PANEL BOARD: PB

CKT NO. DESCRIPTION QTY VA PER CIRCUITS VOLTS

1 LIGHTING OUTLET 28 2800 230


2 LIGHTING OUTLET 30 3000 230
3 CONVENIENCE OUTLET 12 2400 230
4 ACU 1 200 230
3 SPARE
4 SPARE
TOTAL 8400

COMPUTATION:

QTY x 100 (IF LIGHTING) .= WATTS WATTS


QTY x 200(IF CON. OUTLET) .= WATTS VOLTS

WITH 80% DEMAND FACTORS: SERVICE ENTRANCE C

IT= (37.61 x DF) + (25% x HRM) USE:


IT= (37.61 x DF) + (25% x 13.04)
IT= 33.35
Current
CIRCUIT BREAKER SIZE OF WIRE
AMP. LOAD PVC PIPE
AT P ON RUN GROUNDING
12.17 20 1 3.5 mm THHN
2
2.0 mm2 THHN 50mm Ø PVC
13.04 20 1 3.5 mm THHN
2
2.0 mm THHN
2
50mm Ø PVC
10.43 40 1 3.5 mm THHN
2
2.0 mm THHN
2
50mm Ø PVC
1.96 60 1 3.5 mm THHN
2
2.0 mm THHN
2
50mm Ø PVC

37.61 100AT

WITH 100% DEMAND FACTORS:


.=AMP. LOAD
IT= (37.61 x DF) + (25% x HRM)
IT= (37.61 x DF) + (25% x
IT= 40.87

ERVICE ENTRANCE CONDUCTORS MAIN PROTECTION


USE: 100AT,1P,MCB,BOLT ON TYPE
2-8.0mm.sqm THWN/THHN Cu Wire
1-5.5mm.sqm THWN/THHN Cu Wire (G)
in 75mm dia. RSC Conduit
NOTE

GFCI

+ (25% x HRM)
13.04)
7
PANEL BOARD: PB
CKT NO. DESCRIPTION QTY VA PER CIRCUITS VOLTS

1 LIGHTING OUTLET 4 400 230


2 CONVENIENCE OUTLET 3 600 230
3 ACU 1 200 230
4 SPARE
5 SPARE
TOTAL 1200

COMPUTATION:

QTY x 100 (IF LIGHTING) .= WATTS WATTS


QTY x 200(IF CON. OUTLET) .= WATTS VOLTS

WITH 80% DEMAND FACTORS: SERVICE ENTRANCE C

IT= (5.22 x DF) + (25% x HRM) USE:


IT= (5.22 x DF) + (25% x 2.61)
IT= 4.83
Current
CIRCUIT BREAKER SIZE OF WIRE
AMP. LOAD PVC PIPE
AT P ON RUN GROUNDING
1.74 16 1 3.5 mm THHN 2.0 mm2 THHN
2
25mm Ø PVC
2.61 32 1 3.5 mm THHN 2.0 mm THHN
2 2
25mm Ø PVC
0.87 32 1 3.5 mm THHN 2.0 mm THHN
2 2
25mm Ø PVC

5.22 100AT

WITH 100% DEMAND FACTORS:


.=AMP. LOAD
IT= (5.22 x DF) + (25% x HRM)
IT= (5.22 x DF) + (25% x
IT= 5.87

ERVICE ENTRANCE CONDUCTORS MAIN PROTECTION


USE: 100AT,1P,MCB,BOLT ON TYPE
2-8.0mm.sqm THWN/THHN Cu Wire
1-5.5mm.sqm THWN/THHN Cu Wire (G)
in 75mm dia. RSC Conduit
NOTE

(25% x HRM)
2.61)
7
PANEL BOARD: PB
CKT NO. DESCRIPTION QTY VA PER CIRCUITS VOLTS

1 LIGHTING OUTLET 13 1300 230


2 CONVENIENCE OUTLET 14 2800 230
3 SPARE
4 SPARE
TOTAL 4100

COMPUTATION:

