053 V1 EN
transformer with
unconnected delta Autotransformer with
xx05000049.vsd
tertiary winding two circuit breakers
IEC05000049 V1 EN
and two CT-sets on
two-winding power two out of three sides
transformer with two
circuit breakers on
xx05000050.vsd
one side
IEC05000050 V1 EN
xx05000057.vsd
xx05000052.vsd
Stabilization is included for inrush currents as well
as for overexcitation conditions. Adaptive
IEC05000052 V1 EN
stabilization is also included for system recovery
inrush and CT saturation for external faults. A high
set unrestrained differential current protection is
included for a very high speed tripping at a high
internal fault currents.
16 ABB
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
and a voltage dependent resistor which are to overhead lines and cables of different types
mounted externally connected to the IED. and lengths.
Restricted earth fault protection, low impedance The distance protection zones can operate
REFPDIF independently of each other in directional (forward
Restricted earth-fault protection, low-impedance or reverse) or non-directional mode.
function (REFPDIF) can be used on all directly or
low-impedance earthed windings. The REFPDIF Phase selection, quadrilateral characteristic with
function provides high sensitivity (down to 5%) fixed angle FDPSPDIS
and high speed tripping as it measures each The operation of transmission networks today is
winding individually and thus does not need in many cases close to the stability limit. Due to
inrush stabilization. environmental considerations, the rate of
expansion and reinforcement of the power system
The low-impedance function is a percentage is reduced, for example, difficulties to get
biased function with an additional zero sequence permission to build new power lines. The ability to
current directional comparison criterion. This accurately and reliably classify the different types
gives excellent sensitivity and stability during of fault, so that single pole tripping and
through faults. The function allows the use of autoreclosing can be used plays an important role
different CT ratios and magnetizing characteristics in this matter.Phase selection, quadrilateral
on the phase and neutral CT cores and mixing characteristic with fixed angle FDPSPDIS is
with other functions and protection IEDs on the designed to accurately select the proper fault
same cores. loop in the distance function dependent on the
fault type.
ABB 17
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
zones have fully independent measuring and ZSMGAPC can mainly be decomposed in two
settings, which gives high flexibility for all types of different parts:
lines.
1. A fault inception detection logic
2. High SIR detection logic
18 ABB
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
ABB 19
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
generator with two time constants, which is phases with additional criteria from unsymmetrical
based on current measurement. phase currents when required.
Two warning levels are available. This enables Directional over/underpower protection
actions in the power system to be done before GOPPDOP/GUPPDUP
dangerous temperatures are reached. If the The directional over-/under-power protection
temperature continues to increase to the trip GOPPDOP/GUPPDUP can be used wherever a
value, the protection initiates a trip of the high/low active, reactive or apparent power
protected transformer/generator. protection or alarming is required. The functions
can alternatively be used to check the direction of
Breaker failure protection CCRBRF active or reactive power flow in the power system.
Breaker failure protection (CCRBRF) ensures fast There are a number of applications where such
back-up tripping of surrounding breakers in case functionality is needed. Some of them are:
the own breaker fails to open. CCRBRF can be
current based, contact based, or an adaptive • detection of reversed active power flow
combination of these two conditions. • detection of high reactive power flow
Current check with extremely short reset time is Each function has two steps with definite time
used as check criterion to achieve high security delay. Reset times for both steps can be set as
against unnecessary operation. well.
Contact check criteria can be used where the Broken conductor check BRCPTOC
fault current through the breaker is small. The main purpose of the function Broken
conductor check (BRCPTOC) is the detection of
CCRBRF can be single- or three-phase initiated broken conductors on protected power lines and
to allow use with single phase tripping cables (series faults). Detection can be used to
applications. For the three-phase version of give alarm only or trip the line breaker.
CCRBRF the current criteria can be set to operate
only if two out of four for example, two phases or
one phase plus the residual current start. This 6. Voltage protection
gives a higher security to the back-up trip
Two step undervoltage protection UV2PTUV
command.
Undervoltages can occur in the power system
CCRBRF function can be programmed to give a during faults or abnormal conditions. Two step
single- or three-phase re-trip of the own breaker undervoltage protection (UV2PTUV) function can
to avoid unnecessary tripping of surrounding be used to open circuit breakers to prepare for
breakers at an incorrect initiation due to mistakes system restoration at power outages or as long-
during testing. time delayed back-up to primary protection.
Pole discordance protection CCRPLD UV2PTUV has two voltage steps, each with
An open phase can cause negative and zero inverse or definite time delay.
sequence currents which cause thermal stress on
Two step overvoltage protection OV2PTOV
rotating machines and can cause unwanted
Overvoltages may occur in the power system
operation of zero sequence or negative sequence
during abnormal conditions such as sudden
current functions.
power loss, tap changer regulating failures, open
Normally the own breaker is tripped to correct line ends on long lines etc.
such a situation. If the situation persists the
Two step overvoltage protection (OV2PTOV)
surrounding breakers should be tripped to clear
function can be used to detect open line ends,
the unsymmetrical load situation.
normally then combined with a directional reactive
The Polediscordance protection function CCRPLD over-power function to supervise the system
operates based on information from auxiliary voltage. When triggered, the function will cause
contacts of the circuit breaker for the three an alarm, switch in reactors, or switch out
capacitor banks.
20 ABB
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
Two step residual overvoltage protection Underfrequency protection SAPTUF is used for
ROV2PTOV load shedding systems, remedial action schemes,
Residual voltages may occur in the power system gas turbine startup and so on.
during earth faults.
SAPTUF is provided with an undervoltage
Two step residual overvoltage protection blocking.
ROV2PTOV function calculates the residual
voltage from the three-phase voltage input The operation is based on positive sequence
transformers or measures it from a single voltage voltage measurement and requires two phase-
input transformer fed from an open delta or phase or three phase-neutral voltages to be
neutral point voltage transformer. connected. For information about how to connect
analog inputs, refer to Application manual/IED
ROV2PTOV has two voltage steps, each with application/Analog inputs/Setting guidelines
inverse or definite time delay.
