Diesel Generator Set

6BTA Series Engine

> PRELIMINARY Specification Sheet


90 kVA – 110 kVA 50Hz
80 kW – 100 kW 60Hz

Description Features

This Cummins® Power Generation commercial generator set Cummins® Heavy-Duty Engine - Rugged 4-cycle industrial
is a fully integrated power generation system, providing diesel delivers reliable power and fast response to load
optimum performance, reliability, and versatility for changes.
stationary standby and prime power duty applications.
Alternator - Low reactance 2/3 pitch windings; low
This generator set is available with CE waveform distortion with non-linear loads, fault clearing
certification short-circuits capability, and class H insulation.

Cooling system - Standard integral set-mounted radiator


system, designed and tested for rated ambient
All enclosed products are designed to meet temperatures, simplifies facility design requirements for
2000/14/EC or exceed EU noise legislation 2000/14/EC rejected heat.
step 2006
Control system - The PowerCommand® electronic control
is standard equipment and provides total genset system
This generator set has been designed to integration, including auto remote start/stop, alarm and
ISO 8528 comply with ISO 8528 regulation status message display.

Enclosures - Optional sound attenuated enclosures are


available.
This generator set is designed in facilities
certified to ISO9001 and manufactured in Warranty - Backed by a comprehensive warranty and
facilities certified to ISO9001 or ISO9002 Worldwide distributor network.

3-Phase Ratings
Standby Rating Prime Rating Data Sheet
Model
50 Hz 60 Hz 50 Hz 60 Hz
kVA(kW) kW (kVA) kVA(kW) kW (kVA)

C90 D5 90(72) N/A 82(65) N/A DS352-CPGK

C110 D5 110(88) N/A 100(80) N/A DS353-CPGK

C80 D6 N/A 80(100) N/A 73(91) DS354-CPGK

C100 D6 N/A 100(125) N/A 91(114) DS346-CPGK

2010Cummins Power GenerationSpecifications Subject to Change Without Notice


Cummins and PowerCommand are registered trademarks of Cummins Inc. AmpSentry is a trademark of Cummins Inc.
SS28-CPGK
Generator Set Specifications
Governor Regulation Class ISO 8528 G2
Voltage Regulation, No Load to Full Load +/- 1%
Random Voltage Variation +/- 1%
Frequency Regulation Isochronous
Random Frequency Variation +/- 0.25%
Radio Frequency Emissions Compliance BA EN 61000-6-4 /BS EN 61000-6-2

Engine Specifications
Design 4 cycle, in-line, Turbo Charged and After cooled
Bore 102 mm (4.02 in.)
Stroke 120 mm (4.72 in.)
Displacement 5.9 litre (360 in.3 )
Cylinder Block Cast Iron, 6 Cylinder
Battery Capacity 120 AH
Battery Charging Alternator 55 AH
Starting Voltage 12 volt, 55 Amp negative ground
Fuel System Direct Injection
Fuel Filter Spin on fuel filters with water separator
Air Cleaner Type Dry replaceable element with restriction indicator
Lube Oil Filter Type(s) Spin on full flow filter
Standard Cooling System 122°F (50°C) ambient radiator

Alternator Specifications
Design Brushless, single bearing, revolving field
Stator 2/3 pitch winding
Rotor Single bearing, flexible disc coupling
Insulation System Class H
Standby 50Hz - 163°C @ 27°C ambient
Standard Temperature Rise
Standby , 60Hz - 150°C @ 40°C ambient
Exciter Type Self Excited
Phase Rotation A (U), B (V), C (W)
Alternator Cooling Direct drive centrifugal fan
AC Waveform Total Harmonic Distortion (THDV) No load < 1.8%. Non distorting balanced linear load < 5%
Telephone Influence Factor (TIF) <50 per NEMA MG1-22.43
Telephone Harmonic Factor (THF) <2%

Available Voltages
50 Hz Line – Neutral / Line - Line 60 Hz Line – Neutral / Line – Line
 220/380  110/190  115/200  139/240  240 / 416
• 230/400  115/200  120 / 208  220 / 380  255 / 440
• 240/415  120/208  127 / 220  230 / 400  277 / 480
* Note: Some Voltages may not be available on all models - Consult factory for availability .

Generator Set Options


• Sound attenuated canopy • Coolant Heater 240V • Alternator heater
• Mains Operated Battery Charger • Battery • Exciter voltage regulator (PMG)
• Double Walled Fuel tank ( CIRIA 535) • Heavy Duty Air Filter • Low Temp Rise Alternator
• Residential Silencer - Open Genset • AUX101 Output Module • Earth Fault Relay
• HMI114 AC Bar graph • Shunt Trip
* Note: Some options may not be available on all models - Consult factory for availability.

