Capacitor For 100kvar
Capacitor For 100kvar
The current drawn by the capacitor bank can be calculated using the formula:
Where:
2. Breaker Sizing
• Circuit breakers should be sized higher than the full-load current to account for transient
inrush currents (typically 6 to 10 times the rated current during capacitor bank
energization).
• A common rule of thumb is to size the breaker at 1.5 to 2 times the rated current.
BreakerRating=1.5×139 A≈208.5 ABreaker Rating = 1.5 \times 139 \, \text{A} \approx 208.5 \,
\text{A}BreakerRating=1.5×139A≈208.5A
3. Breaker Type
• Type of breaker: Choose a Molded Case Circuit Breaker (MCCB) or an Air Circuit
Breaker (ACB) depending on the system's design.
• Inrush capability: Ensure the breaker can handle high inrush currents due to capacitor
bank switching. A breaker with high instantaneous trip settings or a breaker designed
for capacitor applications is ideal.
4. Additional Considerations
1. Overvoltage Protection:
o Consider using surge arresters or detuned reactors to handle harmonics and
prevent overvoltage.
2. Coordination:
o Ensure proper coordination with upstream and downstream protection devices.
3. Switching Device:
o Use a dedicated contactor or switching device rated for capacitive loads to
manage frequent switching operations.
5. Final Recommendation
4o