ABB 21
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
General current and voltage protection CVGAPC A detection of a difference indicates a fault in the
The protection module is recommended as a circuit and is used as alarm or to block protection
general backup protection with many possible functions expected to give unwanted tripping.
application areas due to its flexible measuring and
setting facilities. Fuse failure supervision SDDRFUF
The aim of the fuse failure supervision function
The built-in overcurrent protection feature has two (SDDRFUF) is to block voltage measuring
settable current levels. Both of them can be used functions at failures in the secondary circuits
either with definite time or inverse time between the voltage transformer and the IED in
characteristic. The overcurrent protection steps order to avoid unwanted operations that
can be made directional with selectable voltage otherwise might occur.
polarizing quantity. Additionally they can be
voltage and/or current controlled/restrained. 2nd The fuse failure supervision function basically has
harmonic restraining facility is available as well. At three different algorithms, negative sequence and
too low polarizing voltage the overcurrent feature zero sequence based algorithms and an
can be either blocked, made non directional or additional delta voltage and delta current
ordered to use voltage memory in accordance algorithm.
with a parameter setting.
The negative sequence detection algorithm is
Additionally two overvoltage and two recommended for IEDs used in isolated or high-
undervoltage steps, either with definite time or impedance earthed networks. It is based on the
inverse time characteristic, are available within negative-sequence measuring quantities, a high
each function. value of voltage 3U 2 without the presence of the
negative-sequence current 3I 2.
The general function suits applications with
underimpedance and voltage controlled The zero sequence detection algorithm is
overcurrent solutions. The general function can recommended for IEDs used in directly or low
also be utilized for generator transformer impedance earthed networks. It is based on the
protection applications where positive, negative zero sequence measuring quantities, a high value
or zero sequence components of current and of voltage 3U 0 without the presence of the
voltage quantities are typically required.
residual current 3I 0 .
22 ABB
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
Synchrocheck, energizing check, and Two types of command models can be used:
synchronizing SESRSYN • Direct with normal security
The Synchronizing function allows closing of • SBO (Select-Before-Operate) with enhanced
asynchronous networks at the correct moment security
including the breaker closing time, which
improves the network stability.
In normal security, the command is processed
Synchrocheck, energizing check, and and the resulting position is not supervised.
synchronizing (SESRSYN) function checks that However with enhanced security, the command is
the voltages on both sides of the circuit breaker processed and the resulting position is supervised.
are in synchronism, or with at least one side dead
to ensure that closing can be done safely. Normal security means that only the command is
evaluated and the resulting position is not
SESRSYN function includes a built-in voltage supervised. Enhanced security means that the
selection scheme for double bus and 1½ breaker command is evaluated with an additional
or ring busbar arrangements. supervision of the status value of the control
object. The command security with enhanced
Manual closing as well as automatic reclosing can security is always terminated by a
be checked by the function and can have different CommandTermination service primitive.
settings.
Control operation can be performed from the
For systems which are running asynchronous a local HMI under authority control if so defined.
synchronizing function is provided. The main
purpose of the synchronizing function is to Voltage control TR1ATCC, TR8ATCC, TCMYLTC
provide controlled closing of circuit breakers and TCLYLTC
when two asynchronous systems are going to be The voltage control functions, Automatic voltage
connected. It is used for slip frequencies that are control for tap changer, single control TR1ATCC,
larger than those for synchrocheck and lower Automatic voltage control for tap changer ,
than a set maximum level for the synchronizing parallel control TR8ATCC and Tap changer
function. control and supervision, 6 binary inputs
TCMYLTC as well as Tap changer control and
Apparatus control APC supervision, 32 binary inputs TCLYLTC are used
The apparatus control functions are used for for control of power transformers with a motor
control and supervision of circuit breakers, driven load tap changer. The functions provide
disconnectors and earthing switches within a bay. automatic regulation of the voltage on the
Permission to operate is given after evaluation of secondary side of transformers or alternatively on
conditions from other functions such as a load point further out in the network.
interlocking, synchrocheck, operator place
selection and external or internal blockings. Control of a single transformer, as well as control
of up to eight transformers in parallel is possible.
Apparatus control features: For parallel control of power transformers, three
• Select-Execute principle to give high reliability alternative methods are available, the master-
• Selection function to prevent simultaneous follower method, the circulating current method
operation and the reverse reactance method. The two
• Selection and supervision of operator place
ABB 23
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
former methods require exchange of information of the logic configuration that do not need
between the parallel transformers and this is extensive command receiving functionality (for
provided for within IEC61850-8-1. example, SCSWI). In this way, simple commands
can be sent directly to the IED outputs, without
Voltage control includes many extra features such confirmation. Confirmation (status) of the result of
as possibility of to avoid simultaneous tapping of the commands is supposed to be achieved by
parallel transformers, hot stand by regulation of a other means, such as binary inputs and SPGGIO
transformer in a group which regulates it to a function blocks. The commands can be pulsed or
correct tap position even though the LV CB is steady.
open, compensation for a possible capacitor bank
on the LV side bay of a transformer, extensive tap AutomationBits, command function for DNP3.0
changer monitoring including contact wear and AUTOBITS
hunting detection, monitoring of the power flow in AutomationBits function for DNP3 (AUTOBITS) is
the transformer so that for example, the voltage used within PCM600 to get into the configuration
control can be blocked if the power reverses etc. of the commands coming through the DNP3
protocol. The AUTOBITS function plays the same
Logic rotating switch for function selection and role as functions GOOSEBINRCV (for IEC 61850)
LHMI presentation SLGGIO and MULTICMDRCV (for LON).
