Chapter 6 Circuit Breakers (Part 2)
Chapter 6 Circuit Breakers (Part 2)
The typicality of this device is, it can detect and protect only that
equipment or installation with which it is attached. It cannot detect
any leakage of insulation in other parts of the system.
Moulded Case Circuit Breaker (MCCB)
• MCCB is an automatic electrical device used
to protect the electrical equipment from
overload, short circuit, instantaneous over
current and earth fault. It is an advanced
version of MCB (Miniature circuit breaker). It
is available from 32 Amps to 1600 Amps with
the voltage range of 230V to 1.1kV.
Construction of MCCB
Different parts of MCCB are as follows:
1. Arc chute
2. Moving contact
3. Terminal connector
4. Overload trip or bimetallic contact
5. Handle knob
1. Arc chute: It is a stack of mutually insulated parallel metal
plates that used to divide the arc being developed in the
moulded case circuit breaker. Arc chute material is made up
of steel and glass fiber material.
2. Moving contact: An electrolyzed brass material is used as a
moving contact.
3. Terminal connector: The terminal connector is a bolt
assembly, made up of steel material. It is used to connect the
external circuit with the MCCB.
4. Bimetallic contact: A temperature-sensitive component, the
composition of steel and copper material is used as
bimetallic contact. Bimetallic contact is assembled in series
with the line current. It is used to trip the breaker under an
overload condition.
5. Handle Knob: It is used to close or open the contact
manually. Also, you cannot force to stop the breaker tripping
by holding knob at the top side. It is called a free trip.
Operation of MCCB
The MCCB working principle is simple. Let us take different fault
conditions such as Overload and short circuit
Overload Trip
• A flow of current that exceeds the rated current with predefined
time limit such a fault is called overload. Actually, it is not a fault, it
is a condition.
• The bimetallic contact involves in overload operation of the
breaker; under the normal condition, it allows the current flow. If
the current flow exceeds the predefined value, then it will get
bend and finally, it will engage the tripping mechanism. The trip
mechanism opens the breaker.
• Also, bimetallic contact will not allow the breaker to reset
instantly. Since it takes some time to reach its original state.
Short circuit trip
• An electromagnetic coil involves short circuit/instantaneous/earth
fault protection of the breaker. Under normal conditions, the CT
generates less current hence the electromagnetic field is
generated by the coil is not enough to pull the plunger. Therefore,
the breaker does not trip.
• During short circuit or instantaneous fault conditions, the CT
generates high current and the coil creates a strong magnetic
field. Hence the coil pulls the plunger and it will trip the circuit
instantly.
• The output of the current transformer will be connected in star.
Under normal conditions, the current flow through the star’s
neural point will be zero. if the leakage found in the line means,
the same will be sensed at the star terminal. if the leakage flow is
higher than the allowable limit means, the MCCB trip the circuit.
Applications:
• It is used for many induction motor’s starters such as star-delta,
DOL starter, Soft starter etc,
• MCCBs are suitable for the controlling LT capacitors for power
factor correction.
• MCCBs provide protection to welding circuits in terms of overloads
and short circuits
• MCCBs are ideally suited for protection of outgoing feeder circuits
of distribution boards.
Applications:
• They are used in the traction system because they are suitable
for repeated duty.
• They are also used for protection of small transformers.
Oil Circuit Breaker
ARC EXTINCTION PHENOMENA
• The separating contacts of the breakers are made to separate
within an insulating oil, which has better insulating properties
than air.
• On occurrence of fault as the breaker contacts open under oil, an
arc is struck between them and the heat of the arc evaporates the
surrounding oil and dissociates it into a substantial volume of
gaseous hydrogen at high pressure.
.
• The oil is pushed away from
the arc and an expanding
hydrogen gas bubble surrounds
the arc region and adjacent
portion of the contacts, as shown
in fig
• The arc extinction is facilitated chiefly by two processes.
• Firstly, the hydrogen gas has high heat conductivity and cools the
arc.
• Secondly, the gas set up turbulence in oil and forces it into the
space between contacts after the final arc interruption at a current
zero and thus arcing products from the arc path are eliminated.
• The result is that arc is extinguished and the circuit current is
interrupted.
Advantages of Oil CB
1. Arc energy is absorbed in decomposing of oil.
2. The gas formed, which is mainly hydrogen, has a good cooling
properties.
3. The oil used is a very good insulator and allows smaller clearance
between line conductors and earth components.
Disadvantages of Oil CB
1. Oil is inflammable and may cause fire hazards, if a defective oil
circuit breaker should fail under pressure and cause and explosion.
2. There is a risk of formation of explosive mixture with air.
3. Due to decomposition of oil in the arc, the oil becomes polluted by
carbon particles, which reduce its dielectric strength. Hence
periodical maintenance and replacement are required.
The plain break oil circuit breakers are widely employed on low
voltage dc and ac circuits. Such circuit breakers are not considered
suitable for short-circuit rating exceeding 250 MVA at 11KV.