Our energy working for you. ™


www.cumminspower.com
2010Cummins Power GenerationSpecifications Subject to Change Without Notice
Cummins and PowerCommand are registered trademarks of Cummins Inc. AmpSentry is a trademark of Cummins Inc.
SS28-CPGK
The PowerCommand®
1.2 - Generator Set Control Status Indications
®
The PowerCommand 1.2 control is a microprocessor based The control has a lamp driver for external fault/status indication.
generator set monitoring control system. The control provides Functions include:
a simple operator interface to the generator set, digital • The lamp flashes during preheat (when used) and while
voltage regulation, digital engine speed governing, start / stop the generator set is starting.
control, and protective functions. • READY TO LOAD - flashing until the set is at rated
® voltage and frequency, then on continuously.
The PowerCommand 1.2 generator set control is suitable for
use on a wide range of generator sets in non-paralleling • Fault conditions are displayed by flashing a two-digit
applications. fault code number.
The PowerCommand Control can be configured for any
frequency, voltage and power configuration from 120 to LED Indicating Lamps - includes LED indicating lamps for the
600 VAC for 50 Hz or 60 Hz operation. following functions;
Power for the control is derived from the generator set • Not in Auto
starting batteries. The control functions over a voltage range • Remote Start
from 8 VDC to 35 VDC. • Warning
A larger HMI reduces setup time, provides more information • Shutdown
per screen, enhanced navigation and serviceability. • Auto
• Run
• Remote Emergency Stop Switch Input. Immediate shut
Major Features down of the generator set on operation.
• 12 or 24 VDC Battery Operation
• Digital Engine Speed Governing to provide isochronous Base Engine Protection
frequency regulation.
• Low Oil Pressure Shutdown
• Digital Voltage Regulation full wave rectified single • High Engine Temperature Shutdown
phase (line to line) sensing. • Under speed /Sensor Fail Shutdown
• Generator Set Monitoring. Monitors status of all critical • Fail to Start
engine and alternator conditions functions. • Battery Charging Alternator Fail Warning
• Engine Starting includes relay drivers for start and fuel HMI220 Operator Interface
shut off (FSO.
• Configurable Inputs and Outputs. Two discrete inputs • Back-Lit Graphics 128 x 128 LCD Display
and two dry contact relay outputs. • English Text and Symbolic Overlay
• Multiple Language LCD Screens
• Generator Set Monitoring: Displays status of all critical
• Dedicated Manual/Off/Auto function switches with mode
engine & alternator generator set functions.
LED’s and configurable access code (key switch).
• Smart Starting Control System: Integrated fuel ramping • Control Set-Up without PC-based tool (InPower).
to limit black smoke & frequency overshoot. • UL508 Recognized / CSA Certified / CE Compliant
• Advanced serviceability - using InPower™, a PC-based • Multiple HMI’s Per Genset (one local and one remote)
software service tool. • Plug and Play operation.

Control System

Includes all functions to locally or remotely start and stop,


and protect the generator set.

Control Switch - RUN/OFF/AUTO


• OFF Mode - the generator set is shut down & cannot
be started; as well as resets faults.
• RUN mode - the generator set will execute its start
sequence.
• AUTO mode - the generator set can be started with a
start signal from a remote device.

Our energy working for you. ™


www.cumminspower.com
2010Cummins Power GenerationSpecifications Subject to Change Without Notice
Cummins and PowerCommand are registered trademarks of Cummins Inc. AmpSentry is a trademark of Cummins Inc.
SS28-CPGK
Ratings Definitions

Standby: OPEN
Applicable for supplying power to varying electrical load for
the duration of power interruption of a reliable utility source.
Emergency Standby Power (ESP) is in accordance with ISO
8528. Fuel Stop power in accordance with ISO 3046, AS
2789, DIN 6271 and BS 5514.
Prime (Unlimited Running Time):
Applicable for supplying power in lieu of commercially
purchased power. Prime power is the maximum power
available at a variable load for an unlimited number of
hours. A 10% overload capability is available for limited
ENCLOSED
time. (Equivalent to Prime Power in accordance with
ISO8528 and Overload Power in accordance with ISO3046,
AS2789, DIN6271, and BS5514). This rating is not
applicable to all generator set models.
Base Load (Continuous):
Applicable for supplying power continuously to a constant
load up to the full output rating for unlimited hours. No
sustained overload capability is available for this rating.
Consult authorized distributor for rating. (Equivalent to
Continuous Power in accordance with ISO8528, ISO3046,
AS2789, DIN6271, and BS5514). This rating is not
applicable to all generator set models. This outline drawing is to provide representative
configuration details for Model series only.

See respective model data sheet for specific model


outline drawing number.

Do not use for Installation design.

Weights and Dimensions


Open Enclosed
A B C Dry Wt. A B C Dry Wt.
Model mm(in) mm(in) mm(in) (kg/lbs) mm(in) mm(in) mm(in) (kg/lbs)
C90 D5 2268(90) 1094(44) 1576(63) 1244(2737) 3151(125) 1142(45) 1714(68) 1944(4277)
C110 D5 2268(90) 1094(44) 1576(63) 1263(2779) 3151(125) 1142(45) 1714(68) 1963(4319)
C80 D6 2268(90) 1094(44) 1576(63) 1263(2779) 3151(125) 1142(45) 1714(68) 1963(4319)
C100 D6 2268(90) 1094(44) 1576(63) 1287(2832) 3151(125) 1142(45) 1714(68) 1987(4372)

* Note: Weights represent a set with standard features. See outline drawings for weights of other configurations.

Cummins Power Generation


Americas Asia Pacific Europe, CIS, Middle East and Africa
1400 73rd Avenue N.E. 10 Toh Guan Road #07-01 Manston Park Columbus Ave
Minneapolis, MN 55432 USA TT International Tradepark Manston Ramsgate
Phone 763 574 5000 Singapore 608838 Kent CT12 5BF United Kingdom
Fax 763 574 5298 Phone 65 6417 2388 Phone 44 1843 255000
Fax 65 6417 2399 Fax 44 1843 255902
Our energy working for you. ™
www.cumminspower.com
2010Cummins Power GenerationSpecifications Subject to Change Without Notice
Cummins and PowerCommand are registered trademarks of Cummins Inc. AmpSentry is a trademark of Cummins Inc.
SS28-CPGK