The logic rotating switch for function selection
and LHMI presentation function (SLGGIO) (or the Single command, 16 signals
selector switch function block) is used to get a The IEDs can receive commands either from a
selector switch functionality similar to the one substation automation system or from the local
provided by a hardware selector switch. HMI. The command function block has outputs
Hardware selector switches are used extensively that can be used, for example, to control high
by utilities, in order to have different functions voltage apparatuses or for other user defined
operating on pre-set values. Hardware switches functionality.
are however sources for maintenance issues,
lower system reliability and an extended purchase
11. Scheme communication
portfolio. The logic selector switches eliminate all
these problems. Scheme communication logic for residual
overcurrent protection ECPSCH
Selector mini switch VSGGIO
To achieve fast fault clearance of earth faults on
The Selector mini switch VSGGIO function block
the part of the line not covered by the
is a multipurpose function used for a variety of
instantaneous step of the residual overcurrent
applications, as a general purpose switch.
protection, the directional residual overcurrent
VSGGIO can be controlled from the menu or from protection can be supported with a logic that
a symbol on the single line diagram (SLD) on the uses communication channels.
local HMI.
In the directional scheme, information of the fault
IEC 61850 generic communication I/O functions current direction must be transmitted to the other
DPGGIO line end. With directional comparison, a short
The IEC 61850 generic communication I/O operate time of the protection including a channel
functions (DPGGIO) function block is used to transmission time, can be achieved. This short
send double indications to other systems or operate time enables rapid autoreclosing function
equipment in the substation. It is especially used after the fault clearance.
in the interlocking and reservation station-wide
The communication logic module for directional
logics.
residual current protection enables blocking as
Single point generic control 8 signals SPC8GGIO well as permissive under/overreaching schemes.
The Single point generic control 8 signals The logic can also be supported by additional
(SPC8GGIO) function block is a collection of 8 logic for weak-end infeed and current reversal,
single point commands, designed to bring in included in Current reversal and weak-end infeed
commands from REMOTE (SCADA) to those parts
24 ABB
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
ABB 25
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
26 ABB
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
Analog and double indication values are also Function for energy calculation and demand
transferred through EVENT function. handling ETPMMTR
Outputs from the Measurements (CVMMXN)
IEC61850 generic communication I/O function
function can be used to calculate energy
SPGGIO
consumption. Active as well as reactive values are
IEC61850 generic communication I/O functions
calculated in import and export direction. Values
(SPGGIO) is used to send one single logical signal
can be read or generated as pulses. Maximum
to other systems or equipment in the substation.
demand power values are also calculated by the
function.
ABB 27
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
28 ABB
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
DNP3.0 communication protocol Binary signal transfer to remote end, 192 signals
An electrical RS485 and an optical Ethernet port If the communication channel is used for transfer
is available for the DNP3.0 communication. DNP3. of binary signals only, up to 192 binary signals
0 Level 2 communication with unsolicited events, can be exchanged between two IEDs. For
time synchronizing and disturbance reporting is example, this functionality can be used to send
provided for communication to RTUs, Gateways information such as status of primary switchgear
or HMI systems. apparatus or intertripping signals to the remote
IED. An IED can communicate with up to 4
Multiple command and transmit remote IEDs.
When 670 IED's are used in Substation
Automation systems with LON, SPA or Line data communication module, short and
IEC60870-5-103 communication protocols the medium range LDCM
Event and Multiple Command function blocks are The line data communication module (LDCM) is
used as the communication interface for vertical used for communication between the IEDs
communication to station HMI and gateway and situated at distances <60 km or from the IED to
as interface for horizontal peer-to-peer optical to electrical converter with G.703 or G.
communication (over LON only). 703E1 interface located on a distances <3 km
away. The LDCM module sends and receives
IEC 62439-3 Parallel Redundant Protocol data, to and from another LDCM module. The
Redundant station bus communication according IEEE/ANSI C37.94 standard format is used.
to IEC 62439-3 Edition 1 and IEC 62439-3 Edition
2 are available as options in 670 series IEDs. IEC Galvanic interface G.703 resp G.703E1
62439-3 parallel redundant protocol is an optional The external galvanic data communication
quantity and the selection is made at ordering. converter G.703/G.703E1 makes an optical-to-
Redundant station bus communication according galvanic conversion for connection to a
to IEC 62439-3 uses both port AB and port CD multiplexer. These units are designed for 64 kbit/s
on the OEM module. resp 2Mbit/s operation. The converter is delivered
with 19” rack mounting accessories.
Select IEC 62439-3 Edition 1
protocol at the time of ordering 19. Hardware description
when an existing redundant
station bus DuoDriver Hardware modules
installation is extended. Power supply module PSM
Select IEC 62439-3 Edition 2 The power supply module is used to provide the
protocol at the time of ordering correct internal voltages and full isolation between
for new installations with the terminal and the battery system. An internal
redundant station bus. fail alarm output is available.
IEC 62439-3 Edition 1 is NOT
compatible with IEC 62439-3 Binary input module BIM
Edition 2. The binary input module has 16 optically isolated
inputs and is available in two versions, one
standard and one with enhanced pulse counting
capabilities on the inputs to be used with the
18. Remote communication pulse counter function. The binary inputs are
freely programmable and can be used for the
Analog and binary signal transfer to remote end
input of logical signals to any of the functions.
Three analog and eight binary signals can be
They can also be included in the disturbance
exchanged between two IEDs. This functionality is
recording and event-recording functions. This
mainly used for the line differential protection.
enables extensive monitoring and evaluation of
However it can be used in other products as well.
operation of the IED and for all associated
An IED can communicate with up to 4 remote
electrical circuits.
IEDs.
ABB 29
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
Serial and LON communication module SLM, Alternative connectors of Ring lug or
supports SPA/IEC 60870-5-103, LON and DNP 3.0 Compression type can be ordered.
The serial and LON communication module (SLM)
is used for SPA, IEC 60870-5-103, DNP3 and High impedance resistor unit
LON communication. The module has two optical The high impedance resistor unit, with resistors
communication ports for plastic/plastic, plastic/ for pick-up value setting and a voltage dependent
glass or glass/glass. One port is used for serial resistor, is available in a single phase unit and a
communication (SPA, IEC 60870-5-103 and three phase unit. Both are mounted on a 1/1 19
DNP3 port or dedicated IEC 60870-5-103 port inch apparatus plate with compression type
depending on ordered SLM module) and one port terminals.
is dedicated for LON communication.