A 110KV, 3500 MVA breaker may need 8 to 12 thousand kg of oil,
while a breaker of the same rating output for 220 KV may need 50
thousand kg of oil.
Minimum oil circuit breaker
• In the bulk oil circuit breakers discussed so far, the oil has to
perform two functions. Firstly, it acts as an arc quenching medium
and secondly, it insulates the live parts from earth. It has been
found that only a small percentage of oil is actually used for arc
extinction while the major part is utilized for insulation purposes.
For this reason, the quantity of oil in bulk oil circuit
breakers reaches a very high figure as the system voltage
increases. This not only increases the expenses, tank size and
weight of the breaker but it also increases the fire risk and
maintenance problems.
• The fact that only a small percentage of oil (about 10% of total) in
the bulk oil circuit breaker is actually used for arc extinction leads
to the question as to why the remainder of the oil, that is
not immediately surrounding the device, should not be omitted
with consequent saving in bulk, weight and fire risk. This led to
the development of low oil circuit breaker.
Fig: Minimum oil circuit breaker
Construction
• The figure shows the cross section of a single phase minimum oil
circuit breaker. There are two compartments separated from each
other but both filled with oil. The upper chamber is the circuit
breaking chamber while the lower one is the supporting chamber.
The two chambers are separated by a partition and oil from one
chamber is prevented from mixing with the other chamber. This
arrangement permits two advantages. Firstly, the circuit breaking
chamber requires a small volume of oil which is just enough for arc
extinction. Secondly, the amount of oil to be replaced is reduced
as the oil in the supporting chamber does not get contaminated by
the arc.
i. Supporting chamber: It is a porcelain chamber mounted on a
metal chamber. It is filled with oil which is physically separated
from the oil in the circuit breaking compartment. The oil inside
the supporting chamber and the annular space formed between
the porcelain insulation and bakelised paper is employed for
insulation purposes only.
(ii) Circuit-breaking chamber: It comprises a synthetic resin bonded
paper cylindrical enclosure within a porcelain insulator. It is filled
with oil and has the following parts :
(a) upper and lower fixed contacts
(b) moving contact
(c) turbulator
The moving contact is hollow and includes a cylinder which
moves down over a fixed piston. The turbulator is an arc control
device build up of oil-impregnated vulcanized fiber plates and has
both axial and radial vents. The axial venting ensures the
interruption of low currents whereas radial venting helps in the
interruption of heavy currents.
(iii) Top chamber: It is a metal chamber and is mounted on the
circuit-breaking chamber. It provides expansion space for the oil in
the circuit breaking compartment. The top chamber is also
provided with a separator which prevents any loss of oil by
centrifugal action caused by circuit breaker operation during fault
conditions.
Operation
Under normal operating conditions, the moving contact remains
engaged with the upper fixed contact. When a fault occurs, the moving
contact is pulled down by the tripping springs and an arc is struck. The
arc energy vaporizes the oil and produces gases under high pressure.
This action constrains the oil to pass through a central hole in the
moving contact and results in forcing series of oil through the respective
passages of the turbulator. The process of turbulation is orderly one, in
which the sections of the arc are successively quenched by the effect of
separate streams of oil moving across each section in turn and bearing
away its gases.
Advantages
• A low oil circuit breaker has the following advantages over a bulk oil
circuit breaker:
(i) It requires lesser quantity of oil.
(ii) It requires smaller space.
(iii) There is reduced risk of fire.
(iv) Maintenance problems are reduced.
Disadvantages:
1. Increased degree of carbonization due to smaller quantity of oil.
2. Rapid deterioration of dielectric strength of oil due to high degree
of carbonization.
3. Difficulty in removal of gases from the contact space in time.
SF6 Circuit Breaker
• In circuit breakers discussed so far (oil CB, air CB) the rate of
recovery of dielectric strength is relatively slow after the
movement of contact separation and hence the arc is usually
extinguished after few half cycles of current have passed zero.
• The prevention of arc reignition needs a high dielectric strength of
the arc path and its fast recovery after current zero.
• Vacuum CB and SF6 CB have better properties in this regard.
• SF6 gas is prepared by burning coarsely crushed sulphur in fluorine
gas, in a gas tight steel box.
• It is transported in liquid form in cylinder.
• SF6 is an electronegative gas having high dielectric strength and
excellent arc quenching properties. It is non poisonous, non-
explosive, inert, heavy gas.
• At 10 bar pressure, it liquefies at 15 degree Celsius and 5 bar at 4
degree Celsius. It is used in gaseous form in CB.
• As the gas is strongly electronegative free electrons are readily
removed from a discharge by the formation of negative ions
through process by which a free electron is attached to a neutral
gas molecule.
SF6 + e- SF6-
SF6 + e- SF5 + F-
ARC extinction Phenomena
• During the arcing period, SF6 gas is blown axially along the arc.
