Product datasheet
Specifications
miniature circuit breaker - xC60 - 4
poles - 6 A - C curve
A9N4P06C
Main
Device application Distribution
Range of product Acti9
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Range Acti9
Product name XC60
Product or component type Miniature circuit-breaker
Device short name xC60
Poles description 4P
Number of protected poles 4
[In] rated current 6A
Network type DC
AC
Trip unit technology Thermal-magnetic
Curve code C
Utilisation category Category A conforming to EN/IEC 60947-2
Suitability for isolation Yes conforming to EN/IEC 60947-2
Complementary
Network frequency 50/60 Hz
[Ue] rated operational voltage 240 V AC 50/60 Hz
380...415 V AC 50/60 Hz
220...250 V DC
Magnetic tripping limit 8 x In +/- 20 %
Breaking capacity 10000 A Icn at 240 V AC 50/60 Hz conforming to EN/IEC 60898-1
10000 A Icn at 415 V AC 50/60 Hz conforming to EN/IEC 60898-1
15 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2
6 kA Icu at 220...250 V DC conforming to EN/IEC 60947-2
[Ics] rated service breaking 7.5 kA conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz
capacity 6 kA conforming to EN/IEC 60947-2 - 220...250 V DC
Limitation class 3 conforming to EN/IEC 60898-1
3 conforming to EN/IEC 60947-2
[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand 6 kV conforming to EN/IEC 60947-2
voltage
Contact position indicator Yes
Control type Toggle
Local signalling ON/OFF indication
27-Nov-2024 1
Mounting mode Clip-on
Mounting support 35 mm DIN rail
Comb busbar and distribution Top: YES
block compatibility
9 mm pitches 8
Height 85 mm
Width 72 mm
Depth 77.5 mm
Net weight 0.415 kg
Colour White
Mechanical durability 20000 cycles
Electrical durability 20000 cycles
Connections - terminals Tunnel type terminals (bottom) 16 mm² flexible
Tunnel type terminals (bottom) 25 mm² rigid
Biconnect (top)
Wire stripping length 13 mm for top or bottom connection
Tightening torque 2 N.m
Earth-leakage protection Separate block
Product compatibility C60 accessories
C60 auxiliary
Overvoltage category IV
Environment
Standards EN/IEC 60898-1
EN/IEC 60947-2
Pollution degree 3
Tropicalisation 2 conforming to IEC 60068-1
Relative humidity 95 % at 55 °C
Ambient air temperature for -30…70 °C
operation
Ambient air temperature for -40…85 °C
storage
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 8.2 cm
Package 1 Width 8.4 cm
Package 1 Length 8.2 cm
Package 1 Weight 400 g
Unit Type of Package 2 BB1
Number of Units in Package 2 3
Package 2 Height 9.4 cm
Package 2 Width 10 cm
Package 2 Length 24.6 cm
Package 2 Weight 1.28 kg
2 27-Nov-2024
Unit Type of Package 3 S03
Number of Units in Package 3 36
Package 3 Height 30 cm
Package 3 Width 30 cm
Package 3 Length 40 cm
Package 3 Weight 16.12 kg
27-Nov-2024 3
Environmental Data
Schneider Electric aims to achieve Net Zero status by 2050 through supply chain
partnerships, lower impact materials, and circularity via our ongoing “Use Better, Use
Longer, Use Again” campaign to extend product lifetimes and recyclability.
How this information helps you
Environmental footprint
Environmental Disclosure Product Environmental Profile
Use Better
Materials and Substances
Packaging made with recycled
Yes
cardboard
Packaging without single use
Yes
plastic
EU RoHS Directive Compliant with Exemptions
REACh Regulation REACh Declaration
China RoHS Regulation China RoHS declaration
Use Again
Repack and remanufacture
No need of specific recycling
Circularity Profile
operations
Halogen free plastic parts &
Halogen content performance
cables product
Take-back No
4 27-Nov-2024