Layout and dimensions
Line data communication module LDCM Dimensions
Each module has one optical port, one for each
remote end to which the IED communicates.
30 ABB
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
B C
D
xx05000003.vsd
IEC05000003 V1 EN
xx05000004.vsd
IEC05000004 V1 EN
Case size A B C D E F
(mm)
ABB 31
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
32 ABB
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
1MRK002801-AC-2-670-1.2-PG V1 EN
ABB 33
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
1MRK002801-AC-4-670-1.2-PG V1 EN
1MRK002801-AC-6-670-1.2-PG V1 EN
34 ABB
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
1MRK002801-AC-10-670-1.2-PG V1 EN
12I, 1A 1A 1A 1A 1A 1A 1A 1A 1A 1A 1A 1A 1A
12I, 5A 5A 5A 5A 5A 5A 5A 5A 5A 5A 5A 5A 5A
9I+3U, 1A 1A 1A 1A 1A 1A 1A 1A 1A 110-220V 110-220V 110-220V
1A
9I+3U, 5A 5A 5A 5A 5A 5A 5A 5A 5A 110-220V 110-220V 110-220V
5A
5I, 1A 1A 1A 1A 1A 1A 5A 5A 5A 5A 110-220V 110-220V 110-220V
+4I, 5A
+3U
7I+5U, 1A 1A 1A 1A 1A 1A 1A 110-220V 110-220V 110-220V 110-220V 110-220V
1A
7I+5U, 5A 5A 5A 5A 5A 5A 5A 110-220V 110-220V 110-220V 110-220V 110-220V
5A
6I+6U, 1A 1A 1A 1A 1A 1A 110-220V 110-220V 110-220V 110-220V 110-220V 110-220V
1A
6I+6U, 5A 5A 5A 5A 5A 5A 110-220V 110-220V 110-220V 110-220V 110-220V 110-220V
5A
6I, 1A 1A 1A 1A 1A 1A 1A - - - - - -
6I, 5A 5A 5A 5A 5A 5A 5A - - - - - -
*) Metering
Note that internal polarity can be adjusted by setting of analog input CT neutral direction and/or on SMAI pre-
processing function blocks.
ABB 35
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
1MRK002801-AC-15-670-1.2-PG V1 EN
1MRK002801-AC-11-670-1.2-PG V1 EN
36 ABB
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
1MRK002801-AC-8-670-1.2-PG V1 EN
1MRK002801-AC-7-670-1.2-PG V1 EN
ABB 37
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
1MRK002801-AC-12-670-1.2-PG V1 EN
Figure 15. Binary output module (BOM). Output contacts named XA corresponds to rear position X31, X41, and
so on, and output contacts named XB to rear position X32, X42, and so on.
1MRK002801-AC-13-670-1.2-PG V1 EN
38 ABB
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
1MRK002801-AC-14-670-1.2-PG V1 EN
Figure 17. Binary in/out module (IOM). Input contacts named XA corresponds to rear position X31, X41, and so
on, and output contacts named XB to rear position X32, X42, and so on.
ABB 39
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
BUS A
BBP-TRIP BUS B
QB1-OPEN
QB1-CL
BLOCK LW 3I>
BBP STEP QB2-OPEN
QB2-CL -QB1
ST BFP 3PH -QB2
BUCH TRIP
SUDDEN P
-QA1
OT TRIP CLOSE QA1 C
CLOSE Reinf C
WT TRIP
TRIP QA1 T
OT WARN TRIP Reinf C
MAIN 2 TRIP T
QA1-OPEN C
WT WARN
QA1-CL
OIL LOW
QA1-SPR UNCH
GAS ALARM
-BI1 P1
TRM1:1-3
TO MAIN 2 RELAY
TO BUS PROT
SIGNALLING
FAULT
QO -T1
TRM1:7
-N.BI1 QW
= TAP POS
MIM1:1 -N.BI1
TC IN MAN
TRM1:8
TC IN AUTO
-BI1
HV BUSBAR TRIP TO BUS PROT
MV BUSBAR TRIP
MAN SC OK TO MAIN 2 RELAY
TRM1:4-6
P1
QA1-OPEN
QA1-CL
TRIP QA1 T
C
TRIP Reinf
T
C
TRM1:10
MCB OK
-BU1
IRF
- +
en05000262.vsd
IEC05000262 V1 EN
Figure 18. Typical connection diagram for two winding transformer in a single breaker arrangement. Note!
Including IO for control option.
40 ABB
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
BUS A
BBP-TRIP -QB1
QB1-OPEN
QB1-CL
BLOCK LW 3I> QB6-OPEN
BBP STEP
QB6-CL -QB62
ST BFP 3PH -BI1 P1
BUCH TRIP TRM1:4-6
SUDDEN P
-QA1
CLOSE QA1 C TO MAIN 2
OT TRIP CLOSE Reinf C
QB61-CL
FAULT
QB9-OPEN
QB9-CL -QB9
TRM2:4
QO -T1
QW
= TAP POS
MIM1:1
TC IN MAN
TC IN AUTO TRM2:5
TRIP QA1 T
TRIP Reinf C
BBP-TRIP T
C
TRM2:10
MCB OK
-BU1
IRF
- +
en05000263.vsd
IEC05000263 V1 EN
Figure 19. Typical connection diagram for two winding transformer in a multi breaker arrangement. Note!
Including IO for control option.