QTY x 100 (IF LIGHTING) .= WATTS WATTS


QTY x 200(IF CON. OUTLET) .= WATTS VOLTS

WITH 80% DEMAND FACTORS: SERVICE ENTRANCE C

IT= (17.83 x DF) + (25% x HRM) USE:


IT= (17.83 x DF) + (25% x 12.17)
IT= 17.30
Current
CIRCUIT BREAKER SIZE OF WIRE
AMP. LOAD PVC PIPE
AT P ON RUN GROUNDING
5.65 15 1 3.5 mm THHN 2.0 mm2 THHN
2
25mm Ø PVC
12.17 20 1 3.5 mm THHN 2.0 mm THHN
2 2
25mm Ø PVC

17.83 60AT

WITH 100% DEMAND FACTORS:


.=AMP. LOAD
IT= (17.83 x DF) + (25% x HRM)
IT= (17.83 x DF) + (25% x
IT= 20.87

ERVICE ENTRANCE CONDUCTORS MAIN PROTECTION


USE: 60AT,1P,MCB,BOLT ON TYPE
2-8.0mm.sqm THWN/THHN Cu Wire
1-5.5mm.sqm THWN/THHN Cu Wire (G)
in 75mm dia. RSC Conduit
NOTE

+ (25% x HRM)
12.17)
7
Table 3.10.1.16 Allowable Ampacities of Insulated Conductors Rated 0 Through 2000 Volts, 60°C Thro
Temperature Rating of Conductor (Se
60°C (140°F) 75°C (167°F)

Types RHW, THHW, THW,


Size Types TW, UF THWN, XHHW, USE, ZW
mm2 (mm
dia.) COPPER
2.0(1.6)* 20 20
3.5(2.0)* 25 25
5.5(2.6)* 30 35
8.0(3.2) 40 50
14 55 65
22 70 85
30 90 110
38 100 125
50 120 145
60 135 160
80 160 195
100 185 220
125 210 255
150 240 280
175 260 305
200 280 330
250 315 375
325 370 435
375 395 470
400 405 485
500 445 540
CORRECTION

Ambient
Temp. (°C) For ambient temperatures other than 30°C (86°F), multiply the allowable ampa
21–25 1.08 1.05
26-30 1 1
31-35 0.91 0.94
36-40 0.82 0.88
41-45 0.71 0.82
46-50 0.58 0.75
51-55 0.41 0.67
56-60 — 0.58
61-70 — 0.33
71-80 — —
ctors Rated 0 Through 2000 Volts, 60°C Through 90°C (140°F Through 194°F), Not More Than Three Current-Car
Temperature Rating of Conductor (See Table 3.10.1.13.)
90°C (194°F) 60°C (140°F) 75°C (167°F)

Types TBS, SA, SIS, FEP,


FEPB, MI, RHH, RHW-2, THHN, Types RHW, THHW,
THHW, THW-2, THWN-2, USE- THW, THWN, XHHW,
2, XHH, XHHW, XHHW-2, ZW- 2 Types TW, UF USE, ZW

R ALUMINUM OR COPPER-CLAD ALUMINUM


25 — —
30 20 20
40 25 30
55 30 40
70 40 50
90 55 65
115 65 80
130 75 90
150 95 110
170 100 120
205 120 145
225 140 170
265 165 200
295 185 225
345 205 245
355 220 265
400 255 305
470 305 365
530 315 380
515 335 405
580 370 440
CORRECTION FACTORS

than 30°C (86°F), multiply the allowable ampacities shown above by the appropriate factor shown below.
1.04 1.08 1.05
1 1 1
0.96 0.91 0.94
0.91 0.82 0.88
0.87 0.71 0.82
0.82 0.58 0.75
0.76 0.41 0.67
0.71 — 0.58
0.58 — 0.33
0.41 — —
ot More Than Three Current-Carrying Conductors in Raceway, Cabl

90°C (194°F)

Types TBS, SA, SIS, FEP,


FEPB, MI, RHH, RHW-2,
THHN, THHW, THW-2,
THWN-2, USE- 2, XHH,
XHHW, XHHW-2, ZW- 2

R-CLAD ALUMINUM Size mm2 (mm dia.)


