Click here for more information:
elandcables.com | N2XSEY XLPE PVC 18/30 (36)kV Cable
N2XSEY XLPE PVC - 18/30 (36)kV Cable
Eland Product Group: A9X
APPLICATION STANDARDS
Medium voltage cables for distribution networks; also for IEC 60228, IEC 60502-2
connection to generation units and plant and process Flame Retardant according to IEC/EN 60332-1-2
connection. To be laid directly in ground, outdoors, indoors and
UV Resistant
in cable ducts e.g. in industrial and switchboard plants.
CHARACTERISTICS THE CABLE LAB®
Voltage Rating Uo/U (Um) AN ISO/IEC 17025 AND IECEE CBTL ACCREDITED FACILITY
18/30 (36)kV Our world-class testing facility assures the quality and compliance of this cable
through a continuous and rigorous testing regime.
Temperature Range
Maximum conductor operating temperature: 90°C
Initial temperature at S.C.C for metallic screen: 80°C
Maximum conductor temperature during S.C: 250°C
Minimum Bending Radius SUSTAINABILITY COMMITMENT
10 x overall diameter
We are on a journey to Net Zero.
We've committed to near-term emissions reductions and a net-zero target with the
Science Based Targets initiative and we're a signatory to the United Nations Global
Compact Sustainable Development Goals.
CONSTRUCTION
Learn more about embodied carbon and our carbon emissions reduction actions,
Conductor our comprehensive recycling services, and wider ESG activities for sustainable
Class 2 Stranded copper conductor operations at: www.elandcables.com/company/about-us/esg-sustainability
Inner Layer
Extruded Inner Semi Conductor (Bonded Type)
Insulation
XLPE (Cross-Linked Polyethylene)
REGULATORY COMPLIANCE
Outer Layer
This cable meets the requirements of the RoHS Directive 2015/65/EU and
Extruded Outer Semi Conductor (Strippable Type)
Reach Directive EC 1907/2006. RoHS compliance has been tested and
confirmed by The Cable Lab®.
Screen
Copper wires with Open Helix Copper Tape Screen
Outer Sheath
PVC (Polyvinyl Chloride)
Sheath Colour
Red Black
UK T 020 7241 8787 | F 020 7241 8700 | [email protected] | www.elandcables.com
International T +44 20 7241 8740 | F +44 20 7241 8700 |
[email protected] technicalspecification | 1 of 2
Click here for more information:
elandcables.com | N2XSEY XLPE PVC 18/30 (36)kV Cable
DIMENSIONS
ELAND PART NO. NO. OF NOMINAL CROSS NOMINAL SCREEN NOMINAL NOMINAL SHEATH NOMINAL OVERALL NOMINAL
CORES SECTIONAL AREA CROSS INSULATION THICKNESS DIAMETER WEIGHT
mm2 SECTIONAL AREA THICKNESS mm mm kg/km
mm2 mm
A9X30KV3050 3 50 16 8 3.1 64.5 4471
A9X30KV3070 3 70 16 8 3.2 68.1 5332
A9X30KV3095 3 95 16 8 3.4 71.3 6324
A9X30KV3120 3 120 16 8 3.5 74.5 7265
A9X30KV3150 3 150 25 8 3.6 78.6 8463
A9X30KV3185 3 185 25 8 3.7 82.1 9720
A9X30KV3240 3 240 25 8 3.9 87.7 11853
A9X30KV3300 3 300 25 8 4 93 13919
A9X30KV3400 3 400 35 8 4.3 99.1 16960
A9X30KV3500 3 500 35 8 4.5 106.8 20577
ELECTRICAL CHARACTERISTICS
NOMINAL MAXIMUM MAXIMUM CAPACITANCE CHARGING DIELECTRIC REACTANCE CONDUCTOR COPPER CURRENT RATING
CROSS CONDUCTOR CONDUCTOR μF/Km CURRENT LOSSES AT 50 HZ S.C.C FOR 1 SCREEN S.C.C A
SECTIONAL DC AC A/Km W/Km ohm/km SEC FOR 1 SEC
AREA RESISTANCE RESISTANCE KA KA
mm2 AT 20 °C AT OPERATING
Ω/Km TEMP. AND
50HZ
Ω/Km
Laid in ground Laid in free air
50 0.387 0.494 0.169 0.799 57.52 0.139 7.15 1.75 225 250
70 0.268 0.342 0.19 0.898 64.62 0.130 10.01 1.75 274 306
95 0.193 0.247 0.205 0.968 69.68 0.125 13.585 1.75 329 370
120 0.153 0.196 0.221 1.043 75.09 0.120 17.16 1.75 374 426
150 0.124 0.159 0.239 1.128 81.23 0.116 21.45 2.73 420 484
185 0.0991 0.128 0.256 1.208 86.95 0.112 26.455 2.73 475 553
240 0.0754 0.098 0.283 1.334 96.06 0.107 34.32 2.73 552 652
300 0.0601 0.078 0.31 1.46 105.11 0.103 42.9 2.73 628 758
400 0.047 0.062 0.338 1.595 114.87 0.099 57.2 3.82 706 857
500 0.0366 0.049 0.376 1.772 127.59 0.095 71.5 3.82 799 988
Laying conditions at trefoil formation are as below:
-Soil thermal resistivity 120 °C.Cm/Watt
-Burial depth 0.5 m
-Ground temperature 15 °C
-Air temperature 25 °C
-Frequency 50 Hz
The information contained within this datasheet is for guidance only and is subject to change without notice or liability. All the information is provided in good faith and is
believed to be correct at the time of publication. When selecting cable accessories, please note that actual cable dimensions may vary due to manufacturing tolerances.
UK T 020 7241 8787 | F 020 7241 8700 | [email protected] | www.elandcables.com
2 of 2 | technicalspecification International T +44 20 7241 8740 | F +44 20 7241 8700 |
[email protected]