ABB 41
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
BUS A
BUS B
BBP-TRIP
QB1-OPEN
ST BFP QB1-CL
3PH QB2-OPEN
QB2-CL
-QB1
BLOCK TW 3I> -QB2
BBP STEP
BUCH TRIP
SUDDEN P
-QA1
CLOSE QA1 C
OT TRIP CLOSE Reinf C
-BI1 P1
TRM1:1-3
QA1-OPEN
TO MAIN 2 RELAY
QA1-CL
SPR UNCH
TO BUS PROT
SIGNALLING
CLOSE QA1
CLOSE Reinf
FAULT
TRIP QA1
TRIP Reinf
QO
TRM1:7
QW
TC IN MAN
TC IN AUTO TRM1:8
TRIP QA1 T
TRIP Reinf C
T
C
TRM1:11
-BU1
MCB OK
-BU1
TRM1:12 Res. for Bus 2
VT
IRF
- + en05000265.vsd
IEC05000265 V1 EN
Figure 20. Typical connection diagram for three winding transformer in a single breaker arrangement. Note!
Including IO for control option.
42 ABB
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
BUS A
TO SECOND BAY
BBP-TRIP -QB1
QB1-OPEN
QB1-CL
BLOCK TW 3I>
QB62-OPEN
BBP STEP
QB62-CL -QB62
ST BFP 3PH
BUCH TRIP
-BI1 P1
TRM1:4-36
SUDDEN P -QA1
CLOSE QA1 C TO MAIN 2
C
OT TRIP CLOSE Reinf
TRIP QA1 T
WT TRIP C
TRIP Reinf
=1-Q0-OPEN MAIN 2 TRIP T
OT WARN C
=2-Q0-OPEN =1-Q0-CL
WT WARN =2-Q0-CL
=1-Q0-SPR UNCH
OIL LOW =2-Q0-SPR UNCH
-BI1 P1
GAS ALARM TRM1:1-3 -QA1
CLOSE QA1 C
C
TO MAIN 2
CLOSE Reinf
TRIP QA1 T
C
TRIP Reinf MAIN 2 TRIP
TO BB PROT T
QB6-OPEN C
QB6-CL
SIGNALLING
QB61-CL
Q9-OPEN
Q9-CL
-Q9
-T1
TRM1:7
= TAP POS
TC IN MAN
TC IN AUTO TRM1:8
QO
TC IN LOC. MCB OR
MCB-OK FUSE QW
TC RAISE
TC LOWER -BU1
TRM2:7-9
-BI1
HV BUSBAR TRIP TO BUS PROT -BI1
MV BUSBAR TRIP TRM2:4-6
CLOSE QA1 TO MAIN 2 RELAY
-QA1 P1
MAN SC OK
CLOSE Reinf C
C
TRIP QA1
TRIP Reinf TRM2:1-3 T
C
P1
QA1-OPEN
QA1-OPEN T
QA1-CL C
QA1-CL
SPR UNCH
SPR UNCH -QA1
CLOSE QA1 C
C
CLOSE Reinf
TRIP QA1 T
C
TRIP Reinf
T
C
TRM1:11
-BU1
MCB OK
-BU1
TRM1:12 Res. for Bus 2
VT
IRF
en05000259.vsd
- +
IEC05000259 V1 EN
Figure 21. Typical connection diagram for three winding transformer in a multi breaker arrangement. Note!
Including IO for control option.
ABB 43
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
General
Definitions
Reference value The specified value of an influencing factor to which are referred the characteristics of the equipment
Nominal range The range of values of an influencing quantity (factor) within which, under specified conditions,
the equipment meets the specified requirements
Operative range The range of values of a given energizing quantity for which the equipment, under specified
conditions, is able to perform its intended functions according to the specified requirements
Table 4. TRM - Energizing quantities, rated values and limits for protection transformer modules
Current Ir = 1 or 5 A (0.2-40) × Ir
Frequency fr = 50/60 Hz ± 5%
44 ABB
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
Table 5. TRM - Energizing quantities, rated values and limits for measuring transformer modules
Frequency fr = 50/60 Hz ± 5%
Power consumption -
each mA-board £2W
each mA input £ 0.1 W
Number of channels 1 or 2
ABB 45
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
Auxiliary DC voltage
Binary inputs 16 -
Power consumption
24/30 V max. 0.05 W/input -
48/60 V max. 0.1 W/input
110/125 V max. 0.2 W/input
220/250 V max. 0.4 W/input
Table 10. BIM - Binary input module with enhanced pulse counting capabilities
Binary inputs 16 -
Power consumption
24/30 V max. 0.05 W/input -
48/60 V max. 0.1 W/input
110/125 V max. 0.2 W/input
220/250 V max. 0.4 W/input
46 ABB
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
Binary inputs 8 -
Power consumption -
24/30 V max. 0.05 W/input
48/60 V max. 0.1 W/input
110/125 V max. 0.2 W/input
220/250 V max. 0.4 W/input
Table 12. IOM - Binary input/output module contact data (reference standard: IEC 61810-2)
Function or quantity Trip and signal relays Fast signal relays (parallel
reed relay)
Binary outputs 10 2
Breaking capacity for AC, cos φ > 0.4 250 V/8.0 A 250 V/8.0 A
ABB 47
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
Table 13. SOM - Static Output Module (reference standard: IEC 61810-2): Static binary outputs
Number of outputs 6 6
Test voltage across open contact, 1 min No galvanic separation No galvanic separation
Continuous 5A 5A
220V / 0.2A
250V / 0.15A
Table 14. SOM - Static Output module data (reference standard: IEC 61810-2): Electromechanical relay outputs
Number of outputs 6
Continuous 8A
1.0s 10A
0.2s 30A
1.0s 10A
110V / 0.4A
125V / 0,35A
220V / 0,2A
250V / 0.15A
48 ABB
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
Table 15. BOM - Binary output module contact data (reference standard: IEC 61810-2)
Binary outputs 24
Influencing factors
Interruption interval
0–50 ms
No restart
ABB 49
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
Harmonic frequency dependence (20% 2nd, 3rd and 5th harmonic of fr ± 1.0%
content)
Harmonic frequency dependence for 2nd, 3rd and 5th harmonic of fr ± 6.0%
distance protection (10% content)
Harmonic frequency dependence for high 2nd, 3rd and 5th harmonic of fr ±5.0%
impedance differential protection (10%
content)