— 2.0(1.6)*
25 3.5(2.0)*
35 5.5(2.6)*
45 8.0(3.2)
60 14
80 22
90 30
105 38
125 50
135 60
165 80
190 100
225 125
250 150
275 175
300 200
345 250
410 325
430 375
460 400
495 500

e factor shown below. Ambient Temp. (°F)


1.04 70-77
1 78-86
0.96 87-95
0.91 96-104
0.87 105-113
0.82 114-122
0.76 123-131
0.71 132-140
0.58 141-158
0.41 159-176
HPx74.6
Current(ampere)= =
V x PowerFactor x Efficiency 12.1630434782609

HP 1.5
V 230
PF 0.05
Eff 0.8
PANEL BOARD: PB-1
CKT NO. DESCRIPTION QTY VA PER CIRCUITS VOLTS

1 LIGHTING OUTLET 3 300 230


2 CONVENIENCE OUTLET 3 600 230
3 SPARE 1 230
4 SPARE 1 230
TOTAL 900

PANEL BOARD: PB-2


CKT NO. DESCRIPTION QTY VA PER CIRCUITS VOLTS

1 LIGHTING OUTLET 4 400 230


2 CONVENIENCE OUTLET 3 600 230
3 SPARE 1 230
4 SPARE 1 230
TOTAL 1000

PANEL BOARD: PB-3


CKT NO. DESCRIPTION QTY VA PER CIRCUITS VOLTS

1 LIGHTING OUTLET 3 300 230


2 CONVENIENCE OUTLET 2 400 230
3 SPARE 1 230
4 SPARE 1 230
TOTAL 700

PANEL BOARD: PB-4


CKT NO. DESCRIPTION QTY VA PER CIRCUITS VOLTS

1 LIGHTING OUTLET 4 400 230


2 CONVENIENCE OUTLET 2 400 230
3 SPARE 1 230
4 SPARE 1 230
TOTAL 800

COMPUTATION:

QTY x 100 (IF LIGHTING) .= WATTS WATTS


QTY x 200(IF CON. OUTLET) .= WATTS VOLTS
CIRCUIT BREAKER SIZE OF WIRE
AMP. LOAD
AT AF P ON RUN GROUNDING
1.30 20 100 2 3.5 mm THHN 2.0 mm2 THHN
2

2.61 30 100 2 5.5 mm2 THHN 2.0 mm2 THHN

3.91 100AT 100AF 2

CIRCUIT BREAKER SIZE OF WIRE


AMP. LOAD
AT AF P ON RUN GROUNDING
1.74 20 100 2 3.5 mm THHN 2.0 mm2 THHN
2

2.61 30 100 2 5.5 mm2 THHN 2.0 mm2 THHN

4.35 100AT 100AF 2

CIRCUIT BREAKER SIZE OF WIRE


AMP. LOAD
AT AF P ON RUN GROUNDING
1.30 20 100 2 3.5 mm2 THHN 2.0 mm2 THHN
1.74 30 100 2 5.5 mm2 THHN 2.0 mm2 THHN

3.04 100AT 100AF 2

CIRCUIT BREAKER SIZE OF WIRE


AMP. LOAD
AT AF P ON RUN GROUNDING
1.74 20 100 2 3.5 mm THHN 2.0 mm2 THHN
2

1.74 30 100 2 5.5 mm2 THHN 2.0 mm2 THHN

3.48 100AT 100AF 2

.=AMP. LOAD
PVC PIPE
20mm Ø PVC
20mm Ø PVC

PVC PIPE
20mm Ø PVC
20mm Ø PVC

PVC PIPE
20mm Ø PVC
20mm Ø PVC

PVC PIPE
20mm Ø PVC
20mm Ø PVC