• The heat is removed from the arc due to axial convection and
radial dissipation.
• Consequently the arc diameter reduces, becomes small and
extinguishes during current zero.
• As the rate of recovery of dielectric strength is very high, the arc
will not restrike.
Construction
• Such a circuit breaker essentially consists of two parts, namely
(i) the interrupter unit and (ii) the gas system.
The interrupter unit:
• It consists of fixed and moving contacts enclosed in a chamber
(called arc interruption chamber) containing SF6 gas. This chamber
is connected to the SF6 gas reservoir. When the contacts of breaker
are opened, the valve mechanism permits a high-pressure SF6 gas
from the reservoir to flow towards the arc interruption chamber.
• The fixed contact is a hollow cylindrical current carrying contact
fitted with an arcing horn. The moving contact is also a hollow
cylinder with rectangular holes in the sides to permit the SF6 gas to
let out through these holes after flowing along and across the arc.
The tips of fixed contact, moving a contact and arcing horn are
coated with copper-tungsten arc-resistant material. Since SF6 gas is
costly, it is reconditioned and reclaimed by a suitable auxiliary
system after each operation of the breaker.
The Gas system:
• Since the gas pressure is very high, a lot of care is to be taken to
prevent gas leakage at joints.
• The low and high-pressure systems are fitted with low-pressure
alarms and set of lockout switches which give a warning the
moment the gas pressure drops below a certain value because
otherwise there will be a reduction in the dielectric strength and
arc quenching ability of the breaker is endangered.
• The gas is stored in the high-pressure chamber at 16 atmospheres
whereas the gas pressure on the low-pressure side is 3
atmospheres.
• The temperature is 20◦C in order to prevent liquefaction of gas in
the high-pressure chamber at low temperature; a heater is fitted
in the high-pressure chamber. A thermostat is set to the switch on
when the ambient temperature falls below 16◦C.
Advantage:
1. Non explosive and chemically inert.
2. No carbon byproducts to life of contacts.
3. Same gas is recirculated in the circuit thereby reducing the
requirement of SF6 gas. One triple pole, 145 KV SF6 CB needs only
about 30 kg of SF6 gas for first filling and no replacement is
required for about 5 years.
4. Minimum maintenance
5. Suitable for all applications including capacitor switching, motor
switching, line switching, faulty condition to interrupt the circuit.
Disadvantage:
1. Sealing problem: Imperfect joints may lead to leakage to SF6
2. SF6 gas is heavier than air and hence settles in the surrounding
and creates suffocation to some extent if leaked to atmosphere.
3. Arced SF6 is poisonous.
Vacuum Circuit breaker
• A vacuum circuit breaker is a kind of circuit breaker where the arc
quenching takes place in vacuum medium. The operation of
switching on and closing of current carrying contacts and
interrelated arc interruption takes place in a vacuum chamber in
the breaker which is called vacuum interrupter.
• Idea behind circuit breaker is elimination of medium between the
contacts.
• Every medium that has pressure below atmospheric which is 760
mm of Hg, is known as vacuum. Low pressure are measured in Torr.
( 1 Torr=1 mm of Hg)
• For pressure of 10-4 to 10-6 torr, the breakdown voltage become
independent of gas density and depends on gap length only.
• The breakdown voltage of vacuum compared with air for one pair
of 9.4 mm diameter tungsten contacts arc given in Table:
Construction
• It is very simple in construction as compared to any other circuit
breaker. Their construction is mainly divided into three parts, i.e., fixed
contacts, moving contact and arc shield which is placed inside the arc
interrupting chamber.
• The outer envelope of vacuum circuit breaker is made up of glass
because the glass envelope help in the examination of the breaker from
outside after the operation. If the glass becomes milky from its original
finish of silvery mirror, then it indicates that the breaker is losing
vacuum.
• The fixed and moving contacts of the breaker are placed inside the arc
shield. The pressure in a vacuum interrupter at the time of sealing off is
kept at about 10-6 torr. The moving contacts of the circuit breaker are
move through a distance of 5 to 10 mm depending upon the operating
voltage.
• The metallic bellows made of stainless steel is used to move the moving
contacts. The design of the metallic bellows is very important because
the life of the vacuum circuit breaker depends on the ability of the
component to perform repeated operations satisfactorily.
Operation and arc extinction
• The cathode surface normally, is not perfectly smooth but have
many micro- projections. During the separation of contacts, the
current will be concentrated in these micro- projections as they
are the last point of the contact. Due to their small area of cross
section the projections will suffer explosive evaporation by
resistive heating and supply sufficient quantity of vapour for the
arc formation.
• The density of vapour depends on the current in the arcing. Due to
the decreasing mode of current wave their rate of release of
vapour fall and after the current zero, the medium regains its
dielectric strength provided vapour density around the contacts
reduced. Hence, the arc does not restrike again because the metal
vapour is quickly removed from the contact zone.