50 ABB
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
100 kHz slow damped oscillatory wave 2.5 kV IEC 61000-4-18, Class III
immunity test
Ring wave immunity test, 100 kHz 2-4 kV IEC 61000-4-12, Class IV
Conducted common mode immunity test 15 Hz-150 kHz IEC 61000-4-16, Class IV
Power frequency magnetic field test 1000 A/m, 3 s IEC 61000-4-8, Class V
100 A/m, cont.
Damped oscillatory magnetic field test 100 A/m IEC 61000-4-10, Class V
1.4-2.7 GHz
ABB 51
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
Damp heat test, steady state Test Ca for 4 days at +40 °C and humidity 93% IEC 60068-2-78
Damp heat test, cyclic Test Db for 6 cycles at +25 to +55 °C and IEC 60068-2-30
humidity 93 to 95% (1 cycle = 24 hours)
Test According to
Immunity EN 50263
Emissivity EN 50263
52 ABB
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
Differential protection
ABB 53
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
54 ABB
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
Impedance protection
ABB 55
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
Table 28. Phase selection, quadrilateral characteristic with fixed angle FDPSPDIS
56 ABB
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
Table 30. Full-scheme distance protection, quadrilateral for earth faults ZMMPDIS
ABB 57
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
Current protection
Inverse characteristics, see 19 curve types See table 93, table 94 and table
table 93, table 94 and table 95 95
58 ABB
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
Inverse characteristics, see table 18 curve types See table 93, table 94 and table
93, table 94 and table 95 95
ABB 59
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
Inverse characteristics, see table 18 curve types See table 93, table 94 and table
93, table 94 and table 95 95
Minimum operate current for step (1.00 - 10000.00)% of IBase ± 1.0% of Ir at I < Ir
1-4 ± 1.0% of I at I > Ir
60 ABB
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
Table 38. Sensitive directional residual overcurrent and power protection SDEPSDE
Inverse characteristics, see table 19 curve types See table 93, table 94 and table
93, table 94 and table 95 95
ABB 61
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
Operate time: Ip = load current before overload IEC 60255–8, class 5 + 200 ms
occurs
æ I 2 - I p2 ö Time constant τ = (1–500)
t = t × ln ç 2 ÷ minutes
ç I - Ib 2 ÷
è ø
EQUATION1356 V1 EN (Equation 1)
I = Imeasured
Alarm level 1 and 2 (50–99)% of heat content trip ± 2.0% of heat content trip
value
Reset level temperature (10–95)% of heat content trip ± 2.0% of heat content trip
62 ABB
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
ABB 63
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
Voltage protection
Operate voltage, low and high step (1-200)% of UBase ± 0.5% of Ur at U < Ur
± 0.5% of U at U > Ur
64 ABB
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
Operate voltage, low and high step (1-200)% of UBase ± 0.5% of Ur at U < Ur
± 1.0% of U at U > Ur
(0.18 × k )
IEEE : t =
( M - 1) 2
EQUATION1319 V1 EN (Equation 2)
where M = (E/f)/(Ur/fr)
ABB 65
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
66 ABB
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
Frequency protection
Operate time, start function 100 ms typically at fset -0.5 Hz to fset +0.5 Hz -
ABB 67
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
Multipurpose protection
See table 93 and table 94 Parameter ranges for customer defined See table 93 and table 94
characteristic no 17:
k: 0.05 - 999.00
A: 0.0000 - 999.0000
B: 0.0000 - 99.0000
C: 0.0000 - 1.0000
P: 0.0001 - 10.0000
PR: 0.005 - 3.000
TR: 0.005 - 600.000
CR: 0.1 - 10.0
Start overvoltage, step 1 and 2 (2.0 - 200.0)% of UBase ± 0.5% of Ur for U<Ur
± 0.5% of U for U>Ur
Start undervoltage, step 1 and 2 (2.0 - 150.0)% of UBase ± 0.5% of Ur for U<Ur
± 0.5% of U for U>Ur
68 ABB
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
High and low voltage limit, voltage (1.0 - 200.0)% of UBase ± 1.0% of Ur for U<Ur
dependent operation ± 1.0% of U for U>Ur
Overcurrent:
Undercurrent:
Overvoltage:
Undervoltage:
ABB 69
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
70 ABB
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
Control
Voltage high limit for synchronizing and (50.0-120.0)% of UBaseBus and ± 0.5% of Ur at U ≤ Ur
synchrocheck UBaseLIne ± 0.5% of U at U >Ur
Phase angle difference limit between bus and (5.0-90.0) degrees ± 2.0 degrees
line
Voltage difference limit between bus and line (0.02-0.5) p.u ± 0.5% of Ur
Voltage high limit for energizing check (50.0-120.0)% of UBaseBus and ± 0.5% of Ur at U ≤ Ur
UBaseLIne ± 0.5% of U at U >Ur
ABB 71
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
72 ABB
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
Table 58. Voltage control TR1ATCC, TR8ATCC, TCMYLTC and TLCYLTC, continued
Function Range or value Accuracy
ABB 73
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
Scheme communication
Table 59. Scheme communication logic for residual overcurrent protection ECPSCH
Table 60. Current reversal and weak-end infeed logic for residual overcurrent protection ECRWPSCH
74 ABB
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
Logic
LogicAND 60 60 160 - -
LogicOR 60 60 160 - -
LogicXOR 10 10 20 - -
LogicInverter 30 30 80 - -
LogicSRMemory 10 10 20 - -
LogicRSMemory 10 10 20 - -
LogicGate 10 10 20 - -
Boolean 16 to Integer 4 4 8 - -
Boolean 16 to integer 4 4 8 - -
with Logic Node
Integer to Boolean 16 4 4 8 - -
Integer to Boolean 16 4 4 8 - -
with Logic Node
ABB 75
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
Monitoring
76 ABB
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
Maximum number of events in the Event list 1000, first in - first out -
Maximum total recording time (3.4 s recording time 340 seconds (100 recordings) at -
and maximum number of channels, typical value) 50 Hz, 280 seconds (80
recordings) at 60 Hz
Function Value
Resolution 1 ms
Function Value
ABB 77
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
Function Value
Resolution 1 ms
Function Value
Function Value
Maximum total recording time (3.4 s recording time and maximum number 340 seconds (100 recordings) at 50 Hz
of channels, typical value) 280 seconds (80 recordings) at 60 Hz
78 ABB
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
Metering
Energy metering kWh Export/Import, kvarh Export/ Input from MMXU. No extra error at steady load
Import
ABB 79
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
Station communication
Function Value
Function Value
Protocol LON
Function Value
Protocol SPA
Function Value
80 ABB
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
Table 81. IEC 62439-3 Edition 1 and Edition 2 parallel redundancy protocol
Function Value
ABB 81
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
Remote communication
Type of LDCM Short range (SR) Medium range (MR) Long range (LR)
Transmission rate / Data rate 2 Mb/s / 64 kbit/s 2 Mb/s / 64 kbit/s 2 Mb/s / 64 kbit/s
Clock source Internal or derived Internal or derived Internal or derived from received
from received from received signal signal
signal
82 ABB
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
Hardware
IED
Table 84. Water and dust protection level according to IEC 60529
Connection system
Terminal blocks suitable for ring lug terminals 250 V AC, 20 A 4 mm2 (AWG12)
Terminal blocks suitable for ring lug terminals 300 V AC 3 mm2 (AWG14)
ABB 83
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
Data Value
Function Value
Time tagging error with synchronization once/min (minute pulse synchronization), ± 1.0 ms typically
events and sampled measurement values
Time tagging error with SNTP synchronization, sampled measurement values ± 1.0 ms typically
Function Value
Accuracy +/-2μs
84 ABB
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
Electrical connector:
Amplitude modulated
– low level 1-3 Vpp
– high level 3 x low level, max 9 Vpp
Accuracy +/-10μs for IRIG-B 00x and +/-100μs for IRIG-B 12x
Optical connector:
ABB 85
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
Inverse characteristic
Reset characteristic:
tr
t = ×k
(I 2
)
-1
EQUATION1250-SMALL V1 EN
I = Imeasured/Iset
86 ABB
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
æ A ö
t = ç P ÷×k
ç ( I - 1) ÷
è ø
EQUATION1251-SMALL V1 EN
I = Imeasured/Iset
Time delay to reset, IEC inverse time (0.000-60.000) s ± 0.5% of set time ± 10 ms
TR
t = ×k
(I PR
- CR )
EQUATION1253-SMALL V1 EN
I = Imeasured/Iset
ABB 87
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
I = Imeasured/Iset
RD type logarithmic inverse characteristic k = (0.05-999) in steps of 0.01 IEC 60255-3, class 5 +
40 ms
æ I ö
t = 5.8 - ç 1.35 × In ÷
è k ø
EQUATION1138-SMALL V1 EN
I = Imeasured/Iset
U> = Uset
U = Umeasured
88 ABB
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
U< = Uset
U = UVmeasured
U< = Uset
U = Umeasured
U< = Uset
U = Umeasured
ABB 89
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
U> = Uset
U = Umeasured
90 ABB
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
22. Ordering
Guidelines
Carefully read and follow the set of rules to ensure problem-free order management.
Please refer to the available functions table for included application functions.
PCM600 can be used to make changes and/or additions to the delivered factory configuration of the pre-configured.
To obtain the complete ordering code, please combine code from the tables, as given in the example below.
Example code: RET670*1.2-A30-A01A02B12C05D01D03E01F02H09-B1-X0-C-B-KA-B3X0-A-ABC-X-XD. Using the code of each
position #1-12 specified as RET670*1-2 2-3 3 3 3 3 3 3 3-4-5-6-7 7-8-9 9 9-10 10 10 10 10 10 10 10 10 10 10 10 10 10-11 11 11 11
11 11-12 12
# 1 - 2 - 3 - 4 - 5 6 - 7 - 8 -
RET670* - - - - - . -
9 - 10 - 11 - 12
- . -
Position
SOFTWARE #1 Notes and Rules
Version number
Version no 1.2
Selection for position #1.
ABB 91
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
92 ABB
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
ABB 93
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
Mounting details with IP40 of protection from the front #6 Notes and Rules
No mounting kit included X
19" rack mounting kit for 1/2 x 19" case of 2xRHGS6 or RHGS12 A Note: Only for A10/A25/A30
19" rack mounting kit for 3/4 x 19" case or 3xRGHS6 B
19" rack mounting kit for 1/1 x 19" case C
Wall mounting kit D Note: Wall mounting not
recommended with
communication modules with
fibre connection (SLM, OEM,
LDCM)
Flush mounting kit E
Flush mounting kit + IP54 mounting seal F
Selection for position #6.
Connection type for Power supply, Input/output and Communication modules #7 Notes and Rules
Compression terminals K
Auxiliary power supply
24-60 VDC A
90-250 VDC B
Selection for position #7.
94 ABB
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
ABB 95
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
X41
X51
X61
X71
X81
X91
X101
X111
X121
X131
5 in 3/4 rack with 2 TRM and 11
in 1/1 rack with 2 TRM
1/2 Case with 1 TRM █ █ █ Note: Only for A10/A25/A30
3/4 Case with 2 TRM █ █ █ █ █
1/1 Case with 2 TRM █ █ █ █ █ █ █ █ █ █ █
No board in slot X X X X X X X X X
Binary output module 24 output A A A A A A A A A A Note: Maximum 4 (BOM+SOM
relays (BOM) +MIM) boards.
BIM 16 inputs, RL24-30 VDC, 30 mA B B B B B B B B B B Note: Only 1 BIM in A10
BIM 16 inputs, RL48-60 VDC, 30 mA C C C C C C C C C C
BIM 16 inputs, RL110-125 VDC, 30 D D D D D D D D D D
mA
BIM 16 inputs, RL220-250 VDC, 30 E E E E E E E E E E
mA
BIM 16 inputs, RL24-30 VDC, 50 mA B B B B B B B B B B
1 1 1 1 1 1 1 1 1 1
BIM 16 inputs, RL48-60 VDC, 50 mA C C C C C C C C C C
1 1 1 1 1 1 1 1 1 1
BIM 16 inputs, RL110-125 VDC, 50 D D D D D D D D D D
mA 1 1 1 1 1 1 1 1 1 1
BIM 16 inputs, RL220-250 VDC, 50 E E E E E E E E E E
mA 1 1 1 1 1 1 1 1 1 1
BIM 16 inputs, RL24-30 VDC for F F F F F F F F F
pulse counting
BIM 16 inputs, RL48-60 VDC for G G G G G G G G G
pulse counting
BIM 16 inputs, RL110-125 VDC for H H H H H H H H H
pulse counting
BIM 16 inputs, RL220-250 VDC for K K K K K K K K K
pulse counting
IOM 8 inputs, 10+2 output, L L L L L L L L L
RL24-30 VDC
IOM 8 inputs, 10+2 output, M M M M M M M M M
RL48-60 VDC
IOM 8 inputs, 10+2 output, N N N N N N N N N
RL110-125 VDC
IOM 8 inputs, 10+2 output, P P P P P P P P P
RL220-250 VDC
IOM 8 inputs, 10+2 output, L1 L1 L1 L1 L1 L1 L1 L1 L1
RL24-30 VDC, 50 mA
IOM 8 inputs, 10+2 output, M M M M M M M M M
RL48-60 VDC, 50 mA 1 1 1 1 1 1 1 1 1
IOM 8 inputs, 10+2 output, N N N N N N N N N
RL110-125 VDC, 50 mA 1 1 1 1 1 1 1 1 1
IOM 8 inputs, 10+2 output, P P P P P P P P P
RL220-250 VDC, 50 mA 1 1 1 1 1 1 1 1 1
IOM with MOV 8 inputs, 10-2 U U U U U U U U U
output, 24-30 VDC
IOM with MOV 8 inputs, 10-2 V V V V V V V V V
output, 48-60 VDC
IOM with MOV 8 inputs, 10-2 W W W W W W W W W
output, 110-125 VDC
IOM with MOV 8 inputs, 10-2 Y Y Y Y Y Y Y Y Y
output, 220-250 VDC
96 ABB
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
Remote end communication, DNP serial comm. #11 Notes and Rules
and time synchronization modules
Slot position (rear view)
X312
X313
X302
X303
X322
X323
Available slots in 1/2 case with 1TRM █ █ █ █ Note: Only 1 LDCM.
Available slots in 3/4 & 1/1 case with 2 TRM █ █ █ █ █ █ Note: Max 2 LDCM.
No remote communication board included X X X X X X
Optical short range LDCM A A A A A A Note: Not in A10/A25
Optical medium range, LDCM 1310 nm B B B B B B Note: Not in A10/A25
GPS time module GTM S S S S
IRIG-B Time synchronization module F
Galvanic RS485 communication module G G G G G G
Selection for position #11.
Serial communication unit for station communication #12 Notes and Rules
Slot position (rear view)
X301
X311
Guidelines
Carefully read and follow the set of rules to ensure problem-free order management. Be aware that certain functions
can only be ordered in combination with other functions and that some functions require specific hardware selections.
Please refer to the available functions table for included application functions.
Accessories
ABB 97
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
External interface converter from C37.94 to G703 Quantity: 1 2 1MRK 002 245-AA
External interface converter from C37.94 to G703.E1 Quantity: 1 2 1MRK 002 245-BA
Two winding transformer with internal neutral on RHGS 6 Case or RHGS 12 Case with mounted
current circuits. Two pcs can be used in RTXP 24 and the on/off switch for dc-supply are
applications for three winding transformers in ordered separately. Please refer to Section
single or multi-breaker arrangement (ordering "Related documents" for reference to
number RK926 215-BD) corresponding documents.
98 ABB
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
Protection cover
Protective cover for rear side of RHGS6, 6U, 1/4 x 19” Quantity: 1MRK 002 420-AE
Protective cover for rear side of terminal, 6U, 1/2 x 19” Quantity: 1MRK 002 420-AC
Protective cover for rear side of terminal, 6U, 3/4 x 19” Quantity: 1MRK 002 420-AB
Protective cover for rear side of terminal, 6U, 1/1 x 19” Quantity: 1MRK 002 420-AA
High impedance resistor unit 3-ph with resistor and voltage Quantity: RK795101-MB
dependent resistor for 20-100V operating voltage
High impedance resistor unit 1-ph with resistor and voltage 1 2 3
dependent resistor for 100-400V operating voltage Quantity: RK795101-CB
High impedance resistor unit 3-ph with resistor and voltage Quantity: RK795101-DC
dependent resistor for 100-400V operating voltage
Combiflex
Key switch for lock-out of settings via LCD-HMI Quantity: 1MRK 000 611-A
Note: To connect the key switch, leads with 10 A Combiflex socket on one end must be used.
Front connection cable between LCD-HMI and PC Quantity: 1MRK 001 665-CA
Manuals
Note: One (1) IED Connect CD containing user documentation (Operator’s manual, Technical reference
manual, Installation and commissioning manual, Application manual and Getting started guide),
Connectivity packages and LED label template is always included for each IED.
ABB 99
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
Rule: Specify additional quantity of IED Connect CD requested. Quantity: 1MRK 002 290-AB
User documentation
Rule: Specify the number of printed manuals requested IEC Quantity: 1MRK 504 114-UEN
Operator’s manual
Reference information
For our reference and statistics we would be pleased to be provided with the following application data:
100 ABB
Transformer protection RET670 1MRK 504 118-BEN C
Pre-configured
Product version: 1.2
Related documents
ABB 101
102
Contact us
www.abb.com/substationautomation